36E77619R0097-013.pdf

PDF 10 MB Posted

Attached to
Construct Clean Core (VA-19-00058573) Federal contract opportunity
Solicitation number
36E77619R0097
Issued by
Department of Veterans Affairs Headquarters

About this file

This document provides details of a federal contract opportunity for construction services. The Department of Veterans Affairs intends to solicit bids and award a firm-fixed-price contract to construct a new clean core surgery suite addition at the Providence VA Medical Center in Rhode Island. The project scope involves constructing approximately 3,900 square feet of new space in a second floor addition and renovating 2,900 square feet of existing space. The construction must not disrupt existing hospital operations and the operating room must remain accessible at all times. The solicitation will be issued as a Request for Proposal for a total SDVOSB set-aside with an estimated value between $5-10 million and a 490-day period of performance. The NAICS code is 236220 and bids are due on or about October 16, 2019.

36E77619R0097 Attachment 10 - Electrical Plans.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Construct Clean Core (VA-19-00058573), newest first.
File Type Posted
36E77619R0097-0007000.docx DOCX document
36E77619R0097-0006000.docx DOCX document
36E77619R0097-0005000.docx DOCX document
36E77619R0097-0005001.pdf PDF
36E77619R0097-0004001.docx DOCX document
36E77619R0097-0004005.pdf PDF
36E77619R0097-0004004.pdf PDF
36E77619R0097-0004002.pdf PDF
36E77619R0097-0004000.docx DOCX document
36E77619R0097-0004003.pdf PDF
36E77619R0097-0003001.pdf PDF
36E77619R0097-0003000.docx DOCX document
36E77619R0097-0002001.pdf PDF
36E77619R0097-0002002.pdf PDF
36E77619R0097-0002000.docx DOCX document
36E77619R0097-0001030.docx DOCX document
36E77619R0097-0001031.pdf PDF
36E77619R0097-014.pdf PDF
36E77619R0097-011.pdf PDF
36E77619R0097-003.docx DOCX document
36E77619R0097-015.docx DOCX document
36E77619R0097-013.pdf PDF
36E77619R0097-009.pdf PDF
36E77619R0097-010.pdf PDF
36E77619R0097-006.pdf PDF
36E77619R0097-008.pdf PDF
36E77619R0097-007.pdf PDF
36E77619R0097-012.pdf PDF
36E77619R0097-004.pdf PDF
36E77619R0097-005.zip ZIP file
36E77619R0097-005.zip ZIP file
36E77619R0097-006.pdf PDF
36E77619R0097-015.docx DOCX document
36E77619R0097-011.pdf PDF
36E77619R0097-014.pdf PDF
36E77619R0097-007.pdf PDF
36E77619R0097-009.pdf PDF
36E77619R0097-008.pdf PDF
36E77619R0097-012.pdf PDF
36E77619R0097-004.pdf PDF
36E77619R0097-003.docx DOCX document
36E77619R0097-010.pdf PDF
36E77619R0097-000.docx DOCX document
36E77619R0097-000.docx DOCX document
Show all 44

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REF:

A1

1.

2.

3.

4.

5.

6.

7.

8.

CONDUIT RUNS ARE SHOWN DIAGRAMATICALLY.

INSTALL CONDUIT WITH A MINIMUM OF BENDS IN

THE SHORTEST PRACTICAL DISTANCE

CONSIDERING THE BUILDINGS CONSTRUCTION

AND OBSTRUCTIONS, EXCEPT WHERE OTHERWISE

NOTED.

ALL ENCLOSURES, CONDUIT BODIES AND THEIR

COVERS WHICH CONTAIN FIRE ALARM SYSTEM

CONDUCTORS SHALL BE PAINTED RED.

FLEXIBLE CONNECTIONS TO MOTORS SHALL BE

FLEXIBLE LIQUID TIGHT CONDUIT.

9.

10.

11.

12.

13.

14.

15.

16.

18.

19.

17.

UNLESS OTHERWISE NOTED, ALL WIRING SHALL

BE 600V, COPPER WITH THHN-THWN INSULATION.

ALL GENERAL NOTES, SYMBOLS, LISTS,

ABBREVIATIONS AND DETAILS ARE TO BE

CONSIDERED APPLICABLE TO ALL ELECTRICAL

DRAWINGS FOR THIS PROJECT.

WHERE MATERIAL IS CALLED OUT IN THE

LEGEND BY MANUFACTURER, TYPE OR

CATALOG NUMBER, SUCH DESIGNATIONS

ARE TO ESTABLISH STANDARDS OR

DESIRED QUALITY. ACCEPTANCE OR

REJECTION OF THE PROPOSED

SUBSTITUTIONS SHALL BE SUBJECT TO

THE APPROVAL OF THE OWNER.

REFER TO ARCHITECTURAL DRAWINGS FOR

EXACT LOCATION OF EQUIPMENT, DEVICES, AND

FURNITURE REQUIREMENTS, PRIOR TO ROUGHING

IN FOR SAME.

IN AREAS AFFECTED BY THIS RENOVATION,

THE ELECTRICAL SUBCONTRACTOR SHALL

MAINTAIN CONTINUITY OF EXISTING ELECTRICAL

SERVICE.

PRIOR TO REMOVAL OF EQUIPMENT, THE

OWNER WILL INDICATE WHICH EXISTING DEVICES

OR MATERIALS SHALL BE SALVAGED AND TURNED

OVER FOR STORAGE.

WHERE EXISTING EQUIPMENT AND DEVICES ARE

TO BE RELOCATED, ALL ASSOCIATED WIRING,

CONDUIT AND ACCESSORIES SHALL BE EXTENDED,

RELOCATED OR REPLACED WHERE REQUIRED.

ALL EXIT SIGNS AND NIGHT LIGHT (NL) FIXTURES

ARE TO BE UNSWITCHED.

NOTES

1.

2. THE ELECTRICAL CONTRACTOR SHALL VERIFY

FIXTURE MOUNTING AND LOCATION AGAINST

PLANS, ELEVATIONS, AND DETAIL DRAWINGS.

EXACT LOCATION OF ALL FIXTURES SHALL BE

CONFIRMED WITH THE ARCHITECT PRIOR TO

ROUGHING IN.

THE ELECTRICAL CONTRACTOR SHALL FURNISH

ALL LIGHTING FIXTURES COMPLETE WITH

MOUNTING ACCESSORIES TO MEET JOB REQUIREMENTS.

3.

4.

SERIES FIXTURES SHALL SATISFY LENGTHS AS

SHOWN ON THE DRAWINGS.

FIXTURE LETTERS SHOWN ON A CONTINUOUS ROW

OF FIXTURES SHALL BE TYPICAL FOR THAT ROW

UNLESS OTHERWISE NOTED.

5.

6.

7.

ALL FIXTURES SHALL BE SUPPORTED FROM THE

BUILDING STRUCTURE, INDEPENDENT OF HUNG

CEILINGS.

(EN)

EXISTING TO BE DISCONNECTED AND

RELOCATED

EXISTING IN NEW LOCATION

GENERAL NOTES LIGHTING FIXTURE NOTES

EXISTING

EQUIPMENT LEGEND

REF:

A2

LEGEND

THE ELECTRICAL SUBCONTRACTOR SHALL VISIT

THE SITE AND INSPECT EXISTING CONDITIONS,

SERVICES, CONDUITS, SPATIAL CONSIDERATIONS

AND ALL OTHER PERTINENT CONDITIONS TO FULLY

FAMILIARIZE HIMSELF WITH CONDITIONS TO BE

ENCOUNTERED IN THE PERFORMANCE OF THIS WORK.

THE ELECTRICAL SUBCONTRACTOR SHALL COORDINATE

THIS WORK WITH THE GENERAL CONTRACTOR DURING

CONSTRUCTION. FAILURE TO DO SO WILL NOT RELIEVE

THE ELECTRICAL SUBCONTRACTOR OF THE RESPONSIBILITY

FOR FULL COMPLETION OF THE WORK IN ACCORDANCE

WITH APPLICABLE DRAWINGS AND SPECIFICATIONS.

VERIFY EXISTING SYSTEMS THAT WILL BE UTILIZED FOR

CONNECTION TO THE NEW SYSTEM. IF DISCREPANCIES

EXIST BETWEEN THE CONTRACT DRAWINGS AND THE

ACTUAL EXISTING CONDITIONS, THE ELECTRICAL

SUBCONTRACTOR SHALL NOTIFY THE ENGINEER/OWNER

PRIOR TO PROCEEDING WITH THE INSTALLATION.

ALL MOTOR SAFETY SWITCHES, DISCONNECTS AND

MOTOR STARTERS THAT ARE NOT PROVIDED BY

OTHER DIVISIONS, SHALL BE PROVIDED BY DIVISION 26,

UNLESS SPECIFICALL NOTED OTHERWISE.

ALL PENETRATIONS THROUGH FIRE-RATED FLOORS,

WALLS AND PARTITIONS SHALL BE SEALED WITH

UL APPROVED FIRE SEALANT MATERIAL TO

MAINTAIN THE RATING OF THE SEPARATION.

UNLESS OTHERWISE INDICATED ALL RECEPTACLES

SHALL BE HOSPITAL GRADE.

U.L. LISTED AND LABELED.

APPLICABLE, PROVIDE ONLY MATERIALS THAT ARE

ANSI, IEEE, IES, AND NEMA STANDARDS. WHERE

MATERIALS AND EQUIPMENT THAT COMPLY WITH

STATE, COUNTY, AND CITY AGENCIES. PROVIDE

REGULATIONS OF THE PERTINENT FEDERAL,

OSHA REGULATIONS, AS WELL AS APPLICABLE

NFPA 70, NATIONAL ELECTRICAL CODE(NEC),

ACCORDANCE WITH THE LATEST EDITION OF

ALL WORK SHALL BE PERFORMED IN

1.

PUBLIC ADDRESS SYSTEM NOTES

1.

a.

b.

c.

PROVIDE NEW CARD READERS

WHERE INDICATED.

PROVIDE NEW DOOR CONTACTS

WHERE INDICATED.

PROVIDE NEW REQUEST TO EXIT

DEVICES WHERE INDICATED.

2.

3.

d.

e. PROVIDE NEW ELECTRIC STRIKES

WHERE INDICATED.

CARD ACCESS

SYSTEM NOTES

COORDINATE ALL CARD ACCESS WORK WITH VA

CAMPUS POLICE DEPARTMENT.

ACCESS CONTROL WORK SHALL BE DONE BY

JOHNSON CONTROLS INC. CONTACT CHRIS

DAVID, SECURITY TEAM LEADER; 39 SALEM ST

LYNNFIELD, MA 01940: OFFICE 781-246-5500,

CELL 508-948-7240.

f. PROVIDE RELAYS AND CONNECTIONS

TO MOTORIZED DOOR OPENERS AS REQUIRED.

PROVIDE CONNECTION TO FIRE

ALARM SYSTEM AS REQUIRED.

#10

BRANCH CIRCUIT

VOLTAGE DROP

#8

CONDUCTOR AWG

MAXIMUM CONDUCTOR LENGTH AT 120V

MAXIMUM CONDUCTOR LENGTH AT 277V

GROUND CONDUCTOR AWG

MAXIMUM CONDUCTOR LENGTH AT 480V 1PH.

MAXIMUM CONDUCTOR LENGTH AT 208V 1PH

#10

#12

#12 #10

1.

2.

3.

4.

NOTES:

INCREASE BRANCH CIRCUIT CONDUCTOR AS INDICATED.

BASED ON 20 AMP CIRCUIT LOADED TO 10 AMP USING

SINGLE PHASE, 2 WIRE CIRCUITS.

SCHEDULE REPRESENTS MINIMUM CONDUCTOR SIZE

BASED ON LENGTH OF BRANCH CIRCUIT CONDUCTOR

FROM PANEL TO PHYSICAL CENTER OR LOAD TO

OVERCOME VOLTAGE DROP. 3% VOLTAGE DROP

ASSUMED.

TRANSITION FROM LARGER CONDUCTOR SIZE TO #12

FOR FINAL TERMINATION TO OUTLET DEVICE. PROVIDE

JUNCTION BOX WITHIN 10' OF OUTLET. EXTEND #12

CONDUCTOR TO OUTLET DEVICE.

CONDUCTOR INSULATION TYPE SHALL BE THHN/THWN,

75 DEG. C, AND 600V CLASS UNLESS SPECIFIED OTHERWISE.

TELE/DATA SYSTEM NOTES

ALL FIXTURES INDICATED WITH 'NL' ARE TO BE

UNSWITCHED NIGHT LIGHT FIXTURES.

MODIFY THE EXISTING JOHNSON CONTROLS INC.

PEGASYS P2000, VERSION 3.4 CARD ACCESS

SYSTEM PRESENTLY SERVING THE HOSPITAL

BUILDING TO ACCOMMODATE THE NEW

DEVICES INDICATED. PROVIDE EXPANSION CARDS

ADDITIONAL POWER SUPPLIES, CABLES AND

ALL OTHER ACCESSORIES FOR A COMPLETE AND

OPERATIONAL SYSTEM.

CONTRACTOR SHALL PROVIDE ALL PULLBOXES

REQUIRED FOR FEEDERS, SIZE AS REQUIRED.

E L E C T R I C A L L E G E N D

HOMERUN TO PNLBRD - ARROWS INDICATE NUMBER OF CIRCUITS. CROSS LINES INDICATE

NUMBER OF CONDUCTORS OTHER THAN TWO (PROVIDE NUMBER OF WIRES REQUIRED TO ALLOW

SWITCHING SHOWN - E10 SERIES LIGHTING DRAWINGS).

CIRCUIT NUMBER(S)

PANEL DESIGNATION

SINGLE POLE SWITCH - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE - SUBLETTER

INDICATES SWITCH CONTROL

THREE-WAY SWITCH - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE

FOUR-WAY SWITCH - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE

WALL MOUNTED OCCUPANCY SENSOR SWITCH - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE

OC OCCUPANCY SENSOR AND POWER PACK - PROVIDE NUMBER OF POWER PACKS REQUIRED TO

HOSPITAL GRADE DUPLEX CONVENIENCE RECEPTACLE - SEE ARCHITECTURAL INTERIOR

GFI HOSPITAL GRADE GFCI DUPLEX CONVENIENCE RECEPTACLE - SEE ARCHITECTURAL INTERIOR

HOSPITAL GRADE DOUBLE DUPLEX CONVENIENCE RECEPTACLE - SEE ARCHITECTURAL

GFI HOSPITAL GRADE GFCI DOUBLE DUPLEX CONVENIENCE RECEPTACLE - SEE ARCHITECTURAL

HOSPITAL GRADE EMERGENCY DUPLEX CONVENIENCE RECEPTACLE - SEE ARCHITECTURAL

HOSPITAL GRADE EMERGENCY GFCI DUPLEX CONVENIENCE RECEPTACLE - SEE ARCHITECTURAL

GFI HOSPITAL GRADE EMERGENCY GFCI DOUBLE DUPLEX CONVENIENCE RECEPTACLE - SEE

SPECIAL RECEPTACLE - SEE ARCHITECTURAL INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS.

VOICE AND DATA OUTLET - JUNCTION BOX WITH SINGLE GANG RAISED RING/FACEPLATE AND

TWO 1" CONDUIT TO ABOVE AN ACCESSIBLE CEILING - REFER TO SPECIFICATION SECTION

27 10 00 STRUCTURED CABLING FOR DATA OUTLET AND CABLING REQUIREMENTS

W

UNLESS NOTED OTHERWISE - JUNCTION BOX WITH SINGLE GANG RAISED RING/FACEPLATE

AND ONE 1" CONDUIT TO ABOVE AN ACCESSIBLE CEILING - REFER TO SPECIFICATION

SECTION 27 10 00 STRUCTURED CABLING FOR DATA OUTLET AND CABLING REQUIREMENTS

V

TV OUTLET - SEE ARCHITECTURAL INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS UNLESS

NOTED OTHERWISE - JUNCTION BOX WITH SINGLE GANG RAISED RING/FACEPLATE AND ONE

1" CONDUIT TO ABOVE AN ACCESSIBLE CEILING - REFER TO SPECIFICATION SECTION 27

10 00 STRUCTURED CABLING FOR DATA OUTLET AND CABLING REQUIREMENTS

J JUNCTION BOX

DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

COMBINATION DISCONNECT SWITCH & MOTOR STARTER

MOTOR RATED SWITCH

EXISTING PANELBOARD

PANELBOARD

LIGHTNING PROTECTION SYSTEM AIR TERMINAL

GROUND ROD

MOUNTED

MOUNTED DIRECTLY ABOVE DOOR

S PUBLIC ADDRESS SPEAKER - CEILING MOUNTED - "V" INDICATES INTEGRAL VOLUME CONTROL

S PUBLIC ADDRESS SPEAKER - WALL MOUNTED - "V" INDICATES INTEGRAL VOLUME CONTROL

CONTROL PANEL

MOTORIZED DOOR ACTIVATION STATION

CARD READER

DOOR CONTACT/SWITCH

ELECTRIC STRIKE

REQUEST TO EXIT BUTTON

REQUEST TO EXIT SENSOR

## KEYNOTE

EXISTING ITEMS SHOWN DASHED

WP WEATHERPROOF

NL NIGHTLIGHT

EQ

CR CRITICAL PANEL

CB

EQUIPMENT PANEL

EMH ELECTRIC MANHOLE

CIRCUIT BREAKER

ATS AUTOMATIC TRANSFER SWITCH

ALL FIXTURES SHALL MEET UTILITY COMPANY INCENTIVE

REQUIREMENTS. CONTRACTOR SHALL COMPLETE ALL

INCENTIVE APPLICATIONS AND SUBMIT ALL REQUIRED

INFORMATION TO THE UTILITY COMPANY PRIOR TO

ORDERING LIGHT FIXTURES. ALL INCENTIVES SHALL BE

TURNED OVER TO THE VA.

1.

a.

2.

b.

c.

PROVIDE NEW FIRE ALARM

SPEAKER/STROBES WHERE

INDICATED.

PROVIDE NEW FIRE ALARM STROBES

WHERE INDICATED.

FIRE ALARM

SYSTEM NOTES

REFER TO ELECTRICAL DRAWINGS FOR QUANTITIES

AND LOCATIONS OF ALL FIRE ALARM DEVICES

ASSOCIATED WITH FIRE PROTECTION SYSTEMS.

d.

e.

f.

PROVIDE NEW FIRE ALARM DUCT SMOKE

DETECTORS WHERE INDICATED.

PROVIDE NEW FIRE ALARM SMOKE

DETECTORS WHERE INDICATED.

h.

MAKE ALL CONNECTIONS AS REQUIRED.

PROVIDE ALL REQUIRED PROGRAMMING.

RELOCATE EXISTING FIRE ALARM DEVICES

AS INDICATED.

3.

1.

a.

b.

2.

3.

CCTVSYSTEM NOTES

COORDINATE ALL CCTV WORK WITH VA

CAMPUS POLICE DEPARTMENT.

CCTV WORK SHALL BE DONE BY

SHANIX TECHNOLOGY. CONTACT DON T. VOLINO,

GENERAL DIRECTOR; 40 WORTHINGTON

ROAD, CRANSTON, RI, 02920: OFFICE 401-941-4222,

CELL 401-439-7547.

CENTRAK EQUIPMENT LOCATION SENSOR-CEILING MOUNTEDCTR

W

CCTV CAMERA - PELCO FIXED ENDUREA SARIX 3MP

CB CODE BLUE BUTTON

NURSE CALL SYSTEM STAFF STATION

PUBLIC ADDRESS VOLUME CONTROL - WALL MOUNTEDV

NURSE CALL SYSTEM DOME LIGHT

(XRE)

F

AIM

AOM

S

FIRE ALARM MANUAL PULL STATION - MOUNTED C/L UP 48"

FIRE ALARM SMOKE DETECTOR - CEILING MOUNTED

FIRE ALARM ADRESSABLE OUTPUT MODULE

FIRE ALARM ADRESSABLE INPUT MODULE

FIRE ALARM STROBE LIGHT UNIT - CANDLE POWER (CD) PER NFPA 72 OR AS NOTED -

15/75 WHERE NOT OTHERWISE INDICATED ON PLANS - WALL MOUNTED

FIRE ALARM SPEAKER/LIGHT UNIT - CANDLE POWER (CD) PER NFPA 72 OR AS NOTED -

15/75 WHERE NOT OTHERWISE INDICATED ON PLANS - WALL MOUNTED

EQUIPMENT TRACKING

SYSTEM NOTES:

1.

1.

WIFI SYSTEM NOTES:

WHERE A DISCREPANCY OCCURS BETWEEN THE

DRAWINGS AND THE SPECIFICATIONS, THE MOST

STRINGENT SHALL PREVAIL. CONTACT THE

ENGINEER FOR CLARIFICATION WHEN SUCH A

SITUATION OCCURS.

CONNECT NEW PUBLIC ADDRESS SPEAKERS TO EXISTING

PUBLIC ADDRESS SYSTEM PRESENTLY SERVING THE

HOSPITAL. CONNECT TO EXISTING SYSTEM WIRING

SERVING SPACE OR AS REQUIRED.

WALL MOUNTED SPEAKER: BOGEN # MB8TSL

CEILING MOUNTED SPEAKER: BOGEN # S86T725PG8U

CEILING SPEAKER W/ VOLUME CONTROL: BOGEN # S86T725PG8UVK

CABLE: HONEYWELL/GENESIS #3123

GFI

LP1#3

ALLOW FOR NUMBER OF OCCUPANCY SENSORS AND SWITCHING SHOWN

ELEVATIONS FOR MOUNTING HEIGHTS. IF NOT SHOWN ON ELEVATION, MOUNT AT 18"AFF

ELEVATIONS FOR MOUNTING HEIGHTS. IF NOT SHOWN ON ELEVATION, MOUNT AT 18"AFF

INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS. IF NOT SHOWN ON ELEVATION, MOUNT AT 18"AFF

INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS. IF NOT SHOWN ON ELEVATION, MOUNT AT 18"AFF

INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS. IF NOT SHOWN ON ELEVATION, MOUNT AT 18"AFF

INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS. IF NOT SHOWN ON ELEVATION, MOUNT AT 18"AFF

IF NOT SHOWN ON ELEVATION, MOUNT AT 18"AFF

HOSPITAL GRADE EMERGENCY DOUBLE DUPLEX CONVENIENCE RECEPTACLE - SEE ARCHITECTURAL

INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS. IF NOT SHOWN ON ELEVATION, MOUNT AT 18"AFF

MOUNT AT 18"AFF

ARCHITECTURAL INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS. IF NOT SHOWN ON ELEVATION, EXIT SIGN WITH ARROWS AS INDICATED OR HATCH INDICATES FACE - CEILING

EXIT SIGN WITH ARROWS AS INDICATED OR HATCH INDICATES FACE - WALL

2.

(XN) EXISTING TO BE REPLACED WITH NEW

PROVIDE A NEW CCTV SYSTEM TO SERVE THE

CLEAN CORE SPACE. NEW CCTV SYSTEM SHALL

BE COMPLETE WITH CAMERAS, CABLE, CAMERA

HOUSINGS, SPLITTERS, AND ALL OTHER ACCESSORIES

FOR A COMPLETE AND OPERATIONAL SYSTEM.

PROVIDE NEW CCTV CAMERAS WITH

HOUSING WHERE INDICATED.

ALL NEW CLEAN CORE TELE/DATA OUTLETS SHALL BE CONNECTED

TO NEW AND EXISTING TELE/DATA DISTRIBUTION EQUIPMENT

IN O.R. ADDITION, BASEMENT LEVEL, TELE/DATA RM 12L.

PROVIDE AND INSTALL THE FOLLOWING NEW EQUIPMENT IN EXISTING

O.R. ADDITION TELE/DATA ROOM 12L:

-NEW NETWORK RACK - CHATSWORTH CABLE MANAGEMENT

RACK 19" MODEL - 55053703

-NEW 4 X 48 PORT PATCH PANELS - OR-SP6U48 ORTRONICS CAT 6

PATCH PANEL 24 PORT, 568A, 110 FOR PROPOSED CLEAN CORE

DATA OUTLETS

-NEW 4 X HORIZONTAL CABLE MANAGEMENT - OR-808045030 ORTRONICS

CABLE MANAGEMENT HORIZONTAL FOR NEW PATCH PANELS

PRIOR TO DEMOLISHING DATA CABLING, COORDINATE WITH VAMC I.T.

STAFF TO DETERMINE IF EXISTING CABLING CAN BE REUSED. ALL

CABLING THAT CAN NOT BE REUSED SHALL BE DEMOLISHED BACK TO

I.T. CLOSET AND REMOVED FROM PATCH PANELS.

REFERENCE ELECTRICAL SPECIFICATION SECTION 270513 FOR VAMC

PROVIDENCE RI TELE/DATA CABLING STANDARDS.

COORDINATE DATA CABLE CONNECTION POINTS WITH

VA I.T. STAFF.

THE WIRELESS WIFI SYSTEM EQUIPMENT AND CABLING

MUST BE MAINTAINED AND INTACT. ANY EXISTING

CABLING SHALL NOT BE DEMOLISHED AS PART OF THE

PROJECT. VAMC I.T STAFF WILL TEMPORARILY REMOVE

THE ACCESS POINTS WITHIN THE CONSTRUCTION AREA

PRIOR TO THE CONSTRUCTION START DATE. VAMC

INFORMATION TECHNOLOGY DEPARTMENT SHALL

REINSTALL WIRELESS ACCESS POINT DEVICES IN

NEW LOCATIONS.

ABBREVIATIONS

SP

BS

VISIPLEX WIRELESS SPEAKER MODEL#VNS2214-1 WITH WIRELESS RECEIVER

VISIPLEX MODEL#VS4500 BASE STATION WITH INTEGRAL 6 WATT TRANSMITTER MODEL#VTX-6,

HANDHELD MICROPHONE MODEL#VS3005 AND ANTENNA MODEL#VS638

PP

POWER POLE WITH CRITICAL BRANCH QUAD RECEPTACLE AND (2) DATA OUTLETS

WIREMOLD CATALOG #25DTP-4ACT. PROVIDE DATA ADAPTER PLATES AS REQUIRED

SIMPLEX RECEPTACLE ABOVE DROP CEILING FOR VISIPLEX WIRELESS SPEAKER - CRITICAL POWER

1.

2.

3.

PHASING NOTES:

ALL ELECTRICAL UTILITY OUTAGES AND CUTOVERS

SHALL BE SCHEDULED OFF HOURS AND WEEKENDS.

COORDINATE ALL ELECTRICAL OUTAGES AND CUTOVERS

WITH VAMC. CONTRACTOR SHALL CARRY ALL REQUIRED

OVERTIME COST FOR THIS WORK IN BASE BID.

REFER TO ARCHITECTURAL DRAWINGS A01.1 AND A01.2

FOR PROJECT PHASING AND ADDITIONAL PHASING NOTES.

OPERATING ROOM (O.R.) AND POST-ANESTHESIA CARE UNIT

(P.A.C.U) SHALL REMAIN OPEN AND ACCESSIBLE AT ALL TIMES

DURING CONSTRUCTION. ANY WORK DONE IN THESE AREAS

SHALL BE PERFORMED ON OFF HOURS AND WEEKENDS ONLY.

COORDINATE ALL PHASING AND CONSTRUCTION WORK WITH

VA CONTRACTING OFFICER'S REPRESENTATIVE (C.O.R) AND

ARCHITECT. IF WORK REQUIRES A SHUTDOWN AND CAN'T

BE PERFORMED OFF HOURS, WEEKENDS OR FEDERAL HOLIDAYS,

A 28 DAY NOTICE IN ADVANCE MUSST BE SUBMITTED TO THE

PROVIDENCE VA MEDICAL CENTER (P.V.A.M.C.), COR AND ARCHITECT.

2.

c.

d.

PROVIDE NEW WORKSTAION AND

DISPLAY IN NURSE MANAGER OFFICE 253.

PROVIDE NEW NETWORK STORAGE

MANAGER FOR RECORDING.

e.

PROVIDE NEW COMPUTER SWITCH

CONNECTING CAMERA VIDEO SIGNAL

TO THE NETWORK.

f. PROGRAM CAMERAS WITH IP ADDRESSES AND

OTHER PROGRAMMING AS REQUIRED.

g.

PROVIDE NEW CCTV CABLING TO

EXISTING RACK IN FIRE COMMAND CENTER.

INSTALL AND TERMINATE RED CATEGORY 6

CABLES FROM CAMERA TO FIRE COMMAND CENTER.

h. RELOCATE EXISTING CCTV CAMERA WHERE INDICATED.

SHANIX BILL OF MATERAL:

(6) PELCO 3MP SARIX CAMERAS, 3-9MM

(6) PELCO SRX ENH+ INDOOR DOME MOUNT

(1) PELCO SARIX IME SERIES VANDAL RESISTANT MINI DOME

(1) CISCO 1000BASE-LX/LH SFP TANSCEIVER MODULE, MMF/SMF, 1310NM

(1) CISCO CATALYST 3850-24P-S LAYER 3 SWITCH-24 POE PORTS IP

(1) CISCO 715W AC CONFIG 1 SECONDARY POWER SUPPLY

(1) CISCO CATALYST 3850 4 X 1GE NETWORK MODULE

(2) CISCO NORTH AMERICAL AC TYPE A POWER CABLE

(1) CISCO 50CM TYPE 1 STACKING CABLE

(1) CISCO UNIVERSAL POWER SUPPLY

(1) VIEWSONIC 43 FULL HD COMMERCIAL DISPLAY, 1920X1080

(1) CHEIF LARGE HEIGHT ADJUSTABLE TILT WALL MOUNT - 37"-63"

(1) PELCO WORKSTATION W/WS5200 SW

(1) PELCO NETWORK STORAGE MANAGER, 24TB

(1) APC 2200VA RM 2U LCD 120V SMART UPS

g.

PROVIDE NEW ADDRESSABLE OUTPUT

MODULES WHERE INDICATED.

1.

a.

2.

b.

c.

d.

e.

f.

MAKE ALL CONNECTIONS AS REQUIRED.

PROVIDE ALL REQUIRED PROGRAMMING.

REFER TO ELECTRICAL DRAWINGS FOR QUANTITIES

AND LOCATIONS OF WIRELESS PUBLIC ADDRESS

DEVICES.

VISIPLEX WIRELESS

PUBLIC ADDRESS

SYSTEM NOTES

MODIFY THE EXISTING VISIPLEX WIRELESS

PUBLIC ADRESS SYSTEM TO ACCOMMODATE

THE NEW DEVICES INDICATED. PROVIDE ALL

POWER SUPPLIES AND OTHER ACCESSORIES

FOR A COMPLETE AND OPERATIONAL SYSTEM.

PROVIDE NEW BASE STATIONS WITH

HANDSET, INTEGRAL 6 WATT TRANSMITTER

AND ANTENNA WHERE INDICATED.

PROVIDE NEW CEILING MOUNTED

WIRELESS SPEAKERS WITH RECEIVER

AND POWER CORD WHERE INDICATED.

PROVIDE ABOVE CEILING POWER OUTLETS

WHERE INDICATED.

PROVIDE NEC COMPLIANT CLASS 2, 12V DC

POWER SUPPLIES COMPATIBLE WITH SPEAKER

RECEIVER AT EACH SPEAKER LOCATION.

NACP FIRE ALARM NOTIFICATION APPLIANCE CONTROL PANEL (N.A.C. PANEL)

a DIMMER SWITCH - 3 INDICATES 3-WAY - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE -

SUBLETTER INDICATES SWITCH CONTROL

WIRELESS ACCESS POINT (WIFI)

WALL PHONE OUTLET - MOUNTED 5' AFF.

CONTRACTOR SHALL PROVIDE AND INSTALL FIVE

24-PORT PATCH PANELS IN EXISTING RACK IN EXISTING

O.R. ADDITION TELE/DATA ROOM 12L. pATCH PANELS

SHALL BE ORTRONICS CATALOG #PHD66U24.

CONTRACTOR SHALL PROVIDE, INSTALL AND TERMINATE

(1) CAT 6 CABLE FROM WIRELESS ACCESS POINT TO

PATCH PANEL IN O.R. ADDITION, BASEMENT LEVEL,

TELE/DATA RM 12L. PROVIDE AND INSTALL (1) BISCUIT

JACK IN CEIILING AT EACH WIRELESS ACCESS POINT.

CAT 6 CABLE SHALL BE CERTIFIED BY CONTRACTOR.

COORDINATE EXACT MOUNTING REQUIREMENTS WITH

VAMC I.T. STAFF. VAMC WILL PROVIDE WIRELESS

ACCESS POINTS.

MODIFY THE EXISTING NOTIFIER NFS2-3030 MAIN FIRE

ALARM CONTROL PANEL TO ACCOMMODATE THE NEW

DEVICES INDICATED. NEW CONTACTS, NOTIFICATION

APPLIANCE CIRCUIT POWER SUPPLY CABINETS AND ALL

OTHER ACCESSORIES FOR A COMPLETE AND

OPERATIONAL SYSTEM.

4.

ALL FIRE ALARM DEVICES SHALL BE PURCHASED FROM

FSI, FIRE SYSTEMS INC.. CONTACT PAULA CASEY. PHONE

NUMBER (508) 999-4444 EXT. 204.

ALL WORK ON THE NEW AND EXISTING FIRE ALARM

SYSTEM SHALL BE DONE BY WYMAN & SONS ELECTRIC.

CONTACT DAVID WYMAN (401) 737-0032. THIS

CONTRACTOR SHALL CONTRACT WITH WYMAN &

SONS ELECTRIC FOR ALL REQUIRED FIRE ALARM

SYSTEM WORK.

NO NEW CENTRAK DEVICES SHALL BE INSTALLED AS PART

OF THIS PROJECT.

EXISTING CENTRAK TRACKING EQUIPMENT INDICATED TO

REMAIN SHALL BE MAINTAINED AND KEPT INTACT. ALL

EXISTING CENTRAK EQUIPMENT CABLING SHALL NOT BE

DEMOLISHED AS PART OF THIS PROJECT. ALL CENTRAK

DEVICES INDICATED TO BE DEMOLISHED SHALL BE REMOVED

BY VAMC CLINICAL ENGINEERING DEPARTMENT PRIOR TO

DEMOLITION. COORDINATE DEMOLITION SCHEDULE WITH

VAMC CLINICAL ENGINEERING DEPARTMENT AS REQUIRED.

EXISTING CENTRAK CABLING SHALL BE TAGGED/

MARKED AND PROTECTED DURING DEMOLITION AND

CONTRUCTION OF CLEAN CORE SCOPE OF WORK.

COORDINATE CENTRAK CABLE MARKING/TAGGING AND

PROTECTION WITH VAMC CLINICAL ENGIEERING DEPARTMENT

AS REQUIRED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F il e P a th

/1

/2

:3

:0

P

M

Office of

Construction and Facilities

Management of Veterans Affairs

U.S. Department

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date:

Auburn, ME

207.784.5100

Boston, MA

617.426.5050

Portland, ME

207.775.0053

Portsmouth, NH

603.626.1242 c

HA PROJECT NUMBER: 13586

PROVIDENCE, RHODE ISLAND

02-22-19

650-337

SPRINKLERED

SURGICAL SUITE

CONSTRUCT CLEAN CORE ADDITION TO

DOCUMENTS

FINAL CONSTRUCTION

E00.1

JWT APG

AND NOTES

ELECTRICAL LEGEND

LAMPS, HANGERS, FITTINGS, ETC. FOR A COMPLETE AND PROPER INSTALLATION

ALL FIXTURES SHALL BE FURNISHED COMPLETE WITH ALL HARDWARE

LIGHTING FIXTURE SCHEDULE

TYPE MANUFACTURER CATALOG NO. MTG. VOLT

NO. WATT

LAMPS

TYPE

REMARKS/BALLAST INFORMATION

LEDUNVR

A

LED

LEDUNVF

K

32.2LEDUNVR

B1

12.5LEDUNVS

F

LED LITHONIA

1LED120/277R

E

TLE-2-RLITHONIA

LED PROVIDE FACES AND CHEVRONS AS INDICATEDTLE-1-RLITHONIA

RECESSED MOUNT SINGLE OR DOUBLE FACED LED EXIT SIGN

24.9LEDUNVF

150LED120R

C

LED120R

D

KENALL

2'x2' LED RECESSED OPERATING ROOM LIGHT FIXTURE

KENALL M4SEDI-22-76LL-40K8-DCC-120-2F-2H-SYM

LITHONIA

LITHONIA

LITHONIA

LITHONIA

LITHONIA

28LEDF

G LED

M4DL4-DCFW-28L-40K9-FW-RIS4-120-DIM1

L

150LED120R

C1

LED KENALL

2'x4' LED RECESSED OPERATING ROOM LIGHT FIXTURE WITH EMERGENCY BATTERY PACK

24.9LEDUNVF

LED LITHONIAL1

M4SEDI-24-150L-40K8-DCC-120-2F-2H-SYM-2C

M4SEDI-24-150L-40K8-DCC-120-2F-2H-SYM-2C-LEL

2'x4' LED RECESSED OPERATING ROOM LIGHT FIXTURE, 2-CIRCUIT

K1

LEDR

H LED

6" LED DOWNLIGHT

18.5

EVO-40-15-6AR-LSS-PPC-MVOLT-GZ10GOTHAM

GRADE

TAPE 12" BELOW GRADE

PLASTIC "ELECTRIC" MARKER

CONCRETE ENCASEMENT

A B

TYPICAL DUCTBANK CONSTRUCTION

SCALE: NO SCALE

DUCTBANK SECTION

SCALE: NO SCALE

* CABLE AMPACITIES ARE BASED ON A MAXIMUM BURIAL DEPTH OF 30" UNLESS

OTHERWISE INDICATED, EXCEPT THAT 25% OF THE LENGTH MAY BE DEEPER TO AVOID

OBSTRUCTIONS OR ENTER A STRUCTURE. ELECTRICAL CONTRACTOR SHALL CONSTRUCT

DUCTBANK TO MEET THESE CONDITIONS. WHERE CONDITIONS DO NOT ALLOW, ELECTRICAL

CONTRACTOR SHALL DE-RATE CONDUCTORS FOR DEEPER BURIAL DEPTHS PER NEC.

BURIAL DEPTHS

MINIMUM - PER NEC TABLE 300.50

MAXIMUM - 30 INCHES (SEE BELOW)

CSP

P P

REF:

A2

LIGHT FIXTURE SCHEDULE DETAILS

LEGEND:

SP - 4" SPARE CONDUIT

P - 4" POWER CONDUIT

C - 4" COMMUNICATION CONDUIT - GENERATOR START AND ANNUNCIATOR CIRCUITING

CONCRETE ENCASED

P P

P P

E00.2 E00.2

LEDC

J LED

LITHONIA

1'x4' LED INDUSTRIAL STRIP LIGHT WITH LENS - CHAIN HUNG

ZL1N-L48-3000LM-FST-MVOLT-40K-80CRI-WH-HC36

4000K COLOR TEMPERATURE

4000K COLOR TEMPERATURE

4000K COLOR TEMPERATURE

4000K COLOR TEMPERATURE

4000K COLOR TEMPERATURE

4000K COLOR TEMPERATURE

4000K COLOR TEMPERATURE

4000K COLOR TEMPERATURE

4000K COLOR TEMPERATURE

4000K COLOR TEMPERATURE

4000K COLOR TEMPERATURE

2'x2' LED RECESSED LIGHT FIXTURE - FLANGE MOUNT

2'x2' LED RECESSED LIGHT FIXTURE WITH BATTERY PACK- FLANGE MOUNT

2'x4' LED RECESSED LIGHT FIXTURE - FLANGE MOUNT

SAME AS TYPE A2 EXCEPT WITH EMERGENCY BATTERY PACK - FLANGE MOUNT

2'x2' LED RECESSED LIGHT FIXTURE WITH BATTERY PACK

32.2LEDUNVR

B

2'x2' LED RECESSED LIGHT FIXTURE

2TL2-33L-FW-A12-EZ1-LP840-ABC GASKET-DGA22

2TL2-33L-FW-A12-EZ1-LP840-EL14L-ABC GASKET-DGA22

LEDUNVR

A2

SURGICAL LED DOWNLIGHT - FLANGE MOUNT

2'x4' LED RECESSED FLAT PANEL LIGHT FIXTURE

2'x4' LED RECESSED FLAT PANEL LIGHT FIXTURE - FLANGE MOUNT

2'x4' LED RECESSED FLAT PANEL LIGHT FIXTURE

EPANL-2X4-4000LM-80CRI-40K-MIN10-2T-MVOLT- DGA24

EPANL-2X2-3400LM-80CRI-35K-MIN10-2T-MVOLT- E10WCP

UCLD-24IN-40K-90CRI-WH-UCD JB-UC PIR M12

UNDER-CABINET LIGHT FIXTURE WITH MOTION SENSOR SWITCHING

EPANL-2X4-4000LM-80CRI-40K-MIN10-2T-MVOLT

EPANL-2X4-4000LM-80CRI-35K-MIN10-2T-MVOLT

EPANL-2X2-3400LM-80CRI-35K-MIN10-2T-MVOLT

2TL4-60L-FW-A12-EZ1-LP840-EL14L-ABC GASKET-DGA24

2TL4-60L-FW-A12-EZ1-LP840-ABC GASKET - DGA24

KENALL

4000K COLOR TEMPERATURE

CONTRACTOR TO PROVIDE NEOPRENE

GASKETING BETWEEN FIXTURE AND CEILING

GASKETING BETWEEN FIXTURE AND CEILING

CONTRACTOR TO PROVIDE NEOPRENE

4000K COLOR TEMPERATURE

GASKETING BETWEEN FIXTURE AND CEILING

CONTRACTOR TO PROVIDE NEOPRENE

3500K COLOR TEMPERATURE

GASKETING BETWEEN FIXTURE AND CEILING

CONTRACTOR TO PROVIDE NEOPRENE

3500K COLOR TEMPERATURE

GASKETING BETWEEN FIXTURE AND CEILING

CONTRACTOR TO PROVIDE NEOPRENE

3500K COLOR TEMPERATURE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F il e P a th

/1

/2

:3

:0

P

M

Office of

Construction and Facilities

Management of Veterans Affairs

U.S. Department

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date:

Auburn, ME

207.784.5100

Boston, MA

617.426.5050

Portland, ME

207.775.0053

Portsmouth, NH

603.626.1242 c

HA PROJECT NUMBER: 13586

PROVIDENCE, RHODE ISLAND

02-22-19

650-337

SPRINKLERED

SURGICAL SUITE

CONSTRUCT CLEAN CORE ADDITION TO

DOCUMENTS

FINAL CONSTRUCTION

E00.2

JWT APG

FIXTURE SCHEDULE AND DETAILS

ELECTRICAL LIGHTING

DP-N-OR

EQ-2-OR

LS-2-OR

CB-2A-OR

DP-CB-OR-2

DP-CB-OR-1

CB-2B-OR

C R

W

C T R

OC OC

WP

G F I

G F I

G F I

G F I

OC

CTR

CTR

CTR

CTR

CTR

OC OC

J

POWERED FURNITURE

OC

W

OC

G F I

GFI

GFI

C T R

C T R

C T R

C T R

R E X

OC

S

S

V

J

DOOR

C T

R

OC

S

J

DOOR

R E X

MGAP

C T R

IPU-E-CYSTO

C B

C R

C T R

C T R

ENCLOSED BREAKER

J

SINK

CEILING MTD.

J

TIMER

TIMER RESET STATION

EQUIPMENT WHIP CONNECTIONS

NURSE CALL C.P.

(XRE)(XRE)(XRE) (XRE)

LEGEND:

EXISTING EQUIPMENT TO BE DEMOLISHED IS INDICATED AS BOLD AND DASHED:

EXISTING EQUIPMENT TO REMAIN IS INDICATED AS LIGHT AND DASHED:

EXISTING EQUIPMENT TO BE BE MODIFIED IS INDICATED AS BOLD AND DASHED WITH TEXT ADJACENT:

(XRE)

(XRE)

(XRE)DEMOLITION NOTES:

VISIPLEX BASE STATION

N-L-2-OR

S

S

S

S

(XRE)

(XRE)

S

OC

S

SECURITY SYSTEM CONTROL PANEL

BSSP

(XRE)

C R

BOOM WITH POWER, AND DATA OUTLETS

J

DOOR

CTR

F

W

S

REX

CTR

J

DOOR

S

W

PHASE 2A

DEMOLISH EXISTING ELECTRICAL DEVICES IN THIS AREA UNDER PHASE 2B

REFER TO ARCHITECTURAL DRAWINGS FOR TEMPORARY WALL LOCATIONS

TEMPORARY WALLS TO BE CONSTRUCTED DURING PHASE 2A

ELECTRICAL DEVICES IN THIS AREA TO REMAIN IN PLACE DURING PHASE 2A

1. ELECTRICAL INDICATED IS AS GENERALLY FOUND (APRIL

2017). THE INTENT OF THE EXISTING CONDITIONS PLAN(S) IS TO

DOCUMENT EXISTING CONDITIONS. HOWEVER, ALL ELECTRICAL

DEVICES MAY NOT NECESSARILY BE INDICATED ON THE

DRAWINGS. FIELD VERIFY AND ADJUST WORK TO SUIT ALL FOUND.

2. REFER TO THIS EXISTING CONDITION PLAN AND LIGHTING

POWER, AND SIGNAL PLAN TO DETERMINE EXTENT OF WORK

IN EACH AREA, INCLUDING WHETHER DEVICES ARE TO REMAIN,

BE REMOVED, REPLACED, ETC... EXCEPT AS NOTED, GENERALLY

THE INTENT IS THAT IF EXISTING DEVICES ARE SHOWN ON THE EXISTING

CONDITIONS PLANS AND NEW DEVICES ARE SHOWN ON THE FLOOR

PLANS THEN EXISTING DEVICES ARE TO BE REMOVED. IF EXISTING

DEVICES ARE SHOWN ON BOTH THEN DEVICES ARE TO REMAIN.

3. ALL EXISTING ITEMS INTENDED FOR REMOVAL SHALL BE REMOVED

WITH ALL ASSOCIATED HARDWARE INCLUDING, BUT NOT LIMITED TO:

CONDUIT, BOXES, WIRING, CABLES, HANGERS, ETC...

4. COORDINATE WITH MECHANICAL AND PLUMBING DRAWINGS FOR

MECHANICAL AND PLUMBING EQUIPMENT TO BE REMOVED. REMOVE

ALL ASSOCIATED CONDUIT, BOXES, WIRING, ETC...

5. CONDUIT IN GOOD CONDITION AND PROPERLY LOCATED MAY BE

REUSED WHERE APPLICABLE, UNLESS NOTED OTHERWISE.

6. IN AREAS NOT RENOVATED BY THIS CONTRACT VERIFY THAT

ELECTRICAL POWER, LIGHTING AND SYSTEMS ARE NOT AFFECTED

BY THE ALTERATIONS. PROVIDE ALL WORK AS REQUIRED TO

MAINTAIN POWER AND PROPER OPERATION OF SYSTEMS.

7. EXISTING CENTRAK TRACKING EQUIPMENT INDICATED TO

REMAIN SHALL BE MAINTAINED AND KEPT INTACT. ALL

EXISTING CENTRAK EQUIPMENT CABLING SHALL NOT BE

DEMOLISHED AS PART OF THIS PROJECT. ALL CENTRAK

DEVICES INDICATED TO BE DEMOLISHED SHALL BE REMOVED

BY VAMC CLINICAL ENGINEERING DEPARTMENT PRIOR TO

DEMOLITION. COORDINATE DEMOLITION SCHEDULE WITH

VAMC CLINICAL ENGINEERING DEPARTMENT AS REQUIRED.

EXISTING CENTRAK CABLING SHALL BE TAGGED/

MARKED AND PROTECTED DURING DEMOLITION AND

CONTRUCTION OF CLEAN CORE SCOPE OF WORK.

COORDINATE CENTRAK CABLE MARKING/TAGGING AND

PROTECTION WITH VAMC CLINICAL ENGIEERING DEPARTMENT

AS REQUIRED.

8. WIRELESS ACCESS POINT DEVICES SHALL BE REMOVED AND STORED BY VAMC INFORMATION

TECHNOLOGY DEPARTMENT. CLEAN CORE RENOVATION PROJECT SHALL PROVIDE AND INSTALL

NEW CAT 6 CABLING TO ALL NEW WIRELESS ACCESS POINT EQUIPMENT LOCATIONS. VAMC INFORMATION

TECHNOLOGY DEPARTMENT SHALL INSTALL WIRELESS ACCESS POINT DEVICES IN NEW LOCATIONS.

9. PRIOR TO DEMOLISHING DATA CABLING, COORDINATE WITH VAMC I.T. STAFF TO DETERMINE IF

EXISTING CABLING CAN BE REUSED. ALL CABLING THAT CAN NOT BE REUSED SHALL BE DEMOLISHED

BACK TO I.T. CLOSET AND REMOVEDFROM PATCH PANELS. ALL NEW CABLING SHALL MEET REQUIREMENTS

OF ELECTRICAL SPECIFICATION SECTION 270513, VAMC PROVIDENCE RI TELE/DATA CABLING STANDARDS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F il e P a th

/1

/2

:3

:0

P

M

Office of

Construction and Facilities

Management of Veterans Affairs

U.S. Department

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date:

Auburn, ME

207.784.5100

Boston, MA

617.426.5050

Portland, ME

207.775.0053

Portsmouth, NH

603.626.1242 c

HA PROJECT NUMBER: 13586

PROVIDENCE, RHODE ISLAND

02-22-19

650-337

SPRINKLERED

SURGICAL SUITE

CONSTRUCT CLEAN CORE ADDITION TO

DOCUMENTS

FINAL CONSTRUCTION

E05.1

APGJWT

EXISTING CONDITIONS

SECOND FLOOR PART PLAN

1/8" = 1'-0"

0 4' 8' 12'

0.5

1.8 2.2 2.5 3 4 5 6 7

G.4'

E4.8

E5

ED

A.5

A.5'

A

3'

B

C.3

D.3

C.5

B' C' D' E' F'

F

F.7' G'

H

D

E E.1

E4

G.3'

4.8'

C

G.5'

4.75'

4.7'

4.5'

4' 4'

4.3' 4.3'

L

EA.1

K

J

EBB

G

F.9

2'

A.6'

1'

252632

52 53

SEE A72.4 FOR EQUIPMENT SCHEDULE.

18 15 28 27 45 16

5'

CLEAN AND STERILE

SUPPLY

EQUIPMENT STORAGE

MECHANICAL

CYSTOSCOPY

SEMI RESTRICTED

CORRIDOR

CLEAN CORE

FUTURE CLEAN EL.

A-EL-3

FUTURE CLEAN EL.

A-EL-2

CLEAN AND STERILE

SUPPLY

CC STORAGE

255A

NURSE MANAGER

OFFICE

ELEC. CL.

SOILED UTILITY

IUSS

ANESTHESIA

WORKROOM

EQUIPMENT STORAGE

WORK AREA

CONTROL STATION

MALE LOCKERS

ANGIOPLASTY

OR-1

OR-2

OR-3

HOUSE KEEPING

215G

FEMALE LOCKERS

CONSULT ROOM

TOILET

202A

MINOR PROCEDURE

OR STORAGE

PATIENT TOILET

215F

PATIENT LOCKERS

215E

VESTIBULE

215D

CLEAN UTILITIES

215C

SOILED UTILITIES

215B

SEMI RESTRICTED

CORRIDOR

STAIR WELL

A-2

ELECTRICAL CLOSET

HOUSE KEEPING

232A

ELEC

232C

ELEC

232D

INTERVENTIONAL PAIN

MANAGEMENT

233A

ELECTRICAL ROOM

201C

EMERGENCY

ELECTRICAL ROOM

201B

ELEVATOR LOBBY

L23

LINEN CHUTE

IT CLOSET

229A

ELECTRICAL CLOSET

CORRIDOR

2-DC-1A

SEMI RESTRICTED

CORRIDOR

EXAM-1

E205

EXAM-2

E206

OFFICE

CORRIDOR

BRONCHOSCOPY

Room

4ZZ

Room

4AAA

Room

4BBB

Room

4CCC

Room

4DDD

SCRUB

210A

SCRUB

210B

OR ACCESS VESTIBULE

OR ACCESS VESTIBULE

OBSERVATION ROOM

PACU

NURSE STATION

PATIENT TOILET

215A

CORRIDOR

C223

STAIR-K

K-2

STAFF TOILET/SHOWER

SEMI RESTRICTED

CORRIDOR

LINK CORRIDOR

L24

MICROSCOPE

E207

EXAM-3

E208

CAST ROOM

E204

CORRIDOR

C22

ELEVATOR LOBBY

L21

CORRIDOR

C21

LOBBY

L22

ELEVATOR

E-EL-2

ELEVATOR

E-EL-1

OR RECEPTION

WAITING ROOM

OFFICE

201A

FUTURE SOILED

ELEVATOR

A-EL-1

DP-N-OR

EQ-2-OR

LS-2-OR

CB-2A-OR

DP-CB-OR-2

DP-CB-OR-1

CB-2B-OR

OC OC

OC

OC

OC

N-L-2-OR

OC

A

3'

2'

MALE LOCKERS

CORRIDOR

C223

SEE DRAWING E40.1 FOR

1/4" SCALE CYSTOSCOPY

PART PLAN

K1

K

K1

K

L1

G

G

G

G a b a a b a

A

A

A

A AL1 L1 L1

J

OC

B

A

A

A1 A1A1A1A1A1A1

A2

A2

OC

A

A

OC

OC

A

OC

A1

A1

A1

OCOC

OCOC

OC

A1 A1A1 A1

A1

A1

A1

A1

A1

OC

OC

A1A1

OC

F

A1 A1

OC

A

A

OC

OC

A

A

A

OC

OC

B

A2 A2

A2

A

OC

(EN)

OC

(EN)

E E

E

E

E

E

E

E

E

E

E

E

E

E

21 21 21 21

NLNL

NL

NLNL

NL

NL

NL

NL

NL

NL

NL

E

E

LS-2-OR#21

L01 PROVIDE AND INSTALL (1) 20A, 1-POLE BREAKER IN EXISTING SPACE 21.

NEW BREAKER SHALL MATCH EXISTING TYPE INCLUDING AIC RATING.

L01

1 1

1 1

21 1 21 1

1 21 21

4 4 4

OC

OC

OC

OC A

A

A

A2

A2

B1

A1

A1 A1A1

A

21NL

1 ab a a a bb b

L

L02 RECIRCUIT EXISTING LIGHT FIXTURE TO BE CONTROLLED ONLY BY EXISTING OCCUPANCY SENSOR.

L02 L02

NL

B1 B1

B1B1B1

N-2-CC#3

N-2-CC

L03 CIRCUIT LIGHT FIXTURE TO EXISTING LIGHTING CIRCUIT SERVING THE CORRIDOR.

L03 L03

OC

N-2-CC#3

CB-2-CC#2

b b b a a a

CB-2-CC#4

OC

B1 B1

B1B1

B1B1

4 4

PHASE 5

PHASE 7

DEMOLISH ALL PHASE 5 ELECTRICAL DEVICES TO ACCOMMODATE NEW PHASE 7 ELECTRICAL DEVICES.L04

L04

H H

(UNISTRUT MOUNTED)

CB-2-CC

PHASING NOTES:

1. REFER TO ARCHITECTURAL DRAWINGS A01.1 AND A01.2

FOR PROJECT PHASING AND ADDITIONAL PHASING NOTES.

J J J

JJJJ

F

F

F

F a aac c c a a a b b bb b b d c c d d d d c c

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F il e P a th

/1

/2

:3

:0

P

M

Office of

Construction and Facilities

Management of Veterans Affairs

U.S. Department

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date:

Auburn, ME

207.784.5100

Boston, MA

617.426.5050

Portland, ME

207.775.0053

Portsmouth, NH

603.626.1242 c

HA PROJECT NUMBER: 13586

PROVIDENCE, RHODE ISLAND

02-22-19

650-337

SPRINKLERED

SURGICAL SUITE

CONSTRUCT CLEAN CORE ADDITION TO

DOCUMENTS

FINAL CONSTRUCTION

E10.1

APGJWT

LIGHTING

SECOND FLOOR PART PLAN

1.8 2.2 2.5 3 4 5 6 7

G.4'

E4.8

E5

ED

A.5

A.5'

A

3'

B

C.3

D.3

C.5

B' C' D' E' F'

F

F.7' G'

H

D

E E.1

E4

G.3'

4.8'

C

G.5'

4.75'

4.7'

4.5'

4' 4'

4.3' 4.3'

L

EA.1

K

J

EBB

G

F.9

2'

A.6'

1'

5'

CLEAN AND STERILE

SUPPLY

EQUIPMENT STORAGE

MECHANICAL

CYSTOSCOPY

SEMI RESTRICTED

CORRIDOR

CLEAN CORE

FUTURE CLEAN EL.

A-EL-3

FUTURE CLEAN EL.

A-EL-2

CLEAN AND STERILE

SUPPLY

CC STORAGE

255A

NURSE MANAGER

OFFICE

ELEC. CL.

SOILED UTILITY

IUSS

ANESTHESIA

WORKROOM

EQUIPMENT STORAGE

WORK AREA

CONTROL STATION

MALE LOCKERS

ANGIOPLASTY

OR-1

OR-2

OR-3

HOUSE KEEPING

215G

FEMALE LOCKERS

CONSULT ROOM

TOILET

202A

MINOR PROCEDURE

OR STORAGE

PATIENT TOILET

215F

PATIENT LOCKERS

215E

VESTIBULE

215D

CLEAN UTILITIES

215C

SOILED UTILITIES

215B

SEMI RESTRICTED

CORRIDOR

STAIR WELL

A-2

ELECTRICAL CLOSET

HOUSE KEEPING

232A

ELEC

232C

ELEC

232D

INTERVENTIONAL PAIN

MANAGEMENT

233A

ELECTRICAL ROOM

201C

EMERGENCY

ELECTRICAL ROOM

201B

ELEVATOR LOBBY

L23

LINEN CHUTE

IT CLOSET

229A

ELECTRICAL CLOSET

CORRIDOR

2-DC-1A

SEMI RESTRICTED

CORRIDOR

EXAM-1

E205

EXAM-2

E206

OFFICE

CORRIDOR

BRONCHOSCOPY

Room

4ZZ

Room

4AAA

Room

4BBB

Room

4CCC

Room

4DDD

SCRUB

210A

SCRUB

210B

OR ACCESS VESTIBULE

OR ACCESS VESTIBULE

OBSERVATION ROOM

PACU

NURSE STATION

PATIENT TOILET

215A

CORRIDOR

C223

STAIR-K

K-2

STAFF TOILET/SHOWER

SEMI RESTRICTED

CORRIDOR

LINK CORRIDOR

L24

MICROSCOPE

E207

EXAM-3

E208

CAST ROOM

E204

CORRIDOR

C22

ELEVATOR LOBBY

L21

CORRIDOR

C21

LOBBY

L22

ELEVATOR

E-EL-2

ELEVATOR

E-EL-1

OR RECEPTION

WAITING ROOM

OFFICE

201A

FUTURE SOILED

ELEVATOR

A-EL-1

DP-N-OR

EQ-2-OR

LS-2-OR

CB-2A-OR

DP-CB-OR-2

DP-CB-OR-1

CB-2B-OR

G F I

G F I

G F I

G F I

J

DOOR

N-L-2-OR

J

DOOR

J

DOOR

PHASE 2A

DEMOLISH EXISTING ELECTRICAL DEVICES IN THIS AREA UNDER PHASE 2B

REFER TO ARCHITECTURAL DRAWINGS FOR TEMPORARY WALL LOCATIONS

TEMPORARY WALLS TO BE CONSTRUCTED DURING PHASE 2A

ELECTRICAL DEVICES IN THIS AREA TO REMAIN IN PLACE DURING PHASE 2A

MALE LOCKERS

SEE DRAWING E40.1 FOR

1/4" SCALE CYSTOSCOPY

PART PLAN

(EN)

(EN)

(EN)

(EN)

J

MGAP

G F

ISINK

SINK

SINK

SINK

G

F I

W

J

J

P01

P01

J JRCPTS.

GROUNDING LOOP.

TO LIGHTING PROTECTION SYSTEM

FROM BOTTOM OF STRUCTURAL COLUMN

PROVIDE LIGHTNING PROTECTION SYSTEM

GROUND ROD

GROUND RODGROUND ROD

GROUND ROD

GROUND ROD

GROUNDING LOOP.

TO LIGHTING PROTECTION SYSTEM

FROM BOTTOM OF STRUCTURAL COLUMN

PROVIDE LIGHTNING PROTECTION SYSTEM

GROUNDING LOOP.

TO LIGHTING PROTECTION SYSTEM

FROM BOTTOM OF STRUCTURAL COLUMN

PROVIDE LIGHTNING PROTECTION SYSTEM

SYSTEM GROUNDING LOOP.

TO LIGHTING PROTECTION

STRUCTURAL COLUMN

FROM BOTTOM OF

PROTECTION SYSTEM

PROVIDE LIGHTNING

SYSTEM GROUNDING LOOP.

TO LIGHTING PROTECTION

STRUCTURAL COLUMN

FROM BOTTOM OF

PROTECTION SYSTEM

PROVIDE LIGHTNING

BUILDING ADDITION.

SYSTEM GROUNDING LOOP AROUND

EXTEND EXISTING LIGHTNING PROTECTION

CONDUCTOR SIZE AND MATERIAL

SHALL MATCH EXISTING GROUND LOOP

NEW GROUND LOOP CONDUCTOR

PROTECTION SYSTEM GROUNDING LOOP.

CONNECT TO EXISTING LIGHTNING

PROTECTION SYSTEM GROUNDING LOOP.

CONNECT TO EXISTING LIGHTNING

G F I

GFI

G F I

J

DOOR

J

DOOR

J

DOOR

IPU-N-CYSTO

NEW PANEL

IPU-E-CYSTO1

NEW PANEL CRASH CART

P03

P03

LS-2-OR#23

LS-2-OR#25

LIGHTS

P02 CIRCUIT TO NORMAL LIGHTING CIRCUIT SERVING THE ROOM.

P02

TEMPORARY LIGHTNING PROTECTION SYSTEM GROUND ROD DURING CONSTRUCTION.

EXTEND EXISTING DOWN CONDUCTORS FROM WING A AND O.R. ADDITION AS REQUIRED.

P04

P05

P04 P04

IPU-E-CYSTO2

NEW PANEL

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

MGAP

J

FREEZER

SPEAKER

SPEAKER SPEAKER

P06 PROVIDE CONNECTION TO EXISTING PEGASYS SYSTEM FOR TEMPERATURE ALARM.

P06

J

DOOR

J

DOOR

PP

PP

PP

PP

PP

SPEAKER

1 1 1

3 3 3

CB-2-CC#1

CB-2-CC#3

N-2-CC#2

PHASE 7

PHASE 5N-2-CC#2

CB-2-CC#1

CB-2-CC#3

P07 DEMOLISH ALL PHASE 5 ELECTRICAL DEVICES TO ACCOMMODATE NEW PHASE 7 ELECTRICAL DEVICES.

P07

CB-2-CC#5

N-2-CC#5

7 7 7 79 9 9 911 13 11 13 11 13 11 13 7

N-2-CC#9

N-2-CC#7

N-2-CC#13

N-2-CC#11

N-2-CC#15

N-2-CC#4

N-2-CC#6

N-2-CC#8

N-2-CC#10

STERILIZER

12 N-2-CC#12

G F I

CB-2-CC#7

N-2-CC

G F I

G F I

CB-2-CC#9

CB-2-CC#13

CB-2-CC#15

CB-2-CC#17

PUMP

PUMP

G F I

J

CB-2-CC#18

N-2-CC#19

CB-2-CC#16

CB-2-CC#14

CB-2-CC#6,8

CB-2-CC#10,12

N-2-CC#23,25

N-2-CC#21

LS-2-OR#27

P08

P09

MONITOR BOOM WITH (2) VIDEO MONITORS, (2) VIDEO OUTLETS AND (2) DUPLEX OUTLETS.

P08

P09

11 11

11 CB-2-CC#11

11 11

N-2-CC#14

N-2-CC#16

N-2-CC#18

(UNISTRUT MOUNTED)

CB-2-CC

PROVIDE AND INSTALL (3) 20A, 1-POLE BREAKERS IN EXISTING SPACE 23,25 FOR MOTORIZED DOORS AND 27 FOR (2) MGAP.

NEW BREAKER SHALL MATCH EXISTING TYPE INCLUDING AIC RATING.

PHASING NOTES:

1. REFER TO ARCHITECTURAL DRAWINGS A01.1 AND A01.2

FOR PROJECT PHASING AND ADDITIONAL PHASING NOTES.

G F I

G F I

G F I 9

G F I

DP1-EQ-CC#13,15,17 DP1-EQ-CC#7,9,11

REFER TO RISER DIAGRAM ON DRAWING E50.1 FOR FEEDER SIZE.

7.5 5

7.5 5

J

J

J

J

J

J

J

N-2-CC#24

SMOKE DAMPER

SMOKE DAMPER

SMOKE DAMPER

UTILITY BOOM WITH (2) CRITICAL QUAD OUTLETS, (2) NORMAL QUAD OUTLETS AND (2) DATA QUAD OUTLETS.

ALL POWER OUTLETS IN EQUIPMENT STORAGE ROOM 254 SHALL BE MOUNTED AT 36" AFF.

P05

P05

P10 MOUNT POWER OUTLET AT 30" AFF.

P10

P11 MOUNT POWER OUTLET AT 6" ABOVE COUNTER HEIGHT.

P10 P10 P10 P10 P10 P10 P10 P10

P11

P11

P11

P12 MOUNT POWER OUTLET AND DATA OUTLET AT AT 4'-6" AFF..

P12

P12

P12

P10

P10P10P10P10P10P10P10

N-2-CC#2424

SINK

SINK

AIR HANDLER 12B001

J

NAC PANEL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F il e P a th

/1

/2

:3

:0

P

M

Office of

Construction and Facilities

Management of Veterans Affairs

U.S. Department

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date:

Auburn, ME

207.784.5100

Boston, MA

617.426.5050

Portland, ME

207.775.0053

Portsmouth, NH

603.626.1242 c

HA PROJECT NUMBER: 13586

PROVIDENCE, RHODE ISLAND

02-22-19

650-337

SPRINKLERED

SURGICAL SUITE

CONSTRUCT CLEAN CORE ADDITION TO

DOCUMENTS

FINAL CONSTRUCTION

E20.1

APGJWT

POWER

SECOND FLOOR PART PLAN

1.5

1.5

1.8 2.2 4 5 6 7 8

G.4'

E4.8

E5

ED

EB.3

A.5

A

3'

B

C.3

D.3

C.5

B' C' D' E' F'

F

F.7' G'

H

D

E

E.1

G.3'

4.8'

C

G.5'

4.75'

4.75'

4.7' 4.7'

4.5'

4.5'

4'

4'

4.3'

L

EA.1

K

J

EBB

G

F.9

2'

A.6'

1'

5'

N

LIGHTINING PROTECTION SYSTEM PRESENTLY INSTALLED ON THE O.R. ADDITION

CONNECT NEW LIGHTNING PROTECTION SYSTEM AIR TERMINALS TO EXISTING

W P

G F I

B-EQ-CC#13

N-2-CC#20

J

2#10+1#10G

IN 3/4"C

EF-13B001

EXHAUST FAN

BRONCOSCOPY

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F il e P a th

/1

/2

:3

:0

P

M

Office of

Construction and Facilities

Management of Veterans Affairs

U.S. Department

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date:

Auburn, ME

207.784.5100

Boston, MA

617.426.5050

Portland, ME

207.775.0053

Portsmouth, NH

603.626.1242 c

HA PROJECT NUMBER: 13586

PROVIDENCE, RHODE ISLAND

02-22-19

650-337

SPRINKLERED

SURGICAL SUITE

CONSTRUCT CLEAN CORE ADDITION TO

DOCUMENTS

FINAL CONSTRUCTION

E20.2

APGJWT

POWER

ROOF PART PLAN

1.8 2.2 2.5 3 4 5 6 7

G.4'

E4.8

E5

ED

A.5

A.5'

A.5'

A

3'

B

A' A.2'

C.3

D.3

C.5

B' C' D' E' F'

F

F.7' G'

H

D

E E.1

E4

G.3'

4.8'

C

G.5'

4.75'

4.7'

4.5'

4' 4'

4.3' 4.3'

L

EA.1

J

EBB

G

F.9

2'

A.6'

1'

252632

52 53

SEE A72.4 FOR EQUIPMENT SCHEDULE.

18 15 28 27 45 16

5'

CLEAN AND STERILE

SUPPLY

EQUIPMENT STORAGE

MECHANICAL

CYSTOSCOPY

SEMI RESTRICTED

CORRIDOR

CLEAN CORE

FUTURE CLEAN EL.

A-EL-3

FUTURE CLEAN EL.

A-EL-2

CLEAN AND STERILE

SUPPLY

CC STORAGE

255A

NURSE MANAGER

OFFICE

ELEC. CL.

SOILED UTILITY

IUSS

ANESTHESIA

WORKROOM

EQUIPMENT STORAGE

WORK AREA

CONTROL STATION

MALE LOCKERS

ANGIOPLASTY

OR-1

OR-2

OR-3

HOUSE KEEPING

215G

FEMALE LOCKERS

CONSULT ROOM

TOILET

202A

MINOR PROCEDURE

OR STORAGE

PATIENT TOILET

215F

PATIENT LOCKERS

215E

VESTIBULE

215D

CLEAN UTILITIES

215C

SOILED UTILITIES

215B

SEMI RESTRICTED

CORRIDOR

STAIR WELL

A-2

ELECTRICAL CLOSET

HOUSE KEEPING

232A

ELEC

232C

ELEC

232D

INTERVENTIONAL PAIN

MANAGEMENT

233A

ELECTRICAL ROOM

201C

EMERGENCY

ELECTRICAL ROOM

201B

ELEVATOR LOBBY

L23

LINEN CHUTE

IT CLOSET

229A

ELECTRICAL CLOSET

CORRIDOR

2-DC-1A

SEMI RESTRICTED

CORRIDOR

EXAM-1

E205

EXAM-2

E206

OFFICE

CORRIDOR

BRONCHOSCOPY

Room

4ZZ

Room

4AAA

Room

4BBB

Room

4CCC

Room

4DDD

SCRUB

210A

SCRUB

210B

OR ACCESS VESTIBULE

OR ACCESS VESTIBULE

OBSERVATION ROOM

PACU

NURSE STATION

PATIENT TOILET

215A

CORRIDOR

C223

STAIR-K

K-2

STAFF TOILET/SHOWER

SEMI RESTRICTED

CORRIDOR

LINK CORRIDOR

L24

MICROSCOPE

E207

EXAM-3

E208

CAST ROOM

E204

CORRIDOR

C22

ELEVATOR LOBBY

L21

CORRIDOR

C21

LOBBY

L22

ELEVATOR

E-EL-2

ELEVATOR

E-EL-1

OR RECEPTION

WAITING ROOM

OFFICE

201A

FUTURE SOILED

ELEVATOR

A-EL-1

DP-N-OR

EQ-2-OR

LS-2-OR

CB-2A-OR

DP-CB-OR-2

DP-CB-OR-1

CB-2B-OR

C R

W

C T R

CTR

CTR

CTR

CTR

W

C T

R

S

NURSE CALL C.P.

VISIPLEX BASE STATION

N-L-2-OR

S

S

S

S

S

S

SECURITY SYSTEM CONTROL PANEL

BS

CTR

F

W

S

REX

CTR

S

W

A

B

B

A

M D O

FFIC

E

O

FFIC

E

TO

ILET

M

EN

S

TO

ILET

W O

M

EN

S C O N

FER

EN

C E

A

Z

R

EC

EP

TIO

N

A D

M

IN

IS

TR

A

TO

R

S

EC

R

ETA

R Y

C H

IEF

C O R R

ID

O R

ELEV

A

TO

R

LO

B B Y

L-

P

P

P

S

A

A

TC

A

B R

EA

K R

O O

M

C

H

F

G

FILE R

O O

M

O

FFIC

E

LA

B

B

LO

O D

A R

TER

IA

L

ELEV

A

TO

R

L-

C

C H A S E

R

EC

P T

P H A R

M A C Y

ELEV

A

TO

R

TC

1L

TELEP

H O N E

C

LO

S

ET

ELEV

A

TO

R

C

LO

S

ET

C

LO

S

ET

D W 1C

W A

ITER

P H A R

M A C Y

C L2

C H A S E

C 1L

C H A S E

C B

C H A S E

R O O

M

P A S S

EN

G

ER

S

TA

IR

ELEC

TR

IC

A L

FU

TU

R E

P H A R

M A C Y

O

FFIC

E

IN

P A

TIEN

T

P H A R

M A C Y

IN

P A

TIEN

T

P H A R

M A C Y

IN

P A

TIEN

T

D U

M B

C O

M M U N

IC

A

TIO

N

S

ER

V

IC

E

ELEC

TR

IC

A L

P A S S

EN

G

ER

ELEV

A

TO

R

P A S S

EN

G

ER TO

ILET

TO

ILET

R O O

M

ELEC

TR

IC

A L

FU

TU

R E

MALE LOCKERS

CORRIDOR

C223

SEE DRAWING E40.1 FOR

1/4" SCALE CYSTOSCOPY

PART PLAN

C B

SSSSS

S

S

S

SS

W

S

S

S

S

V

S

CLEAN CORE AIR HANDLER

S

15cd

15cd 15cd

S

15cd

15cd

S

15cd

15cd

S

15cd

S

15cd

S

15cd

15cd

S

15cd

(EN)

WP

S

15cd

S

S

S

15cd

15cd

15cd

S

15cd

15cd

S

15cd

15cd

1.

WIFI SYSTEM NOTES:

THE WIRELESS WIFI SYSTEM EQUIPMENT AND CABLING

MUST BE MAINTAINED AND INTACT. ANY EXISTING

CABLING SHALL NOT BE DEMOLISHED AS PART OF THE

PROJECT. VAMC I.T STAFF WILL TEMPORARILY REMOVE

THE ACCESS POINTS WITHIN THE CONSTRUCTION AREA

PRIOR TO THE CONSTRUCTION START DATE.

EQUIPMENT TRACKING

SYSTEM NOTES:

1. THE EXISTING CEILING MOUNTED CENTRAK EQUIPMENT

TRACKING EQUIPMENT SYSTEM DEVICES PRESENTLY

INSTALLED IN THE SCOPE OF WORK AREA SHALL BE

RELOCATED TO NEW LOCATIONS PER THE VAMC I.T.

DEPT. DIRECTION. NEW DEVICES SHALL BE ADDED IN

NEW ADDITION AS INDICATED ON DRAWINGS.

W

W

15cd

C R

D C

D C

C R

D C

D

CA

O M

A O

M

D C

D C

A O

M

DOOR RELEASEDOOR RELEASE

S 15cd

15cd

15cd

(EN)

(EN)

S

15cd

15cd

C01

C01

ALL TELEPHONE, DATA, CCTV AND PUBLIC ADDRESS SPEAKER CABLING TO BE RUN FROM DEVICE TO EXISTING DATA AND CCTV RACKS IN I.T. CLOSET 100.

SP

SPSP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

C R

C R

C R

R E X

D

CA

O M

DOOR RELEASE

R E X

R E X

B S

(EN)

DH

S SP

S

PHASE 7

PHASE 5

DEMOLISH ALL PHASE 5 ELECTRICAL DEVICES TO ACCOMMODATE NEW PHASE 7 ELECTRICAL DEVICES.C02

C02

SP (EN)

15cd

S

N-2-CC

(UNISTRUT MOUNTED)

CB-2-CC

PHASING NOTES:

1. REFER TO ARCHITECTURAL DRAWINGS A01.1 AND A01.2

FOR PROJECT PHASING AND ADDITIONAL PHASING NOTES.

AOM

ELEVATOR

DOOR RELEASE

NACP

W

W

W

W

W

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F il e P a th

/1

/2

:3

:0

P

M

Office of

Construction and Facilities

Management of Veterans Affairs

U.S. Department

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date:

Auburn, ME

207.784.5100

Boston, MA

617.426.5050

Portland, ME

207.775.0053

Portsmouth, NH

603.626.1242 c

HA PROJECT NUMBER: 13586

PROVIDENCE, RHODE ISLAND

02-22-19

650-337

SPRINKLERED

SURGICAL SUITE

CONSTRUCT CLEAN CORE ADDITION TO

DOCUMENTS

FINAL CONSTRUCTION

E30.1

APGJWT

SYSTEMS

SECOND FLOOR PART PLAN

1.8

4.3'

1.8

4.3'

1.8

4.3'

CYSTOSCOPY

CYSTOSCOPY

GENERATOR

PART PLAN - CYSTOSCOPY 263 - LIGHTING

SCALE: 1/4" = 1'-0"

PART PLAN - CYSTOSCOPY 263 - POWER

SCALE: 1/4" = 1'-0"

PART PLAN - CYSTOSCOPY 263 - SYSTEMS

SCALE: 1/4" = 1'-0"

C

C1

C1

C

CC1

C

D

C1

D

C1 C1C

75cd

S

C a,b a,b a,b a,b

L01

L01

L01

L02

L02

L03

L03

P01

P02

P03

S01

S02

S03

EPO

P04

BS

SP

SPEAKER

a,b a,b a,b

CB-2-CC#19

CB-2-CC#17

GENERATOR CABINET

WARMING UNIT

HYPO. UNIT

MED. DISP.

ANEST. CART

ANEST. APPAR.

MONITOR

EXTREM. PUMP

BLOOD WARMER

BLOOD WARMER

BLOOD WARMER

COMPUTER

CB

W

IPU-E-CYSTO1#2,6

IPU-E-CYSTO2#1,5

IPU-N-CYSTO#1,5

UTILITY COLUMN WITH (2) CRITICAL QUAD RECEPTACLES, (1) NORMAL QUAD RECEPTACLE AND (2) DATA OUTLETS.

P01

IPU-E-CYSTO1#1

IPU-E-CYSTO1#5

IPU-E-CYSTO1#9

IPU-E-CYSTO1#13

IPU-E-CYSTO1#17

IPU-E-CYSTO1#21

IPU-E-CYSTO1#23

IPU-E-CYSTO1#25

IPU-E-CYSTO2#2

IPU-E-CYSTO2#6

IPU-E-CYSTO2#10

IPU-E-CYSTO2#14

IPU-E-CYSTO2#18

IPU-E-CYSTO2#22

9 9

IPU-N-CYSTO#13

IPU-N-CYSTO#17

IPU-N-CYSTO#9

IPU-N-CYSTO#19

GENERATOR CABINET

3#14 IN 1/2" C TO X-RAY IN USE SIGN AT ALTERNATE DOOR TO CYSTO ROOM.

3#14 IN 1/2" C TO GENERATOR CABINET.

CONDUITS TO PENETRATE INTO GENERATOR CABINET WITHOUT THE NEED FOR A JUNCTION BOX.

P02

"X-RAY IN USE" SIGN AND LIGHTING RELAY CONTROLLED VIA GENERATOR CABINET. LITHONIA 'X-RAY IN USE' SIGN

MODEL LQM-P-W-1-R-120/277-SW-09. PROVIDE LIGHTING RELAY AT SIGN TO CONTROL LIGHTING CIRCUIT.

S01

S02

EMERGENCY OFF PUSHBUTTON FOR OPERATION OF SHUNT TRIP MAIN CIRCUIT BREAKER. PROVIDE RED MUSHROOM BUTTON IN

PROTECTIVE LEXAN COVER.

2#12 IN 3/4"C FROM 'EPO' TO MAIN BREAKER.

8"x8"x6x DEEP JUNCTION BOX. SPLIT REMOVABLE COVER PLATE SHALL CONTAIN A 3" GROMMETTED OPENING. LOCATE BOX BELOW

COUNTER AND PROVIDE A 3" GROMMETTED OPENING IN COUNTERTOP FOR CABLE ACCESS TO EQUIPMENT.

S03

GENERATOR CABINET

S04

S04

VENDOR COMPUTER

S05

4" CONDUIT WITH PULLSTRING FROM JUNCTION BOX TO GENERATOR CABINET.

BASEPLATE

DC DC

DC

S06 2#12 IN 3/4"C FROM DOOR CONTACT SWITCH TO GENERATOR CABINET

S06

S06

5#4 IN 1 1/4"C FROM MAIN BREAKER TO GENERATOR CABINET. PROVIDE ADDITIONAL 10' CABLE LOOP AT GENERATOR CABINET.

P03

480V, 50A, 3-POLE SHUNT TRIP MAIN BREAKER

5#4 IN 1 1/4"C.

P04

S07

S07 3" AND 1 1/2" CONDUIT WITH PULLSTRING FROM JUNCTION BOX TO BASEPLATE.

S05

(2) 4" AND (2) 3" CONDUITS WITH PULLSTRINGS FROM GENERATOR CABINET TO BASEPLATE.

EPO

S01

S02

P05

P05

(4) PORT PATIENT GROUND MODULE WITH #10G TO PANEL IPU-N-CYSTO GROUND BUS. GROUND MODULE TO BE HOSPITAL

SYSTEMS, INC. CATALOG #358184 OR APPROVED EQUAL.

DP1-EQ-CC#2,4,6

a b a,b a,b a,b a,b

17,19 a,b a,b a,b

17,19

17,19

17,19

17,19 17,19 17,19

17,19

17,19

17,19

17,19

17,1917,1917,19 a b

LUTRON GRX-TVI

L04

17 19

L04

L05

LUTRON 3-WAY MAESTRO MASTER DIMMER CAT# MAF-6AM-120-IV CONNECTED TO LUTRON CAT# GRX-TVI POWER INTERFACE

MODULE CONTROLLING LIGHTING CIRCUIT.

LUTRON 3-WAY MAESTRO SLAVE DIMMER CAT# MA-R-120-IV CONNECTED TO MAESTRO MASTER 3-WAY DIMMER.

L05

W

P06 MOUNT POWER OULET AND DATA OUTLET AT 4'-6"AFF.

P06

P06

P06

IPU-E-CYSTO2#26

IPU-E-CYSTO2#30

30 30

MOUNT OUTLETS AT 6'-0" AFF.

MONITORS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F il e P a th

/1

/2

:3

:0

P

M

Office of

Construction and Facilities

Management of Veterans Affairs

U.S. Department

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date:

Auburn, ME

207.784.5100

Boston, MA

617.426.5050

Portland, ME

207.775.0053

Portsmouth, NH

603.626.1242 c

HA PROJECT NUMBER: 13586

PROVIDENCE, RHODE ISLAND

02-22-19

650-337

SPRINKLERED

SURGICAL SUITE

CONSTRUCT CLEAN CORE ADDITION TO

DOCUMENTS

FINAL CONSTRUCTION

E40.1

APGJWT

ENLARGED PART PLANS

CYSTOSCOPY 263

SECOND FLOOR

GROUND FLOOR

WING 'D'

BASEMENT LEVEL

SUB-BASEMENT LEVEL

P01

P02

P04

WING 'A'

P06

P01

GENERAL NOTES:

1. PROVIDE ALL PULLBOXES REQUIRED FOR NEW

AND EXTENDED FEEDERS, SIZE AS REQUIRED.

EXISTING 480/277V

SWITCHBOARD #1

800A 480/277

4-POLE

ATS

WITH

BYPASS

ISOLATION

P02

EXISTING 480/277V

SWITCHBOARD #4

EXISTING OUTDOOR

RUSSELECTRIC GENERATOR

PARALLELING GEAR

PROVIDE NEW 800A BREAKER IN EXISTING SPACE TO SERVE

NEW PANEL DP1-EQ-CC.

P03

WING 'B'

PULLBOX PULLBOX

CLEAN CORE ADDITION

EXISTING

PANEL

DP-CB-OR

DP-N-OR

IPU-E-CYSTO

PANEL TO BE DEMOLISHED

DP-EQ-OR

EXISTING

PULLBOX

IN BARBER

SHOP

STORAGE

ROOM

EXISTING

OFFICE

PULLBOX

EXISTING

PULLBOX

ELECTRICAL DUCTBANK

OR ADDITION

P03 REUTILIZE EXISTING 800A BREAKER TO SERVE NEW PANEL

DP1-EQ-CC

8#600MCM+2#1/0 IN (2)4"C.

P05

P04

6#250MCM+2#2 IN (2)2 1/2"C.

P05

P05 P04

P05 P05

4#350MCM+1#3 IN 4"C.

P06

P07

P08

P07 P07

3#10+1#10G IN 3/4"C.

P08

7.5 5

P07

P09 NEW NORMAL 600A, 480V AND 1200A, 208V POWER FEEDERS

BETWEEN EXISTING WING B PULLBOXES AND EXISTING WING A

PULLBOXES. NEW 480V FEEDER SHALL BE (8) 350MCM & (2) #1G

IN (2) 3"C. NEW 208V FEEDER SHALL BE (12) 600MCM & (3) 3/0G

IN (3) 4"C.

P09

P04

PANEL

DP1-EQ-CC

WITH

INTEGRAL

SURGE

PROTECTION

DEVICE

PANEL

IPU-N-CYSTO

WITH

EXTERNAL

SURGE

PROTECTION

DEVICE

PANEL

IPU-E-CYSTO1

WITH

EXTERNAL

SURGE

PROTECTION

DEVICE

P09

CB-2-CC

WITH

SURGE

PROTECTION

DEVICE

P09

P09 4#1+1#8G IN 1 1/2"C.

P07

IPU-E-CYSTO2

WITH

EXTERNAL

SURGE

PROTECTION

DEVICE

P10 PROVIDE #10 GROUND IN 3/4"C BETWEEN PANEL GROUND BUS BARS IN COMPLIANCE WITH NEC ARTICLE 517.

P10P10

PANEL

N-2-CC

WITH

SURGE

PROTECTION

DEVICE

P11 PROVIDE ALL REQUIRED PROGRAMMING FOR EXISTING RUSSELECTRIC GENERATOR PARALLELING GEAR TO ACCOMMODATE NEW STARTING CIRCUIT

FROM NEW ATS-EQ-CC1. COORDINATE LOADING AND UNLOADING SEQUENCE WITH VA FACILITIES STAFF.

P11

P12 PROVIDE (2) NEW 50A, 2-POLE BREAKERS TO SERVE NEW PANELS IPU-E-CYSTO1 AND IPU-E-CYSTO1. PROVIDE (1) NEW 100A, 3-POLE

BREAKER TO SERVE NEW PANEL CB-2-CC. NEW BREAKERS SHALL MATCH EXISTINTG TYPE INCLUDING AIC RATING.

P12 P13

P13

B-EQ-CC

WITH

SURGE

PROTECTION

DEVICE

30KVA

480V:

208/120V

XFMR

P15

P14

P15

P14 3#6+1#10G IN 1"C

4#1+1#8G IN 1 1/2"C.

57.5

3#12+1#12G IN 3/4"C.

P16 8#10 IN 1"C GENERATOR START/STOP SIGNAL CIRCUITING.

P16

OR CHILLER

CH-1GB001

OR CHILLER

CH-IGB002

AIR HANDLER 12B001

REUTILIZE EXISTING 600A BREAKER TO SERVE NEW OR

CHILLER CH-1GB002. PROVIDE NEW 450A RATING PLUG.

PROVIDE (1) NEW 100A, 3-POLE BREAKER TO SERVE NEW PANEL N-2-CC. NEW BREAKER SHALL MATCH EXISTING TYPE INCLUDING

AIC RATING.

2. CONTRACTOR SHALL FOLLOW ALL REQUIREMENTS

OF NFPA 70E FOR ALL WORK INCLUDING WORK

ASSOCIATED WITH THE RUSSELECTRIC GENERATOR

PARALLELING GEAR.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F il e P a th

/1

/2

:3

:0

P

M

Office of

Construction and Facilities

Management of Veterans Affairs

U.S. Department

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date:

Auburn, ME

207.784.5100

Boston, MA

617.426.5050

Portland, ME

207.775.0053

Portsmouth, NH

603.626.1242 c

HA PROJECT NUMBER: 13586

PROVIDENCE, RHODE ISLAND

02-22-19

650-337

SPRINKLERED

SURGICAL SUITE

CONSTRUCT CLEAN CORE ADDITION TO

DOCUMENTS

FINAL CONSTRUCTION

E50.1

APGJWT

RISER DIAGRAM

ELECTRICAL

ID ID

WATT LOADS

MOUNTING:

LOCATION:

LOAD DESCRIPTION

A M

P

P O

L E

CRKT

DWG

NO. P

O

L E

WATTS

PH A PH B PH C

WATTS

P O

L E

CRKT

DWG

NO. P

O

L E

A M

P

LOAD DESCRIPTION

FEEDER:AIC RATING:

MAIN BREAKER:VOLTAGE:

BUSES:

PH & WIRES:

120/208

3P 4W

MLO

22K AIC

SURFACE

SEE DRAWING E50.1CB-2-CC

TUB 1 OF 1 - REMARKS:

RM 217 & 211 RCPTS 20 1 1 1 800 1182 --- --- 382 2 2 1 20 BRONCOSCOPY LIGHTING

RM 217 & 211 RCPTS 20 1 3 3 800 --- 1175 --- 375 4 4 1 20 LIGHTING RM 217,256,257

CORRIDOR 210 RCPT 20 1 5 5 200 --- --- 700 500 6 6 1 20 RM 250 BOOM

RM 259 RCPT FREEZER 20 1 7 7 725 1225 --- --- 500 8 8 1 20 RM 250 BOOM

* RM 256 RCPTS 20 1 9 9 200 --- 1000 --- 800 10 10 1 20 RM 250 BOOM

* WIRELESS SPEAKERS 20 1 11 11 600 --- --- 1400 800 12 12 1 20 RM 250 BOOM

RM 253 RCPTS 20 1 13 13 1000 1400 --- --- 400 14 14 1 20 RM 250 RCPTS

RM 251 RCPTS 20 1 15 15 400 --- 800 --- 400 16 16 1 20 RM 250 RCPTS

RM 263 LIGHTS 20 1 17 17 1050 --- --- 1850 800 18 18 1 20 RM 250 RCPTS

RM 263 LIGHTS 20 1 19 19 1050 1050 --- --- 0 20 20 1 20 SPARE

SPARE 20 1 21 21 0 --- 0 --- 0 22 22 1 20 SPARE

SPARE 20 1 23 23 0 --- --- 0 0 24 24 1 20 SPARE

SPARE 20 1 25 25 0 0 --- --- 0 26 26 1 20 SPARE

SPARE 20 1 27 27 0 --- 0 --- 0 28 28 1 20 SPARE

SPARE 20 1 29 29 0 --- --- 0 0 30 30 1 20 SPARE

SPARE 20 1 31 31 0 0 --- --- 0 32 32 1 20 SPARE

SPARE 20 1 33 33 0 --- 0 --- 0 34 34 1 20 SPARE

SPARE 20 1 35 35 0 --- --- 0 0 36 36 1 20 SPARE

SPARE 20 1 37 37 0 0 --- --- 0 38 38 1 20 SPARE

SPARE 20 1 39 39 0 --- 0 --- 0 40 40 1 20 SPARE

SPARE 20 1 41 41 0 --- --- 0 0 42 42 1 20 SPARE

TOTAL AMPS: 32.7 4857 2975 3950 TOTAL WATTS: 11782

REMARKS:

* INDICATES GFCI CIRCUIT BREAKER.

10/11/2018

ID ID

WATT LOADS

MOUNTING:

LOCATION:

LOAD DESCRIPTION

A M

P

P O

L E

CRKT

DWG

NO. P

O

L E

WATTS

PH A PH B PH C

WATTS

P O

L E

CRKT

DWG

NO. P

O

L E

A M

P

LOAD DESCRIPTION

FEEDER:AIC RATING:

MAIN BREAKER:VOLTAGE:

BUSES:

PH & WIRES:

120/208

3P 4W

45A MAIN BRKR

10K AIC

SEE DRAWING E50.1IPU-N-CYSTO

BOOM RCPT 20 2 1 1 400 200 --- --- 0 2 2 2 20 SPARE

- - - 3 --- 200 --- 4 - - -

BOOM RCPT 20 2 5 5 400 --- --- 200 0 6 6 2…