36E77619R0097-010.pdf
PDF Posted
- Attached to
- Construct Clean Core (VA-19-00058573) Federal contract opportunity
- Solicitation number
- 36E77619R0097
About this file
This document provides details for a federal contract opportunity to construct a clean core addition to a surgical suite at a Department of Veterans Affairs medical center. The project involves constructing new surgery suite space and renovating existing space to relocate locker rooms and offices. Construction services will be performed measuring approximately 6,800 gross square feet of new and existing space. The solicitation will be a request for proposal conducted in accordance with FAR Parts 15, 19, and 36 and evaluated using lowest price technically acceptable procedures. The NAICS code is 236220 with a size standard of $39.5 million. The solicitation is designated as a total Service-Disabled Veteran-Owned Small Business set-aside and will be issued on or around October 16, 2019. The period of performance is approximately 490 calendar days. The magnitude of construction is estimated between $5 million to $10 million.
36E77619R0097 Attachment 7 - Structural Plans.pdf
View the file
Other files for this federal contract opportunity
Show all 44
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A.2'A'
5' 4.8'
21.51 3 4 5 6 7
C
C.5
D
E
G
H
K
L
B
A
2.5 8
E4.8
EBB
EA.1
J
A.5
2.2
E.1
C.3
D.3
1.80.5
F8B* F8
F8.5 F10B**
F7C
F6*
F5*
F7A
F5*
F5*
F8.5 F7
F11.5
F11
F10C***
F5.5 F7A
F10 F7.5B
F10A F7.5A**
F5B**
F5.5B F10B
P1A P3A P3A
P1B
P1A
P3B
P1A P3A
P3A
P1A
P1A
P1A P1A
P1A
P1A
P3A
P3A
P1A P1A P3C
P3C
P3D
P1A P2A
P1A
P1A
P2A P12
P12
P2B
13'-10 5/8" 8'-1" 7'-1" 4'-5 3/4"5'-8 3/4" 12'-5 1/2" 18'-4" 18'-4" 18'-4" 18'-4" 19'-10 1/2"
5'-9"
4'-4"
'-8
/4
'-8
/4
'-4
4'
-3
/4
3' -1
1/
2" 7'
-1
/4
3' -2
/8
'-1
/8
/8
17'-8 5/8"
13'-11 3/4"
3'-2 1/2"
8'-9 1/4"
9'- 2 1
/4"
'-5
3/ 4"
7'- 1 3
/4"
'-1
1"
2'- 0 7
/8"
45.00°
45.00° P3D
EXISTING 2' ± WIDE ELECTRICAL
DUCT BANK TO REMAIN.
TOP OF BANK EL. 77.3±
BOT OF BANK EL. 75.9±
P3B P1A
P2B
G.C. NOTE
CONTRACTOR SHALL HAVE A LICENSED SURVEYOR VERIFY
ALL EXISTING DIMENSIONS, FLOOR ELEVATIONS, AND
FLOOR-TO-FLOOR HEIGHTS BEFORE ORDERING, FABRICATING
OR DETAILING STRUCTURAL COLUMNS AND HORIZONTAL FRAMING.
THIS INFORMATION MUST BE CONFIRMED AT ALL LOCATIONS.
FOUNDATION NOTES:
1. TOP OF CONCRETE ELEVATION IS REFERENCED
(+/-) FROM ELEVATION 78.63' (0'-0").
2. (-X") INDICATES TOP OF CONCRETE ELEVATION.
3. [-X'-Y"] INDICATES TOP OF FOOTING ELEVATION.
4. PX INDICATES REINFORCED CONCRETE PIER. (SEE SCHEDULE)
5. TOP OF CONCRETE PIER ELEVATION = (-1'-0") UNLESS NOTED OTHERWISE.
6. FX INDICATES REINFORCED CONCRETE SPREAD FOOTING. (SEE SCHEDULE)
7. TOP OF FOOTING ELEVATION = [-4'-0"] UNLESS NOTED OTHERWISE.
8. PIERS AND SPREAD FOOTINGS ARE CENTERED
ON COLUMNS UNLESS NOTED OTHERWISE.
9. SEE S31.1 FOR ALTERNATE FOUNDATION PLANS.
10. EXISTING 18"x18" CONCRETE COLUMN AND FOOTING TO REMAIN. FIELD VERIFY
ELEVATIONS.
11. EXISTING W12X40 COLUMN TO REMAIN. SHORE EXISTING W12X40 COLUMN TO
REMOVE EXISTING 18"x18"x7'-0" TALL CONCRETE PIER AND 4'-0"x4'-0"x1'-0" TALL
FOOTING. REBUILD PIER AND FOOTING AS INDICATED.
12. G.C. TO SUBMIT SHORING PLANS PREPARED BY AN ENGINEER
LICENSED IN RHODE ISLAND FOR REVIEW PRIOR TO DOING ANY WORK.
13. SEE ADDITIONAL APPLICABLE FOUNDATION NOTES ON DRAWING S50.1.
14. SECTIONS AND DETAILS SHOWN ON STRUCTURAL DRAWINGS SHALL BE
CONSIDERED TYPICAL FOR SIMILAR FOUNDATION CONDITIONS NOT
SPECIFICALLY REFERENCED.
15. +/- DIMENSIONS SHALL BE CONSIDERED APPROXIMATE AND SHALL BE VERIFIED
BY G.C. BEFORE PROCEEDING WITH WORK.
16. BOF[0] INDICATES BOTTOM OF EXISTING FOOTING.
EXISTING SLAB-ON-GRADE
T/SLAB (0'-8")
F13
[-2'-1"] [-1'-1"]
[-1'-1"] [-1'-1"]
[-4'-9"]
[-3'-4"]
[-7'-9"]
[-4'-8"]
(5'-8")
(5'-8")
(8") (8")
(8") (0")
[-7'-9"]
F6 S50.1
3 3/4" 8"
7'-8" 7 5/8"
7'-8" 8"
7/
8" 8"
9' -6
/4
1'
-4
F6 S50.1
12'-1 1/2"
5 5/8"
8'- 8"
5 7 /8"
8"
TYP.
FT
G
O
FF
SE
T
1/
2"
1'-3 1/4"
4' -0
F8C P2B
[-6'-9"]
[-7'-3"]
CONCRETE
BEAM
F1 S50.2
F4 S50.2
SUMP
PIT
3'-6 3/4" 4'-0"
4'-3 5/8" 4'-0"
(-8")
(0")
(0")
(-8")
(8") (0")
(0")
SUMP PIT
(-4")
(-4") (-4")
(-4")
(-4")
SIM.
CF1*
CF2
CF3
[-3'-9"]
[-2'-9"]
[-2'-9"]
[-4'-3"]
[-1'-0"+/-]
[-4'-3"]
[-3'-9"]
[-3'-9"] [-4'-6"]
[-5'-3"]
[-1'-1"]
[-3'-4"]
[-3'-9"]
[-4'-9"](-1'-0")
1'- 5 1
/4"4'- 7 1
/2"
MATCH BOTTOM
OF EXISTING
FOOTING ELEVATION
F8 S50.2
6'-8 7/8"
4'-9 1/2"
D1 S50.2
(9)
D3 S50.2
1' -4
(-1'-0")
(SIM.)
D6
S50.2
NOTE: FOOTING AND
PIER AT -7'-9" PLACED,
THEN BACK-FILLED FOR
ELEVATOR MAT FOOTING
INSTALL
CONCRETE
BEAM
MATCH BOTTOM OF
EXISTING FOOTING
ELEVATION
BOF[-4'-3"]
BOF[-4'-9"]
BOF[-3'-11"]
BOF[-3'-1"]
BOF[-3'-1"] BOF[-5'-3"]
BOF[-7'-3"] BOF[-7'-3"]
BOF[-5'-3"]
BOF[-3'-1"] BOF[-3'-4"]
BOF[-4'-9"]
BOF[-6'-9"]
BOF[-8'-9"]
BOF[-10'-9"]
BOF[-12'-9"]
EX. 6'x6'x1'-4"
FOOTING
BOF[-6'-2"]
SEE NOTE 10
SEE NOTE 11
SEE NOTE 11
0 4' 8' 12'
1/8" = 1'-0"
Graphic Scale
Graphic Scale
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CONSTRUCTION
DOCUMENTS
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Auburn, ME 207.784.5100
Boston, MA 617.426.5050
Portland, ME 207.775.0053
Portsmouth, NH 603.626.1242 c HA PROJECT NUMBER: 13586
CONSTRUCT CLEAN CORE ADDITION TO
SURGICAL SUITE
PROVIDENCE, RHODE ISLAND
650-337SCALE:
C :\U se rs
\p ls m i\D oc um en ts
R ev it
L oc al s\
6-st ru c-ce nt ra l_ pl sm i.r vt
2/
/2
:3 8:
A
M
S10.1
FOUNDATION PLAN, NOTES AND
DETAILS
2-22-19 RMP/JCF MRM
SCALE: 1/8" = 1'-0"F2 FOUNDATION PLAN
Revisions: Date:
4.8'
21.51 3 4 5 6 7
C
C.5
D
E
G
H
K
L
B
A
2.5 8
E4.8
EBB
EA.1
J
A.5
4'-4"
2.2
G.C. NOTE
CONTRACTOR SHALL HAVE A LICENSED SURVEYOR VERIFY
ALL EXISTING DIMENSIONS, FLOOR ELEVATIONS, AND
FLOOR-TO-FLOOR HEIGHTS BEFORE ORDERING, FABRICATING
OR DETAILING STRUCTURAL COLUMNS AND HORIZONTAL FRAMING.
THIS INFORMATION MUST BE CONFIRMED AT ALL LOCATIONS WHERE
NEW FLOORS MEET EXISTING FLOORS
E.1
C.3
D.3
1.8
W14X22
W
X2
W16X36
W16X31
W
X2
W 12X26
W 10X22
W
X50
FRAMING PLAN NOTES:
1. TOP OF STEEL ELEVATION IS (11'-2") REFERENCED FROM
ELEVATION 78.63' (0'-0") U.N.O.
2. SEE ADDITIONAL APPLICABLE FRAMING NOTES ON DRAWING
S60.1.
3. ALL STEEL BEAMS TO CONFORM TO ASTM A992 (Fy=50KSI).
4. ALL RECTANGULAR HSS COLUMNS TO CONFORM TO ASTM A500
(GR. B)(Fy=46 KSI).
5. INDICATES DIAGONAL STEEL BRACING. SEE S40.2 FOR
BRACING ELEVATIONS.
6. SEE S40.1 FOR COLUMN AND BASE PLATE SCHEDULES.
7. V.I.F. = VERIFY IN FIELD.
8. DENOTES MOMENT CONNECTION. CONNECTION SHALL
BE DESIGNED FOR FULL MOMENT CAPACITY OF BEAM.
9. G.C./STEEL FABRICATOR TO COORDINATE CONNECTION DESIGN
AT BEAMS/COLUMNS ADJACENT TO EXISTING BUILDING
10. +/- DIMENSIONS SHALL BE CONSIDERED APPROXIMATE AND
SHALL BE VERIFIED BY G.C. BEFORE PROCEEDING WITH WORK.
11. SEE CONNECTION SCHEDULE ON S40.1 FOR BEAM END
REACTIONS.
2'-0"
V.I.F.
2'-6"
0.5
W
X3
W14X22
W14X30
13'-10 5/8" 8'-1" 7'-1" 4'-5 3/4"5'-8 3/4" 12'-5 1/2" 18'-4" 18'-4" 18'-4" 18'-4" 19'-10 1/2"
5'-9"
'-8
/4
'-8
/4
'-4
4'
-3
/4
3' -1
1/
2" 7'
-1
/4
3' -2
/8
'-1
/8
/8
17'-8 5/8"
13'-11 3/4"
3'-2 1/2"
8'-9 1/4"
2'- 0 7
/8"
45.00°
45.00°
W
X22
W14X30
W
X3
W
X2
W14X30
W16X31
W
X1
W
X26
9'- 2 1
/4"
'-5
3/ 4"
7'- 1 3
/4"
'-1
1"
4'-9 1/2"
6'-8 7/8"
0 4' 8' 12'
1/8" = 1'-0"
Graphic Scale
Graphic Scale
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CONSTRUCTION
DOCUMENTS
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Auburn, ME 207.784.5100
Boston, MA 617.426.5050
Portland, ME 207.775.0053
Portsmouth, NH 603.626.1242 c HA PROJECT NUMBER: 13586
CONSTRUCT CLEAN CORE ADDITION TO
SURGICAL SUITE
PROVIDENCE, RHODE ISLAND
650-337SCALE:
C :\U se rs
\p ls m i\D oc um en ts
R ev it
L oc al s\
6-st ru c-ce nt ra l_ pl sm i.r vt
2/
/2
:3 8:
A
M
S20.1
FIRST FLOOR FRAMING PLAN
2-22-19 RMP/JCF MRM
SCALE: 1/8" = 1'-0"F2 FIRST FLOOR FRAMING PLAN
4.8'
21.51 3 4 5 6 7
C
C.5
D
E
G
H
K
L
B
A
2.5 8
E4.8
EBB
EA.1
J
2.2
E.1
C.3
D.3
1.8
D9 S60.2
D1 S60.2
F9 S60.2
B1 S60.2
B3 S60.2
B6 S60.2
D3 S60.2 C6
S60.2
F7 S60.2
F1 S60.2
F4 S60.2
0.5
13'-10 5/8" 8'-1" 7'-1" 4'-5 3/4"5'-8 3/4" 12'-5 1/2" 18'-4" 18'-4" 18'-4" 18'-4" 19'-10 1/2"
5'-9"
4'-4"
17'-8 5/8"
13'-11 3/4"
3'-2 1/2"
8'-9 1/4"
9'- 2 1
/4"
'-5
3/ 4"
7'- 1 3
/4"
'-1
1"
2'- 0 7
/8"
'-5
/2
'-4
4' -3
/4
3'
-1
1/ 2"
7' -1
/4
3'
-2
/8
'-1
/8
W
X3
(1 2)
W
X2
(1 2)
W
X2
(1 2)
W
X4
(1 6)
W
X4
(1 2)
W
X2
(1 2)
W14X22 (6)
W14X30 (12) W14X22 (9)
W
X1
(8
W10X17 (7)
W14X22 (12) W14X22 (8) W14X22 (8) W14X22 (8)
W
X2
(1 0)
W16X36 (14) W16X31 (16) W16X31 (16) W16X31 (16) W16X31 (14)
W
X1
(8
W
X1
(8
W
X1
(8
W10X17 (6) W10X17 (7) W10X17 (7) W10X17 (7) W10X17 (7)
W16X31 (12)
W
X1
(8
W14X22 (16)
W 10X33 (12)
W 10X17 (8)
W
X26 (8
W 12X30 (25)
W 10X17 (8)
W14X22 (8)
W
X26 (1
0) W 12X26 (9)
W
X22 (1
0)
W 10X17 (8)
W
X1
(8
W12X19 (10)
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W10X17 (6)
W14X26 (10) W14X26 (10) W14X26 (10) W14X26 (10)
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(1 0)
W
X1
(1 0)
W
X1
(1 0)
W14X38 (8)
W14X22 (8)
W
X2
(1 2)
W
X2
(1 2)
W
X2
(1 2)
W
X2
(1 2)
W
X26 (1
0)
W 10X17 (9)
W 10X17 (9)
W 10X17 (9)
W10X17 (3)
W10X17 (3)
W10X17
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(1 0)
W
X1
(8
W
X1
(8
W
X1
(8
W
X1
(3
W
X1
(8
W12X19
W12X19
W12X19
W12X19
W
X1
(8
W
X1
(8
W 10X17 (8)
W14X22
W14X22 (4)
W
X1
(8
W
X1
(8
W10X17 (2)
W10X17 (3)
W10X17 (3)
L8 X4X
1/2
W14X22 (8)
W18X40 (14) W
X2
(1
2) W
X2
(1
2) W
X3
(1
5)
W
X3
(1 5)
W
X3
(1 5)
W
X3
(1 5)
W10X17
W14X22 (3)
W10X17 (8)
W14X22 (4) W14X22 (14)
W10X17
(TYP.)
W10X17
W10X17 (TYP.)
W10X17 (TYP.)
W10X17 (TYP.)
45.00°
45.00°
S1
S1
G.C. NOTE
CONTRACTOR SHALL HAVE A LICENSED SURVEYOR VERIFY
ALL EXISTING DIMENSIONS, FLOOR ELEVATIONS, AND
FLOOR-TO-FLOOR HEIGHTS BEFORE ORDERING, FABRICATING
OR DETAILING STRUCTURAL COLUMNS AND HORIZONTAL FRAMING.
THIS INFORMATION MUST BE CONFIRMED AT ALL LOCATIONS WHERE
NEW FLOORS MEET EXISTING FLOORS
FRAMING PLAN NOTES:
1. TOP OF STEEL ELEVATION IS (23'-1") REFERENCED FROM
ELEVATION 78.63' (0'-0") U.N.O.
2. SEE ADDITIONAL APPLICABLE FRAMING NOTES ON DRAWING
S60.1.
3. ALL STEEL BEAMS TO CONFORM TO ASTM A992 (Fy=50KSI).
4. ALL RECTANGULAR HSS COLUMNS TO CONFORM TO ASTM A500
(GR. B)(Fy=46 KSI).
5. INDICATES DIAGONAL STEEL BRACING. SEE S40.2 FOR
BRACING ELEVATIONS.
6. INDICATES SPAN OF 6" CONCRETE SLAB ON 1 1/2" - 18 GA.
COMPOSITE DECK (GALVANIZED)REINFORCE W/ 6x6- W2.1xW2.1 WWF.
7. SEE S40.1 FOR COLUMN AND BASE PLATE SCHEDULES.
8. (6) INDICATES NUMBER OF 3/4" DIA. x 4" LONG WELDED SHEAR
STUDS.
9. DENOTES MOMENT CONNECTION. CONNECTION SHALL
BE DESIGNED FOR FULL MOMENT CAPACITY OF BEAM.
10. V.I.F. = VERIFY IN FIELD.
11. G.C. COORDINATE ALL FRAMING PENETRATIONS.
12. SEE S31.1 FOR ALTERNATE FRAMING PLANS.
13. INDICATES SLAB BONDOUT AT RECESSED TRACK RAIL
AT MOVABLE STORAGE. COORDINATE BONDOUT SIZE/RAIL
LAYOUT W/ SUPPLIER.
14. G.C./STEEL FABRICATOR TO COORDINATE CONNECTION DESIGN
AT BEAMS/COLUMNS ADJACENT TO EXISTING BUILDING
15. +/- DIMENSIONS SHALL BE CONSIDERED APPROXIMATE AND
SHALL BE VERIFIED BY G.C. BEFORE PROCEEDING WITH WORK.
16. BEAMS ARE SPACED EQUALLY BETWEEN COLUMN GRIDS
UNLESS NOTED OTHERWISE ON PLANS.
17. ALL HSS CMU SUPPORT BEAMS SHALL HAVE 3/4"Ø SHEAR STUDS
6" LONG AT 16" O.C.
18. SEE CONNECTION SCHEDULE ON S40.1 FOR BEAM END
REACTIONS.
S1
/8
HSS18X6X1/2
D1 S60.2
HSS8X6X1/2
HSS8X6X1/2
HSS8X6X1/2
HSS8X6X1/2
HSS8X6X1/2
HSS8X6X1/2
D1 S60.2
D1 S60.2
B8 S60.2
F4 S60.2
F4 S60.2
D6 S60.2
D6 S60.2
F9 S60.2
F9 S60.2
SIM.
F1 S60.3
SIM.
F1 S60.3
SIM.
W
X3
W
X3
W
X3
W10X33
D4 S60.4
F1 S40.3
F4 S40.3
F6 S40.3
B6 S60.2
SIM.
4'-11"
W14X22 (3)
W14X22
W14X22 (6) W14X22 (6)
HSS8X6X1/2
( 21'-6" )
HSS8X6X1/2
( 21'-6" )
W14X22 (8)
S1
HSS8X6X1/2
( 21'-6" )
HSS18X6X1/2
( 22'-4" )
HSS18X6X1/2
HSS18X6X5/8
( 22'-4" )
H S
S
X6 X1
/2 ( 2
2' -4
HSS14X6X1/2
( 22'-0" )
HSS14X6X1/2 ( 22'-0" )HSS14X6X1/2 ( 22'-0" )HSS14X6X1/2
( 22'-0" )
W
X2
(1 0)
(21'-6")
(21'-6")
(21'-6")
(21'-6")
(21'-6")
HSS8X6X1/2 ( 21'-6" )
HSS8X6X1/2
( 21'-6" )
SIM.
SIM.
HSS6X6X1/4 HANGER
W
X3
(1 5)
W
X3
(1 5)
H S
S
X6 X1
/2 ( 2
2' -4
H
S S
X6
X1 /2
( 2 2'
-4
D1 S60.2
SIM.
HSS6X6X1/4
HANGER
4'-9 1/2"
6'-8 7/8"
W10X12 W10X12 (4)
W10X12 (8)
W10X12 (8)
W10X17 (6)
W10X12 (8)
B6 S60.3B8
S60.3
F7 S40.3
W
X26
A1 S60.4
TYP
A1 S60.4
SIM.
S60.4 C1
S60.4 C7
(21'-6")
8' -4
S60.4 C7
SIM
W12X26 (4)
W12X26 (4)
1'-0" 3'-0"
2' -6
2'
-1 0"
CYSTOSCOPY TABLE
SUPPORT ZONE
MAX. CAPACITY 600 PSF
GENERATOR SUPPORT
ZONE 375 PSF MAX.
F1 S60.1
(22'-4")
(22'-4")
S60.4
C1 SIM.
S60.4
C1 SIM.
S60.4 C5
S60.4 C7
S60.4 C1
S60.4 C1
B3 S31.1
0 4' 8' 12'
1/8" = 1'-0"
Graphic Scale
Graphic Scale
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CONSTRUCTION
DOCUMENTS
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Auburn, ME 207.784.5100
Boston, MA 617.426.5050
Portland, ME 207.775.0053
Portsmouth, NH 603.626.1242 c HA PROJECT NUMBER: 13586
CONSTRUCT CLEAN CORE ADDITION TO
SURGICAL SUITE
PROVIDENCE, RHODE ISLAND
650-337SCALE:
C :\U se rs
\p ls m i\D oc um en ts
R ev it
L oc al s\
6-st ru c-ce nt ra l_ pl sm i.r vt
2/
/2
:3 8:
A
M
S20.2
SECOND FLOOR FRAMING
2-22-19 RMP/JCF MRM
SCALE: 1/8" = 1'-0"F2 SECOND FLOOR FRAMING PLAN
21.51 3 4 5 6 7
C
C.5
D
E
G
H
K
L
B
A
2.5 8
E4.8
EBB
EA.1
J
2.2
E.1
D8 S60.3
D1 S60.3
B1 S60.3
D2 S60.3
C.3
D.3
1.8
D6 S60.3
F4 S60.2
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
K
K
K
K
K
K
K
K
K
K
K
K
K
K
K
K
K
K
K
K
K
K
K
K
K
K
K
K
K
K
W
X2
W
X2
K
W
X2
W
X2
W
X2
W
X2
W
X2
W
X2
W 8X
W
X1
W
X2
W
X2
W
X3
W 8X10
W14X22
W14X22
W 8X10
W 8X10
W 10X12
W14X22
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K2.
5K
W 8X
W 8X24W
8X24
W 8X10W
8X10
W 14X22
W
X17
W 14X22
W
X14
W10X12
W
X14
FRAMING PLAN NOTES:
1. TOP OF STEEL ELEVATION IS (38'-0 1/2") REFERENCED FROM
ELEVATION 78.63' (0'-0") U.N.O.
2. SEE ADDITIONAL APPLICABLE FRAMING NOTES ON DRAWING
S60.1.
3. ALL STEEL BEAMS TO CONFORM TO ASTM A992 (Fy=50KSI).
4. ALL RECTANGULAR HSS COLUMNS TO CONFORM TO ASTM A500
(GR. B)(Fy=46 KSI).
5. INDICATES DIAGONAL STEEL BRACING. SEE S40.2 FOR
BRACING ELEVATIONS.
6. INDICATES SPAN OF 1 1/2" - 18 GA. TYPE B ROOF DECK
(GALVANIZED).
7. SEE S40.1 FOR COLUMN AND BASE PLATE SCHEDULES.
8. G.C. COORDINATE ALL FRAMING PENETRATIONS.
9. SEE S31.1 FOR ALTERNATE FRAMING PLANS.
10. INDICATES MOMENT CONNECTION. CONNECTION SHALL
BE DESIGNED FOR FULL MOMENT CAPACITY OF BEAM.
11. G.C./STEEL FABRICATOR TO COORDINATE CONNECTION DESIGN
AT BEAMS/COLUMNS ADJACENT TO EXISTING BUILDING.
12. +/- DIMENSIONS SHALL BE CONSIDERED APPROXIMATE AND
SHALL BE VERIFIED BY G.C. BEFORE PROCEEDING WITH WORK.
13. "TJ" INDICATES BOLTED TIE JOIST. SEE F5/S60.1.
14. PROVIDE STEEL JOIST BRIDGING PER SJI REQUIREMENTS.
15. PROVIDE UPLIFT BRIDGING AT FIRST BOTTOM CHORD PANEL
POINT (TYP.) NET UPLIFT PRESSURE = XX PSF.
16. BEAMS AND JOISTS ARE SPACED EQUALLY BETWEEN COLUMN
GRIDS UNLESS NOTED OTHERWISE ON PLANS.
17. SEE CONNECTION SCHEDULE ON S40.1 FOR BEAM END
REACTIONS.
D1
0.5
W
X2
W
X2
W
X2
W 8X
W 8X
W 8X10
2.
5K
13'-10 5/8" 8'-1" 7'-1" 4'-5 3/4"5'-8 3/4" 12'-5 1/2" 18'-4" 18'-4" 18'-4" 18'-4" 19'-10 1/2"
5'-9"
4'-4"
17'-8 5/8"
13'-11 3/4"
3'-2 1/2"
8'-9 1/4"
9'- 2 1
/4"
'-5
3/ 4"
7'- 1 3
/4"
2'- 0 7
/8"
45.00° 45.00°
'-5
/2
'-4
4' -3
/4
3'
-1
1/ 2"
7' -1
/4
3'
-2
/8
'-1
/8
/8
W
X2
W
X4
W
X2
W
X2
K
C S
W
X3
W6X16 W6X16
W6X16 W6X16
W
X2
W
X2
K
C S
K
C S
K
C S
K
C S
K
C S
W14X22
D1
D1
D1
G.C. NOTE
CONTRACTOR SHALL HAVE A LICENSED SURVEYOR VERIFY
ALL EXISTING DIMENSIONS, FLOOR ELEVATIONS, AND
FLOOR-TO-FLOOR HEIGHTS BEFORE ORDERING, FABRICATING
OR DETAILING STRUCTURAL COLUMNS AND HORIZONTAL FRAMING.
THIS INFORMATION MUST BE CONFIRMED AT ALL LOCATIONS WHERE
NEW FLOORS MEET EXISTING FLOORS
W
X2
K
C S
K
C S
K
C S
K
C S
2'-11 3/8"
5' -7
/4
3'-0 7/8"
W
X2
B3 S60.3
B1 S60.3
B3 S60.3
B1 S60.3
B5 S60.3
B5 S60.3
B7 S60.3
L6X3-1/2X3/8
F3 S60.3
D1
4 1/8" 8'-3 5/8"
7 5/8"
8'-3 5/8"
1/
4"
'-9
/4
W8X24 (37'-2 1/2") HOIST BEAM
BEARING PLATE 1/2"x7"x1'-0" W/
(2) 3/4" DIA. x 8" LONG F1554 (GR. 36)
HEADED STUDS. (TYP. AT W6 & W8
BEARING AT ELEVATOR)
EQ
C O
O R
D
EQ
F1 S60.4
W 6X
W
6X
F5 S60.4 W8X24 (37'-2 1/2")
HOIST BEAM
BEARING PLATE 1/2"x7"x1'-0" W/
(2) 3/4" DIA. x 8" LONG F1554 (GR. 36)
HEADED STUDS. (TYP. AT W6 & W8
BEARING AT ELEVATOR)
12'-0 3/4"
6"9'-
3/ 4"
1'- 8 7
/8"
F7 S60.4
F3 S60.4
D1 S60.4
W 10X12
W 10X12
W 8X10
W 8X10
1'- 8 7
/8"
W 8X10
W8X10 D1
W8X10
D6 S60.4
6'-3"
D10 S60.4
D10 S60.4
2.
5K
W12X16W12X16W12X16W12X16W12X16W12X16
F1 S40.3
F4 S40.3
F6 S40.3
W14X22W14X22 ( 37'-10" )
W14X22 ( 37'-10" )
W18X40 ( 37'-10" )
W14X22 ( 37'-10" )
W14X22 ( 37'-10" )
W14X22
W14X22 W14X22
W14X22 ( 37'-10" )
W10X12 ( 37'-10" ) W10X12 ( 37'-10" )
W8X10 ( 37'-10" )
W14X30 ( 37'-10" )
W12X14 ( 37'-10" )
W14X22 ( 37'-10" )
W14X22 ( 37'-10" )
W12X14 ( 37'-10" )
W8X10 ( 37'-10" )
W12X14 ( 37'-10" )
W14X22 ( 37'-10" )
W12X14 ( 37'-10" )
W12X14 ( 37'-10" )
W8X10 ( 37'-10" )
W14X22 ( 37'-10" )
W12X14 ( 37'-10" )
W14X30 ( 37'-10" )
W8X10 ( 37'-10" )
W14X22 ( 37'-10" )
W16X36 ( 37'-10" )
W14X22 ( 37'-10" )
W12X14 ( 37'-10" )
K
K
4'-9 1/2"
6'-8 7/8"
TJ
TJ
TJ
EQ
EQ
EQ
F7 S40.3
W14X22
W14X22D1
W8X10 ( 37'-10" )W8X10 ( 37'-10" )
D1W12X16
2.
5K
2.
5K
2.
5K
2.
5K
2.
5K
F3 S60.1
F3 S60.1
B9 S60.3
0 4' 8' 12'
1/8" = 1'-0"
Graphic Scale
Graphic Scale
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CONSTRUCTION
DOCUMENTS
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Auburn, ME 207.784.5100
Boston, MA 617.426.5050
Portland, ME 207.775.0053
Portsmouth, NH 603.626.1242 c HA PROJECT NUMBER: 13586
CONSTRUCT CLEAN CORE ADDITION TO
SURGICAL SUITE
PROVIDENCE, RHODE ISLAND
650-337SCALE:
C :\U se rs
\p ls m i\D oc um en ts
R ev it
L oc al s\
6-st ru c-ce nt ra l_ pl sm i.r vt
2/
/2
:3 9:
A
M
S30.1
ROOF FRAMING
2-22-19 RMP/JCF MRM
SCALE: 1/8" = 1'-0"F2 ROOF FRAMING PLAN
C
D
G
H
45.00°
45.00°
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
K
C S
'-4
19'-10 1/2"
D1
SEE S30.1 FOR
ADDITIONAL BASE BID
INFORMATION
NOT SHOWN HERE
2 3
C.5
D
E
2.52.2
E.1
C.3
D.3
1.8
SEE S10.1 FOR
ADDITIONAL BASE BID
INFORMATION
NOT SHOWN HERE
ELEVATOR PIT NOT
CONSTRUCTED UNDER
DEDUCT ALTERNATE 2A
C.5
D
E
2.52.2
E.1
D.3 HSS12X8X1/2
W10X33
W
X1
W
X3
W
X1
6" LIGHT GAUGE JOISTS
AT 12" O.C.
SPAN OF 3/4" USG
CONCRETE DECK
F7 S31.1
F9 S31.1
3/
4"
17'-4 5/8" 9 5/8"
6' -2
/4
HSS8X8X1/4
POST
HSS6X6X1/4
POST
HSS6X6X1/4
POST
NOTES:
1. * INDICATES DIMENSION TO
BE VERIFIED W/ ELEVATOR SUPPLIER.
2. TOP OF STEEL ELEVATION IS (23'-0 1/4").
3. SEE S20.2 FOR ADDITIONAL BASE BID
INFORMATION NOT SHOWN HERE.
8 3/8"
D7 S31.1
C.5
D
E
2.52.2
E.1
D.3
W8X10 W
8X
W 8X
W 8X
W8X24 W8X24 W
8X
W 8X
W 8X
W 8X
D1
HSS6X6X3/8
POST (TYP.)
NOTES:
1. * INDICATES DIMENSION TO
BE VERIFIED W/ ELEVATOR SUPPLIER.
2. TOP OF STEEL ELEVATION IS (38'-0 1/2").
3. SEE S30.1 FOR ADDITIONAL BASE BID
INFORMATION NOT SHOWN HERE.
3/
4"
6' -2
/4
HSS12X8X1/2
17'-4 5/8" 9 5/8"
8 3/8"
5'
C
D
G
H
K
E4.8
J
45.00°
45.00°
P2B
F5.5
SEE S10.1 FOR
ADDITIONAL BASE BID
INFORMATION
NOT SHOWN HERE
ELEVATOR PIT
NOT CONSTRUCTED
UNDER DEDUCT
ALTERNATE 2A
[-7'-9"]
F.99
5'
D
G
H
K
E4.8
J
W 10X17
W
X17
W 10X17
W
X17
6" LIGHT GAUGE
JOISTS AT 12" O.C.
SPAN OF 3/4" USG
CONCRETE DECK
4'-10"
NOTES:
1. * INDICATES DIMENSION TO
BE VERIFIED W/ ELEVATOR SUPPLIER.
2. TOP OF STEEL ELEVATION IS (23'-0 1/4").
3. SEE S20.2 FOR ADDITIONAL BASE BID
INFORMATION NOT SHOWN HERE.
HSS6X6X1/4
POST
HSS6X6X1/4
POST
7'-
5'- 8 1
/8"
1'-1 5/8"
B3 S31.1
F.99
6 1/4"
5'
G.4'
G.5'
4.5'
G
H
K
E4.8
J
W 8X10
W 8X
W 8X10
W 8X
W
8X
W 8X10
W 8X10
D1
HSS6X6X3/8
BP1
HSS6X6X1/4 POST
(TYP. 2 LOCATIONS)
NOTES:
1. * INDICATES DIMENSION TO
BE VERIFIED W/ ELEVATOR SUPPLIER.
2. TOP OF STEEL ELEVATION IS (38'-0 1/2").
3. SEE S30.1 FOR ADDITIONAL BASE BID
INFORMATION NOT SHOWN HERE.
4'-10"
HSS6X6X3/8
BP1
F.99
C.5
3/4" USG CONCRETE DECK
6" LIGHT GAUGE JOISTS
(SEE PLAN)
HSS (SEE PLAN)
W BEAM
(SEE PLAN)
8" LIGHT GAUGE
STUD WALL
6" LIGHT GAUGE
STUD WALL
3/8" STIFFENER
PLATE FULLY WELDED
BOTH SIDES OF BEAM WEB
10'-2 5/8" 9 3/4"
VERIFY W/ ELEVATOR SUPPLIER
6'-2 3/4" +/- 2 1/2"HSS COLUMN
(SEE PLAN)
TYP.
L3x3x1/4 x 0'-4"
(TYP. 2 SIDES OF COLUMN)
2.2
3/4" USG
CONCRETE DECK
HSS POST
(SEE PLAN)
6" LIGHT GAUGE JOIST
(BEYOND) (SEE PLAN)
W BEAM
(SEE PLAN)
8 3/8" 1/2"
L3x3x1/4 x 0'-4" LONG
EACH SIDE OF POST
D.3
7 1/4"
8 1/4"
W BEAM
(SEE PLAN)
CONCRETE SLAB ON
METAL DECK (SEE PLAN)
HSS COLUMN
(SEE SCHEDULE)
L3x3x1/4 x 0'-4"
CENTER ON GRID 2.2
HSS (SEE PLAN)
9 1/4"
8"
1/2" STIFFENER PLATE
1/2" BENT PLATE
7'-11"
1/2" 1/2"
3/4" USG CONCRETE DECK
6" LIGHT GAUGE JOISTS
(SEE PLAN)
W BEAM
(SEE PLAN)
W BEAM
(SEE PLAN)
HSS POST
(SEE PLAN)
HSS POST
(SEE PLAN)
0 4' 8' 12'
1/8" = 1'-0"
Graphic Scale
Graphic Scale
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CONSTRUCTION
DOCUMENTS
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Auburn, ME 207.784.5100
Boston, MA 617.426.5050
Portland, ME 207.775.0053
Portsmouth, NH 603.626.1242 c HA PROJECT NUMBER: 13586
CONSTRUCT CLEAN CORE ADDITION TO
SURGICAL SUITE
PROVIDENCE, RHODE ISLAND
650-337SCALE:
C :\U se rs
\p ls m i\D oc um en ts
R ev it
L oc al s\
6-st ru c-ce nt ra l_ pl sm i.r vt
2/
/2
:3 9:
A
M
S31.1
DEDUCT ALTERNATE PLANS AND
DETAILS
2-22-19 RMP/JCF MRM
SCALE: 1/8" = 1'-0"B1 PARTIAL ROOF FRAMING PLAN (DEDUCT ALTERNATE 3A)
SCALE: 1/8" = 1'-0"F1 PARTIAL FOUNDATION PLAN (DEDUCT ALTERNATE 2A)
SCALE: 1/8" = 1'-0"F3
PARTIAL SECOND FLOOR FRAMING
PLAN (DEDUCT ALTERNATE 2A)
SCALE: 1/8" = 1'-0"F5
PARTIAL ROOF FRAMING PLAN
(DEDUCT ALTERNATE 2A)
SCALE: 1/8" = 1'-0"D1 PARTIAL FOUNDATION PLAN (DEDUCT ALTERNATE 2A)
SCALE: 1/8" = 1'-0"D3
PARTIAL SECOND FLOOR FRAMING
PLAN (DEDUCT ALTERNATE 2A)
SCALE: 1/8" = 1'-0"D5 PARTIAL ROOF FRAMING PLAN (DEDUCT ALTERNATE 2A)
SCALE: 3/4" = 1'-0"F7 SECTION (DEDUCT ALTERNATE 2A)
SCALE: 1 1/2" = 1'-0"F9 SECTION
SCALE: 1 1/2" = 1'-0"D7 SECTION
SCALE: 3/4" = 1'-0"B3 SECTION
TYPE "A"
1 1/2"1 1/2"
1/
2"
1/ 2"
STEEL COLUMN
(SEE SCHEDULE)
ANCHOR BOLTS
(SEE SCHEDULE)
EQ
EQ
EQ EQ
PLATE WASHER
TYPE "B"
2"2"
2" 2"
STEEL COLUMN
(SEE SCHEDULE)
ANCHOR BOLTS
(SEE SCHEDULE)
EQ
EQ
EQ EQ
PLATE WASHER
TYPE "C"
1 1/2"1 1/2"
1/
2"
1/ 2"
STEEL COLUMN
(SEE SCHEDULE)
ANCHOR BOLTS
(SEE SCHEDULE)
1/
2"
1/ 2"
4 1/2" 2"
PLATE WASHER
CONNECTION SCHEDULE
BEAM SIZE BEAM REACTION
(FIRST & SECOND FLOOR LEVEL)
BEAM REACTION
(ROOF LEVEL)
W8X10
W10X12
W10X17
W10X19
W10X22
W10X26
W10X33
W12X14
W12X19
W12X26
W12X30
W12X35
W12X40
W12X50
W14X22
W14X26
W14X30
W14X38
W14X43
W14X48
W16X26
W16X31
W16X36
W16X45
W16X67
W18X40
8.0 KIPS
11.0 KIPS
16.0 KIPS
18.0 KIPS
14.0 KIPS
8.0 KIPS
17.0 KIPS
14.0 KIPS
16.0 KIPS
18.0 KIPS
35.0 KIPS
15.0 KIPS
14.0 KIPS
34.0 KIPS
46.0 KIPS
24.0 KIPS
44.0 KIPS
12.0 KIPS
25.0 KIPS
25.0 KIPS
30.0 KIPS
27.0 KIPS
62.0 KIPS
40.0 KIPS
49.0 KIPS
43.0 KIPS
NOTE: ALL CONNECTIONS WILL HAVE A MINIMUM OF 2 3/4" DIA. A325 BOLTS
AND A 1/4" SHEAR TAB.
8.0 KIPS
W8X24 8.0 KIPS
8.0 KIPS
10.0 KIPS
8.0 KIPS
8.0 KIPS
W12X16 8.0 KIPS
14.0 KIPS
14.0 KIPS
10.0 KIPS
11.0 KIPS
15.0 KIPS
W16X40 15.0 KIPS
27.0 KIPS
Graphic Scale
Graphic Scale
Graphic Scale
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CONSTRUCTION
DOCUMENTS
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Auburn, ME 207.784.5100
Boston, MA 617.426.5050
Portland, ME 207.775.0053
Portsmouth, NH 603.626.1242 c HA PROJECT NUMBER: 13586
CONSTRUCT CLEAN CORE ADDITION TO
SURGICAL SUITE
PROVIDENCE, RHODE ISLAND
650-337SCALE:
C :\U se rs
\p ls m i\D oc um en ts
R ev it
L oc al s\
6-st ru c-ce nt ra l_ pl sm i.r vt
2/
/2
:3 9:
A
M
S40.1
SCHEDULES
2-22-19 RMP/JCF MRM
BASE PLATE SCHEDULE
MARK DEPTH WIDTH THICKNESS ANCHORS EMBEDMENT PLATE TYPE
BP1 1'-0" 1'-0" 3/4" (4) 3/4" DIA. F1554 (GR.36) 9" A
BP2 1'-0" 1'-0" 1" (4) 3/4" DIA. F1554 (GR.36) 9" A
BP4* 1'-1" 1'-1" 1 1/4" (4) 1" DIA. F1554 (GR.36) 24" B
BP5* 1'-1" 1'-1" 1 1/2" (4) 1 1/4" DIA. F1554 (GR.36) 24" B
BP6 1'-2" 1'-2" 3/4" (4) 3/4" DIA. F1554 (GR.36) 9" A
BP7 1'-2" 1'-2" 1" (4) 3/4" DIA. F1554 (GR.36) 9" A
BP8 1'-2" 1'-2" 1 1/4" (4) 3/4" DIA. F1554 (GR.36) 9" A
BP9* 1'-3" 1'-3" 1 1/4" (4) 1" DIA. F1554 (GR.36) 24" B
BP10* 1'-3" 1'-3" 1 1/2" (4) 1" DIA. F1554 (GR.36) 24" B
BP11 9 1/2" 1'-0" 3/4" (4) 3/4" DIA. F1554 (GR.36) 9" C
BP12 1'-0" 1'-0" 1 1/4" (4) 3/4" DIA. F1554 (GR.36) 9" A
BP13 1'-2" 1'-2" 1 1/2" (4) 3/4" DIA. F1554 (GR.36) 9" A
BP14* 1'-0" 1'-0" 1 1/4" (4) 3/4" DIA. F1554 (GR.36) 24" A
BP15* 1'-3" 1'-3" 1 1/2" (4) 1 1/4" DIA. F1554 (GR.36) 30" B
BP16* 1'-1" 1'-1" 1 1/2" (4) 1 1/4" DIA. F1554 (GR.36) 30" B
STEEL COLUMN SCHEDULE
LOCATION TYPE
BASE PLATE
(BP)
SHEAR
LUG
A-0.5 HSS8X8X5/16 BP6
A-1 HSS8X8X5/16 BP6
A-1.5 HSS6X6X3/8 BP12 SL-2
A-2 HSS6X6X3/8 BP1
A.5-1 HSS6X6X1/4 BP5* SL-1
B-0.5 HSS8X8X1/2 BP7
B-1 HSS8X8X5/16 BP13 SL-1
B-1.5 HSS8X8X5/16 BP6
B-2 HSS8X8X1/4 BP6
C-2.5 HSS6X6X1/2 BP1
C-3 HSS6X6X1/2 BP1
C-4 HSS8X8X1/2 BP7
C-5 HSS8X8X1/2 BP7
C-6 HSS8X8X1/2 BP7
C-7 HSS8X8X5/16 BP7
C-9 HSS8X8X3/8 BP6
C.3-0.5 HSS8X8X5/16 BP6
C.3-1 HSS6X6X3/8 BP14* SL-2-2
C.3-1.5 HSS8X8X5/16 BP7
C.5-1.5 HSS6X6X5/16 BP1
C.5-2.2 HSS8X8X5/16 BP6
C.5-3 HSS6X6X1/4 BP1
D-1.5 HSS6X6X5/16 BP1
D-3 HSS6X6X5/8 BP4* SL-2
D-4 HSS8X8X3/8 BP8
D-5 HSS8X8X3/8 BP7
D-6 HSS8X8X3/8 BP7
D-7 HSS8X8X5/16 BP15* SL-1-1
D-8 HSS8X8X5/8 BP15* SL-1-1A
D.3-1.8 HSS6X6X5/16 BP1
D.3-2.2 HSS6X6X3/8 BP11
E-3 HSS8X8X1/2 BP10* SL-2-2
E-4 HSS8X8X1/2 BP9* SL-2
E-5 HSS8X8X1/2 BP6
E-6 HSS8X8X1/2 BP6
E-7 HSS8X8X1/2 BP15* SL-1
G-10 HSS6X6X1/4 BP1
H-9 HSS6X6X1/2 BP16* SL-2
H-10 HSS6X6X1/4 BP1
J-11 HSS8X8X3/8 BP6
K-10 HSS6X6X5/8 BP1
K-11 HSS8X8X3/8 BP6
* INDICATES SUPPLEMENTAL TENSION REINFORCEMENT REQUIRED. SEE DETAIL F6/S50.2.
FOOTING SCHEDULE
FOOTING
MARK LENGTH WIDTH THICKNESS
REINFORCING
(BOTTOM) U.N.O.
F8B* 19'-10" 8'-0" 2'-0" SEE D3/S50.1
F8C 20'-0" 8'-0" 2'-0" (24) #6 (SHORT WAY)
(17) #6 (LONG WAY)
F10 10'-0" 10'-0" 2'-0" (12) #6 (EACH WAY)
F10A 10'-0" 9'-0" 2'-0" (12) #6 (EACH WAY)
F10B 10'-0" 10'-0" 1'-6" (12) #6 (EACH WAY)
F10B** 11'-9" 14'-0" 2'-1" SEE A1/S50.1
F10C*** 23'-4" 10'-0" 2'-0" SEE C9/S50.1
F11 11'-0" 11'-0" 2'-6" (17) #6 (EACH WAY)
F11.5 12'-0" 12'-0" 2'-0" (15) #6 EACH WAY
F13 11'-6" 18'-0" 2'-0" (22) #6 (SHORT WAY)
(14) #6 (LONG
WAY)(TOP AND
BOTTOM)
FOOTING SCHEDULE
FOOTING
MARK LENGTH WIDTH THICKNESS
REINFORCING
(BOTTOM) U.N.O.
CF1* SEE C4/S50.1 SEE C4/S50.1 2'-6" SEE C4/S50.1
CF2 SEE C6/S50.1 SEE C6/S50.1 2'-6" SEE C6/S50.1
CF3 SEE D1/S50.1 SEE D1/S50.1 2'-6" SEE D1/S50.1
F4.5 4'-6" 4'-6" 1'-8" (7) #5 (EACH WAY)
F5* 5'-0" 5'-0" 1'-0" (6) #6 (EACH WAY)
F5.5 5'-6" 5'-6" 1'-0" (6) #6 (EACH WAY)
F5.5B 6'-0" 6'-0" 2'-0" (11) #6 (EACH WAY)
F5B** 15'-6" 5'-0" 1'-6" SEE A2/S50.1
F6* 6'-0" 6'-0" 2'-0" (13) #6 (EACH WAY)
F7 7'-0" 7'-0" 1'-0" (6) #6 (EACH WAY)
F7.5A** 7'-6" 4'-0" 1'-6" (8) #6 (SHORT WAY)
(4) #6 (LONG WAY)
F7.5B 7'-6" 4'-6" 2'-6" (12) #6 (SHORT WAY)
(7) #6 (LONG WAY)
F7A 7'-0" 7'-0" 2'-0" (10) #6 (EACH WAY)
F7C 7'-0" 7'-0" 2'-0" (11) #6 (EACH WAY)
F8 8'-0" 8'-0" 1'-0" (6) #6 (EACH WAY)
F8.5 8'-6" 8'-6" 2'-0" (11) #6 (EACH WAY)
PIER SCHEDULE
PIER
MARK LENGTH WIDTH VERTICAL REINFORCING BENT TIES
P1A 20" 20" (8) #6 #4 AT 12"
P1B 20" 20" (8) #6 #4 AT 8"
P2A 24" 24" (8) #6 #4 AT 12"
P2B 24" 24" (8) #6 #4 AT 10"
P3A 29" 29" (12) #6 #4 AT 12"
P3B 29" 29" (12) #6 #4 AT 10"
P3C 29" 29" (20) #6 #4 AT 6"
P3D 29" 29" (16) #6 #4 AT 10"
P12 18" 18" (8) #6 #4 AT 10"
FOOTING SCHEDULE NOTES:
* 90 DEGREE HOOK ALL BARS BOTH ENDS.
** 90 DEGREE HOOK SHORT BARS BOTH ENDS.
*** 90 DEGREE HOOK LONG BARS BOTH ENDS.
NOTE: SEE BASE PLATE SCHEDULE ON S40.1 FOR LOCATIONS WHERE
SUPPLEMENTAL TENSION REINFORCEMENT IS REQUIRED IN PIERS.
SEE DETAIL F6/S50.2.
A
C C.5 D E
HS
S5
X5 X5
/1
6 HSS5X5X5/16
HS
S6
X6 X5
/1
6 HSS6X6X5/16
H S
S 6X
6X 1/
H S
S 6X
6X 1/
4H S
S 6X
6X 5/
H S
S 8X
8X 1/
8'-2 1/4" 7'-1 3/4" 13'-4"
W10X33
W10X17 W10X17 W14X22
W14X22
W14X22 W14X22
HS
S4
X4 X1
/4
HSS4X4X1/4
S40.2 F5
S40.2
F7 TYP.
TYP.
S40.2
F5 TYP.
SIM.
S40.2
F1 TYP.
SIM.
(1 5K
) (15K)
(3 0K
) (30K)
(4 5K
(45K)
3 4
HSS
5X
5X 5/1
6 HSS5X5X5/16
HSS5X5X5/16HSS
5X
5X 5/1
18'-4"
W14X22
W14X30
H S
S 8X
8X 1/
W14X22
H S
S 8X
8X 1/
HS
S4
X4 X1
/4
HSS4X4X1/4
S40.2 F7
S40.2
F5 TYP.
S40.2 F1
TYP.
TYP.
SIM.
(1 0K
(10K)
(4 5K
) (45K)
(5 0K
) (50K)
D E
HS
S5
X5 X5
/1
6 HSS5X5X5/16
HS
S6
X6 X5
/1
6 HSS6X6X5/16
13'-4"
W14X22
W14X22
H S
S 8X
8X 1/
H S
S 8X
8X 5/
W14X26
HS
S4
X4 X1
/4
HSS4X4X1/4
S40.2 F5
S40.2
F7 TYP.
TYP.
S40.2
F1 TYP.
SIM.
(1 5K
) (15K)
(5 0K
) (50K)
(5 5K
) (55K)
7 8
HSS5X
5X
5/1
6 HSS5X5X5/16
HSS5X
5X
5/1
6 HSS5X5X5/16
19'-10 1/2"
W16X31
W16X31
H S
S 8X
8X 5/
H S
S 8X
8X 5/
W16X36
HS
S4
X4 X1
/4
HSS4X4X1/4
S40.2 F7
S40.2 F5
TYP.
TYP.
S40.2
F1 TYP.
SIM.
(1 5K
) (15K)
(4 0K
) (40K)
(4 5K
(45K)
B C.3 22'-7 3/4"
W12X26
H S
S 8X
8X 1/
H S
S 8X
8X 5/
HSS5X5X5/16
W12X26 S40.2
F3 TYP.
S40.2
F1 TYP.
SIM.
(15K)
21.51
HS
S4
X4 X1
/4
HS
S5
X5 X5
/1
HSS5X5X5/16
8'-1" 7'-1"
W14X22 W14X22
W14X22
H S
S 6X
6X 3/
H S
S 6X
6X 3/
H S
S 8X
8X 5/
W14X22
S40.2 F1
S50.1 F3
S40.2 F7
TYP.
SIM.S40.2
F1
(1 5K
(3 0K
(35K)
1.5
W14X30 W14X22
W14X30
W14X22 W14X22
H S
S 6X
6X 5/
2.2
HSS
5X
5X 5/1
H S
S 8X
8X 5/
11'-6 3/4"
S40.2 F3
S40.2
F1TYP.
TYP.
(1 5K
1.51
HS
S5
X5 X5
/1
HS
S5
X5 X5
/1 6H
S S
6X 6X
3/
H S
S 8X
8X 5/
W14X22
W14X22
8'-1"
W14X22
HS
S5
X5 X5
/1
S40.2
F1TYP.
SIM.
S40.2
F3 TYP.
S40.2
F7TYP.
SIM.
(5 K)
(2 5K
(3 5K
BA A.5
HSS5X
5X
5/1
6 HSS5X5X5/16
10'-8 3/4" 14'-8 3/4" 22'-7 3/4"
W14X22 W14X43
W14X30
H S
S 8X
8X 5/
H S
S 8X
8X 5/
H S
S 6X
6X 3/
C.3
W14X22
H S
S 6X
6X 1/
HS
S5 X5
X5 /1
6 HSS5X5X5/16 S40.2
F7
S40.2 F5
S40.2
F1 TYP.
SIM.
TYP.(5
5K
(55K)
(40 K)
(40K)
W14X22
W14X22
W14X22
H S
S 8X
8X 5/
H S
S 6X
6X 1/
HS
S5
X5 X5
/1
6 HSS5X5X5/16
HS
S5
X5 X5
/1
6 HSS5X5X5/16
HS
S5
X5 X5
/1
6 HSS5X5X5/16 S40.2
F7
S40.2 F5
TYP.
TYP.
S40.2
F1 TYP.
SIM.
(1 5K
) (15K)
(3 5K
) (35K)
(5 0K
(50K)
TYP.
TYP.
NOTES:
1. SAW CUT TUBES.
2. BRACING ON COLUMN CENTERLINE.
3. ENLARGED BASE PLATES DUE TO SPECIALITY
ENGINEER DESIGN SHALL BE COORDINATED
BY G.C. TO FIT ON PIER.
HSS COLUMN
WORK POINT
HSS BRACE
1/2" GUSSET/THROUGH
PLATE MIN. (AS REQ'D)
1" CLR. (ALL SIDES)
SHEAR LUG WHERE INDICATED ON
BRACED FRAME ELEVATIONS
(SEE SHEAR LUG DETAILS FOR ADD'L INFO)
SHEAR KEY
(WHERE INDICATED
ON PLAN)
1/
2"
PL. WASHER:
- 2"x2"x1/4" AT 3/4" DIA. A.R.
- 3"x3"x3/8" AT 1" DIA. A.R.
WELDED 4 SIDES @ ALL BRACED FRAMES
AND BEAM TO COLUMN MOMENT
CONNECTIONS AND SHEAR WALLS
WHERE REINF. INTERFERES W/
KEY DISCONTINUE & SPLICE ON
EITHER SIDE OF KEY
OMIT LEVELING PLATE AT ALL
SHEAR LUG LOCATIONS. UTILIZE
NUTS BELOW BASEPLATE TO
SUPPORT COLUMN
GROUT BELOW BASEPLATE
AND AROUND SHEAR LUG
AFTER COLUMN IS PLACED
& PLUMB IN FINAL LOCATION
2"
MIN
ERECTION BOLT
STEEL COLUMN
WORK POINT
NOTES:
1. SAW CUT TUBES.
2. BRACING ON COLUMN
CENTERLINE.
STEEL BEAM
ERECTION BOLT
TYP.
GUSSET PLATE
HSS BRACE
1/4" CAP PLATE
2" MIN.
NOTES:
1. SAW CUT TUBES.
2. BRACING ON COLUMN
CENTERLINE.
WORK POINT
STEEL COLUMN
GUSSET PLATE
(TYP.)
TYP.
TYP.
ERECTION BOLT
STEEL BEAM
ERECTION
BOLT
HSS BRACE
HSS BRACE
2" MIN.
NOTES:
1. SAW CUT TUBES.
2. BRACING ON COLUMN CENTERLINE.
3. PROVIDE SAME DETAILING FOR BRACING ABOVE BEAM.
4. PROVIDE BEAM BOTTOM FLANGE DIAGONAL BRACE
CENTERED BETWEEN STIFFENER PLATES.
(2) 3/8" STIFFENER
PLATES (BOTH SIDES)
STEEL BEAM
WORK POINT
HSS BRACE
(TYP.)
ERECTION BOLT
ERECTION BOLT
HSS BRACE
GUSSET PLATE
W BEAM
(SEE PLAN)
GUSSET PLATE
SECTION A
W BEAM
OR JOIST
(SEE PLAN)
1/4" CONNECTION PLATE
(FULLY WELDED) (TYP.)
L3x3x1/4 BRACE.
CENTER BETWEEN
STIFFENER PLATES
SHEAR LUG SECTION
BASE PLATE (MATCH SHEAR LUG
PLATE THICKNESS, MIN.)
(SEE COLUMN SCHEDULE)
SHEAR LUG SCHEDULE
MARK DIMENSIONS TYPE
SL-1 1 1/2"x3 1/2"x0'-10" LONG A
SL-1-1A 1 1/2"x3 1/2"x0'-10" LONG C
SL-2 1 1/4"x3 1/2"x0'-8" LONG A
SL-2-2 1 1/4"x3 1/2"x0'-8" LONG B
SL-1-1 1 1/2"x3 1/2"x0'-10" LONG B
TYPE - A TYPE - B TYPE - C
SCHEDULE
SEE BASE PLATE
SC
H
ED
U
LE
SE
E
BA
SE
P
LA
TE
SHEAR
LUG
SHEAR
LUG
SHEAR
LUG
SCHEDULE
SEE BASE PLATE
SCHEDULE
SEE BASE PLATE
SC
H
ED
U
LE
SE
E
BA
SE
P
LA
TE
SC
H
ED
U
LE
SE
E
BA
SE
P
LA
TE 45.00°
BRACING NOTES:
1. LOADS INDICATED ON FRAME ELEVATIONS ARE
THE UNFACTORED AXIAL LOAD.
2. LOADS SHOWN MAY BE IN TENSION OR COMPRESSION.
3. CONNECTION DESIGN AND CALCULATIONS TO BE
COMPLETED BY AN ENGINEER REGISTERED IN THE
STATE OF RHODE ISLAND. SUBMIT CALCULATIONS
FOR REVIEW. DESIGN OF CONNECTIONS SHALL BE
COMPLETED USING THE UNIFORM FORCE METHOD.
4. SLIP CRITICAL BOLTS (SC) ARE REQUIRED AT ALL
MOMENT CONNECTIONS AND BRACED FRAME
CONNECTIONS.
A.2'A'
5'
21.51 3 4 5 6 7
C
C.5
D
E
G
H
K
L
B
A
2.5 8
E4.8
EBB
EA.1
S4 0.
B
J
S4 0.
B
S40.2 B3
2.2
E.1
C.3
D.3
1.8
S40.2 B6
S40.2 D3
S4 0.
B
S4 0.
D
S40.2 D1
0.5
S40.2 D5
S40.2 B8
0 4' 8' 12'
1/8" = 1'-0"
Graphic Scale
Graphic Scale
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CONSTRUCTION
DOCUMENTS
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Auburn, ME 207.784.5100
Boston, MA 617.426.5050
Portland, ME 207.775.0053
Portsmouth, NH 603.626.1242 c HA PROJECT NUMBER: 13586
CONSTRUCT CLEAN CORE ADDITION TO
SURGICAL SUITE
PROVIDENCE, RHODE ISLAND
650-337SCALE:
C :\U se rs
\p ls m i\D oc um en ts
R ev it
L oc al s\
6-st ru c-ce nt ra l_ pl sm i.r vt
2/
/2
:3 9:
A
M
S40.2
BRACING ELEVATIONS AND
DETAILS
2-22-19 RMP/JCF MRM
SCALE: 1/8" = 1'-0"D3 BRACED FRAME ON LINE 3
SCALE: 1/8" = 1'-0"B7 BRACED FRAME ON LINE E
SCALE: 1/8" = 1'-0"D2 BRACED FRAME ON LINE 7
SCALE: 1/8" = 1'-0"D1 BRACED FRAME ON LINE D
SCALE: 1/8" = 1'-0"D5 BRACED FRAME ON LINE 0.5
SCALE: 1/8" = 1'-0"B4 BRACED FRAME ON LINE A
SCALE: 1/8" = 1'-0"B3 BRACED FRAME ON LINE C.5
SCALE: 1/8" = 1'-0"B6 BRACED FRAME ON LIN C.3
SCALE: 1/8" = 1'-0"B1 BRACED FRAME ON LINE1
SCALE: 1/8" = 1'-0"B8 BRACED FRAME ON LINE H
NO SCALEF7 TYP. BRACE DETAIL
NO SCALEF3 TYP. BRACE DETAIL
NO SCALEF1 TYP. BRACE DETAIL
NO SCALEF5 TYP. BRACE DETAIL
NO SCALEF9 SHEAR LUG DETAILS
SCALE: 1/16" = 1'-0"D6 BRACING KEY PLAN
COL
4 5 6
HSS10X6X1/2 HSS10X6X1/2
HSS8X6X1/2HSS8X6X1/2
18'-4" 18'-4"
D1 S40.3
(33'-10")
(28'-10 5/8") (28'-10 5/8")
(33'-10")
A1 S60.4
A1 S60.4
D1 S40.3
D3 S40.3
10.5 13'-10 5/8"
HSS8X6X1/2
HSS8X6X1/2
(33'-8")
(28'-11")
D1 S40.3
SIM.
D3 S40.3
SIM.
A' 2 1.5 1 7'-1" 8'-1"
HSS8X6X1/2 HSS8X6X1/2
HSS8X6X1/2HSS8X6X1/2
(33'-7 1/2") (33'-7 1/2")
(29'-1 1/2") (29'-1 1/2")
D1 S40.3
SIM.
A1
S60.4
A1 S60.4
D3 S40.3
SIM.
HSS BEAM
(SEE FRAMING ELEVATIONS
ON S40.3)
PL 1/2"x14" (CONT.)
10 1/8"
1'-0 1/4" 1 3/4"
BA C.3
25'-5 1/2" 22'-7 3/4"
HSS18X6X1/2
HSS18X6X1/2
HSS18X6X1/2
HSS18X6X1/2
D1 S40.3
SIM.
(34'-6")
(28'-11")
(34'-6")
(28'-11")
A1 S60.4
A1 S60.4
D1 S40.3
SIM.
D3 S40.3
SIM. D3
S40.3
SIM.
1/2" PLATE (CONT.)
10 1/8"
1'-0 1/4" AT F4 & F7/S40.3
5 3/4" AT F1 & F6/S40.3
1 3/4"
0 4' 8' 12'
1/8" = 1'-0"
Graphic Scale
Graphic Scale
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CONSTRUCTION
DOCUMENTS
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Auburn, ME 207.784.5100
Boston, MA 617.426.5050
Portland, ME 207.775.0053
Portsmouth, NH 603.626.1242 c HA PROJECT NUMBER: 13586
CONSTRUCT CLEAN CORE ADDITION TO
SURGICAL SUITE
PROVIDENCE, RHODE ISLAND
650-337SCALE:
C :\U se rs
\p ls m i\D oc um en ts
R ev it
L oc al s\
6-st ru c-ce nt ra l_ pl sm i.r vt
2/
/2
:4 0:
A
M
S40.3
FRAMING ELEVATIONS AND
DETAILS
2-22-19 RMP/JCF MRM
SCALE: 1/4" = 1'-0"F1 FRAMING ELEVATION ALONG LINE E
SCALE: 1/4" = 1'-0"F4 FRAMING ELEVATION ALONG LINE C.3
SCALE: 1/4" = 1'-0"F6 FRAMING ELEVATION ALONG LINE A
SCALE: 1 1/2" = 1'-0"D1 SECTION
SCALE: 1/4" = 1'-0"F7 FRAMING ELEVATION ALONG LINE 0.5
SCALE: 1 1/2" = 1'-0"D3 SECTION
COLUMN (SEE SCHEDULE)
BASE PLATE (SEE SCHEDULE)
DOWELS TO MATCH
VERTICAL PIER REINFORCING
SPLICE MIN. 24 BAR DIA.
PIER REINFORCING
(SEE SCHEDULE)
FOOTING REINFORCING
EACH WAY
(SEE FOOTING SCHEDULE)
SEE FOUNDATION PLAN
FOR TOP OF FOOTING
ELEVATIONS
HEADED ANCHOR RODS
(SEE BASE PLATE SCHEDULE)
2" 3"
PI
ER
S C
H
ED
U
LE
TI
E
SP
AC
IN
G
P
ER
1/ 2"
T
IE
S P
AC
IN
G
#4 TIES
(SEE PIER SCHEDULE)
(U .N
.O
9"
3/4" NON-SHRINK GROUT
AND 1/4" LEVELING PLATE
(U.N.O. AT SHEAR LUG LOCATIONS)
PLATE WASERS:
PL 2"x2"x1/4" AT 3/4" DIA. ANCHOR RODS PL 3"x3"x3/8" AT 1" DIA. ANCHOR RODS PL 3 1/2"x3 1/2"x1/2" AT 1 1/4" DIA. ANCHOR RODS
(WELD WASHERS AT LATERAL/MOMENT FRAMES ONLY)
COLUMN (SEE SCHEDULE)
BASE PLATE (SEE SCHEDULE)
3/4" NON-SHRINK GROUT
AND 1/4" LEVELING PLATE
(U.N.O. AT SHEAR LUG LOCATIONS)
FOOTING REINFORCING
EACH WAY
(SEE FOOTING SCHEDULE)
3" C
LE
AR
SEE FOUNDATION PLAN
FOR TOP OF FOOTING
ELEVATIONS
HEADED ANCHOR RODS
(SEE BASE PLATE SCHEDULE)
SC
H
ED
U
LE
SE
E
BA
SE
P
LA
TE
PLATE WASHERS:
PL 2"x2"x1/4" AT 3/4" DIA. ANCHOR RODS PL 3"x3"x3/8" AT 1" DIA. ANCHOR RODS PL 3 1/2"x3 1/2"x1/2" AT 1 1/4" DIA. ANCHOR RODS
(WELD WASHERS AT LATERAL/ MOMENT FRAMES ONLY)
SOIL BEARING
1. WALL AND COLUMN FOOTINGS DESIGNED FOR AN ANTICIPATED
SOIL BEARING OF 2000 PSF.
2. IF ADEQUATE SOIL BEARING IS NOT ENCOUNTERED AT THE
INDICATED BOTTOM OF FOOTING LOCATION, CONTRACTOR IS TO
REPORT TO THE STRUCTURAL ENGINEER BEFORE PROCEEDING WITH
FOOTING PLACEMENT.
3. ALL EXCAVATIONS FOR THE FOUNDATION SHALL BE APPROVED BY
THE ENGINEER BEFORE PLACING ANY CONCRETE FOOTINGS. COORDINATE
INSPECTION W/ CONSTRUCTION DOCUMENTS AND SPECIAL INSPECTION
REQUIREMENTS.
CONCRETE
1. STRENGTH OF CONCRETE AT 28 DAYS SHALL BE:
WALLS AND FOOTINGS - 4500 PSI
EXTERIOR SLABS - 4500 PSI
INTERIOR SLABS - 3000 PSI
2. ALL EXTERIOR FOOTINGS TO BE MIN. 3'-4" BELOW FINISH GRADE.
3. TOP OF ALL FOOTINGS TO BE MIN. 8" BELOW BOTTOM OF FLOOR
SLAB UNLESS NOTED OTHERWISE.
4. BOTTOM OF ALL FOOTINGS TO BE ON ADEQUATE SOIL BEARING.
5. IF BASEMENT AND FIRST FLOOR SLABS ARE NOT POURED BEFORE
BACKFILLING, FOUNDATION WALLS TO BE ADEQUATELY BRACED
BEFORE BACKFILLING AND UNTIL ABOVE SLABS ARE PLACED AND SET.
6. SEE SPECIFICATIONS FOR SPECIAL REQUIREMENTS FOR
ARCHITECTURAL EXPOSED CONCRETE, ANCHORING OF MASONRY TO
CONCRETE WALLS AND COLUMNS, AND CHAMFER OF EXTERNAL
CORNERS OF CONCRETE BEAMS, GIRDERS, COLUMNS, ETC.
7. SEE ARCHITECTURAL AND MECHANICAL DRAWINGS AND
SPECIFICATIONS FOR SIZE AND LOCATION OF DOOR FRAMES,
THRESHOLDS, ETC., AND CONCRETE PADS, PIERS, PIPE SLEEVES, ETC.
CONCRETE REINFORCING
1. ALL REINFORCING STEEL TO BE ASTM-A615 GRADE 60, DETAILED AND
FABRICATED IN ACCORDANCE WITH THE "ACI MANUAL OF STANDARD
PRACTICE" (ACI-315-LATEST).
2. REINFORCEMENT TO HAVE MIN. CONCRETE COVER AS FOLLOWS:
A. CONCRETE DEPOSITED AGAINST GROUND, INCLUDING
FOOTINGS - 3"
B. CONCRETE EXPOSED TO EARTH OR WEATHER,
INCLUDING WALKS, PIERS, WALLS, COLUMNS, AND
EXTERIOR SLABS - 1 1/2" (#5 OR SMALLER) AND 2" (#6 OR LARGER)
C. CONCRETE NOT EXPOSED TO WEATHER OR IN
CONTACT WITH GROUND:
I. SLABS, WALLS, AND JOISTS - 3/4"
II. BEAMS AND COLUMNS, TIES, STIRRUPS,
REINFORCEMENT - 1 1/2"
3. ALL CONCRETE SLABS, PADS, BEAMS AND PIERS SHALL BE
REINFORCED SUCH THAT THE RATIO OF REINFORCEMENT
AREA TO GROSS CONCRETE AREA EXCEEDS 0.0033 UNLESS NOTED
OTHERWISE.
4. ALL ITEMS THAT ARE TO BE EMBEDDED INTO CONCRETE SHALL BE SECURED
IN PLACE PRIOR TO THE CONCRETE PLACEMENT. UTILIZE ADDITIONAL
REINFORCEMENT, TEMPLATES, OR OTHER APPROVED METHODS TO SECURELY
PLACE ALL EMBEDMENTS AT PROPER LOCATIONS. "WET-SETTING" OF ANY
EMBEDMENTS INTO PLASTIC CONCRETE IS NOT ALLOWED. EMBEDMENTS
INCLUDE, BUT ARE NOT LIMITED TO, ANCHOR RODS, REBAR REINFORCEMENTS,
DOWELS, ANGLES, PLATES, ANCHOR INSERTS, SLEEVES, AND SHELF BULKHEADS.
5. INSTALLATION AND SECURE PLACEMENT OF CONCRETE REINFORCEMENT SHALL
BE INSPECTED BY AN INDEPENDANT TESTING AGENCY IN ACCORDANCE WITH
THE REQUIREMENTS OF THIS PROJECT, INCLUDING THE STATEMENT OF
SPECIAL INSPECTIONS. CONCRETE REINFORCEMENT SHALL BE PLACED AND
SECURED WITHIN FORMS A MINIMUM OF 24 HOURS PRIOR TO THE SCHEDULED
CONCRETE PLACEMENT TO CONDUCT THE INSPECTION.
SEE FOUNDATION PLAN
FOR OVERALL PIT DIMENSIONS
1' -0
3' -4
1'-4"
TYP.
6"
6" PVC
WATER STOP
(4 SIDES)
6" PVC
WATER STOP
(4 SIDES)
x 2'-0"
2'-0" 3"
COVER PLATE
(SEE ARCH'L)
L2x2x3/16
(TYP. 4 SIDES)
PROVIDE RECESS IN CONCRETE FLOOR
AROUND SUMP TO RECEIVE COVER PLATE
AND BE FLUSH WITH ELEVATOR PIT FLOOR
1' -0
2'
-0
#5 AT 12" EACH WAY
EACH FACE
#5 BENT BARS AT 12" C.C.
EACH WAY AT PIT
#5 AT 12"
EACH WAY
#5 DOWELS AT 12"
(TYP.) (2'-0"x2'-0")
#5 AT 12"
EACH WAY
TOP AND BOTTOM
#5 DOWELS
AT 12" O.C.
9" 7"
3/ 4"
8"
3/4" 3/4" CHAMFER
M A
N U
FA
C
TU
R
ER
4' -0
" V
ER
IF
Y
W
IT
H
EL
EV
AT
O R
O P N
G
8" A
T D
O O
R
21.51
A
2'-0" 5'-0" 3'-3" 4'-9" 4'-10"
ZONE 1
ZONE 2 ZONE 3 ZONE 4 ZONE 5
(3
B
A R
S
(7
B
A R
S
(5
B
A R
S
(7
B
A R
S
(7
B
A R
S
TO
P
A N
D B
O
TT
TO
P
A N
D B
O
TT
TO
P
A N
D B
O
TT
TO
P
A N
D B
O
TT
TO
P
A N
D B
O
TT
4' -0
4'
-0
4'-6"
(12) #6 BARS TOP AND BOTT
B
C.3
3' -9
5'
-9
(6) #6 BARS
TOP & BOTT
(7) #6 BARS
TOP & BOTT
(27) #6 BARS
TOP & BOTT
(1 3)
BA
R
S
TO
P
B
O
TT
(6
B
A R
S
TO
P
B
O
TT
(9
B
A R
S
TO
P
B
O
TT
4'-3" 4'-0"
8'-10"
6' -0
/4
ZO
N
E
1' -6
ZO
N
E
4' -6
ZO
N
E
'-0
ZO
N
E
4' -9
ZO
N
E
3' -8
ZONE 6
1'-9"
ZONE 7
4'-9"
ZONE 8
3'-6"
ZONE 9
4'-6"
ZONE 10
2'-7"
(4
B
A R
S
TO
P
B
O
TT
(3)#6 BARS T&B
(9)#6 BARS T&B
(3)#6 BARS T&B
(9)#6 BARS T&B
(16) #6 BARS
TOP & BOTT
C
D
5'-0" 5'-0"
2' -0
4'
-0
'-6
3'
-9
2' -1
(3) #6 BARS
TOP & BOTT
(5) #6 BARS
TOP & BOTT
(14) #6 BARS
TOP & BOTT
(5) #6 BARS
TOP & BOTT
(3) #6 BARS
TOP & BOTTZO
N
E
ZO
N
E
ZO
N
E
ZO
N
E
ZO
N
E
4' -0
4'
-0
(1 2)
BA
R
S
TO
P
B
O
TT
G
2' -6
2'
-6
2'-9"3'-6"3'-0"3'-6"2'-9"
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5
(3
B
A R
S
TO
P
B
O
TT
(6
B
A R
S
TO
P
B
O
TT
(4
B
A R
S
TO
P
B
O
TT
(6
B
A R
S
TO
P
B
O
TT
(3
B
A R
S
TO
P
B
O
TT
4'-2 1/8" 4'-2 1/8"
(8)#6 BARS TOP& BOTT
3 4
D
E
ZO
N
E
2' -1
5'
-9
7' -9
5'
-6
3' -9
(9) #6 BARS
TOP & BOTT
(13) #6 BARS
TOP & BOTT
(9) #6 BARS
TOP & BOTT
(7) #6 BARS
TOP & BOTTZO
N
E
ZO
N
E
ZO
N
E
ZO
N
E
(5
B
A R
S
TO
P
B
O
TT
(9
B
A R
S
TO
P
B
O
TT
(2 1)
BA
R
S
TO
P
B
O
TT(9
B A
R S
TO
P
B
O
TT
(6
B
A R
S T
O P
B
O
TT
3'-9" 5'-6" 12'-9" 5'-9" 2'-1"
ZONE 6 ZONE 7 ZONE 8 ZONE 9 ZONE 10
6'-6" 6'-6" 5'-0"
6' -6
6'
-6
5' -0
(5) #6 BARS
TOP & BOTT
(2 0)
B A
R S
T O
P
B O
TT
(20) #6 BARS
TOP & BOTT
21.5
B
6' -6
7'
-6
3'-0" 7'-1" 1'-8"
ZONE 1
1'-3"
ZONE 2
3'-6"
ZONE 3
4'-0"
ZONE 4
3'-0"
(3
B
A R
S T
O P
B
O
TT
(5
B
A R
S T
O P
B
O
TT
(9
B
A R
S T
O P
B
O
TT
(7
B
A R
S T
O P
B
O
TT
(17) *6 BARS TOP & BOTT
D
E
H
6'-6"
6'-6"
7'-3" 7'-3"
4'-6" 5'-6" 15'-3" 5'-6" 1'-9"
ZONE 6 ZONE 7 ZONE 8 ZONE 9
ZONE
ZO
N
E
3' -7
ZO
N
E
5' -9
ZO
N
E
7' -9
ZO
N
E
5' -6
ZO
N
E
3' -3
(8
B
A R
S T
O P
B
O
TT
(9
B
A R
S T
O P
B
O
TT
(2 4)
B A
R S
T O
P
B O
TT
(9
B
A R
S T
O P
B
O
TT
(3
B
A R
S T
O P
B
O
TT
(6) #6 BARS TOP & BOTT
(9) #6 BARS TOP & BOTT
(12) #6 BARS TOP & BOTT
(9) #6 BARS TOP & BOTT
(6) #6 BARS TOP & BOTT
(4) #6 TOP & BOTT
(7) #6 TOP & BOTT
(13) #6 TOP & BOTT
(9) #6 TOP & BOTT(6) #6 TOP & BOTT
'-1
0"
6' -6
6'
-0
5'-4 1/2"
4'- 6"
ZONE 152'-
2"
ZONE 144'-
9"
ZONE 137'-
9"
ZONE 125'-
6"
ZONE 113'-
3"
(20
6 T
OP &
B
OTT
(19) #6 BARS TOP & BOTT
6' -6
(2 2)
B A
R S
TO
P
B
O
TT
SUPPLEMENTAL TENSION
REINFORCING WHERE
REQUIRED, SEE PIER
SCHEDULE
ALTERNATE POSITION
OF HOOKS IN PLACING
SUCCESSIVE SETS
OF BARS
VERTICAL REINFORCING
#6 TIES (SEE PIER
SCHEDULE)
TYPICAL PIERS P3A/P3B
29" x 29" (12) #6 BARS
TYPICAL PIERS P2A/P2B
24" x 24" (8) #6 BARS
ALTERNATE POSITION
OF HOOKS IN PLACING
SUCCESSIVE SETS
OF BARS
VERTICAL REINFORCING
#6 TIES (SEE PIER
SCHEDULE)
TYPICAL PIERS P1A/P1B
20" x 20" (8) #6 BARS
TYPICAL PIERS P3D
29" x 29" (16) #6 BARS
TYPICAL PIERS P3C
29" x 29" (20) #6 BARS
SUPPLEMENTAL
TENSION REINFORCING
WHERE REQUIRED,
SEE PIER SCHEDULE
ALTERNATE POSITION
OF HOOKS IN PLACING
SUCCESSIVE SETS
OF BARS
VERTICAL
REINFORCING
#6 TIES (SEE PIER
SCHEDULE)
0 2' 4' 6'
1/4" = 1'-0"
Graphic Scale
Graphic Scale
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CONSTRUCTION
DOCUMENTS
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Auburn, ME 207.784.5100
Boston, MA 617.426.5050
Portland, ME 207.775.0053
Portsmouth, NH 603.626.1242 c HA PROJECT NUMBER: 13586
CONSTRUCT CLEAN CORE ADDITION TO
SURGICAL SUITE
PROVIDENCE, RHODE ISLAND
650-337SCALE:
C :\U se rs
\p ls m i\D oc um en ts
R ev it
L oc al s\
6-st ru c-ce nt ra l_ pl sm i.r vt
2/
/2
:4 0:
A
M
S50.1
TYPICAL FOUNDATION NOTES
AND DETAILS
2-22-19 RMP/JCF MRM
NO SCALEF1 TYP. PIER AND FOOTING DETAIL
NO SCALEF3 TYP. COLUMN FOOTING DETAIL
NO SCALEF8 GENERAL FOUNDATION NOTES
NO SCALEF6 TYP. SECTION AT ELEVATOR PIT
SCALE: 1/4" = 1'-0"D3 REINFORCING LAYOUT AT FOOTING F8B*
SCALE: 1/4" = 1'-0"C4 REINFORCING LAYOUT AT FOOTING CF1*
SCALE: 1/4" = 1'-0"C9 REINFORCING LAYOUT AT FOOTING F10C***
SCALE: 1/4" = 1'-0"A2 REINFORCING LAYOUT AT FOOTING F5B**
SCALE: 1/4" = 1'-0"C6 REINFORCING LAYOUT AT FOOTING CF2
SCALE: 1/4" = 1'-0"A1 REINFORCING LAYOUT AT FOOTING F10B**
SCALE: 1/4" = 1'-0"D1 REINFORCING LAYOUT AT FOOTING CF3
SCALE: 1/2" = 1'-0"D6 TYPICAL PIER REINFORCING DETAILS
CD
1'-0" 15'-4" 1'-0"
4' -9
6"
EXISTING FOOTING
FINISH GRADE
P2B
P2B
24"x57" CONCRETE
BEAM
F4 S50.2
F11 F8C
F1
S50.2
FINISH GRADE 1'-0"1'-0"
F8C
4' -9
#4 STIRRUPS AT 12" O.C.
(5) #8 TOP BARS
W/ 90 DEGREE HOOKS
EACH END
(5) #8 BOTTOM BARS
W/ 90 DEGREE HOOKS
EACH END
"/3
0"
S E
E B
A S
E P
LA
TE
S C
H E
D U
LE
FOOTING
(SEE PLAN)
PIER
(SEE PLAN)
ANCHOR BOLT
(SEE BASE PLATE SCHEDULE
3" MAX.
#7 BAR WITH STANDARD
90 DEGREE HOOK BOTH ENDS
(TYP. EACH ANCHOR
BOLT LOCATION)
SC
H
ED
U
LE
SE
E
FO
O
TI
N
G
11E4.8
EXISTING PIER AND
FOOTING TO BE
DEMOLISHED
EXISTING FOOTING
EXISTING BASE
PLATE TO
REMAIN
EXISTING COLUMN TO REMAIN
INSTALL NEW ANCHOR
RODS TO MATICH EXISITNG
8" CMU WALL
ELEVATOR PIT
PIER (SEE PLAN)
FOOTING (SEE PLAN) PLACE NEW FOOTING,
THEN BACKFILL AS REQ'D
TO INSTALL ELEVATOR PIT
11E4.8
EXISTING PIER AND
FOOTING TO BE
DEMOLISHED
EXISTING BASE
PLATE TO REMAIN
EXISTING
COLUMN TO
REMAIN
INSTALL NEW
ANCHOR RODS TO
MATCH EXISTING
HSS COLUMN (SEE SCHEDULE)
PIER (SEE PLAN)
FOOTING
(SEE PLAN)
PIER (SEE PLAN)
21.51 8'-1" 7'-1"
EXISTING
FOOTING
MATCH BOTTOM OF
EXISTING FOOTING
ELEVATION
F8B*
P3A P3A P1B
(2) #4 BARS
TOP AND BOTTOM &
(2) #4 AT MID-POINT
(2) #4 VERT. BARS
AT 12" O.C.
EXISTING FOOTING
HSS COLUMN
(SEE SCHEDULE)
PIER
(SEE PLAN)
1' -6
DRILL AND EPOXY GROUT
VERTICAL PIER REINFORCING
18" INTO EXISTING FOOTING
0 1' 2' 3'
1/2" = 1'-0"
0 6" 1' 2'
3/4" = 1'-0"
Graphic Scale
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CONSTRUCTION
DOCUMENTS
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Auburn, ME 207.784.5100
Boston, MA 617.426.5050
Portland, ME 207.775.0053
Portsmouth, NH 603.626.1242 c HA PROJECT NUMBER: 13586
CONSTRUCT CLEAN CORE ADDITION TO
SURGICAL SUITE
PROVIDENCE, RHODE ISLAND
650-337SCALE:
C :\U se rs
\p ls m i\D oc um en ts
R ev it
L oc al s\
6-st ru c-ce nt ra l_ pl sm i.r vt
2/
/2
:4 0:
A
M
S50.2
FOUNDATION DETAILS
2-22-19 RMP/JCF MRM
SCALE: 1/2" = 1'-0"F1 SECTION
SCALE: 1/2" = 1'-0"F4 SECTION
SCALE: 3/4" = 1'-0"F6 TYPICAL SUPPLEMENTAL TENSION REINFORCEMENT
SCALE: 1/2" = 1'-0"F8 SECTION
SCALE: 1/2" = 1'-0"D1 SECTION
SCALE: 1/2" = 1'-0"D3 SECTION
SCALE: 1/2" = 1'-0"D6 SECTION
MASONRY
1. ALL MASONRY WALLS AND PARTITIONS SHALL BE REINFORCED.
2. COMPRESSIVE STRENGTH OF MASONRY, F'm, SHALL BE MIN. 1500 PSI.
3. COMPRESSIVE STRENGTH OF LOAD BEARING CONCRETE MASONRY UNITS SHALL
BE IN ACCORDANCE WITH ASTM C90, F'm SHALL BE MIN 1900 PSI.
4. MORTAR SHALL BE TYPE S, WITH A MIN. COMPRESSIVE STRENGTH OF
1800 PSI AT 28 DAYS.
5. GROUT SHALL HAVE A COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS.
6. WHERE BEAMS, JOISTS, OR COLUMNS BEAR ON MASONRY, THE MASONRY
SHALL BE SOLID OR FILLED SOLID, A MIN. OF 2'-0" TO EACH SIDE OF THE
CENTERLINE OF BEARING, FOUR COURSES HIGH, OR A CONTINUOUS CONCRETE
FILLED BOND BEAM SHALL BE LOCATED UNDER THE BEARING.
7. ALL ITEMS THAT ARE TO BE EMBEDDED INTO MASONRY SHALL BE SECURED
IN PLACE PRIOR TO THE GROUT PLACEMENT. UTILIZE ADDITIONAL
REINFORCEMENT, TEMPLATES, OR OTHER APPROVED METHODS TO SECURELY
PLACE ALL EMBEDMENTS AT PROPER LOCATIONS. "WE-SETTING" OF ANY
EMBEDMENTS INTO GROUT IS NOT ALLOWED. EMBEDMENTS INCLUDE, BUT
ARE NOT LIMITED TO, ANCHOR RODS, REBAR REINFORCEMENTS, DOWELS,
ANGLES, PLATES, ANCHOR INSERTS AND SLEEVES.
STRUCTURAL STEEL
1. STRUCTURAL STEEL SHALL BE ASTM A992, GR. 50 (Fy=50 KSI). EXCEPT STRUCTURAL TUBING TO BE Fy=46 KSI, UNLESS NOTED OTHERWISE.
2. CONNECTIONS SHALL BE DESIGNED BY THE STEEL FABRICATOR.
3. CONTRACTOR SHALL APPLY TWO BRUSH COATS OF ASPHALT TO COLUMNS AND
BASE PLATES EXPOSED TO FILL AFTER COLUMN IS IN PLACE.
4. VERIFY WITH MECHANICAL DRAWINGS FOR LOCATION OF DUCTS, PIPING, ETC.
THROUGH FLOOR AND ROOF CONSTRUCTION BEFORE SPACING JOISTS.
5. ALL STEEL CONNECTIONS NOT SPECIFICALLY DETAILED ON THE STRUCTURAL
DRAWINGS SHALL BE EVALUATED BY A PROFESSIONAL ENGINEER HIRED BY THE
STEEL FABRICATOR. COMPLETE CONNECTION DESIGN CALCULATIONS SHALL BE
SUBMITTED FOR ALL MEMBER CONNECTIONS ASSOCIATED WITH THE LATERAL
FORCE RESISTING SYSTEM (BRACED FRAMES, ETC.). ALL GRAVITY LOAD
CONNECTIONS SHOWN ON THE SHOP DRAWING SUBMITTAL SHALL BE EVALUATED
BY THE FABRICATOR’S ENGINEER, BUT CALCULATIONS SHALL NOT BE SUBMITTED
FOR REVIEW. GRAVITY LOAD CONNECTIONS UNLESS OTHERWISE INDICATED IN
THE CONNECTION SCHEDULE SHALL BE DESIGNED FOR THE FULL UNIFORM LOAD
CAPACITY OF THE BEAM (1/2 VOL. METHOD). FOR NON-COMPOSITE CONSTRUCTION
AND 1.5 TIMES THE FULL UNIFORM LOAD CAPACITY FOR COMPOSITE CONSTRUCTION.
STEEL FABRICATOR’S ENGINEER SHALL INCLUDE A STAMPED
LETTER CERTIFYING THAT ALL DETAILED CONNECTIONS SHOWN IN THE SHOP
DRAWING SUBMITTAL HAVE BEEN REVIEWED AND ARE ADEQUATE TO SUPPORT
THE SPECIFIED LOADS. THE CONNECTION DESIGN PACKAGE, STAMPED BY THE
PROFESSIONAL ENGINEER, SHALL BE FORWARDED TO HARRIMAN PRIOR TO OR
WITH THE STRUCTURAL STEEL SHOP DRAWINGS FOR REVIEW. SHOP DRAWINGS
WILL NOT BE REVIEWED WITHOUT RECEIPT OF ALL SUPPORTING CONNECTION
DESIGN INFORMATION.
6. ALL STAIR STRUCTURES SHALL BE DESIGNED BY A SPECIALY ENGINEER HIRED
BY THE FABRICATOR. ALL DESIGNS SHALL MEET THE REQUIREMENTS OF THE
2009 INTERNATIONAL BUILDING CODE (IBC). STAIRS AND LANDINGS SHALL BE
DESIGNED FOR 100 PSF LIVE LOAD. COORDINATE ALL DETAILS WITH THE
ARCHITECTURAL DRAWINGS, AND SUBMIT COMPLETE FABRICATION DRAWINGS
WITH ALL NECESSARY SUPPORTING ENGINEERING CALCULATIONS FOR REVIEW.
DRAWINGS AND CALCULATIONS SHALL BE STAMPED BY A PROFESSIONAL
ENGINEER LICENSED IN THE STATE OF THE PROJECT.
STEEL ROOF DECK
1. ROOF DECK TYPE "B", 1 1/2" DEEP x 18 GAUGE, G60 GALVANIZED
FASTENING PATTERN:
DECK ATTACHMENT - 5/8" DIAMETER PUDDLE WELDS OR APPROVED
MECHANICAL FASTENERS
PATTERN - 36/4 EXCEPT AS OTHERWISE NOTED
SIDELAPS - #10 SCREWS STITCH AT 12" O.C. MAX. SPACING.
COMPOSITE FLOOR DECK
1. COMPOSITE FLOOR DECK 1-1/2" DEEP x 18 GAUGE. G60 GALVANIZED
FASTENING PATTERN:
DECK ATTACHMENT - 5/8" DIAMETER PUDDLE WELDS OR APPROVED
MECHANICAL FASTENERS
PATTERN - AT SUPPORTS. MAX. 12" O.C.
SIDELAPS - 5/8" DIAMETER PUDDLE WELDS AT MIDSPAN OR 3'-0" ON
CENTER, WHICHEVER IS SMALLER
MISCELLANEOUS
1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING
CONDITIONS
BEFORE PROCEEDING WITH THE WORK.
2. CONTRACTOR SHALL REPORT ANY VARIATIONS FOUND AT THE
SITE BEFORE PROCEEDING WITH THAT PART OF THE WORK.
DESIGN INFORMATION
APPLICABLE UNIFIED FACILITIES CRITERIA (UFC) GUIDES:
UFC 1-200-01 GENERAL BUILDING REQUIREMENTS
UFC 3-301-01 STRUCTURAL ENGINEERING
UFC 3-310-04 SEISMIC DESIGN FOR BUILDINGS
DESIGN CODE = RHODE ISLAND STATE BUILDING CODE, 2013.
LIVE LOAD:
MECHANICAL ROOMS - 150 PSF
CORRIDORS, LOBBIES, STAIRS AND EXITS - 100 PSF
FUTURE FLOORS - 100 PSF
CLINICAL AND SUPPORT SERVICES - 80 PSF + 20 PSF
PARTITION ALLOWANCE
ROLLING STORAGE/RECORD FILES - 300 PSF
SNOW LOAD:
Pg = 30 PSF Ce = 1.0 Ct = 1.0 Is = 1.20 Pf = 30 PSF
WIND LOAD:
BASIC WIND SPEED (V) = 144 MPH (3 SEC GUST)
I = 1.15 (CATEGORY IV)
EXPOSURE - B (HURRICANE REGION)
INTERNAL PRESSURE COEFFICIENT (GCpi) = +/- 0.18
SEISMIC LOAD:
Occupancy Category - IV Ie = 1.50 Sds = 0.246, Sd1 = 0.100
SITE CLASS - D
SEISMIC DESIGN CATEGORY - C
S.F.R. SYSTEM - STEEL SYSTEM NOT SPECIFICALLY
DESIGNED FOR SEISMIC RESISTANCE.
GRIND
SMOOTH
6" CMU
BRICK VENEER
BENT PLATE
3/8"x5"x0'-9 1/2" (LLH) (GALV.)
W/ MIN. 8" MIN. BEARING EACH END
L6x4x3/8 (LLV) (GALV.)
W/ 8" MIN. BEARING
EACH END
1/2" 4" 9 1/2"
STEEL JOIST
BRIDGING
STEEL DECK
ANGLE CROSS
BRIDGING
HVAC DUCT
BRIDGING
ANGLE CROSS
BRIDGING
1/2" DIA. BOLT
(TYP.)
NOTE: MAKE CROSS BRIDGING HORIZONTAL IN
LAST BRIDGING BAY BEFORE TERMINATING BRIDGING,
SIMILAR TO THIS DETAIL
MIN. 4" REINFORCED
CONCRETE SLAB
STEEL DECK
FASTEN TO SUPPORTS
FLOOR JOISTFLOOR JOIST
STEEL BEAM
PER SJI
PROVIDE ERECTION BOLTS
PER SJI REQUIREMENTS
DETAIL SIMILAR AT ROOF
1/4" 1/4"
CONCRETE MASONRY LINTEL SCHEDULE
NOM. BLOCK HEIGHTNOM. BLOCK WIDTH REINFORCING
6" (1) #5
8" 8" (2) #5
8" 16" (2) #5
8"
MASONRY OPENING
6'-0" OR LESS
6'-11" OR LESS
7'-0" TO 12'-0"
WIDTH
NOM.
WIDTH
NOM.
OPENING
MASONRY
CMU LINTEL
5/
8"
1' -3
/8
"GROUT
REINFORCING*
NOTES:
1. LINTEL SCHEDULE BASED ON F'm = 1900 PSI.
2. LINTEL UNITS MUST BE SHORED (MIN. 3
DAYS).
3. MIN. BEARING AT EACH END = 8".
4. USE OF MORTAR TO FILL LINTELS IS NOT
PERMITTED.
5. COORDINATE WITH ARCHITECTURAL
DRAWINGS FOR ALL WALL OPENINGS WHERE
A CONCRETE MASONRY LINTEL IS REQUIRED.
REINFORCING
* AT EXTERIOR CMU LINTELS, PROVIDE REINFORCING TOP AND BOTTOM.
T/WALL
1/
M
AS
O N
R Y
O P
EN
IN
G
M
IN
ROOF OR FLOOR
OPENING
ROOF OR FLOOR
FRAMING
L4x4x5/16, TYP.
(4 SIDES)
L5x5x5/16 CLIPS
L4x4x5/16, TYP.
(4 SIDES)
NOTES:
1. PROVIDE AT ALL OPENINGS LARGER THAN 12". LOCATIONS ARE NOT ALL IDENTIFIED
ON THE PLANS AND SHALL BE COORDINATED BY THE CONTRACTOR FOLLOWING
INSTRUCTIONS PROVIDED BELOW.
2. FOR OPENINGS UP TO 6" - NO REINFORCING REQUIRED.
3. FOR OPENINGS FROM 6" TO 12" - USE 24"x24" 16 GA. COVER PLATE
SCREWED TO DECK…
This is the start of the file's text. The full file is on GovTribe.