0004 - 596-22-700 Spec Section 08 71 00 Revisions.pdf
PDF 199 KB Posted
- Solicitation number
- 36C77625B0040
About this file
This document is a Door Hardware specification for the EHRM Infrastructure Upgrades project at the Sousley VA Campus in Lexington, Kentucky. The specification provides detailed requirements for door hardware installation, including continuous hinges, butt hinges, door closing devices, overhead closers, door stops, locks, and electrical hardware components. Key technical specifications include:
Hardware requirements cover a range of door types with specific installation guidelines, such as hinge size requirements based on door thickness and width, and provisions for fire-rated doors. The document includes multiple hardware sets for different door configurations, with many sets featuring advanced security elements like electric strikes, card readers, PIR rex sensors, and magnetic switches. Manufacturers must comply with ANSI/BHMA standards, and hardware must meet accessibility requirements, with special attention to fire safety, egress, and coordination with security systems. The specification also mandates anti-microbial coatings on hand-operated hardware and provides detailed installation, warranty, and finishing instructions.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA 596-22-700 | EHRM Infrastructure Upgrades Sousley VA Campus - Lexington, KY
Bid Documents – Addendum 01 05-01-22
08 71 00-1
DOOR HARDWARE
SECTION 08 71 00
DOOR HARDWARE
PART 1 - GENERAL
1.1 DESCRIPTION
Door hardware and related items necessary for complete installation and operation of doors.
1.2 RELATED WORK
Caulking: Section 07 92 00 JOINT SEALANTS.
Application of Hardware: Section 08 16 00, INTERIOR WOOD DOORS.
Painting: Section 09 91 00, PAINTING.
Card Readers: Section 28 13 11, PHYSICAL ACCESS CONTROL SYSTEMS.
Electrical: Division 26, ELECTRICAL.
1.3 GENERAL
All hardware shall comply with ABAAS, (Architectural Barriers Act
Accessibility Standard) unless specified otherwise.
Provide rated door hardware assemblies where required by most current version of the International Building Code (IBC).
Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to
NFPA requirements.
Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.
The following items shall be of the same manufacturer, except as otherwise specified:
1. Mortise locksets.
2. Hinges for hollow metal and wood doors.
3. Surface applied overhead door closers.
4. Exit devices.
5. Floor closers.
Bid Documents – Addendum 01 05-01-22
08 71 00-2
DOOR HARDWARE
1.4 WARRANTY
Automatic door operators shall be subject to the terms of FAR Clause
52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below:
1. Locks, latchsets, and panic hardware: 5 years.
2. Door closers and continuous hinges: 10 years.
1.5 MAINTENANCE MANUALS
In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled
"INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.
1.6 SUBMITTALS
Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. Submit 6 copies of the schedule per Section 01 33
23. Submit 2 final copies of the final approved schedules to VAMC Locksmith as record copies (VISN Locksmith if the VAMC does not have a locksmith).
Hardware Schedule: AHC certified hardware consultant to prepare and submit hardware schedule in the following form:
Hardware Item
Quantity Size Reference Publication Type No.
Finish Mfr.
Name and Catalog No.
Key Control Symbols
UL Mark (if fire rated and listed)
ANSI/BHMA
Finish Designation
Samples and Manufacturers' Literature:
1. Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers
Association shall be submitted for approval. Tag and mark all items with manufacturer's name, catalog number and project number.
2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.
Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent
Bid Documents – Addendum 01 05-01-22
08 71 00-3
DOOR HARDWARE
testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval.
1.7 DELIVERY AND MARKING
Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to COR for reference purposes. Tag shall identify items by Project Specification number and manufacturer's catalog number. These items shall remain on file in
COR's office until all other similar items have been installed in project, at which time the COR will deliver items on file to Contractor for installation in predetermined locations on the project.
1.8 PREINSTALLATION MEETING
Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contractor and Installer, Project
Engineer and VA Locksmith, Hardware Consultant, and Hardware Manufacturer’s
Representative. Review the following:
1. Inspection of door hardware.
2. Job and surface readiness.
3. Coordination with other work.
4. Protection of hardware surfaces.
5. Substrate surface protection.
6. Installation.
7. Adjusting.
8. Repair.
9. Field quality control.
10. Cleaning.
1.9 INSTRUCTIONS
Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated on drawings by symbols. Symbols for hardware sets consist of letters (e.g., "HW") followed by a number. Each number designates a set of hardware items applicable to a door type.
Keying: All cylinders shall be keyed into existing Master Key System. Provide removable core cylinders that are removable only with a special key or tool without disassembly of knob or lockset. Cylinders shall be 7 pin type. Keying information shall be furnished at a later date by the COR.
Bid Documents – Addendum 01 05-01-22
08 71 00-4
DOOR HARDWARE
1.10 APPLICABLE PUBLICATIONS
The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.
ASTM International(ASTM):
F883-13.................Padlocks
E2180-18................Standard Test Method for Determining the
Activity of Incorporated Antimicrobial Agent(s)
In Polymeric or Hydrophobic Materials
American National Standards Institute/Builders Hardware Manufacturers
Association (ANSI/BHMA):
A156.1-06...............Butts and Hinges
A156.2-03...............Bored and Pre-assembled Locks and Latches
A156.3-08...............Exit Devices, Coordinators, and Auto Flush Bolts
A156.4-08...............Door Controls (Closers)
A156.5-14...............Cylinders and Input Devices for Locks.
A156.6-05...............Architectural Door Trim
A156.8-05...............Door Controls-Overhead Stops and Holders
A156.11-14..............Cabinet Locks
A156.12-05 .............Interconnected Locks and Latches
A156.13-05..............Mortise Locks and Latches Series 1000
A156.14-07 .............Sliding and Folding Door Hardware
A156.15-06..............Release Devices-Closer Holder, Electromagnetic and Electromechanical
A156.16-08..............Auxiliary Hardware
A156.17-04 .............Self-Closing Hinges and Pivots
A156.18-06..............Materials and Finishes
A156.20-06 .............Strap and Tee Hinges, and Hasps
A156.21-09..............Thresholds
A156.22-05..............Door Gasketing and Edge Seal Systems
A156.23-04..............Electromagnetic Locks
A156.24-03..............Delayed Egress Locking Systems
A156.25-07 .............Electrified Locking Devices
A156.26-06..............Continuous Hinges
A156.28-07 .............Master Keying Systems
Bid Documents – Addendum 01 05-01-22
08 71 00-5
DOOR HARDWARE
A156.29-07 .............Exit Locks and Alarms
A156.30-03 .............High Security Cylinders
A156.31-07 .............Electric Strikes and Frame Mounted Actuators
A156.36-10..............Auxiliary Locks
A250.8-03...............Standard Steel Doors and Frames
National Fire Protection Association (NFPA):
80-10...................Fire Doors and Other Opening Protectives
101-09..................Life Safety Code
Underwriters Laboratories, Inc. (UL):
Building Materials Directory (2008)
PART 2 - PRODUCTS
2.1 CONTINUOUS HINGES
A. ANSI/BHMA A156.26, Grade 1-600.
1. Listed under Category N in BHMA's "Certified Product Directory."
B. General: Minimum 0.120-inch- (3.0-mm-) thick, hinge leaves with minimum overall width of 4 inches (102 mm); fabricated to full height of door and frame and to template screw locations; with components finished after milling and drilling are complete
C. Continuous, Barrel-Type Hinges: Hinge with knuckles formed around a
Teflon-coated 6.35mm (0.25-inch) minimum diameter pin that extends entire length of hinge.
1. Base Metal for Interior Hinges: Stainless steel.
2. Base Metal for Hinges for Fire-Rated Assemblies: Stainless steel.
3. Provide with non-removable pin (hospital tip option) at lockable outswing doors.
4. Where required to clear adjacent casing, trim, and wall conditions and allow full door swing, provide wide throw hinges of minimum width required.
5. Provide with manufacturer’s cut-outs for separate mortised power transfers and/or mortised automatic door bottoms where they occur.
6. Where thru-wire power transfers are integral to the hinge, provide hinge with easily removable portion to allow easy access to wiring connections.
7. Where models are specified that provide an integral wrap-around edge guard for the hinge edge of the door, provide manufacturer’s adjustable threaded stud and machine screw mechanism to allow the door to be adjusted within the wrap-around edge guard.
2.2 BUTT HINGES
ANSI A156.1. Provide only three-knuckle hinges, except five-knuckle where the required hinge type is not available in a three-knuckle version
Bid Documents – Addendum 01 05-01-22
08 71 00-6
DOOR HARDWARE
(e.g., some types of swing-clear hinges). The following types of butt hinges shall be used for the types of doors listed, except where otherwise specified:
1. Interior Doors: Type A8112/A5112 for doors 900 mm (3 feet) wide or less and Type A8111/A5111 for doors over 900 mm (3 feet) wide.
Provide quantity and size of hinges per door leaf as follows:
1. Doors up to 1210 mm (4 feet) high: 2 hinges.
2. Doors 1210 mm (4 feet) to 2260 mm (7 feet 5 inches) high: 3 hinges minimum.
3. Doors greater than 2260 mm (7 feet 5 inches) high: 4 hinges.
4. Doors up to 900 mm (3 feet) wide, standard weight: 114 mm x 114 mm
(4-1/2 inches x 4-1/2 inches) hinges.
5. Doors over 900 mm (3 feet) to 1065 mm (3 feet 6 inches) wide, standard weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).
6. Doors over 1065 mm (3 feet 6 inches) to 1210 mm (4 feet), heavy weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).
7. Provide heavy-weight hinges where specified.
8. At doors weighing 330 kg (150 pounds) or more, furnish 127 mm (5 inch) high hinges.
See Articles "MISCELLANEOUS HARDWARE" and "HARDWARE SETS" for pivots and hinges other than butts specified above and continuous hinges specified below.
2.3 DOOR CLOSING DEVICES
Closing devices shall be products of one manufacturer for each type specified.
2.4 OVERHEAD CLOSERS
Conform to ANSI A156.4, Grade 1.
Closers shall conform to the following:
1. The closer shall have minimum 50 percent adjustable closing force over minimum value for that closer and have adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening.
2. Where specified, closer shall have hold-open feature.
3. Size Requirements: Provide multi-size closers, sizes 1 through 6, except where multi-size closer is not available for the required application.
4. Material of closer body shall be forged or cast.
5. Arm and brackets for closers shall be steel, malleable iron or high strength ductile cast iron.
Bid Documents – Addendum 01 05-01-22
08 71 00-7
DOOR HARDWARE
6. Where closers are exposed to the exterior or are mounted in rooms that experience high humidity, provide closer body and arm assembly of stainless steel material.
7. Closers shall have full size metal cover; plastic covers will not be accepted.
8. Closers shall have adjustable hydraulic back-check, separate valves for closing and latching speed, adjustable back-check positioning valve, and adjustable delayed action valve.
9. Provide closers with any accessories required for the mounting application, including (but not limited to) drop plates, special soffit plates, spacers for heavy-duty parallel arm fifth screws, bull-nose or other regular arm brackets, longer or shorter arm assemblies, and special factory templating. Provide special arms, drop plates, and templating as needed to allow mounting at doors with overhead stops and/or holders.
10. Closer arms or backcheck valve shall not be used to stop the door from overswing, except in applications where a separate wall, floor, or overhead stop cannot be used.
11. Provide parallel arm closers with heavy duty rigid arm.
12. Where closers are to be installed on the push side of the door, provide parallel arm type except where conditions require use of top jamb arm.
13. Provide all surface closers with the same body attachment screw pattern for ease of replacement and maintenance.
14. All closers shall have a 1 ½” (38mm) minimum piston diameter.
2.5 DOOR STOPS
Conform to ANSI A156.16.
Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction. For concrete, masonry or quarry tile construction, use expansion shields for mounting door stops.
Where cylindrical locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251 (rubber pads having concave face) to receive turn piece or button.
Provide floor stops (Type L02141 or L02161) in office areas; Type L02121 x 3 screws into floor elsewhere. Wall bumpers, where used, must be installed to impact the trim or the door within the leading half of its width. Floor
Bid Documents – Addendum 01 05-01-22
08 71 00-8
DOOR HARDWARE
stops, where used, must be installed within 4-inches of the wall face and impact the door within the leading half of its width.
Where drywall partitions occur, use floor stops, Type L02141 or L02161 in office areas, Type L02121 elsewhere.
Omit stops where floor mounted door holders are required and where automatic operated doors occur.
Provide overhead surface applied stop Type C02541, ANSI A156.8 on patient toilet doors in bedrooms where toilet door could come in contact with the bedroom door.
Provide door stops on doors where combination closer magnetic holders are specified, except where wall stops cannot be used or where floor stops cannot be installed within 4-inches of the wall.
Where the specified wall or floor stop cannot be used, provide concealed overhead stops (surface-mounted where concealed cannot be used).
2.6 OVERHEAD DOOR STOPS AND HOLDERS
Conform to ANSI Standard A156.8. Overhead holders shall be of sizes recommended by holder manufacturer for each width of door. Set overhead holders for 110 degree opening, unless limited by building construction or equipment. Provide Grade 1 overhead concealed slide type: stop-only at rated doors and security doors, hold-open type with exposed hold-open on/off control at all other doors requiring overhead door stops.
2.7 FLOOR DOOR HOLDERS
Conform to ANSI Standard A156.16. Provide extension strikes for Types
L01301 and L01311 holders where necessary.
2.8 LOCKS AND LATCHES
Conform to ANSI A156.2. Locks and latches for doors 45 mm (1-3/4 inch) thick or over shall have beveled fronts. Lock cylinders shall have not less than seven pins. Cylinders for all locksets shall be removable core type.
Cylinders shall be furnished with construction removable cores and construction master keys. Cylinder shall be removable by special key or tool.
Construct all cores so that they will be interchangeable into the core housings of all mortise locks, rim locks, cylindrical locks, and any other type lock included in the Great Grand Master Key System. Disassembly of lever or lockset shall not be required to remove core from lockset. All locksets or latches on double doors with fire label shall have latch bolt with 19 mm (3/4 inch) throw, unless shorter throw allowed by the door manufacturer’s fire
Bid Documents – Addendum 01 05-01-22
08 71 00-9
DOOR HARDWARE
label. Provide temporary keying device or construction core to allow opening and closing during construction and prior to the installation of final cores.
In addition to above requirements, locks and latches shall comply with following requirements:
1. Mortise Lock and Latch Sets: Conform to ANSI/BHMA A156.13. Mortise locksets shall be series 1000, minimum Grade 2. All locksets and latchsets, except on designated doors in Psychiatric (Mental Health) areas, shall have lever handles fabricated from cast stainless steel.
Provide sectional (lever x rose) lever design matching facility standard. No substitute lever material shall be accepted. All locks and latchsets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension. Lock function F02 shall be furnished with emergency tools/keys for emergency entrance. All lock cases installed on lead lined doors shall be lead lined before applying final hardware finish. Furnish armored fronts for all mortise locks. Where mortise locks are installed in high-humidity locations or where exposed to the exterior on both sides of the opening, provide non-ferrous mortise lock case.
2.9 ELECTROMAGNETIC LOCKS
ANSI/BHMA A156.23; electrically powered, of strength and configuration indicated; with electromagnet attached to frame and armature plate attached to door. Listed under Category E in BHMA's "Certified Product Directory."
1. Type: Full exterior or full interior, as required by application indicated.
2. Strength Ranking: 1500 pound force (6672 N).
3. Inductive Kickback Peak Voltage: Not more than 53 V.
4. Residual Magnetism: Not more than 4 pound force (18 N) to separate door from magnet.
2.10 ELECTRIC LOCKS
ANSI/ BHMA A156.31 Grade 1.
General: Use fail-secure electric locks at all single doors.
Bid Documents – Addendum 01 05-01-22
08 71 00-10
DOOR HARDWARE
2.11 KEYS
Stamp all keys with change number and key set symbol. Furnish keys in quantities as follows:
Locks/Keys Quantity
Cylinder locks 2 keys each
Cylinder lock change key blanks
100 each different key way
Master-keyed sets 6 keys each
Grand Master sets 6 keys each
Great Grand Master set 5 keys
Control key 2 keys
2.12 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING
Conform to ANSI Standard A156.6.
Provide protective plates as specified below:
1. Kick plates, mop plates and armor plates of metal, Type J100 series.
2. Provide kick plates and mop plates where specified. Kick plates shall be 254 mm (10 inches) or 305 mm (12 inches) high. Mop plates shall be
152 mm (6 inches) high. Both kick and mop plates shall be minimum
1.27 mm (0.050 inches) thick. Provide kick and mop plates beveled on all 4 edges (B4E). On push side of doors where jamb stop extends to floor, make kick plates 38 mm (1-1/2 inches) less than width of door, except pairs of metal doors which shall have plates 25 mm (1 inch) less than width of each door. Extend all other kick and mop plates to within 6 mm (1/4 inch) of each edge of doors. Kick and mop plates shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames.
3. Kick plates and/or mop plates are not required on following door sides:
a. Armor plate side of doors;
b. Closet side of closet doors;
4. Armor plates for doors are listed under Article "Hardware Sets".
Armor plates shall be thickness as noted in the hardware set, 875 mm
(35 inches) high and 38 mm (1-1/2 inches) less than width of doors, except on pairs of metal doors. Provide armor plates beveled on all 4 edges (B4E). Plates on pairs of metal doors shall be 25 mm (1 inch) less than width of each door. Where top of intermediate rail of door
Bid Documents – Addendum 01 05-01-22
08 71 00-11
DOOR HARDWARE
is less than 875 mm (35 inches) from door bottom, extend armor plates to within 13 mm (1/2 inch) of top of intermediate rail. On doors equipped with panic devices, extend armor plates to within 13 mm (1/2 inch) of panic bolt push bar.
2.13 FLUSH BOLTS (LEVER EXTENSION)
Conform to ANSI A156.16. Flush bolts shall be Type L24081 unless otherwise specified. Furnish proper dustproof strikes conforming to ANSI
A156.16, for flush bolts required on lower part of doors.
Face plates for cylindrical strikes shall be rectangular and not less than 25 mm by 63 mm (1 inch by 2-1/2 inches).
Friction-fit cylindrical dustproof strikes with circular face plate may be used only where metal thresholds occur.
Provide extension rods for top bolt where door height exceeds 2184 mm (7 feet 2 inches).
2.14 MISCELLANEOUS HARDWARE
Access Doors (including Sheet Metal, Screen and Woven Wire Mesh Types):
Except for fire-rated doors and doors to Temperature Control Cabinets, equip each single or double metal access door with Lock Type E07213, conforming to
ANSI A156.11. Key locks as directed. Ship lock prepaid to the door manufacturer. Hinges shall be provided by door manufacturer.
Mutes: Conform to ANSI A156.16. Provide door mutes or door silencers
Type L03011 or L03021, depending on frame material, of white or light gray color, on each steel or wood door frame, except at fire-rated frames, lead-lined frames and frames for sound-resistant, lightproof and electromagnetically shielded doors. Furnish 3 mutes for single doors and 2 mutes for each pair of doors, except double-acting doors. Provide 4 mutes or silencers for frames for each Dutch type door. Provide 2 mutes for each edge of sliding door which would contact door frame.
2.15 FINISHES
Exposed surfaces of hardware shall have ANSI A156.18, finishes as specified below. Finishes on all hinges, pivots, closers, thresholds, etc., shall be as specified below under "Miscellaneous Finishes." For field painting
(final coat) of ferrous hardware, see Section 09 91 00, PAINTING.
626 or 630: All surfaces on exterior and interior of buildings, except where other finishes are specified.
Miscellaneous Finishes:
1. Hinges --exterior doors: 626 or 630.
Bid Documents – Addendum 01 05-01-22
08 71 00-12
DOOR HARDWARE
2. Hinges --interior doors: 652 or 630.
3. Pivots: Match door trim.
4. Door Closers: Factory applied paint finish. Dull or Satin Aluminum color.
5. Thresholds: Mill finish aluminum.
6. Cover plates for floor hinges and pivots: 630.
7. Other primed steel hardware: 600.
Hardware Finishes for Existing Buildings: U.S. Standard finishes shall match finishes of hardware in (similar) existing spaces except where otherwise specified.
Anti-microbial Coating: All hand-operated hardware (levers, pulls, push bars, push plates, paddles, and panic bars) shall be provided with an anti-microbial/anti-fungal coating that has passed ASTM E2180 tests. Coating to consist of ionic silver (Ag+). Silver ions surround bacterial cells, inhibiting growth of bacteria, mold, and mildew by blockading food and respiration supplies.
2.16 BASE METALS
Apply specified U.S. Standard finishes on different base metals as following:
Finish Base Metal
652 Steel
626 Brass or bronze
630 Stainless steel
PART 3 - EXECUTION
3.1 HARDWARE HEIGHTS
For existing buildings locate hardware on doors at heights to match existing hardware. The Contractor shall visit the site, verify location of existing hardware and submit locations to VA COR for approval.
3.2 INSTALLATION
Closer devices, including those with hold-open features, shall be equipped and mounted to provide maximum door opening permitted by building construction or equipment. Closers shall be mounted on side of door inside rooms, inside stairs, and away from corridors. At exterior doors, closers shall be mounted on interior side. Where closers are mounted on doors they shall be mounted with hex nuts and bolts; foot shall be fastened to frame with machine screws.
Bid Documents – Addendum 01 05-01-22
08 71 00-13
DOOR HARDWARE
Hinge Size Requirements:
Door Thickness Door Width Hinge Height
45 mm (1-3/4 inch) 900 mm (3 feet) and less 113 mm (4-1/2 inches)
45 mm (1-3/4 inch) Over 900 mm (3 feet) but not more than 1200 mm (4 feet)
125 mm (5 inches)
35 mm (1-3/8 inch) (hollow core wood doors)
Not over 1200 mm (4 feet) 113 mm (4-1/2 inches)
Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and surrounding conditions.
Where new hinges are specified for new doors in existing frames or existing doors in new frames, sizes of new hinges shall match sizes of existing hinges; or, contractor may reuse existing hinges provided hinges are restored to satisfactory operating condition as approved by COR. Existing hinges shall not be reused on door openings having new doors and new frames.
Coordinate preparation for hinge cut-outs and screw-hole locations on doors and frames.
Hinges Required Per Door:
Door Description Number butts
Doors 1500 mm (5 ft) or less in height 2 butts
Doors over 1500 mm (5 ft) high and not over 2280 mm (7 ft 6 in) high
3 butts
Doors over 2280 mm (7 feet 6 inches) high 4 butts
Dutch type doors 4 butts
Doors with spring hinges 1370 mm (4 feet 6 inches) high or less
2 butts
Doors with spring hinges over 1370 mm (4 feet 6 inches) 3 butts
Fastenings: Suitable size and type and shall harmonize with hardware as to material and finish. Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic or quarry floor tile, or solid masonry.
Fiber or rawl plugs and adhesives are not permitted. All fastenings exposed to weather shall be of nonferrous metal.
After locks have been installed; show in presence of COR that keys operate their respective locks in accordance with keying requirements. (All keys, Master Key level and above shall be sent Registered Mail to the Medical
Bid Documents – Addendum 01 05-01-22
08 71 00-14
DOOR HARDWARE
Center Director along with the bitting list. Also a copy of the invoice shall be sent to the COR for his records.) Installation of locks which do not meet specified keying requirements shall be considered sufficient justification for rejection and replacement of all locks installed on project.
3.3 FINAL INSPECTION
Installer to provide letter to VA Resident/Project Engineer that upon completion, installer has visited the Project and has accomplished the following:
1. Re-adjust hardware.
2. Evaluate maintenance procedures and recommend changes or additions, and instruct VA personnel.
3. Identify items that have deteriorated or failed.
4. Submit written report identifying problems.
3.4 DEMONSTRATION
Demonstrate efficacy of mechanical hardware and electrical, and electronic hardware systems, including adjustment and maintenance procedures, to satisfaction of Resident/Project Engineer and VA Locksmith.
3.5 HARDWARE SETS
Following sets of hardware correspond to hardware symbols shown on drawings. Only those hardware sets that are shown on drawings will be required. Disregard hardware sets listed in specifications but not shown on drawings.
Hardware Consultant working on a project will be responsible for providing additional information regarding these hardware sets. The numbers shown in the following sets come from BHMA standards.
Bid Documents – Addendum 01 05-01-22
08 71 00-15
DOOR HARDWARE
HW Set # 004
For use on Door #(s):
419-1 13B-17 19-25 24A-3 31-1 112-25 220-2 122-2 131A-3 147A-1 229-1 214-25 331-1 222A-3
Provide each SGL door(s) with the following:
QTY DESCRIPTION CATALOG NUMBER FINISH MFR
EA
EA
EA
CONT. HINGE
PIR REX SENSOR
BALANCED MAGNETIC
SWITCH
112XY
BY SECURITY CONTRACTOR
BY SECURITY CONTRACTOR
IVE
-EXISTING DOOR AND FRAME. CONTRACTOR TO FIELD VERIFY EXISTING
CONDITIONS/PREPS, AND PROVIDE ALL MATERIALS AND LABOR FOR COMPLETE
INSTALLATION.
-INGRESS BY THE CARD READER OR KEY OVERRIDE.
-CARD READER REQUIRED IN ORDER TO DEACTIVATE DOOR CONTACT ALARM WHEN USING KEY
OVERRIDE.
-EGRESS BY ACTUATOR OR INSIDE LEVER.
-WIRE THE ELECTRIC STRIKE TO THE FIRE ALARM SYSTEM TO BECOME FAIL-SECURE UPON
ACTIVATION OF THE FIRE ALARM SYSTEM.
-COORDINATE WITH SECURITY CONTRACTOR.
HW Set # 005
For use on Door #(s):
25-17 1-25
Provide each SGL door(s) with the following:
QTY DESCRIPTION CATALOG NUMBER FINISH MFR
EA
EA
CYLINDER
BALANCED MAGNETIC
SWITCH
SFIC TYPE AS REQ
BY SECURITY CONTRACTOR
BES
EA REMAINING HARDWARE TO BE
COORDINATED BY BLAST DR/FR
SUPPLIER
andrew.morris Cloud andrew.morris Polygon andrew.morris Text Box andrew.morris Text Box 08/15/2025
Bid Documents – Addendum 01 05-01-22
08 71 00-16
DOOR HARDWARE
HARDWARE GROUP NO. 101
For use on Door #(s):
135-29
Provide each SGL door(s) with the following:
QTY DESCRIPTION CATALOG NUMBER FINISH MFR
1 EA CONT. HINGE 112XY 628 IVE
1 EA ENTRY / OFFICE LOCK MA541H DG 626 FAL
1 EA CYLINDER SFIC TYPE AS REQ BES
1 EA LOCK GUARD LG1 OR AS REQ
(OMIT AT INSWING DOORS)
630 IVE
1 EA SURFACE CLOSER SC81A RW/PA X MTG BRKT,
SPCR & PLATE AS REQ
689 FAL
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA GASKETING 488S PSA (SILENCERS @ NON-
RATED DOORS)
BK ZER
HW Set # CE201
For use on Door #(s):
31B-1
Provide each SGL door(s) with the following:
QTY DESCRIPTION CATALOG NUMBER FINISH MFR
1 EA CONT. HINGE 112XY 628 IVE
1 EA STOREROOM LOCK MA581H DG 626 FAL
1 EA CYLINDER SFIC TYPE AS REQ BES
1 EA ELECTRIC STRIKE 6200 SERIES FSE DS CON -
TYPE AS REQ
630 VON
1 EA LOCK GUARD LG1 OR AS REQ
(OMIT AT INSWING DOORS)
630 IVE
1 EA SURFACE CLOSER SC81A RW/PA X MTG BRKT,
SPCR & PLATE AS REQ
689 FAL
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA WALL/FLOOR STOP WS406CCV/FS436 AS REQD 630 IVE
1 EA GASKETING 488S PSA (SILENCERS @ NON-
RATED DOORS)
BK ZER
1 EA HARNESS (TO POWER
SUPPLY)
CON-6W - CONNECTION LEADS SCH
1 EA BALANCED MAGNETIC
SWITCH
BY SECURITY CONTRACTOR
1 EA POWER SUPPLY PS902 900-FA VON
1 EA PIR REX SENSOR BY SECURITY CONTRACTOR
1 EA CARD READER BY SECURITY CONTRACTOR
-INGRESS BY THE CARD READER OR KEY OVERRIDE.
-CARD READER REQUIRED IN ORDER TO DEACTIVATE DOOR CONTACT ALARM WHEN USING KEY
OVERRIDE.
-FREE EGRESS AT ALL TIMES BY INSIDE LEVER.
-AT FIRE-RATED DOORS, WIRE THE ELECTRIC STRIKE TO THE FIRE ALARM SYSTEM TO
BECOME FAIL-SECURE UPON ACTIVATION OF THE FIRE ALARM SYSTEM.
Bid Documents – Addendum 01 05-01-22
08 71 00-17
DOOR HARDWARE
HW Set # GCE201
For use on Door #(s):
6-12 2-47
Provide each SGL door(s) with the following:
QTY DESCRIPTION CATALOG NUMBER FINISH MFR
1 EA CONT. HINGE 112XY 628 IVE
1 EA STOREROOM LOCK MA581H DG 626 FAL
1 EA CYLINDER SFIC TYPE AS REQ BES
1 EA ELECTRIC STRIKE 6200 SERIES FSE DS CON -
TYPE AS REQ
630 VON
1 EA LOCK GUARD LG1 OR AS REQ
(OMIT AT INSWING DOORS)
630 IVE
1 EA SURFACE CLOSER SC81A RW/PA X MTG BRKT,
SPCR & PLATE AS REQ
689 FAL
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA WALL/FLOOR STOP WS406CCV/FS436 AS REQD 630 IVE
1 EA GASKETING 488S PSA (SILENCERS @ NON-
RATED DOORS)
BK ZER
1 EA HARNESS (TO POWER
SUPPLY)
CON-6W - CONNECTION LEADS SCH
1 EA BALANCED MAGNETIC
SWITCH
BY SECURITY CONTRACTOR
1 EA POWER SUPPLY PS902 900-FA VON
1 EA PIR REX SENSOR BY SECURITY CONTRACTOR
1 EA CARD READER BY SECURITY CONTRACTOR
-INGRESS BY THE CARD READER OR KEY OVERRIDE.
-CARD READER REQUIRED IN ORDER TO DEACTIVATE DOOR CONTACT ALARM WHEN USING KEY
OVERRIDE.
-FREE EGRESS AT ALL TIMES BY INSIDE LEVER.
-COORDINATE WITH SECURITY CONTRACTOR.
-HARDWARE SET IS A GUIDELINE; GENERAL CONTRACTOR SHOULD CONDUCT A COORDINATION
MEETING WITH THE GATE FABRICATOR AND HARDWARE SUPPLIER BEFORE EITHER THE GATE
IS FABRICATED OR THE HARDWARE ORDERED.
-PROVIDE MOUNTING ACCESSORIES AS REQUIRED TO MOUNT HARDWARE TO GATE.
Bid Documents – Addendum 01 05-01-22
08 71 00-18
DOOR HARDWARE
HW Set # CE201C
For use on Door #(s):
1A-28 15-16 19B-29 31A-1 102-16 102-4 125A-17 135A-29 207A-16 217A-17 13C-17
Provide each SGL door(s) with the following:
QTY DESCRIPTION CATALOG NUMBER FINISH MFR
1 EA CONT. HINGE 112XY 628 IVE
1 EA STOREROOM LOCK MA581H DG 626 FAL
1 EA SFIC PERMANENT CORE TYPE AS REQ BES
1 EA ELECTRIC STRIKE 6200 SERIES FSE DS CON -
TYPE AS REQ
630 VON
1 EA LOCK GUARD LG1 OR AS REQ
(OMIT AT INSWING DOORS)
630 IVE
1 EA SURFACE CLOSER SC81A SS X MTG BRKT, SPCR &
PLATE AS REQ
689 FAL
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA GASKETING 488S PSA (SILENCERS @ NON-
RATED DOORS)
BK ZER
1 EA HARNESS (TO POWER
SUPPLY)
CON-192P SCH
1 EA BALANCED MAGNETIC
SWITCH
BY SECURITY CONTRACTOR
1 EA POWER SUPPLY PS902 900-FA VON
1 EA PIR REX SENSOR BY SECURITY CONTRACTOR
1 EA CARD READER BY SECURITY CONTRACTOR
-INGRESS BY THE CARD READER OR KEY OVERRIDE.
-CARD READER REQUIRED IN ORDER TO DEACTIVATE DOOR CONTACT ALARM WHEN USING KEY
OVERRIDE.
-FREE EGRESS AT ALL TIMES BY INSIDE LEVER.
-WIRE THE ELECTRIC STRIKE TO THE FIRE ALARM SYSTEM TO BECOME FAIL-SECURE UPON
ACTIVATION OF THE FIRE ALARM SYSTEM.
Bid Documents – Addendum 01 05-01-22
08 71 00-19
DOOR HARDWARE
HW Set # CEM200
For use on Door #(s):
22-17
Provide each PR door(s) with the following:
QTY DESCRIPTION CATALOG NUMBER FINISH MFR
1 EA CONT. HINGE 112XY 628 IVE
1 EA CONT. HINGE 112XY EPT 628 IVE
1 EA POWER TRANSFER EPT10 CON 689 VON
1 EA AUTO FLUSH BOLT FB31P 630 IVE
1 EA DUST PROOF STRIKE DP2 626 IVE
1 EA STOREROOM LOCK MA581H DG 626 FAL
1 EA SFIC PERMANENT CORE AS REQ
1 EA ELECTRIC STRIKE 6220 FSE DS CON - TYPE AS
REQ
630 VON
1 EA LOCK GUARD LG1 OR AS REQ
(OMIT AT INSWING DOORS)
630 IVE
1 EA MAGNETIC LOCK M492P MTG BRKT AS REQ 628 SCE
1 EA COORDINATOR COR X FL (MTG BRACKETS AS
REQ'D)
628 IVE
2 EA SURFACE CLOSER SC81A SS X MTG BRKT, SPCR &
PLATE AS REQ
689 FAL
2 EA GASKETING 488S PSA (SILENCERS @ NON-
RATED DOORS)
BK ZER
1 EA MEETING STILE 44STST (188S SEAL @ SMOKE
DOORS)
STST ZER
1 EA HARNESS (TO POWER
SUPPLY)
CON-192P SCH
2 EA BALANCED MAGNETIC
SWITCH
BY SECURITY CONTRACTOR
1 EA POWER SUPPLY PS902 900-FA VON
1 EA PIR REX SENSOR BY SECURITY CONTRACTOR
1 EA CARD READER BY SECURITY CONTRACTOR
1 EA REX BUTTON BY SECURITY CONTRACTOR
-INGRESS BY THE CARD READER OR KEY OVERRIDE.
-FREE EGRESS AT ALL TIMES BY INSIDE LEVER.
-WIRE THE ELECTRIC STRIKE TO THE FIRE ALARM SYSTEM TO BECOME FAIL SECURE UPON
ACTIVATION OF THE FIRE ALARM SYSTEM.
-WIRE THE MAGNETIC LOCK TO THE FIRE ALARM SYSTEM FOR RELEASE UPON ACTIVATION
OF THE FIRE ALARM SYSTEM.
Bid Documents – Addendum 01 05-01-22
08 71 00-20
DOOR HARDWARE
HW Set # E201
For use on Door #(s):
126-17 23-17
134A-29 24-17
218-17 135-29
6B-16 115B-16 222A-16
Provide each SGL door(s) with the following:
QTY DESCRIPTION CATALOG NUMBER FINISH MFR
1 EA CONT. HINGE 112XY 628 IVE
1 EA STOREROOM LOCK MA581H DG 626 FAL
1 EA CYLINDER SFIC TYPE AS REQ BES
1 EA LOCK GUARD LG1 OR AS REQ
(OMIT AT INSWING DOORS)
630 IVE
1 EA SURFACE CLOSER SC81A RW/PA X MTG BRKT,
SPCR & PLATE AS REQ
689 FAL
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA GASKETING 488S PSA (SILENCERS @ NON-
RATED DOORS)
BK ZER
-AT EXISTING DOOR, CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS/PREPS AND
PROVIDE ALL MATERIALS AND LABOR FOR COMPLETE INSTALLATION.
HW Set # E201C
For use on Door #(s):
21-29
Provide each SGL door(s) with the following:
QTY DESCRIPTION CATALOG NUMBER FINISH MFR
1 EA CONT. HINGE 112XY 628 IVE
1 EA STOREROOM LOCK MA581H DG 626 FAL
1 EA SFIC PERMANENT CORE AS REQ
1 EA LOCK GUARD LG1 OR AS REQ
(OMIT AT INSWING DOORS)
630 IVE
1 EA SURFACE CLOSER SC81A SS X MTG BRKT, SPCR &
PLATE AS REQ
689 FAL
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA GASKETING 488S PSA (SILENCERS @ NON-
RATED DOORS)
BK ZER
-EXISTING DOOR AND FRAME. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS/PREPS
AND PROVIDE ALL MATERIALS AND LABOR FOR COMPLETE INSTALLATION.
- - - E N D - - -andrew.morris Cloud andrew.morris Polygon andrew.morris Text Box andrew.morris Text Box 08/15/2025 andrew.morris Cloud andrew.morris Polygon andrew.morris Text Box andrew.morris Text Box 08/15/2025
File details come from the government source that posted it. Updated .