10 - 596-22-700 Drawings 06_Mechanical.pdf

PDF 7 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction Lexington - Leestown, KY 596-22-700
Solicitation number
36C77625B0040
Issued by

About this file

The document is a set of mechanical engineering drawings for the Electronic Health Record Modernization (EHRM) Infrastructure Upgrades Construction Project at the Lexington VA Health Care System. The comprehensive drawing set includes detailed mechanical plans for multiple buildings (Buildings 1, 2, 3, 4, 12, 16, 17, 25, 27, 28, and 29), focusing on replacing existing HVAC systems with new ductless split-system cooling units.

Key technical specifications include installing LG Electronics ductless mini-split systems with indoor wall-mounted units and corresponding outdoor condensing units, ranging from 12,000 to 30,000 BTUH cooling capacity. The project involves demolishing existing mechanical systems, routing new refrigerant and condensate piping, and integrating the new units with the building's existing Building Automation System (BAS). Specialized computer room areas, such as the Main Computer Room (MCR) in Building 17, will receive additional precision cooling equipment like Liebert computer room air conditioning (CRAC) units to ensure critical infrastructure cooling.

View the file

Other files

File Type Posted
36C77625B0040 0006.pdf PDF
0006 - 596-22-700 DBA Wages - Fayette County - 08-22-2025.pdf PDF
36C77625B0040 0005.pdf PDF
0004 - 596-22-700 Responses to Tech Questions - 8-19-25.pdf PDF
0004 - 596-22-700 Spec Section 23 07 11.pdf PDF
0004 - 596-22-700 Spec Section 00 01 10 Revisions.pdf PDF
0004 - 596-22-700 Spec Section 01 00 00 Revisions.pdf PDF
0004 - 596-22-700 Drawings 02_Civil Revisions.pdf PDF
0004 - 596-22-700 Spec Section 02 82 13.13 Revisions.pdf PDF
0004 - 596-22-700 Drawings 00_General Revisions.pdf PDF
0004 - 596-22-700 TR Photos - Question 58.pdf PDF
0004 - 596-22-700 Lexington TR Notes-MASTER.pdf PDF
36C77625B0040 0004.pdf PDF
0004 - 596-22-700 Spec Section 08 11 13 Revisions.pdf PDF
0004 - 596-22-700 Spec Section 08 71 00 Revisions.pdf PDF
0004 - 596-22-700 Drawings 01_Environmental Revisions.pdf PDF
36C77625B0040 0003.pdf PDF
0003 - 596-22-700 Responses to Tech Questions - 8-12-25.pdf PDF
0003 - 596-22-700 DBA Wages - Fayette County - 08-08-2025.pdf PDF
36C77625B0040 0002.pdf PDF
0002 - 596-22-700 DBA Wages - Fayette County - 07-18-2025.pdf PDF
36C77625B0040 0001.pdf PDF
0001 - 596-22-700 Site Visit Sign-in Sheet - 7-8-25.pdf PDF
IFB 36C77625B0040 - 6-25-25.pdf PDF
02 - 596-22-700 Specs 2.pdf PDF
12 - 596-22-700 Drawings 08_Telecom.pdf PDF
16 - 596-22-700 PCRA.pdf PDF
01 - 596-22-700 Specs 1.pdf PDF
03 - 596-22-700 Spec Section 01 31 00.01.pdf PDF
04 - 596-22-700 Drawings 00_General.pdf PDF
08 - 596-22-700 Drawings 04_Architectural.pdf PDF
11 - 596-22-700 Drawings 07_Electrical.pdf PDF
07 - 596-22-700 Drawings 03_Structural.pdf PDF
09 - 596-22-700 Drawings 05_Fire Protection.pdf PDF
15 - 596-22-700 ICRA III.pdf PDF
17 - 596-22-700 Brand Name Justification.pdf PDF
18 - 596-22-700 DBA Wages - Fayette County - 06-06-2025.pdf PDF
19 - 596-22-700 VAAR 852.219-75 LOS - Construction.docx DOCX document
05 - 596-22-700 Drawings 01_Environmental.pdf PDF
06 - 596-22-700 Drawings 02_Civil.pdf PDF
13 - 596-22-700 Drawings 09_Security.pdf PDF
14 - 596-22-700 ICRA II.pdf PDF
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ABBREVIATIONS

HVAC PIPING TYPES

GENERAL DUCT SYMBOLS

A/E ARCHITECT / ENGINEER

AAHX AIR TO AIR HEAT EXCHANGER

AB AIR BLENDER

AAV AUTOMATIC AIR VENT

ACC AIR COOLED CONDENSER

ACU AIR CONDITIONING UNIT

AF AFTER FILTER

AFCV AIR FLOW CONTROL VALVE

AFF ABOVE FINISHED FLOOR

AFW AIR FOIL WHEEL (FAN)

AHU AIR-HANDLING UNIT

AMP AMPERAGE

AP ACCESS PANEL

APD AIR PRESSURE DROP

ARI AIR CONDITIONING AND REFRIGERATION

INSTITUTE

AS AIR SEPARATOR

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

AW AIR WASHER

AXF AXIAL FLOW

B

B BOILER

BD BUTTERFLY DAMPER

BDD BACKDRAFT DAMPER

BFP BACKFLOW PREVENTER

BHP BRAKE HORSEPOWER

BHX BOILER BLOWDOWN HEAT EXCHANGER

BIW BACKWARD INCLINED WHEEL (FAN)

BSC BIOLOGICAL SAFETY CABINETS

BT BLOWOFF TANK

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C

C CENTIGRADE (CELSIUS)

CC COOLING COIL

CCD COOLING COIL CONDENSATE DRAIN

CENT CENTRIFUGAL

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFT CUBIC FEET

CFP CHEMICAL FEED PUMP

CH CHILLER

CHP CHILLED WATER PUMP

CHW CHILLER WATER

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CI CAST IRON

CM CUBIC METER

CM/S CUBIC METER PER SECOND

CO CARBON MONOXIDE

CO2 CARBON DIOXIDE

COMP COMPRESSOR UNIT

COP COEFFICIENT OF PERFORMANCE

CP CONDENSATE PUMP

CS CONDENSATE STORAGE TANK

CSG CLEAN STEAM GENERATOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONSTANT VOLUME

CW COLD WATER (POTABLE)

CC CHILLED WATER COOLING COIL

CWP CONDENSER WATER PUMP

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

A

F

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

FA FREE AREA

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT

FCUC FAN COIL UNIT COOLING ONLY

FCUH FAN COIL UNIT HEATING ONLY

FCW FORWARD CURVED WHEEL (FAN)

E

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC EVAPORATIVE COOLER

ECC ENGINEERING CONTROL CENTER

ECU EVAPORATIVE CONDENSER UNIT

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EGS EMERGENCY GAS SHUTOFF

EGT ENTERING GLYCOL TEMPERATURE

EH EXHAUST HOOD

EJ EXPANSION JOINT

EMD END OF MAIN DRIP (STEAM)

ENT ENTERING

ERC ELECTRIC REHEAT COIL

ERP ELECTRIC RADIANT PANEL

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

ETO ETHYLENE OXIDE

ETR EXISTING TO REMAIN

EUH ELECTRIC UNIT HEATER

EWC EVAPORATIVE WATER COOLER

EWT ENTERING WATER TEMPERATURE

EX. EXISTING

D

DB DECIBELS

Db DRY-BULB TEMPERATURE

DDC DIRECT DIGITAL CONTROLS

DEG DEGREE

DIA DIAMETER

DIW DEIONIZED WATER

DP DEW POINT TEMPERATURE

DPA DIFFERENTIAL PRESSURE ASSEMBLY

DPS DIFFERENTIAL PRESSURE SENSOR

DX DIRECT EXPANSION

FD FIRE DAMPER

FF FINAL FILTER

FHX FLUE GAS/FEEDWATER HEAT EXCHANGER

FM FLOW METER

FOP FUEL OIL PUMP

FOT FUEL OIL TANK

FOHX FUEL OIL HEAT EXCHANGER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FPTU FAN POWERED TERMINAL UNIT

FRP FIBER REINFORCED POLYESTER

FS FLOW SWITCH

FSTAT FREEZESTAT

FT FEET

FT-LB FOOT-POUND

FTR FIN TUBE RADIATION

FV FACE VELOCITY

FSD COMBINATION FIRE / SMOKE DAMPER

G

GA GAUGE

GAL GALLONS

GH GRAVITY HOOD

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GS GALVANIZED STEEL

K kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR

J

J INTENTIONALLY LEFT BLANK

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

IBT INVERTED BUCKET TRAP

ICF IN-LINE CENTRIFUGAL FAN

ID INSIDE DIAMETER

IFB INTEGRAL FACE AND BYPASS

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCH WATER COLUMN

IN WG INCH WATER GAUGE

IN-LB INCH-POUND

IPLV INTEGRATED PART LOAD VALUE

IRH INFRARED HEATER

IS INSECT SCREEN

IU INDUCTION UNIT

IV INLET VANES

H

HU HUMIDIFIER

H&CW HOT & COLD WATER

HAC HOUSEKEEPING AID CLOSET

HB HOSE BIBB

HC HEATING COIL

HD HEAD

HOA HAND/OFF/AUTOMATIC

HP HEAT PUMP

HP HORSEPOWER

HPDT HIGH PRESSURE DRIP TRAP

HPC HIGH PRESSURE STEAM CONDENSATE RETURN

HPS HIGH PRESSURE STEAM (61-300 PSIG)

HRC HEAT RECOVERY COIL

HRD HEAT RECOVERY DEVICE

HRP HYDRONIC RADIANT (CEILING) PANEL

HRW HEAT RECOVERY WHEEL

HSTAT HUMIDISTAT

HTM HUMIDIFIER TERMINAL

HUM HUMIDIFIER UNIT MOUNTED

HVU HEATING AND VENTILATING UNIT

HW HOT WATER

HC HOT WATER HEATING COIL

HHP HEATING HOT WATER PUMP

HHR HEATING HOT WATER RETURN

HHS HEATING HOT WATER SUPPLY

HHUH HOT WATER UNIT HEATER

HX HEAT EXCHANGER

HZ HERTZ

I

L

L LITER

L/h LITERS PER HOUR (OR LITERS/HOUR) L/m LITERS PER MINUTE (OR LITERS/MINUTE) L/s LITERS PER SECOND (OR LITERS/SECOND)

LAT LEAVING AIR TEMPERATURE

LBS/HR POUNDS PER HOUR

LF LINEAR FOOT (FEET)

LGT LEAVING GLYCOL TEMPERATURE

LH LATENT HEAT

LPG LIQUID PROPANE GAS

LPC LOW PRESSURE STEAM CONDENSATE RETURN

CLPC LOW PRESSURE STEAM CONDENSATE (CLEAN)

LLHX LIQUID TO LIQUID HEAT EXCHANGER

LPS LOW PRESSURE STEAM (0-15 PSIG)

CLPS LOW PRESSURE STEAM (CLEAN)

LSD LINEAR SLOT DIFFUSER

LTCP LOCAL TEMPERATURE CONTROL PANEL

LVG LEAVING

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

NOM NOMINAL

NPLV NON-STANDARD PART LOAD VALUE

NPSH NET POSITIVE SUCTION HEAD

NTS NOT TO SCALE

N

NA NOT APPLICABLE

NC NOISE CRITERIA

NG NATURAL GAS

NGFM NATURAL GAS FLOWMETER

NOAA NATIONAL OCEANIC & ATMOSPHERIC

ADMINISTRATION

M

M METER, SI UNIT

M/s METERS PER SECOND

(OR METERS/SECOND)

MA MIXED AIR

MAT MIXED AIR TEMPERATURE

MAU MAKE-UP AIR UNIT

MAV MANUAL AIR VENT

MAX MAXIMUM

MB MIXING BOX

MBH 1000 BTUH

MCA MINIMUM BRANCH CIRCUIT AMPACITY

MERV MINIMUM EFFICIENCY REPORTING VALUE

MH MANHOLE

MHP MOTOR HORSEPOWER

MIN MINIMUM

MM MILLIMETER

MOV MOTOR OPERATED VALVE

MPC MEDIUM PRESSURE STEAM CONDENSATE

RETURN

MPS MEDIUM PRESSURE STEAM (16-60 PSIG)

MTD MEAN TEMPERATURE DIFFERENCE

MVD MANUAL VOLUME DAMPER

MZ MULTI-ZONE

P

P PUMP

PA PASCAL

PC PUMPED CONDENSATE

PCF POUNDS PER CUBIC FOOT (FEET)

PD PRESSURE DROP

PF PRE-FILTER

PG PRESSURE GAGE

PGW PROPYLENE GLYCOL-WATER (SOLUTION)

PHC PREHEAT COIL

PPM PARTS PER MILLION

PRS PRESSURE REGULATING (VALVE) STATION

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH – ABSOLUTE

PSIG POUNDS PER SQUARE INCH – GAGE

PSS PRIMARY SECONDARY SYSTEM

PSV PRESSURE SAFETY VALVE

PTAC PACKAGED TERMINAL AIR CONDITIONER

O

OA OUTSIDE AIR

OAI OUTSIDE AIR INTAKE

OD OUTSIDE DIAMETER

OFM OIL FLOWMETER

OSD ORGANIC SOIL FILTER

Q

Q INTENTIONALLY LEFT BLANK

T&PCV TEMPERATURE AND PRESSURE

CONTROL VALVE

TAB TESTING, ADJUSTING, BALANCE

TD TEMPERATURE DIFFERENCE

TDH TOTAL DYNAMIC HEAD

TDS TOTAL DISSOLVED SOLIDS

TG TRANSFER GRILLE

TP TRAP

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

TWU THRU-WALL UNIT

SA SUPPLY AIR

SAD SOUND ATTENUATING DEVICE

SAT SUPPLY AIR TEMPERATURE

SC SHADING COEFFICIENT

SCFM STANDARD CUBIC FEET PER MINUTE

SCR SILICON CONTROLLED RECTIFIER

DSD DUCT SMOKE DETECTOR

SD SMOKE DAMPER

SEN SENSIBLE HEAT

SF SUPPLY FAN

SH STEAM HUMIDIFIER

SHC STEAM HEATING COIL

SI SQUARE INCHES

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT (FEET)

SS STAINLESS STEEL

SSHX STEAM TO STEAM HEAT EXCHANGER

SSR SOLID SEPARATOR

ST STEAM TRAP

SUH STEAM UNIT HEATER

SVS STEAM VENT SILENCER

SWHX STEAM TO WATER HEAT EXCHANGER

R

R/E RETURN OR EXHAUST

RA RETURN AIR

RAD REFRIGERANT AIR DRYER

RAF RADIO FREQUENCY

RAHX ROTARY AIR HEAT EXCHANGER

RAT RETURN AIR TEMPERATURE

RCCH REMOTE CONDENSER CHILLER

RCU RECIPROCATING CHILLER UNIT

RD REFRIGERANT DISCHARGE

REA RELIEF AIR

RF RETURN FAN

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RHG REFRIGERANT HOT GAS

RL REFRIGERANT LIQUID LINE

RLA RUN LOAD AMPERE

RO REVERSE OSMOSIS

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION

RTU ROOF TOP UNIT

RV RELIEF VALVE

T

UC UNDER CUT

UH UNIT HEATER

UL UNDERWRITERS LABORATORY

URV UPBLAST UNIT VENTILATOR

U

X INTENTIONALLY LEFT BLANK

W

W WATTS

WAG WASTE ANESTHESIA GAS

Wb WET-BULB (TEMPERATURE)

WC WATER COOLED

WCCH WATER COOLED CHILLER

WCCU WATER COOLED CONDENSING UNIT

WCHP WATER COOLED HEAT PUMPS

WCPU WATER COOLED PACKAGED UNIT

WF WATER FILTER

WFM WATER FLOWMETER

WG WATER GAGE

WPD WATER SIDE PRESSURE DROP

V VALVE

VAF VANE-AXIAL FAN

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER (MANUAL OPPOSED BLADE)

VFD VARIABLE FREQUENCY DRIVE

VI VIBRATION ISOLATOR

VIV VARIABLE INLET VANES

VP VACUUM PUMP

VPS VARIABLE PRIMARY SYSTEM

VR VACUUM (STEAM CONDENSATE) RETURN

VSD VARIABLE SPEED DRIVE

VUH VERTICAL UNIT HEATER

X

V

GENERAL NOTES:

A. MECHANICAL PLANS AND SECTIONS ARE INTENDED TO ACCURATELY ILLUSTRATE THE

SCOPE OF WORK BUT ARE STILL DIAGRAMMATIC IN NATURE.

B. MECHANICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE

CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY

FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.

C. THE EXISTING CONDITIONS DEPICTED IN THESE PLANS ARE BASED ON AS-BUILT

DOCUMENTATION AND INFORMATION OBTAINED FROM FIELD SURVEYS AND ARE AS

ACCURATE AS POSSIBLE. DUE TO OBSTRUCTIONS, CEILINGS, ETC., NOT ALL CONDITIONS

COULD BE VERIFIED. THE CONTRACTOR SHALL SURVEY THE SITE PRIOR TO BID AND

NOTIFY THE ARCHITECT/ENGINEER OF ANY CONFLICTS, OBSTRUCTIONS, OR

INCONSISTENCIES PREVENTING INSTALLATION OF THE MECHANICAL SYSTEM.

D. ALL EXPOSED UNINSULATED PIPING SHALL BE PAINTED PER THE SPECIFICATION SECTION

"PAINTING".

E. PROVIDE VIBRATION ISOLATION AS RECOMMENDED BY THE MANUFACTURER FOR ALL

MOTORIZED MECHANICAL EQUIPMENT TO PREVENT TRANSMISSION OF VIBRATION TO

BUILDING STRUCTURE.

F. PROVIDE VIBRATION ISOLATORS FOR ALL PIPING SUPPORTS CONNECTED TO AND WITHIN

50' OF ISOLATED EQUIPMENT (EXCEPT AT BASE ELBOW SUPPORTS AND ANCHOR POINTS)

THROUGHOUT MECHANICAL EQUIPMENT ROOMS.

G. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL,

STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC., SHOWN ON OTHER CONTRACT DOCUMENT

DRAWINGS.

H. MAINTAIN A MINIMUM OF 6′-8″ CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS,

SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL ROOMS.

I. ALL TESTING SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR PIPING

INSULATION IS APPLIED.

J. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE

LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND DOWNSTREAM AS

RECOMMENDED BY THE MANUFACTURER FOR GOOD ACCURACY.

K. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS CERTIFIED

DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED

FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND

COORDINATE ALL DUCT AND PIPING DIMENSIONS BEFORE FABRICATION.

CWR

CWS

CD

LPC

LPS

MPC

MPS

HPC

HPS

CONDENSATE DRAIN

CONDENSER WATER SUPPLY

CONDENSER WATER RETURN

HIGH PRESSURE STEAM CONDENSATE

HIGH PRESSURE STEAM SUPPLY

MEDIUM PRESSURE STEAM CONDENSATE

MEDIUM PRESSURE STEAM SUPPLY

LOW PRESSURE STEAM CONDENSATE

LOW PRESSURE STEAM SUPPLY

VACUUM RETURN

FEEDWATER PUMP DISCHARGE

FEEDWATER PUMP SUCTION

VR

CONTINUOUS BLOWDOWN

CHEMICAL FEED

BOILER BLOWOFF BO

CF

CBD

FWPD

FWPS

A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO

INSTALL COMPLETE AND OPERABLE PIPING SYSTEMS AS INDICATED ON THE DRAWINGS, AS

SPECIFIED AND AS REQUIRED BY CODE.

B. UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO UNDERSIDE OF

STRUCTURE OR SLAB, WITH SPACE FOR INSULATION IF REQUIRED.

C. INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS, FLANGES, AND OTHER

APPURTENANCES REQUIRING ACCESS ARE ACCESSIBLE.

D. ALL VALVES SHALL BE INSTALLED SO THAT VALVE REMAINS IN SERVICE WHEN EQUIPMENT

OR PIPING ON EQUIPMENT SIDE OF VALVE IS REMOVED.

E. ALL BALANCING VALVES AND BUTTERFLY VALVES SHALL BE PROVIDED WITH POSITION

INDICATORS AND MAXIMUM ADJUSTABLE STOPS (MEMORY STOPS).

F. ALL VALVES (EXCEPT CONTROL VALVES) AND STRAINERS SHALL BE FULL SIZE OF PIPE

BEFORE REDUCING SIZE TO MAKE CONNECTIONS TO EQUIPMENT AND CONTROLS.

G. UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE OF EQUIPMENT, IN

BYPASSES, AND IN LONG PIPING RUNS (100' OR MORE) TO PERMIT DISASSEMBLY FOR

ALTERATION AND REPAIRS.

H. ALL PIPING SHALL CLEAR DOORS AND WINDOWS.

I. ALL VALVES SHALL BE ADJUSTED FOR SMOOTH AND EASY OPERATION.

J. ALL PIPING WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN

PIPING AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE

OWNER.

K. PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS CONNECTED TO PUMPS,

CHILLERS, COOLING TOWERS, AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION

ISOLATION EXCEPT WATER COILS. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AS CLOSE

TO THE EQUIPMENT AS POSSIBLE OR AS INDICATED ON THE DRAWINGS.

L. SLOPE REFRIGERANT PIPING ONE PERCENT IN THE DIRECTION OF OIL RETURN. LIQUID

LINES MAY BE INSTALLED LEVEL.

M. INSTALL HORIZONTAL REFRIGERANT SUCTION LINES WITH 1/2″ PER 10' DOWNWARD SLOPE

TO THE COMPRESSOR, WITH NO LONG TRAPS OR DEAD ENDS WHICH MAY CAUSE OIL TO

SEPARATE FROM THE SUCTION GAS AND RETURN TO THE COMPRESSOR IN DAMAGING

SLUGS.

N. PROVIDE LINE SIZE LIQUID INDICATORS IN MAIN LIQUID LINE LEAVING CONDENSER OR

RECEIVER. INSTALL MOISTURE LIQUID INDICATORS IN LIQUID LINES BETWEEN FILTER

DRYERS AND THERMOSTATIC EXPANSION VALVES AND IN LIQUID LINE TO RECEIVER.

A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO

INSTALL COMPLETE AND OPERABLE HVAC SYSTEMS AS INDICATED ON THE DRAWINGS, AS

SPECIFIED AND AS REQUIRED BY CODE.

B. CERTAIN ITEMS SUCH AS RISES AND DROPS IN DUCTWORK, ACCESS DOORS, VOLUME

DAMPERS, ETC., ARE INDICATED ON THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY

FOR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS THE

EXTENT OF THE REQUIREMENTS FOR THESE ITEMS.

C. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM THERMOSTATS AND HUMIDISTATS 4′-0″

(CENTERLINE) ABOVE FINISHED FLOOR.

D. ALL DUCTWORK SHALL CLEAR DOORS AND WINDOWS.

E. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR

DIMENSIONS AND DUCT SIZE SHALL BE INCREASED TO COMPENSATE FOR DUCT LINING

THICKNESS.

F. ALL AIR HANDLING UNITS SHALL OPERATE WITHOUT MOISTURE CARRYOVER.

G. LOCATE ALL MECHANICAL EQUIPMENT TO ALLOW UNOBSTRUCTED ACCESS TO UNIT

ACCESS PANELS, CONTROLS AND VALVING.

H. UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO THE UNDERSIDE OF

THE STRUCTURE, WITH SPACE FOR INSULATION IF REQUIRED.

I. ALL DUCTWORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN

DUCTS, INCLUDING DIVIDED DUCTS AND TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE

PROVIDED AT NO ADDITIONAL COST TO THE OWNER.

J. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS FOR ALL SMOKE

DETECTORS, FIRE DAMPERS, SMOKE DAMPERS, VOLUME DAMPERS, HUMIDIFIERS, COILS,

AND OTHER ITEMS LOCATED IN THE DUCTWORK WHICH REQUIRE SERVICE AND/OR

INSPECTION.

K. PROVIDE ACCESS DOORS IN DUCTWORK FOR OPERATION, ADJUSTMENT, AND

MAINTENANCE OF ALL FANS, VALVES, AND MECHANICAL EQUIPMENT.

L. SMOKE DETECTORS SHALL BE FURNISHED AND WIRED BY THE ELECTRICAL OR FIRE

ALARM CONTRACTOR. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR

MOUNTING THE SMOKE DETECTOR IN DUCTWORK AS SHOWN ON THE DRAWINGS AND IN

ACCORDANCE WITH MANUFACTURER’S PRINTED INSTRUCTIONS.

PIPING GENERAL NOTES: HVAC/SHEET METAL GENERAL NOTES:

EXISTING TO BE DEMOLISHED

LIMIT OF DEMOLITION

CONNECT NEW TO EXISTINGEXISTING TO REMAIN

NEW DUCT (INSIDE DIMENSIONS: W" X D")

RS

RL

REFRIGERANT SUCTION

REFRIGERANT LIQUID

SUPPLY AIR DUCT UP

SUPPLY AIR DUCT DOWN

H

T

H

T

26-P-3

MH-100

PUMP NO. 3 IN BUILDING NO. 26

EQUIPMENT ABBREVIATION (PUMP)

DETAIL NUMBER

SHEET NUMBER

SHEET NUMBER

SECTION NUMBER

THERMOSTAT

HUMIDISTAT

TEMPERATURE SENSOR

HUMIDITY SENSOR

BUILDING NUMBER WHERE EQUIPMENT

IS LOCATED

26-DS-100-A

ROOM NUMBER (ROOM NO. 100)

ITEM (DUCTLESS SPLIT UNIT)

BUILDING NUMBER WHERE EQUIPMENT

IS LOCATED

UNIT IDENTIFIER

DUCTLESS SPLIT UNIT TAG

MECHANICAL EQUIPMENT TAG

1 OWNER FURNISHED, CONTRACTOR

INSTALLED EQUIPMENT DESIGNATION

EXISTING TO BE DEMOLISHED

EXISTING TO REMAIN

NEW PIPE

CONNECT NEW TO EXISTING

LIMIT OF DEMOLITION

GENERAL PIPING SYMBOLS

GENERAL ANNOTATIONS

AV

STRAINERFLOAT & THERMOSTATIC

STEAM TRAP

INVERTED BUCKET

STEAM TRAP

FLANGE CONNECTION PIPE DROP

PIPE RISER TEE DOWN

TEE UP

UNION

PRESSURE REDUCING

VALVE

BALL VALVE

ANGLE GLOBE VALVE

SAFETY RELIEF VALVE

GLOBE VALVE

MANUAL OR

AUTOMATIC AIR VENT

EXPANSION JOINT

EJ

PRESSURE AND

TEMPERATURE TEST PLUG

QUICK-COUPLE HOSE

CONNECTOR

FLOW METER

HVAC PIPING SYMBOLS

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CHR

CHS

HEATING HOT WATER RETURN

HEATING HOT WATER SUPPLY

HHR

HHS QV CRYOGEN VENT

DR DRIP RETURN

CAP

REDUCER (ECCENTRIC)

TYPE

AIRFLOW (CFM)

SD-1

TYPE

AIRFLOW (CFM)

RG-1

TYPE

AIRFLOW (CFM)

EG-1

SQUARE TO ROUND TRANSITION

ELBOW WITH TURNING

VANES

ROUND ELBOW

EXHAUST, RELIEF, MAKE UP, OR

OUTSIDE AIR DUCT DOWN

EXHAUST, RELIEF, MAKE UP, OR

OUTSIDE AIR DUCT UP

RETURN DUCT DOWN

RETURN DUCT UP

BRANCH DUCT WITH HIGH EFFICIENCY

TAKE-OFF (HETO) BRANCH FITTING &

MANUAL VOLUME DAMPER

BRANCH DUCT WITH CONICAL

FITTING & MANUAL VOLUME

DAMPER

DAMPERS: (BD, FD, FSD, MD, SD, VD)

BD

XX-XX

ANCHOR

TEEDIRECTION OF FLOW

S

L. CONCRETE HOUSEKEEPING PADS TO SUIT MECHANICAL EQUIPMENT SHALL BE SIZED AND

LOCATED BY THE MECHANICAL CONTRACTOR. MINIMUM CONCRETE PAD THICKNESS SHALL

BE 4". PAD SHALL EXTEND BEYOND THE EQUIPMENT A MINIMUM OF 4" ON EACH SIDE.

CONCRETE HOUSEKEEPING PADS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR.

M. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE

SPECIFICATIONS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE

ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE BEST CONDITIONS AND

RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND SHALL HAVE THE

APPROVAL OF THE ENGINEER OR OWNERS REPRESENTATIVE BEFORE BEING INSTALLED.

DO NOT SCALE DRAWINGS.

N. ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND AS SHOWN

IN DETAILS FOR PIPING, DUCTWORK, AND EQUIPMENT (UNLESS OTHERWISE NOTED) SHALL

BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR.

O. PROVIDE ACCESS PANELS FOR INSTALLATION IN WALLS AND CEILINGS WHERE REQUIRED

TO SERVICE DAMPERS, VALVES, SMOKE DETECTORS, AND OTHER CONCEALED

MECHANICAL EQUIPMENT.

P. ALL DUCTWORK, PIPING AND EQUIPMENT SUPPORTED FROM STRUCTURAL STEEL SHALL

BE COORDINATED WITH GENERAL CONTRACTOR. ALL ATTACHMENTS TO STEEL BAR

JOISTS, TRUSSES, OR JOIST GIRDERS SHALL BE AT PANEL POINTS. REFER TO

SPECIFICATIONS FOR CONNECTION TYPE(S) ALLOWED.

Q. ALL ROOF MOUNTED EQUIPMENT CURBS FOR EQUIPMENT PROVIDED BY THE MECHANICAL

CONTRACTOR SHALL BE FURNISHED BY THE MECHANICAL CONTRACTOR. COORDINATE

INSTALLATION WITH GENERAL CONTRACTOR.

R. LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE

COORDINATED WITH ALL OTHER TRADES INVOLVED.

S. ALL OPENINGS IN RATED WALLS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE

FIRE STOPPED WITH AN APPROVED FIRE STOPPING MATERIAL.

T. ALL AIR CONDITIONING CONDENSATE DRAIN LINES FROM EACH AIR HANDLING UNIT AND

ROOFTOP UNIT SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET, WITH P-TRAP, AND

PIPED TO NEAREST DRAIN. SEE DETAILS AND SPECIFICATIONS FOR DEPTH OF AIR

CONDITIONING CONDENSATE TRAP.

U. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION.

V. ROOFTOP EQUIPMENT WITHIN 10' OF ROOF EDGE OR DROPOFF SHALL BE SUPPLIED WITH

HANDRAILS AND ALL NECESSARY BUILDING MODIFICATIONS TO ENSURE A SAFE

MAINTENANCE AREA IS MAINTAINED.

O. PROVIDE LINE SIZE STRAINER UPSTREAM OF EACH AUTOMATIC VALVE. PROVIDE SHUTOFF

VALVE ON EACH SIDE OF STRAINER.

P. PROVIDE PERMANENT FILTER DRYERS IN LOW TEMPERATURE SYSTEMS AND SYSTEMS

USING HERMETIC COMPRESSORS.

Q. PROVIDE REPLACEABLE CARTRIDGE FILTER DRYERS WITH THREE-WAY VALVE BYPASS

AASSEMBLY FOR SOLENOID VALVES, ADJACENT TO RECEIVERS.

R. PROVIDE REFRIGERANT CHARGING VALVE CONNECTIONS IN LIQUID LINE BETWEEN

RECEIVER SHUTOFF VALVE AND EXPANSION VALVE.

S. REFRIGERANT PIPING IS LIMITED TO 610' PER SYSTEM. PIPING LENGTHS AND DERATING HAS

BEEN TAKEN INTO ACCOUNT WHEN SIZING EQUIPMENT. REFER TO MANUFACTURER

SPECIFIC DATA.

DIRECTION OF PIPE

PITCH (DOWN)

FM

MV

HVAC VALVE SYMBOLS

PC PUMPED CONDENSATE

ROOM TAG

FLEXIBLE CONNECTOR

PUMP

REDUCER (CONCENTRIC)

GATE VALVE

BUTTERFLY VALVE

CHECK VALVE

THERMOMETER

PRESSURE GAUGE

STRAINER WITH BLOWOFF

AND HOSE CONNECTION

YR YEAR

Y

Z INTENTIONALLY LEFT BLANK

Z

M

CONTROL VALVE

CONTROL VALVE, THREE WAY

MOTOR CONTROLLED

VALVE

M

M

A. MECHANICAL TRADES BIDDING DEMOLITION WORK SHALL ALLOW FOR A FULL DAY ON SITE TO REVIEW EXISTING MECHANICAL SERVICES AND EQUIPMENT IN DEMOLITION AND REMOVED AREAS. ACCESS WILL BE GIVEN TO ROOF AND EXISTING MECHANICAL AND ELECTRICAL ROOMS AS REQUIRED. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK. BRING ANY DISCREPANCIES FROM THE DRAWINGS AND NOTES TO THE ENGINEER OF RECORD IMMEDIATELY. MINOR CHANGES IN THE SCOPE OF THE

DEMOLITION WORK SHALL NOT JUSTIFY AN ADDITIONAL COST.

B. DEMOLISHED WORK SHALL INCLUDE FOR TEMPORARY AND PERMANENT WORK REQUIRED TO KEEP

NON-SCOPE AREAS IN OPERATION. COORDINATE UTILITY SHUT-OFFS AND TEMPORARY POWER,

STORAGE, AND ACCESS NEEDED TO COMPLETE WORK WITH GENERAL CONTRACTOR AND

CONTRACTING OFFICER'S REPRESENTATIVE (COR).

C. REMOVAL OF EXISTING EQUIPMENT WILL REQUIRE ISOLATION OF EXISTING PIPING BRANCHES AND/OR MAINS USING SHUTOFF VALVES. INSTALL NEW ISOLATION VALVES AS REQUIRED TO COMPLETION

DEMOLITION WORK.

D. ALL DRAINED PIPING RISERS AND MAINS SHALL BE REFILLED AND PROPERLY VENTED BY THE

CONTRACTOR ONCE NEW WORK HAS BEEN COMPLETED.

E. COORDINATE REMOVAL, REPLACEMENT, AND/OR REPAIRS OF ANY EXISTING WALLS, CEILING, ETC.

REQUIRED FOR MECHANICAL DEMOLITION WORK WITH GENERAL CONTRACTOR.

F. PROVIDE TIGHTLY SEALED AND INSULATED TERMINATIONS FOR ALL PIPING, DUCTWORK, AND EQUIPMENT REMOVED FROM THE PROJECT. THERE SHALL BE NO "DEAD LEG" SECTIONS OF PIPING

WHERE WATER CAN SIT AND BECOME STAGNANT.

G. REFER TO THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) FOR INSTRUCTIONS REGARDING THE

REMOVAL AND RETURN OR DEMOLITION OF EXISTING EQUIPMENT AND FIXTURES.

H. PORTIONS OF EXISTING SYSTEMS ARE SHOWN FOR CLARITY AND MAY NOT BE NECESSARY TO MODIFY OR REVISE THEM. ALL EXISTING SYSTEMS ARE SHOWN BASED ON AVAILABLE AS-BUILT DRAWINGS AND SITE SURVEYS OF ACCESSIBLE AREAS. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS.

I. ALL WORK MUST BE COORDINATED AND SCHEDULED WITH THE CONTRACTING OFFICER'S

REPRESENTATIVE TO ENSURE THE LEAST AMOUNT OF DISRUPTION OF BUILDING ACTIVITIES AS

POSSIBLE.

J. ALL ACCESSIBLE ABANDONED PIPING AND DUCTWORK SHALL BE REMOVED AND PROPERLY DISPOSED

OF.

K. SUPPLY AIR DUCTWORK AND PIPING NOT SHOWN HATCHED IS TO BE RETAINED, ANY DAMAGE TO

EXISTING INSULATION AND DUCTS TO BE REPAIRED TO MATCH EXISTING.

GENERAL DEMOLITION NOTES:

DS DUCTLESS MINI-SPLIT

ROOM NAME

000A

150 SF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:2 :3

P

M

LEGEND AND ABBREVIATIONS

BAJ 117RDC

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

M-000

SPUR #: 2207.00

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

M-401

M-401

1-CU-419

1-CU-331

1-CU-229

1-CU-1477

EXISTING PHONE ROOM

440 SF

TR

31A

121 SF

1-CU-031A7

TR

147A-1

134 SF

M-401

M-401

M-401

TR

229-1

94 SF

M-401

M-401

M-401

TR

331-1

87 SF

TR

419-1

97 SF

M-401

M-401

KEY PLAN

LEESTOWN ROAD

N

PARTITION LEGEND

1 HOUR FIRE RATED

2 HOUR FIRE RATED

NOTE: NOT ALL SYMBOLS MAY BE USED

3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:2 :3

P

M

BLDG 1 - REFERENCE PLANS

BAJ 118RDC

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

M-101

SPUR #: 2207.00

N

1" = 20'-0"

B1 - GROUND LEVEL1

N

1" = 20'-0"

B1 - LEVEL 12

N

1" = 20'-0"

B1 - LEVEL 23

N

1" = 20'-0"

B1 - LEVEL 34

N

1" = 20'-0"

B1 - LEVEL 45

KEYNOTES

1 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS

SPLIT-SYSTEM. REFER TO ENLARGED PLANS FOR MORE INFORMATION.

7 CONTRACTOR SHALL INSTALL NEW OUTDOOR CONDENSING UNIT IN THE LOCATION SHOWN. ENSURE THE UNIT HAS SUFFICIENT CLEARANCE SPACE, IS MOUNTED PROPERLY, AND IS PROTECTED AS NECESSARY.

ROUTE AND CONNECT REFRIGERANT PIPING TO THE ASSOCIATED INDOOR UNIT(S) AS SHOWN AND PER

MANUFACTURER INSTRUCTIONS.

9 NO HVAC SCOPE REQUIRED IN THIS ROOM. EXISTING MECHANICAL SYSTEMS TO REMAIN IN PLACE AND BE

REUSED.

11 CONTRACTOR SHALL ROUTE PUMPED CONDENSATE PIPING TO THE APPROXIMATE LOCATION SHOWN AND CONNECT TO NEAREST DRAINAGE SYSTEM PER CODE AND DETAIL 7/M-501. CONTRACTOR TO ABATE THE PENETRATION FOR ASBESTOS AND OTHER HAZARDOUS MATERIAL PRIOR TO DEMOLITION. SEE HAZARDOUS MATERIALS DRAWINGS FOR MORE DETAILS. DRIP PAN DRAINAGE SHALL BE TIED INTO CONDENSATE PIPING

SYSTEM.

BLDG 1

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for

2-CU-220

2-CU-122

TR

122-2

126 SF

M-402

M-402

1 11

M-402

M-402

TR

220-2

143 SF

TR

24A-3

64 SF

M-402

M-402

3-CU-222A

3-CU-131A

3-CU-024A

M-402

M-402

TR

131A-3

66 SF

M-402

M-402

TR

222A-3

67 SF

LEESTOWN ROAD

KEY PLAN

N

PARTITION LEGEND

1 HOUR FIRE RATED

2 HOUR FIRE RATED

NOTE: NOT ALL SYMBOLS MAY BE USED

3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:2 :3

P

M

BLDG 2 & 3 - REFERENCE PLANS

BAJ 119RDC

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

M-102

SPUR #: 2207.00

N

1" = 20'-0"

B2 - GROUND LEVEL1

N

1" = 20'-0"

B2 - LEVEL 12

N

1" = 20'-0"

B2 - LEVEL 23

N

1" = 20'-0"

B3 - GROUND LEVEL4

N

1" = 20'-0"

B3 - LEVEL 15

N

1" = 20'-0"

B3 - LEVEL 26

KEYNOTES

1 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS

SPLIT-SYSTEM. REFER TO ENLARGED PLANS FOR MORE INFORMATION.

7 CONTRACTOR SHALL INSTALL NEW OUTDOOR CONDENSING UNIT IN THE LOCATION SHOWN. ENSURE THE UNIT HAS SUFFICIENT CLEARANCE SPACE, IS MOUNTED PROPERLY, AND IS PROTECTED AS NECESSARY.

ROUTE AND CONNECT REFRIGERANT PIPING TO THE ASSOCIATED INDOOR UNIT(S) AS SHOWN AND PER

MANUFACTURER INSTRUCTIONS.

11 CONTRACTOR SHALL ROUTE PUMPED CONDENSATE PIPING TO THE APPROXIMATE LOCATION SHOWN AND CONNECT TO NEAREST DRAINAGE SYSTEM PER CODE AND DETAIL 7/M-501. CONTRACTOR TO ABATE THE PENETRATION FOR ASBESTOS AND OTHER HAZARDOUS MATERIAL PRIOR TO DEMOLITION. SEE HAZARDOUS MATERIALS DRAWINGS FOR MORE DETAILS. DRIP PAN DRAINAGE SHALL BE TIED INTO CONDENSATE PIPING

SYSTEM.

BLDG 2 & 3

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for

TR

102-4

119 SF

M-402

M-402

4-CU-1027

ELEC.

6C-12

99 SF

WAREHOUSE AREA

Not Enclosed

WORK SHOP

8-37

2330 SF

SHOP

2-47

1128 SF

SERVICE

2-48

118 SF

KEY PLAN

LEESTOWN ROAD

N

PARTITION LEGEND

1 HOUR FIRE RATED

2 HOUR FIRE RATED

NOTE: NOT ALL SYMBOLS MAY BE USED

3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:2 :3

P

M

BLDG 4, 12, 37, 47, & 48 - REFERENCE

PLANS

BAJ 120RDC

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

M-103

SPUR #: 2207.00

N

1" = 20'-0"

B4 - LEVEL 11

N

1" = 20'-0"

B12 - LEVEL 12

N

1" = 20'-0"

B37 - LEVEL 13

KEYNOTES

1 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS

SPLIT-SYSTEM. REFER TO ENLARGED PLANS FOR MORE INFORMATION.

7 CONTRACTOR SHALL INSTALL NEW OUTDOOR CONDENSING UNIT IN THE LOCATION SHOWN. ENSURE THE UNIT HAS SUFFICIENT CLEARANCE SPACE, IS MOUNTED PROPERLY, AND IS PROTECTED AS NECESSARY.

ROUTE AND CONNECT REFRIGERANT PIPING TO THE ASSOCIATED INDOOR UNIT(S) AS SHOWN AND PER

MANUFACTURER INSTRUCTIONS.

11 CONTRACTOR SHALL ROUTE PUMPED CONDENSATE PIPING TO THE APPROXIMATE LOCATION SHOWN AND CONNECT TO NEAREST DRAINAGE SYSTEM PER CODE AND DETAIL 7/M-501. CONTRACTOR TO ABATE THE PENETRATION FOR ASBESTOS AND OTHER HAZARDOUS MATERIAL PRIOR TO DEMOLITION. SEE HAZARDOUS MATERIALS DRAWINGS FOR MORE DETAILS. DRIP PAN DRAINAGE SHALL BE TIED INTO CONDENSATE PIPING

SYSTEM.

12 NO HVAC SCOPE REQUIRED IN THIS ROOM. EXISTING MECHANICAL SYSTEMS TO REMAIN IN PLACE AND BE REUSED. NEW TELECOM ENCLOSURE TO BE INSTALLED. REFER TO ARCHITECTURAL, ELECTRICAL, AND

TELECOMMUNICATIONS DRAWINGS FOR MORE INFORMATION.

BLDG 4, 12, 37, 47 & 48

N

1" = 20'-0"

B47 - LEVEL 14

N

1" = 20'-0"

B48 - LEVEL 15

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for

CLOSET

6B-16

80 SF

M-403

M-403

TR

15-16

111 SF

16-CU-207A

16-CU-102

16-CU-15

CLOSET

115B-16

82 SF

TR

102-16

111 SF

M-403

M-403

CLOSET

222A-16

82 SF

M-403

TR

207A-16

109 SF

M-403

TR

13C-17

125 SF

M-403

M-403

17-CU-217A

17-CU-125A

17-CU-13C

M-404

M-404

CLOSET (DEMARC)

13B-17

141 SF

NEW MCR

22-17

732 SF

MECH PAD

22B-17

390 SF

CLOSET

24-17

105 SF

FIRE CONTROL PANEL

AND CLEAN AGENT

STORAGE

23-17

112 SF

EXISTING 2-TON

CONDENSER

CLOSET

126-17

80 SF

TR

125A-17

137 SF

M-403

M-403

CLOSET

218-17

79 SF

TR

217A-17

124 SF

M-403

M-403

LEESTOWN ROAD

KEY PLAN

N

PARTITION LEGEND

1 HOUR FIRE RATED

2 HOUR FIRE RATED

NOTE: NOT ALL SYMBOLS MAY BE USED

3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:2 :4

P

M

BLDG 16 & 17 - REFERENCE PLANS

BAJ 121RDC

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

M-104

SPUR #: 2207.00

N

1" = 20'-0"

B16 - GROUND LEVEL1

N

1" = 20'-0"

B16 - LEVEL 12

N

1" = 20'-0"

B16 - LEVEL 23

N

1" = 20'-0"

B17 - GROUND LEVEL4

N

1" = 20'-0"

B17 - LEVEL 15

N

1" = 20'-0"

B17 - LEVEL 26

KEYNOTES

1 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS

SPLIT-SYSTEM. REFER TO ENLARGED PLANS FOR MORE INFORMATION.

7 CONTRACTOR SHALL INSTALL NEW OUTDOOR CONDENSING UNIT IN THE LOCATION SHOWN. ENSURE THE UNIT HAS SUFFICIENT CLEARANCE SPACE, IS MOUNTED PROPERLY, AND IS PROTECTED AS NECESSARY.

ROUTE AND CONNECT REFRIGERANT PIPING TO THE ASSOCIATED INDOOR UNIT(S) AS SHOWN AND PER

MANUFACTURER INSTRUCTIONS.

9 NO HVAC SCOPE REQUIRED IN THIS ROOM. EXISTING MECHANICAL SYSTEMS TO REMAIN IN PLACE AND BE

REUSED.

10 NO HVAC SCOPE REQUIRED IN THIS ROOM. EXISTING MECHANICAL SYSTEMS TO REMAIN IN PLACE AND BE REUSED. NEW FIBER TO BE INSTALLED. REFER TO ARCHITECTURAL AND TELECOMMUNICATIONS DRAWINGS

FOR MORE INFORMATION.

11 CONTRACTOR SHALL ROUTE PUMPED CONDENSATE PIPING TO THE APPROXIMATE LOCATION SHOWN AND CONNECT TO NEAREST DRAINAGE SYSTEM PER CODE AND DETAIL 7/M-501. CONTRACTOR TO ABATE THE PENETRATION FOR ASBESTOS AND OTHER HAZARDOUS MATERIAL PRIOR TO DEMOLITION. SEE HAZARDOUS MATERIALS DRAWINGS FOR MORE DETAILS. DRIP PAN DRAINAGE SHALL BE TIED INTO CONDENSATE PIPING

SYSTEM.

33 NEW MAIN COMPUTER ROOM TO BE CONSTRUCTED IN THIS LOCATION. REFER TO ENLARGED PLANS FOR

MORE INFORMATION.

34 SPACE TO BE MODIFIED DURING EHRM CONSTRUCTION. REFER TO ENLARGED PLANS FOR MORE

INFORMATION.

BLDG 16 & 17

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for

19-25

88 SF

M-405

M-405

25-CU-214

25-CU-112

25-CU-019 7

TR

112-25

87 SF

M-405

M-405

TR

214-25

85 SF

M-405

M-405

N

KEY PLAN

LEESTOWN ROAD

PARTITION LEGEND

1 HOUR FIRE RATED

2 HOUR FIRE RATED

NOTE: NOT ALL SYMBOLS MAY BE USED

3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:2 :4

P

M

BLDG 25 - REFERENCE PLANS

BAJ 122RDC

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

M-105

SPUR #: 2207.00

N

1" = 20'-0"

B25 - GROUND LEVEL1

N

1" = 20'-0"

B25 - LEVEL 12

N

1" = 20'-0"

B25 - LEVEL 23

KEYNOTES

1 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS

SPLIT-SYSTEM. REFER TO ENLARGED PLANS FOR MORE INFORMATION.

7 CONTRACTOR SHALL INSTALL NEW OUTDOOR CONDENSING UNIT IN THE LOCATION SHOWN. ENSURE THE UNIT HAS SUFFICIENT CLEARANCE SPACE, IS MOUNTED PROPERLY, AND IS PROTECTED AS NECESSARY.

ROUTE AND CONNECT REFRIGERANT PIPING TO THE ASSOCIATED INDOOR UNIT(S) AS SHOWN AND PER

MANUFACTURER INSTRUCTIONS.

11 CONTRACTOR SHALL ROUTE PUMPED CONDENSATE PIPING TO THE APPROXIMATE LOCATION SHOWN AND CONNECT TO NEAREST DRAINAGE SYSTEM PER CODE AND DETAIL 7/M-501. CONTRACTOR TO ABATE THE

PENETRATION FOR ASBESTOS AND OTHER HAZARDOUS MATERIAL PRIOR TO DEMOLITION. SEE

HAZARDOUS MATERIALS DRAWINGS FOR MORE DETAILS. DRIP PAN DRAINAGE SHALL BE TIED INTO

CONDENSATE PIPING SYSTEM.

BLDG 25

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for

2F-27

135 SF

TR

16D-27

134 SF

TR

136A-27

134 SF

TR

117A-27

134 SF

TR

217A-27

133 SF

TR

236A-27

135 SF

TR

1A-28

120 SF

M-406

M-406

28-CU-001A 7

TR

156-28

111 SF

TR

247-28

107 SF

N

KEY PLAN

LEESTOWN ROAD

PARTITION LEGEND

1 HOUR FIRE RATED

2 HOUR FIRE RATED

NOTE: NOT ALL SYMBOLS MAY BE USED

3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:2 :4

P

M

BLDG 27 & 28 - REFERENCE PLANS

BAJ 123RDC

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

M-106

SPUR #: 2207.00

N

1" = 20'-0"

B27 - GROUND LEVEL1

N

1" = 20'-0"

B27 - LEVEL 12

N

1" = 20'-0"

B27 - LEVEL 23

N

1" = 20'-0"

B28 - GROUND LEVEL4

N

1" = 20'-0"

B28 - LEVEL 15

N

1" = 20'-0"

B28 - LEVEL 26

KEYNOTES

1 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS

SPLIT-SYSTEM. REFER TO ENLARGED PLANS FOR MORE INFORMATION.

7 CONTRACTOR SHALL INSTALL NEW OUTDOOR CONDENSING UNIT IN THE LOCATION SHOWN. ENSURE THE UNIT HAS SUFFICIENT CLEARANCE SPACE, IS MOUNTED PROPERLY, AND IS PROTECTED AS NECESSARY.

ROUTE AND CONNECT REFRIGERANT PIPING TO THE ASSOCIATED INDOOR UNIT(S) AS SHOWN AND PER

MANUFACTURER INSTRUCTIONS.

10 NO HVAC SCOPE REQUIRED IN THIS ROOM. EXISTING MECHANICAL SYSTEMS TO REMAIN IN PLACE AND BE REUSED. NEW FIBER TO BE INSTALLED. REFER TO ARCHITECTURAL AND TELECOMMUNICATIONS DRAWINGS

FOR MORE INFORMATION.

11 CONTRACTOR SHALL ROUTE PUMPED CONDENSATE PIPING TO THE APPROXIMATE LOCATION SHOWN AND CONNECT TO NEAREST DRAINAGE SYSTEM PER CODE AND DETAIL 7/M-501. CONTRACTOR TO ABATE THE PENETRATION FOR ASBESTOS AND OTHER HAZARDOUS MATERIAL PRIOR TO DEMOLITION. SEE HAZARDOUS MATERIALS DRAWINGS FOR MORE DETAILS. DRIP PAN DRAINAGE SHALL BE TIED INTO CONDENSATE PIPING

SYSTEM.

BLDG 27 & 28

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for

M-406

M-406

TR

19B-29

144 SF

29-CU-19B

29-CU-135A

M-406

M-406

TR

135A-29

129 SF

N

KEY PLAN

LEESTOWN ROAD

PARTITION LEGEND

1 HOUR FIRE RATED

2 HOUR FIRE RATED

NOTE: NOT ALL SYMBOLS MAY BE USED

3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:2 :4

P

M

BLDG 29 - REFERENCE PLANS

BAJ 124RDC

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

M-107

SPUR #: 2207.00

N

1" = 20'-0"

B29 - GROUND LEVEL1

N

1" = 20'-0"

B29 - LEVEL 12

KEYNOTES

1 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS

SPLIT-SYSTEM. REFER TO ENLARGED PLANS FOR MORE INFORMATION.

7 CONTRACTOR SHALL INSTALL NEW OUTDOOR CONDENSING UNIT IN THE LOCATION SHOWN. ENSURE THE UNIT HAS SUFFICIENT CLEARANCE SPACE, IS MOUNTED PROPERLY, AND IS PROTECTED AS NECESSARY.

ROUTE AND CONNECT REFRIGERANT PIPING TO THE ASSOCIATED INDOOR UNIT(S) AS SHOWN AND PER

MANUFACTURER INSTRUCTIONS.

9 NO HVAC SCOPE REQUIRED IN THIS ROOM. EXISTING MECHANICAL SYSTEMS TO REMAIN IN PLACE AND BE

REUSED.

11 CONTRACTOR SHALL ROUTE PUMPED CONDENSATE PIPING TO THE APPROXIMATE LOCATION SHOWN AND CONNECT TO NEAREST DRAINAGE SYSTEM PER CODE AND DETAIL 7/M-501. CONTRACTOR TO ABATE THE

PENETRATION FOR ASBESTOS AND OTHER HAZARDOUS MATERIAL PRIOR TO DEMOLITION. SEE

HAZARDOUS MATERIALS DRAWINGS FOR MORE DETAILS. DRIP PAN DRAINAGE SHALL BE TIED INTO

CONDENSATE PIPING SYSTEM.

BLDG 29

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for

31A

D21

TR

31A

1-DS-031A 215 RL

RS

3/4" CD

5 19

T

1-DS-031A

TR

147A-1

5" CHR

6" CHS

2 1/2" DCW

20"x10" EA

20"x10" EA

"x

" E

A

1 1/2" HHS

24"x12" EA UP

THRU CEILING

20"x10" EA DN

THRU FLOOR

1 1/4" DCW

FCU D2

D6

TR

147A-1

20"x10" EA

5" CHR

6" CHS

2 1/2" DCW

24"x12" EA UP

THRU CEILING

20"x10" EA DN

THRU FLOOR

"x

" E

A

1 1/4" DCW

20"x10" EA

1-DS-147A2

RS

RL

T

1-DS-147A

3/4" CD

1" CD

REFRIGERANT PIPING

TO FLOORS ABOVE

(TYP)

TR

229-1

1" DCW

1" DHW

"x

" E

A

24"x12" EA DN

THRU FLOOR

24"x14" EA UP

THRU CEILING

FCU

1 1/2" HHS

D2

D6

10"ø EA

TR

229-1

24"x12" EA DN

THRU FLOOR

24"x14" EA UP

THRU CEILING

1" DHW

1" DCW24

"x

" E

A

10"ø EA

1-DS-2292

RS

RL

3/4" CD

22 23

T

1-DS-229

REFRIGERANT PIPING

TO FLOORS ABOVE

(TYP)

TR

331-1

FCU

3/4" DCW

3/4" DHW

2 1/2" HHS

12"x6" RA

"x

" E

A

"x

" E A

14"x18" EA

24"x14" EA DN

THRU FLOOR

28"x14" EA UP

THRU CEILING

D5

D6

D2

D5

12"x6"

TR

331-1

24"x14" EA DN

THRU FLOOR

28"x14" EA UP

THRU CEILING

3/4" DHW

3/4" DCW

14"x18" EA

"x

" E

A

"x

" E A

12"x6" RA

1-DS-3312

RS

RL

3/4" CD

T

1-DS-331

REFRIGERANT PIPING

TO FLOORS ABOVE

(TYP)

TR

419-1

FCU

"x

" E

A

20"x14" EA

12"x6" EA

3" CHR

3" CHS

3" HHR

3" HHS

28"x14" EA DN

THRU FLOOR

28"x14" EA UP

THRU CEILING

D6

D2

2" HHS

D5

TR

419-1

28"x14" EA DN

THRU FLOOR

28"x14" EA UP

THRU CEILING

3" CHR

3" CHS

3" HHR

3" HHS

"x

" E

A

20"x14" EA

1-DS-4192

RS

RL

3/4" CD

T

1-DS-419

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:2 :5

P

M

BLDG 1 - ENLARGED PLANS

BAJ 125RDC

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

M-401

SPUR #: 2207.00

1/4" = 1'-0" 1/ M-101

B1 - GROUND LEVEL - 31A - DEMO11/4" = 1'-0" 1/ M-101

B1 - GROUND LEVEL - 31A - NEW21/4" = 1'-0" 2/ M-101

B1 - LEVEL 1 - 147A - DEMO31/4" = 1'-0" 2/ M-101

B1 - LEVEL 1 - 147A - NEW4

1/4" = 1'-0" 3/ M-101

B1 - LEVEL 2 - 229 - DEMO51/4" = 1'-0" 3/ M-101

B1 - LEVEL 2 - 229 - NEW61/4" = 1'-0" 4/ M-101

B1 - LEVEL 3 - 331 - DEMO71/4" = 1'-0" 4/ M-101

B1 - LEVEL 3 - 331 - NEW8

1/4" = 1'-0" 5/ M-101

B1 - LEVEL 4 - 419 - DEMO91/4" = 1'-0" 5/ M-101

B1 - LEVEL 4 - 419 - NEW10

BLDG 1

DEMOLITION KEYNOTES

D2 CONTRACTOR SHALL DEMOLISH EXISTING CEILING-MOUNTED FAN COIL UNIT, ASSOCIATED PIPING, AND

ACCESSORIES. PREPARE SPACE FOR INSTALLATION OF NEW INDOOR MINI SPLIT UNIT(S).

D5 EXISTING DUCT(S) AND GRILLE(S) TO BE DEMOLISHED BACK TO NEAREST BRANCH/MAIN TAKEOFF AND

CAPPED. PREPARE SPACE FOR INSTALLATION OF NEW INDOOR MINI SPLIT UNIT(S).

D6 EXISTING HYDRONIC LINE(S) TO BE DEMOLISHED BACK TO NEAREST BRANCH/MAIN TAKEOFF AND CAPPED.

PREPARE SPACE FOR INSTALLATION OF NEW INDOOR MINI SPLIT UNIT(S).

D21 CONTRACTOR SHALL DEMOLISH EXISTING RADIATOR, ASSOCIATED PIPING, AND ACCESSORIES. PROVIDE PATCH AND REPAIR PENETRATIONS LEFT IN PLACE. PREPARE SPACE FOR INSTALLATION OF NEW

COOLING-ONLY DIRECT-EXPANSION DUCTLESS SPLIT-SYSTEM.

KEYNOTES

2 CONTRACTOR SHALL INSTALL NEW DUCTLESS SPLIT INDOOR UNIT, CONTROLS, AND ACCESSORIES IN THE LOCATION SHOWN. MOUNT UNIT AS HIGH AS POSSIBLE TO AVOID OBSTRUCTIONS.