10 - 596-22-700 Drawings 06_Mechanical.pdf
PDF 7 MB Posted
- Solicitation number
- 36C77625B0040
About this file
The document is a set of mechanical engineering drawings for the Electronic Health Record Modernization (EHRM) Infrastructure Upgrades Construction Project at the Lexington VA Health Care System. The comprehensive drawing set includes detailed mechanical plans for multiple buildings (Buildings 1, 2, 3, 4, 12, 16, 17, 25, 27, 28, and 29), focusing on replacing existing HVAC systems with new ductless split-system cooling units.
Key technical specifications include installing LG Electronics ductless mini-split systems with indoor wall-mounted units and corresponding outdoor condensing units, ranging from 12,000 to 30,000 BTUH cooling capacity. The project involves demolishing existing mechanical systems, routing new refrigerant and condensate piping, and integrating the new units with the building's existing Building Automation System (BAS). Specialized computer room areas, such as the Main Computer Room (MCR) in Building 17, will receive additional precision cooling equipment like Liebert computer room air conditioning (CRAC) units to ensure critical infrastructure cooling.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ABBREVIATIONS
HVAC PIPING TYPES
GENERAL DUCT SYMBOLS
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AB AIR BLENDER
AAV AUTOMATIC AIR VENT
ACC AIR COOLED CONDENSER
ACU AIR CONDITIONING UNIT
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERAGE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARI AIR CONDITIONING AND REFRIGERATION
INSTITUTE
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
B
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BFP BACKFLOW PREVENTER
BHP BRAKE HORSEPOWER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BIW BACKWARD INCLINED WHEEL (FAN)
BSC BIOLOGICAL SAFETY CABINETS
BT BLOWOFF TANK
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C
C CENTIGRADE (CELSIUS)
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CENT CENTRIFUGAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CFP CHEMICAL FEED PUMP
CH CHILLER
CHP CHILLED WATER PUMP
CHW CHILLER WATER
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CI CAST IRON
CM CUBIC METER
CM/S CUBIC METER PER SECOND
CO CARBON MONOXIDE
CO2 CARBON DIOXIDE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CS CONDENSATE STORAGE TANK
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CC CHILLED WATER COOLING COIL
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
A
F
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT
FCUC FAN COIL UNIT COOLING ONLY
FCUH FAN COIL UNIT HEATING ONLY
FCW FORWARD CURVED WHEEL (FAN)
E
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC EVAPORATIVE COOLER
ECC ENGINEERING CONTROL CENTER
ECU EVAPORATIVE CONDENSER UNIT
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EGS EMERGENCY GAS SHUTOFF
EGT ENTERING GLYCOL TEMPERATURE
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ERC ELECTRIC REHEAT COIL
ERP ELECTRIC RADIANT PANEL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETO ETHYLENE OXIDE
ETR EXISTING TO REMAIN
EUH ELECTRIC UNIT HEATER
EWC EVAPORATIVE WATER COOLER
EWT ENTERING WATER TEMPERATURE
EX. EXISTING
D
DB DECIBELS
Db DRY-BULB TEMPERATURE
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DPA DIFFERENTIAL PRESSURE ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
FD FIRE DAMPER
FF FINAL FILTER
FHX FLUE GAS/FEEDWATER HEAT EXCHANGER
FM FLOW METER
FOP FUEL OIL PUMP
FOT FUEL OIL TANK
FOHX FUEL OIL HEAT EXCHANGER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPTU FAN POWERED TERMINAL UNIT
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
FSD COMBINATION FIRE / SMOKE DAMPER
G
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GS GALVANIZED STEEL
K kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR
J
J INTENTIONALLY LEFT BLANK
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
IN-LB INCH-POUND
IPLV INTEGRATED PART LOAD VALUE
IRH INFRARED HEATER
IS INSECT SCREEN
IU INDUCTION UNIT
IV INLET VANES
H
HU HUMIDIFIER
H&CW HOT & COLD WATER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPC HIGH PRESSURE STEAM CONDENSATE RETURN
HPS HIGH PRESSURE STEAM (61-300 PSIG)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING) PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HTM HUMIDIFIER TERMINAL
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HC HOT WATER HEATING COIL
HHP HEATING HOT WATER PUMP
HHR HEATING HOT WATER RETURN
HHS HEATING HOT WATER SUPPLY
HHUH HOT WATER UNIT HEATER
HX HEAT EXCHANGER
HZ HERTZ
I
L
L LITER
L/h LITERS PER HOUR (OR LITERS/HOUR) L/m LITERS PER MINUTE (OR LITERS/MINUTE) L/s LITERS PER SECOND (OR LITERS/SECOND)
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LGT LEAVING GLYCOL TEMPERATURE
LH LATENT HEAT
LPG LIQUID PROPANE GAS
LPC LOW PRESSURE STEAM CONDENSATE RETURN
CLPC LOW PRESSURE STEAM CONDENSATE (CLEAN)
LLHX LIQUID TO LIQUID HEAT EXCHANGER
LPS LOW PRESSURE STEAM (0-15 PSIG)
CLPS LOW PRESSURE STEAM (CLEAN)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
N
NA NOT APPLICABLE
NC NOISE CRITERIA
NG NATURAL GAS
NGFM NATURAL GAS FLOWMETER
NOAA NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
M
M METER, SI UNIT
M/s METERS PER SECOND
(OR METERS/SECOND)
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MERV MINIMUM EFFICIENCY REPORTING VALUE
MH MANHOLE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MPC MEDIUM PRESSURE STEAM CONDENSATE
RETURN
MPS MEDIUM PRESSURE STEAM (16-60 PSIG)
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
MZ MULTI-ZONE
P
P PUMP
PA PASCAL
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PF PRE-FILTER
PG PRESSURE GAGE
PGW PROPYLENE GLYCOL-WATER (SOLUTION)
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRS PRESSURE REGULATING (VALVE) STATION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH – ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
PTAC PACKAGED TERMINAL AIR CONDITIONER
O
OA OUTSIDE AIR
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
OFM OIL FLOWMETER
OSD ORGANIC SOIL FILTER
Q
Q INTENTIONALLY LEFT BLANK
T&PCV TEMPERATURE AND PRESSURE
CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TG TRANSFER GRILLE
TP TRAP
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TWU THRU-WALL UNIT
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCR SILICON CONTROLLED RECTIFIER
DSD DUCT SMOKE DETECTOR
SD SMOKE DAMPER
SEN SENSIBLE HEAT
SF SUPPLY FAN
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SS STAINLESS STEEL
SSHX STEAM TO STEAM HEAT EXCHANGER
SSR SOLID SEPARATOR
ST STEAM TRAP
SUH STEAM UNIT HEATER
SVS STEAM VENT SILENCER
SWHX STEAM TO WATER HEAT EXCHANGER
R
R/E RETURN OR EXHAUST
RA RETURN AIR
RAD REFRIGERANT AIR DRYER
RAF RADIO FREQUENCY
RAHX ROTARY AIR HEAT EXCHANGER
RAT RETURN AIR TEMPERATURE
RCCH REMOTE CONDENSER CHILLER
RCU RECIPROCATING CHILLER UNIT
RD REFRIGERANT DISCHARGE
REA RELIEF AIR
RF RETURN FAN
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RO REVERSE OSMOSIS
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RV RELIEF VALVE
T
UC UNDER CUT
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
URV UPBLAST UNIT VENTILATOR
U
X INTENTIONALLY LEFT BLANK
W
W WATTS
WAG WASTE ANESTHESIA GAS
Wb WET-BULB (TEMPERATURE)
WC WATER COOLED
WCCH WATER COOLED CHILLER
WCCU WATER COOLED CONDENSING UNIT
WCHP WATER COOLED HEAT PUMPS
WCPU WATER COOLED PACKAGED UNIT
WF WATER FILTER
WFM WATER FLOWMETER
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
VI VIBRATION ISOLATOR
VIV VARIABLE INLET VANES
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE) RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
X
V
GENERAL NOTES:
A. MECHANICAL PLANS AND SECTIONS ARE INTENDED TO ACCURATELY ILLUSTRATE THE
SCOPE OF WORK BUT ARE STILL DIAGRAMMATIC IN NATURE.
B. MECHANICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE
CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY
FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.
C. THE EXISTING CONDITIONS DEPICTED IN THESE PLANS ARE BASED ON AS-BUILT
DOCUMENTATION AND INFORMATION OBTAINED FROM FIELD SURVEYS AND ARE AS
ACCURATE AS POSSIBLE. DUE TO OBSTRUCTIONS, CEILINGS, ETC., NOT ALL CONDITIONS
COULD BE VERIFIED. THE CONTRACTOR SHALL SURVEY THE SITE PRIOR TO BID AND
NOTIFY THE ARCHITECT/ENGINEER OF ANY CONFLICTS, OBSTRUCTIONS, OR
INCONSISTENCIES PREVENTING INSTALLATION OF THE MECHANICAL SYSTEM.
D. ALL EXPOSED UNINSULATED PIPING SHALL BE PAINTED PER THE SPECIFICATION SECTION
"PAINTING".
E. PROVIDE VIBRATION ISOLATION AS RECOMMENDED BY THE MANUFACTURER FOR ALL
MOTORIZED MECHANICAL EQUIPMENT TO PREVENT TRANSMISSION OF VIBRATION TO
BUILDING STRUCTURE.
F. PROVIDE VIBRATION ISOLATORS FOR ALL PIPING SUPPORTS CONNECTED TO AND WITHIN
50' OF ISOLATED EQUIPMENT (EXCEPT AT BASE ELBOW SUPPORTS AND ANCHOR POINTS)
THROUGHOUT MECHANICAL EQUIPMENT ROOMS.
G. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL,
STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC., SHOWN ON OTHER CONTRACT DOCUMENT
DRAWINGS.
H. MAINTAIN A MINIMUM OF 6′-8″ CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS,
SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL ROOMS.
I. ALL TESTING SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR PIPING
INSULATION IS APPLIED.
J. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE
LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND DOWNSTREAM AS
RECOMMENDED BY THE MANUFACTURER FOR GOOD ACCURACY.
K. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS CERTIFIED
DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED
FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND
COORDINATE ALL DUCT AND PIPING DIMENSIONS BEFORE FABRICATION.
CWR
CWS
CD
LPC
LPS
MPC
MPS
HPC
HPS
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
HIGH PRESSURE STEAM CONDENSATE
HIGH PRESSURE STEAM SUPPLY
MEDIUM PRESSURE STEAM CONDENSATE
MEDIUM PRESSURE STEAM SUPPLY
LOW PRESSURE STEAM CONDENSATE
LOW PRESSURE STEAM SUPPLY
VACUUM RETURN
FEEDWATER PUMP DISCHARGE
FEEDWATER PUMP SUCTION
VR
CONTINUOUS BLOWDOWN
CHEMICAL FEED
BOILER BLOWOFF BO
CF
CBD
FWPD
FWPS
A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO
INSTALL COMPLETE AND OPERABLE PIPING SYSTEMS AS INDICATED ON THE DRAWINGS, AS
SPECIFIED AND AS REQUIRED BY CODE.
B. UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO UNDERSIDE OF
STRUCTURE OR SLAB, WITH SPACE FOR INSULATION IF REQUIRED.
C. INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS, FLANGES, AND OTHER
APPURTENANCES REQUIRING ACCESS ARE ACCESSIBLE.
D. ALL VALVES SHALL BE INSTALLED SO THAT VALVE REMAINS IN SERVICE WHEN EQUIPMENT
OR PIPING ON EQUIPMENT SIDE OF VALVE IS REMOVED.
E. ALL BALANCING VALVES AND BUTTERFLY VALVES SHALL BE PROVIDED WITH POSITION
INDICATORS AND MAXIMUM ADJUSTABLE STOPS (MEMORY STOPS).
F. ALL VALVES (EXCEPT CONTROL VALVES) AND STRAINERS SHALL BE FULL SIZE OF PIPE
BEFORE REDUCING SIZE TO MAKE CONNECTIONS TO EQUIPMENT AND CONTROLS.
G. UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE OF EQUIPMENT, IN
BYPASSES, AND IN LONG PIPING RUNS (100' OR MORE) TO PERMIT DISASSEMBLY FOR
ALTERATION AND REPAIRS.
H. ALL PIPING SHALL CLEAR DOORS AND WINDOWS.
I. ALL VALVES SHALL BE ADJUSTED FOR SMOOTH AND EASY OPERATION.
J. ALL PIPING WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN
PIPING AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE
OWNER.
K. PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS CONNECTED TO PUMPS,
CHILLERS, COOLING TOWERS, AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION
ISOLATION EXCEPT WATER COILS. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AS CLOSE
TO THE EQUIPMENT AS POSSIBLE OR AS INDICATED ON THE DRAWINGS.
L. SLOPE REFRIGERANT PIPING ONE PERCENT IN THE DIRECTION OF OIL RETURN. LIQUID
LINES MAY BE INSTALLED LEVEL.
M. INSTALL HORIZONTAL REFRIGERANT SUCTION LINES WITH 1/2″ PER 10' DOWNWARD SLOPE
TO THE COMPRESSOR, WITH NO LONG TRAPS OR DEAD ENDS WHICH MAY CAUSE OIL TO
SEPARATE FROM THE SUCTION GAS AND RETURN TO THE COMPRESSOR IN DAMAGING
SLUGS.
N. PROVIDE LINE SIZE LIQUID INDICATORS IN MAIN LIQUID LINE LEAVING CONDENSER OR
RECEIVER. INSTALL MOISTURE LIQUID INDICATORS IN LIQUID LINES BETWEEN FILTER
DRYERS AND THERMOSTATIC EXPANSION VALVES AND IN LIQUID LINE TO RECEIVER.
A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO
INSTALL COMPLETE AND OPERABLE HVAC SYSTEMS AS INDICATED ON THE DRAWINGS, AS
SPECIFIED AND AS REQUIRED BY CODE.
B. CERTAIN ITEMS SUCH AS RISES AND DROPS IN DUCTWORK, ACCESS DOORS, VOLUME
DAMPERS, ETC., ARE INDICATED ON THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY
FOR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS THE
EXTENT OF THE REQUIREMENTS FOR THESE ITEMS.
C. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM THERMOSTATS AND HUMIDISTATS 4′-0″
(CENTERLINE) ABOVE FINISHED FLOOR.
D. ALL DUCTWORK SHALL CLEAR DOORS AND WINDOWS.
E. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR
DIMENSIONS AND DUCT SIZE SHALL BE INCREASED TO COMPENSATE FOR DUCT LINING
THICKNESS.
F. ALL AIR HANDLING UNITS SHALL OPERATE WITHOUT MOISTURE CARRYOVER.
G. LOCATE ALL MECHANICAL EQUIPMENT TO ALLOW UNOBSTRUCTED ACCESS TO UNIT
ACCESS PANELS, CONTROLS AND VALVING.
H. UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO THE UNDERSIDE OF
THE STRUCTURE, WITH SPACE FOR INSULATION IF REQUIRED.
I. ALL DUCTWORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN
DUCTS, INCLUDING DIVIDED DUCTS AND TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE
PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
J. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS FOR ALL SMOKE
DETECTORS, FIRE DAMPERS, SMOKE DAMPERS, VOLUME DAMPERS, HUMIDIFIERS, COILS,
AND OTHER ITEMS LOCATED IN THE DUCTWORK WHICH REQUIRE SERVICE AND/OR
INSPECTION.
K. PROVIDE ACCESS DOORS IN DUCTWORK FOR OPERATION, ADJUSTMENT, AND
MAINTENANCE OF ALL FANS, VALVES, AND MECHANICAL EQUIPMENT.
L. SMOKE DETECTORS SHALL BE FURNISHED AND WIRED BY THE ELECTRICAL OR FIRE
ALARM CONTRACTOR. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
MOUNTING THE SMOKE DETECTOR IN DUCTWORK AS SHOWN ON THE DRAWINGS AND IN
ACCORDANCE WITH MANUFACTURER’S PRINTED INSTRUCTIONS.
PIPING GENERAL NOTES: HVAC/SHEET METAL GENERAL NOTES:
EXISTING TO BE DEMOLISHED
LIMIT OF DEMOLITION
CONNECT NEW TO EXISTINGEXISTING TO REMAIN
NEW DUCT (INSIDE DIMENSIONS: W" X D")
RS
RL
REFRIGERANT SUCTION
REFRIGERANT LIQUID
SUPPLY AIR DUCT UP
SUPPLY AIR DUCT DOWN
H
T
H
T
26-P-3
MH-100
PUMP NO. 3 IN BUILDING NO. 26
EQUIPMENT ABBREVIATION (PUMP)
DETAIL NUMBER
SHEET NUMBER
SHEET NUMBER
SECTION NUMBER
THERMOSTAT
HUMIDISTAT
TEMPERATURE SENSOR
HUMIDITY SENSOR
BUILDING NUMBER WHERE EQUIPMENT
IS LOCATED
26-DS-100-A
ROOM NUMBER (ROOM NO. 100)
ITEM (DUCTLESS SPLIT UNIT)
BUILDING NUMBER WHERE EQUIPMENT
IS LOCATED
UNIT IDENTIFIER
DUCTLESS SPLIT UNIT TAG
MECHANICAL EQUIPMENT TAG
1 OWNER FURNISHED, CONTRACTOR
INSTALLED EQUIPMENT DESIGNATION
EXISTING TO BE DEMOLISHED
EXISTING TO REMAIN
NEW PIPE
CONNECT NEW TO EXISTING
LIMIT OF DEMOLITION
GENERAL PIPING SYMBOLS
GENERAL ANNOTATIONS
AV
STRAINERFLOAT & THERMOSTATIC
STEAM TRAP
INVERTED BUCKET
STEAM TRAP
FLANGE CONNECTION PIPE DROP
PIPE RISER TEE DOWN
TEE UP
UNION
PRESSURE REDUCING
VALVE
BALL VALVE
ANGLE GLOBE VALVE
SAFETY RELIEF VALVE
GLOBE VALVE
MANUAL OR
AUTOMATIC AIR VENT
EXPANSION JOINT
EJ
PRESSURE AND
TEMPERATURE TEST PLUG
QUICK-COUPLE HOSE
CONNECTOR
FLOW METER
HVAC PIPING SYMBOLS
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CHR
CHS
HEATING HOT WATER RETURN
HEATING HOT WATER SUPPLY
HHR
HHS QV CRYOGEN VENT
DR DRIP RETURN
CAP
REDUCER (ECCENTRIC)
TYPE
AIRFLOW (CFM)
SD-1
TYPE
AIRFLOW (CFM)
RG-1
TYPE
AIRFLOW (CFM)
EG-1
SQUARE TO ROUND TRANSITION
ELBOW WITH TURNING
VANES
ROUND ELBOW
EXHAUST, RELIEF, MAKE UP, OR
OUTSIDE AIR DUCT DOWN
EXHAUST, RELIEF, MAKE UP, OR
OUTSIDE AIR DUCT UP
RETURN DUCT DOWN
RETURN DUCT UP
BRANCH DUCT WITH HIGH EFFICIENCY
TAKE-OFF (HETO) BRANCH FITTING &
MANUAL VOLUME DAMPER
BRANCH DUCT WITH CONICAL
FITTING & MANUAL VOLUME
DAMPER
DAMPERS: (BD, FD, FSD, MD, SD, VD)
BD
XX-XX
ANCHOR
TEEDIRECTION OF FLOW
S
L. CONCRETE HOUSEKEEPING PADS TO SUIT MECHANICAL EQUIPMENT SHALL BE SIZED AND
LOCATED BY THE MECHANICAL CONTRACTOR. MINIMUM CONCRETE PAD THICKNESS SHALL
BE 4". PAD SHALL EXTEND BEYOND THE EQUIPMENT A MINIMUM OF 4" ON EACH SIDE.
CONCRETE HOUSEKEEPING PADS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR.
M. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE
SPECIFICATIONS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE
ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE BEST CONDITIONS AND
RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND SHALL HAVE THE
APPROVAL OF THE ENGINEER OR OWNERS REPRESENTATIVE BEFORE BEING INSTALLED.
DO NOT SCALE DRAWINGS.
N. ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND AS SHOWN
IN DETAILS FOR PIPING, DUCTWORK, AND EQUIPMENT (UNLESS OTHERWISE NOTED) SHALL
BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR.
O. PROVIDE ACCESS PANELS FOR INSTALLATION IN WALLS AND CEILINGS WHERE REQUIRED
TO SERVICE DAMPERS, VALVES, SMOKE DETECTORS, AND OTHER CONCEALED
MECHANICAL EQUIPMENT.
P. ALL DUCTWORK, PIPING AND EQUIPMENT SUPPORTED FROM STRUCTURAL STEEL SHALL
BE COORDINATED WITH GENERAL CONTRACTOR. ALL ATTACHMENTS TO STEEL BAR
JOISTS, TRUSSES, OR JOIST GIRDERS SHALL BE AT PANEL POINTS. REFER TO
SPECIFICATIONS FOR CONNECTION TYPE(S) ALLOWED.
Q. ALL ROOF MOUNTED EQUIPMENT CURBS FOR EQUIPMENT PROVIDED BY THE MECHANICAL
CONTRACTOR SHALL BE FURNISHED BY THE MECHANICAL CONTRACTOR. COORDINATE
INSTALLATION WITH GENERAL CONTRACTOR.
R. LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE
COORDINATED WITH ALL OTHER TRADES INVOLVED.
S. ALL OPENINGS IN RATED WALLS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE
FIRE STOPPED WITH AN APPROVED FIRE STOPPING MATERIAL.
T. ALL AIR CONDITIONING CONDENSATE DRAIN LINES FROM EACH AIR HANDLING UNIT AND
ROOFTOP UNIT SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET, WITH P-TRAP, AND
PIPED TO NEAREST DRAIN. SEE DETAILS AND SPECIFICATIONS FOR DEPTH OF AIR
CONDITIONING CONDENSATE TRAP.
U. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION.
V. ROOFTOP EQUIPMENT WITHIN 10' OF ROOF EDGE OR DROPOFF SHALL BE SUPPLIED WITH
HANDRAILS AND ALL NECESSARY BUILDING MODIFICATIONS TO ENSURE A SAFE
MAINTENANCE AREA IS MAINTAINED.
O. PROVIDE LINE SIZE STRAINER UPSTREAM OF EACH AUTOMATIC VALVE. PROVIDE SHUTOFF
VALVE ON EACH SIDE OF STRAINER.
P. PROVIDE PERMANENT FILTER DRYERS IN LOW TEMPERATURE SYSTEMS AND SYSTEMS
USING HERMETIC COMPRESSORS.
Q. PROVIDE REPLACEABLE CARTRIDGE FILTER DRYERS WITH THREE-WAY VALVE BYPASS
AASSEMBLY FOR SOLENOID VALVES, ADJACENT TO RECEIVERS.
R. PROVIDE REFRIGERANT CHARGING VALVE CONNECTIONS IN LIQUID LINE BETWEEN
RECEIVER SHUTOFF VALVE AND EXPANSION VALVE.
S. REFRIGERANT PIPING IS LIMITED TO 610' PER SYSTEM. PIPING LENGTHS AND DERATING HAS
BEEN TAKEN INTO ACCOUNT WHEN SIZING EQUIPMENT. REFER TO MANUFACTURER
SPECIFIC DATA.
DIRECTION OF PIPE
PITCH (DOWN)
FM
MV
HVAC VALVE SYMBOLS
PC PUMPED CONDENSATE
ROOM TAG
FLEXIBLE CONNECTOR
PUMP
REDUCER (CONCENTRIC)
GATE VALVE
BUTTERFLY VALVE
CHECK VALVE
THERMOMETER
PRESSURE GAUGE
STRAINER WITH BLOWOFF
AND HOSE CONNECTION
YR YEAR
Y
Z INTENTIONALLY LEFT BLANK
Z
M
CONTROL VALVE
CONTROL VALVE, THREE WAY
MOTOR CONTROLLED
VALVE
M
M
A. MECHANICAL TRADES BIDDING DEMOLITION WORK SHALL ALLOW FOR A FULL DAY ON SITE TO REVIEW EXISTING MECHANICAL SERVICES AND EQUIPMENT IN DEMOLITION AND REMOVED AREAS. ACCESS WILL BE GIVEN TO ROOF AND EXISTING MECHANICAL AND ELECTRICAL ROOMS AS REQUIRED. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK. BRING ANY DISCREPANCIES FROM THE DRAWINGS AND NOTES TO THE ENGINEER OF RECORD IMMEDIATELY. MINOR CHANGES IN THE SCOPE OF THE
DEMOLITION WORK SHALL NOT JUSTIFY AN ADDITIONAL COST.
B. DEMOLISHED WORK SHALL INCLUDE FOR TEMPORARY AND PERMANENT WORK REQUIRED TO KEEP
NON-SCOPE AREAS IN OPERATION. COORDINATE UTILITY SHUT-OFFS AND TEMPORARY POWER,
STORAGE, AND ACCESS NEEDED TO COMPLETE WORK WITH GENERAL CONTRACTOR AND
CONTRACTING OFFICER'S REPRESENTATIVE (COR).
C. REMOVAL OF EXISTING EQUIPMENT WILL REQUIRE ISOLATION OF EXISTING PIPING BRANCHES AND/OR MAINS USING SHUTOFF VALVES. INSTALL NEW ISOLATION VALVES AS REQUIRED TO COMPLETION
DEMOLITION WORK.
D. ALL DRAINED PIPING RISERS AND MAINS SHALL BE REFILLED AND PROPERLY VENTED BY THE
CONTRACTOR ONCE NEW WORK HAS BEEN COMPLETED.
E. COORDINATE REMOVAL, REPLACEMENT, AND/OR REPAIRS OF ANY EXISTING WALLS, CEILING, ETC.
REQUIRED FOR MECHANICAL DEMOLITION WORK WITH GENERAL CONTRACTOR.
F. PROVIDE TIGHTLY SEALED AND INSULATED TERMINATIONS FOR ALL PIPING, DUCTWORK, AND EQUIPMENT REMOVED FROM THE PROJECT. THERE SHALL BE NO "DEAD LEG" SECTIONS OF PIPING
WHERE WATER CAN SIT AND BECOME STAGNANT.
G. REFER TO THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) FOR INSTRUCTIONS REGARDING THE
REMOVAL AND RETURN OR DEMOLITION OF EXISTING EQUIPMENT AND FIXTURES.
H. PORTIONS OF EXISTING SYSTEMS ARE SHOWN FOR CLARITY AND MAY NOT BE NECESSARY TO MODIFY OR REVISE THEM. ALL EXISTING SYSTEMS ARE SHOWN BASED ON AVAILABLE AS-BUILT DRAWINGS AND SITE SURVEYS OF ACCESSIBLE AREAS. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS.
I. ALL WORK MUST BE COORDINATED AND SCHEDULED WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE TO ENSURE THE LEAST AMOUNT OF DISRUPTION OF BUILDING ACTIVITIES AS
POSSIBLE.
J. ALL ACCESSIBLE ABANDONED PIPING AND DUCTWORK SHALL BE REMOVED AND PROPERLY DISPOSED
OF.
K. SUPPLY AIR DUCTWORK AND PIPING NOT SHOWN HATCHED IS TO BE RETAINED, ANY DAMAGE TO
EXISTING INSULATION AND DUCTS TO BE REPAIRED TO MATCH EXISTING.
GENERAL DEMOLITION NOTES:
DS DUCTLESS MINI-SPLIT
ROOM NAME
000A
150 SF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:2 :3
P
M
LEGEND AND ABBREVIATIONS
BAJ 117RDC
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
M-000
SPUR #: 2207.00
No. REVISION DESCRIPTION DATE
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
M-401
M-401
1-CU-419
1-CU-331
1-CU-229
1-CU-1477
EXISTING PHONE ROOM
440 SF
TR
31A
121 SF
1-CU-031A7
TR
147A-1
134 SF
M-401
M-401
M-401
TR
229-1
94 SF
M-401
M-401
M-401
TR
331-1
87 SF
TR
419-1
97 SF
M-401
M-401
KEY PLAN
LEESTOWN ROAD
N
PARTITION LEGEND
1 HOUR FIRE RATED
2 HOUR FIRE RATED
NOTE: NOT ALL SYMBOLS MAY BE USED
3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:2 :3
P
M
BLDG 1 - REFERENCE PLANS
BAJ 118RDC
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
M-101
SPUR #: 2207.00
N
1" = 20'-0"
B1 - GROUND LEVEL1
N
1" = 20'-0"
B1 - LEVEL 12
N
1" = 20'-0"
B1 - LEVEL 23
N
1" = 20'-0"
B1 - LEVEL 34
N
1" = 20'-0"
B1 - LEVEL 45
KEYNOTES
1 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS
SPLIT-SYSTEM. REFER TO ENLARGED PLANS FOR MORE INFORMATION.
7 CONTRACTOR SHALL INSTALL NEW OUTDOOR CONDENSING UNIT IN THE LOCATION SHOWN. ENSURE THE UNIT HAS SUFFICIENT CLEARANCE SPACE, IS MOUNTED PROPERLY, AND IS PROTECTED AS NECESSARY.
ROUTE AND CONNECT REFRIGERANT PIPING TO THE ASSOCIATED INDOOR UNIT(S) AS SHOWN AND PER
MANUFACTURER INSTRUCTIONS.
9 NO HVAC SCOPE REQUIRED IN THIS ROOM. EXISTING MECHANICAL SYSTEMS TO REMAIN IN PLACE AND BE
REUSED.
11 CONTRACTOR SHALL ROUTE PUMPED CONDENSATE PIPING TO THE APPROXIMATE LOCATION SHOWN AND CONNECT TO NEAREST DRAINAGE SYSTEM PER CODE AND DETAIL 7/M-501. CONTRACTOR TO ABATE THE PENETRATION FOR ASBESTOS AND OTHER HAZARDOUS MATERIAL PRIOR TO DEMOLITION. SEE HAZARDOUS MATERIALS DRAWINGS FOR MORE DETAILS. DRIP PAN DRAINAGE SHALL BE TIED INTO CONDENSATE PIPING
SYSTEM.
BLDG 1
No. REVISION DESCRIPTION DATE
The information on this document is preliminary or incomplete, not for
2-CU-220
2-CU-122
TR
122-2
126 SF
M-402
M-402
1 11
M-402
M-402
TR
220-2
143 SF
TR
24A-3
64 SF
M-402
M-402
3-CU-222A
3-CU-131A
3-CU-024A
M-402
M-402
TR
131A-3
66 SF
M-402
M-402
TR
222A-3
67 SF
LEESTOWN ROAD
KEY PLAN
N
PARTITION LEGEND
1 HOUR FIRE RATED
2 HOUR FIRE RATED
NOTE: NOT ALL SYMBOLS MAY BE USED
3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:2 :3
P
M
BLDG 2 & 3 - REFERENCE PLANS
BAJ 119RDC
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
M-102
SPUR #: 2207.00
N
1" = 20'-0"
B2 - GROUND LEVEL1
N
1" = 20'-0"
B2 - LEVEL 12
N
1" = 20'-0"
B2 - LEVEL 23
N
1" = 20'-0"
B3 - GROUND LEVEL4
N
1" = 20'-0"
B3 - LEVEL 15
N
1" = 20'-0"
B3 - LEVEL 26
KEYNOTES
1 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS
SPLIT-SYSTEM. REFER TO ENLARGED PLANS FOR MORE INFORMATION.
7 CONTRACTOR SHALL INSTALL NEW OUTDOOR CONDENSING UNIT IN THE LOCATION SHOWN. ENSURE THE UNIT HAS SUFFICIENT CLEARANCE SPACE, IS MOUNTED PROPERLY, AND IS PROTECTED AS NECESSARY.
ROUTE AND CONNECT REFRIGERANT PIPING TO THE ASSOCIATED INDOOR UNIT(S) AS SHOWN AND PER
MANUFACTURER INSTRUCTIONS.
11 CONTRACTOR SHALL ROUTE PUMPED CONDENSATE PIPING TO THE APPROXIMATE LOCATION SHOWN AND CONNECT TO NEAREST DRAINAGE SYSTEM PER CODE AND DETAIL 7/M-501. CONTRACTOR TO ABATE THE PENETRATION FOR ASBESTOS AND OTHER HAZARDOUS MATERIAL PRIOR TO DEMOLITION. SEE HAZARDOUS MATERIALS DRAWINGS FOR MORE DETAILS. DRIP PAN DRAINAGE SHALL BE TIED INTO CONDENSATE PIPING
SYSTEM.
BLDG 2 & 3
No. REVISION DESCRIPTION DATE
The information on this document is preliminary or incomplete, not for
TR
102-4
119 SF
M-402
M-402
4-CU-1027
ELEC.
6C-12
99 SF
WAREHOUSE AREA
Not Enclosed
WORK SHOP
8-37
2330 SF
SHOP
2-47
1128 SF
SERVICE
2-48
118 SF
KEY PLAN
LEESTOWN ROAD
N
PARTITION LEGEND
1 HOUR FIRE RATED
2 HOUR FIRE RATED
NOTE: NOT ALL SYMBOLS MAY BE USED
3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:2 :3
P
M
BLDG 4, 12, 37, 47, & 48 - REFERENCE
PLANS
BAJ 120RDC
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
M-103
SPUR #: 2207.00
N
1" = 20'-0"
B4 - LEVEL 11
N
1" = 20'-0"
B12 - LEVEL 12
N
1" = 20'-0"
B37 - LEVEL 13
KEYNOTES
1 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS
SPLIT-SYSTEM. REFER TO ENLARGED PLANS FOR MORE INFORMATION.
7 CONTRACTOR SHALL INSTALL NEW OUTDOOR CONDENSING UNIT IN THE LOCATION SHOWN. ENSURE THE UNIT HAS SUFFICIENT CLEARANCE SPACE, IS MOUNTED PROPERLY, AND IS PROTECTED AS NECESSARY.
ROUTE AND CONNECT REFRIGERANT PIPING TO THE ASSOCIATED INDOOR UNIT(S) AS SHOWN AND PER
MANUFACTURER INSTRUCTIONS.
11 CONTRACTOR SHALL ROUTE PUMPED CONDENSATE PIPING TO THE APPROXIMATE LOCATION SHOWN AND CONNECT TO NEAREST DRAINAGE SYSTEM PER CODE AND DETAIL 7/M-501. CONTRACTOR TO ABATE THE PENETRATION FOR ASBESTOS AND OTHER HAZARDOUS MATERIAL PRIOR TO DEMOLITION. SEE HAZARDOUS MATERIALS DRAWINGS FOR MORE DETAILS. DRIP PAN DRAINAGE SHALL BE TIED INTO CONDENSATE PIPING
SYSTEM.
12 NO HVAC SCOPE REQUIRED IN THIS ROOM. EXISTING MECHANICAL SYSTEMS TO REMAIN IN PLACE AND BE REUSED. NEW TELECOM ENCLOSURE TO BE INSTALLED. REFER TO ARCHITECTURAL, ELECTRICAL, AND
TELECOMMUNICATIONS DRAWINGS FOR MORE INFORMATION.
BLDG 4, 12, 37, 47 & 48
N
1" = 20'-0"
B47 - LEVEL 14
N
1" = 20'-0"
B48 - LEVEL 15
No. REVISION DESCRIPTION DATE
The information on this document is preliminary or incomplete, not for
CLOSET
6B-16
80 SF
M-403
M-403
TR
15-16
111 SF
16-CU-207A
16-CU-102
16-CU-15
CLOSET
115B-16
82 SF
TR
102-16
111 SF
M-403
M-403
CLOSET
222A-16
82 SF
M-403
TR
207A-16
109 SF
M-403
TR
13C-17
125 SF
M-403
M-403
17-CU-217A
17-CU-125A
17-CU-13C
M-404
M-404
CLOSET (DEMARC)
13B-17
141 SF
NEW MCR
22-17
732 SF
MECH PAD
22B-17
390 SF
CLOSET
24-17
105 SF
FIRE CONTROL PANEL
AND CLEAN AGENT
STORAGE
23-17
112 SF
EXISTING 2-TON
CONDENSER
CLOSET
126-17
80 SF
TR
125A-17
137 SF
M-403
M-403
CLOSET
218-17
79 SF
TR
217A-17
124 SF
M-403
M-403
LEESTOWN ROAD
KEY PLAN
N
PARTITION LEGEND
1 HOUR FIRE RATED
2 HOUR FIRE RATED
NOTE: NOT ALL SYMBOLS MAY BE USED
3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:2 :4
P
M
BLDG 16 & 17 - REFERENCE PLANS
BAJ 121RDC
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
M-104
SPUR #: 2207.00
N
1" = 20'-0"
B16 - GROUND LEVEL1
N
1" = 20'-0"
B16 - LEVEL 12
N
1" = 20'-0"
B16 - LEVEL 23
N
1" = 20'-0"
B17 - GROUND LEVEL4
N
1" = 20'-0"
B17 - LEVEL 15
N
1" = 20'-0"
B17 - LEVEL 26
KEYNOTES
1 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS
SPLIT-SYSTEM. REFER TO ENLARGED PLANS FOR MORE INFORMATION.
7 CONTRACTOR SHALL INSTALL NEW OUTDOOR CONDENSING UNIT IN THE LOCATION SHOWN. ENSURE THE UNIT HAS SUFFICIENT CLEARANCE SPACE, IS MOUNTED PROPERLY, AND IS PROTECTED AS NECESSARY.
ROUTE AND CONNECT REFRIGERANT PIPING TO THE ASSOCIATED INDOOR UNIT(S) AS SHOWN AND PER
MANUFACTURER INSTRUCTIONS.
9 NO HVAC SCOPE REQUIRED IN THIS ROOM. EXISTING MECHANICAL SYSTEMS TO REMAIN IN PLACE AND BE
REUSED.
10 NO HVAC SCOPE REQUIRED IN THIS ROOM. EXISTING MECHANICAL SYSTEMS TO REMAIN IN PLACE AND BE REUSED. NEW FIBER TO BE INSTALLED. REFER TO ARCHITECTURAL AND TELECOMMUNICATIONS DRAWINGS
FOR MORE INFORMATION.
11 CONTRACTOR SHALL ROUTE PUMPED CONDENSATE PIPING TO THE APPROXIMATE LOCATION SHOWN AND CONNECT TO NEAREST DRAINAGE SYSTEM PER CODE AND DETAIL 7/M-501. CONTRACTOR TO ABATE THE PENETRATION FOR ASBESTOS AND OTHER HAZARDOUS MATERIAL PRIOR TO DEMOLITION. SEE HAZARDOUS MATERIALS DRAWINGS FOR MORE DETAILS. DRIP PAN DRAINAGE SHALL BE TIED INTO CONDENSATE PIPING
SYSTEM.
33 NEW MAIN COMPUTER ROOM TO BE CONSTRUCTED IN THIS LOCATION. REFER TO ENLARGED PLANS FOR
MORE INFORMATION.
34 SPACE TO BE MODIFIED DURING EHRM CONSTRUCTION. REFER TO ENLARGED PLANS FOR MORE
INFORMATION.
BLDG 16 & 17
No. REVISION DESCRIPTION DATE
The information on this document is preliminary or incomplete, not for
19-25
88 SF
M-405
M-405
25-CU-214
25-CU-112
25-CU-019 7
TR
112-25
87 SF
M-405
M-405
TR
214-25
85 SF
M-405
M-405
N
KEY PLAN
LEESTOWN ROAD
PARTITION LEGEND
1 HOUR FIRE RATED
2 HOUR FIRE RATED
NOTE: NOT ALL SYMBOLS MAY BE USED
3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:2 :4
P
M
BLDG 25 - REFERENCE PLANS
BAJ 122RDC
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
M-105
SPUR #: 2207.00
N
1" = 20'-0"
B25 - GROUND LEVEL1
N
1" = 20'-0"
B25 - LEVEL 12
N
1" = 20'-0"
B25 - LEVEL 23
KEYNOTES
1 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS
SPLIT-SYSTEM. REFER TO ENLARGED PLANS FOR MORE INFORMATION.
7 CONTRACTOR SHALL INSTALL NEW OUTDOOR CONDENSING UNIT IN THE LOCATION SHOWN. ENSURE THE UNIT HAS SUFFICIENT CLEARANCE SPACE, IS MOUNTED PROPERLY, AND IS PROTECTED AS NECESSARY.
ROUTE AND CONNECT REFRIGERANT PIPING TO THE ASSOCIATED INDOOR UNIT(S) AS SHOWN AND PER
MANUFACTURER INSTRUCTIONS.
11 CONTRACTOR SHALL ROUTE PUMPED CONDENSATE PIPING TO THE APPROXIMATE LOCATION SHOWN AND CONNECT TO NEAREST DRAINAGE SYSTEM PER CODE AND DETAIL 7/M-501. CONTRACTOR TO ABATE THE
PENETRATION FOR ASBESTOS AND OTHER HAZARDOUS MATERIAL PRIOR TO DEMOLITION. SEE
HAZARDOUS MATERIALS DRAWINGS FOR MORE DETAILS. DRIP PAN DRAINAGE SHALL BE TIED INTO
CONDENSATE PIPING SYSTEM.
BLDG 25
No. REVISION DESCRIPTION DATE
The information on this document is preliminary or incomplete, not for
2F-27
135 SF
TR
16D-27
134 SF
TR
136A-27
134 SF
TR
117A-27
134 SF
TR
217A-27
133 SF
TR
236A-27
135 SF
TR
1A-28
120 SF
M-406
M-406
28-CU-001A 7
TR
156-28
111 SF
TR
247-28
107 SF
N
KEY PLAN
LEESTOWN ROAD
PARTITION LEGEND
1 HOUR FIRE RATED
2 HOUR FIRE RATED
NOTE: NOT ALL SYMBOLS MAY BE USED
3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:2 :4
P
M
BLDG 27 & 28 - REFERENCE PLANS
BAJ 123RDC
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
M-106
SPUR #: 2207.00
N
1" = 20'-0"
B27 - GROUND LEVEL1
N
1" = 20'-0"
B27 - LEVEL 12
N
1" = 20'-0"
B27 - LEVEL 23
N
1" = 20'-0"
B28 - GROUND LEVEL4
N
1" = 20'-0"
B28 - LEVEL 15
N
1" = 20'-0"
B28 - LEVEL 26
KEYNOTES
1 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS
SPLIT-SYSTEM. REFER TO ENLARGED PLANS FOR MORE INFORMATION.
7 CONTRACTOR SHALL INSTALL NEW OUTDOOR CONDENSING UNIT IN THE LOCATION SHOWN. ENSURE THE UNIT HAS SUFFICIENT CLEARANCE SPACE, IS MOUNTED PROPERLY, AND IS PROTECTED AS NECESSARY.
ROUTE AND CONNECT REFRIGERANT PIPING TO THE ASSOCIATED INDOOR UNIT(S) AS SHOWN AND PER
MANUFACTURER INSTRUCTIONS.
10 NO HVAC SCOPE REQUIRED IN THIS ROOM. EXISTING MECHANICAL SYSTEMS TO REMAIN IN PLACE AND BE REUSED. NEW FIBER TO BE INSTALLED. REFER TO ARCHITECTURAL AND TELECOMMUNICATIONS DRAWINGS
FOR MORE INFORMATION.
11 CONTRACTOR SHALL ROUTE PUMPED CONDENSATE PIPING TO THE APPROXIMATE LOCATION SHOWN AND CONNECT TO NEAREST DRAINAGE SYSTEM PER CODE AND DETAIL 7/M-501. CONTRACTOR TO ABATE THE PENETRATION FOR ASBESTOS AND OTHER HAZARDOUS MATERIAL PRIOR TO DEMOLITION. SEE HAZARDOUS MATERIALS DRAWINGS FOR MORE DETAILS. DRIP PAN DRAINAGE SHALL BE TIED INTO CONDENSATE PIPING
SYSTEM.
BLDG 27 & 28
No. REVISION DESCRIPTION DATE
The information on this document is preliminary or incomplete, not for
M-406
M-406
TR
19B-29
144 SF
29-CU-19B
29-CU-135A
M-406
M-406
TR
135A-29
129 SF
N
KEY PLAN
LEESTOWN ROAD
PARTITION LEGEND
1 HOUR FIRE RATED
2 HOUR FIRE RATED
NOTE: NOT ALL SYMBOLS MAY BE USED
3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:2 :4
P
M
BLDG 29 - REFERENCE PLANS
BAJ 124RDC
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
M-107
SPUR #: 2207.00
N
1" = 20'-0"
B29 - GROUND LEVEL1
N
1" = 20'-0"
B29 - LEVEL 12
KEYNOTES
1 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS
SPLIT-SYSTEM. REFER TO ENLARGED PLANS FOR MORE INFORMATION.
7 CONTRACTOR SHALL INSTALL NEW OUTDOOR CONDENSING UNIT IN THE LOCATION SHOWN. ENSURE THE UNIT HAS SUFFICIENT CLEARANCE SPACE, IS MOUNTED PROPERLY, AND IS PROTECTED AS NECESSARY.
ROUTE AND CONNECT REFRIGERANT PIPING TO THE ASSOCIATED INDOOR UNIT(S) AS SHOWN AND PER
MANUFACTURER INSTRUCTIONS.
9 NO HVAC SCOPE REQUIRED IN THIS ROOM. EXISTING MECHANICAL SYSTEMS TO REMAIN IN PLACE AND BE
REUSED.
11 CONTRACTOR SHALL ROUTE PUMPED CONDENSATE PIPING TO THE APPROXIMATE LOCATION SHOWN AND CONNECT TO NEAREST DRAINAGE SYSTEM PER CODE AND DETAIL 7/M-501. CONTRACTOR TO ABATE THE
PENETRATION FOR ASBESTOS AND OTHER HAZARDOUS MATERIAL PRIOR TO DEMOLITION. SEE
HAZARDOUS MATERIALS DRAWINGS FOR MORE DETAILS. DRIP PAN DRAINAGE SHALL BE TIED INTO
CONDENSATE PIPING SYSTEM.
BLDG 29
No. REVISION DESCRIPTION DATE
The information on this document is preliminary or incomplete, not for
31A
D21
TR
31A
1-DS-031A 215 RL
RS
3/4" CD
5 19
T
1-DS-031A
TR
147A-1
5" CHR
6" CHS
2 1/2" DCW
20"x10" EA
20"x10" EA
"x
" E
A
1 1/2" HHS
24"x12" EA UP
THRU CEILING
20"x10" EA DN
THRU FLOOR
1 1/4" DCW
FCU D2
D6
TR
147A-1
20"x10" EA
5" CHR
6" CHS
2 1/2" DCW
24"x12" EA UP
THRU CEILING
20"x10" EA DN
THRU FLOOR
"x
" E
A
1 1/4" DCW
20"x10" EA
1-DS-147A2
RS
RL
T
1-DS-147A
3/4" CD
1" CD
REFRIGERANT PIPING
TO FLOORS ABOVE
(TYP)
TR
229-1
1" DCW
1" DHW
"x
" E
A
24"x12" EA DN
THRU FLOOR
24"x14" EA UP
THRU CEILING
FCU
1 1/2" HHS
D2
D6
10"ø EA
TR
229-1
24"x12" EA DN
THRU FLOOR
24"x14" EA UP
THRU CEILING
1" DHW
1" DCW24
"x
" E
A
10"ø EA
1-DS-2292
RS
RL
3/4" CD
22 23
T
1-DS-229
REFRIGERANT PIPING
TO FLOORS ABOVE
(TYP)
TR
331-1
FCU
3/4" DCW
3/4" DHW
2 1/2" HHS
12"x6" RA
"x
" E
A
"x
" E A
14"x18" EA
24"x14" EA DN
THRU FLOOR
28"x14" EA UP
THRU CEILING
D5
D6
D2
D5
12"x6"
TR
331-1
24"x14" EA DN
THRU FLOOR
28"x14" EA UP
THRU CEILING
3/4" DHW
3/4" DCW
14"x18" EA
"x
" E
A
"x
" E A
12"x6" RA
1-DS-3312
RS
RL
3/4" CD
T
1-DS-331
REFRIGERANT PIPING
TO FLOORS ABOVE
(TYP)
TR
419-1
FCU
"x
" E
A
20"x14" EA
12"x6" EA
3" CHR
3" CHS
3" HHR
3" HHS
28"x14" EA DN
THRU FLOOR
28"x14" EA UP
THRU CEILING
D6
D2
2" HHS
D5
TR
419-1
28"x14" EA DN
THRU FLOOR
28"x14" EA UP
THRU CEILING
3" CHR
3" CHS
3" HHR
3" HHS
"x
" E
A
20"x14" EA
1-DS-4192
RS
RL
3/4" CD
T
1-DS-419
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:2 :5
P
M
BLDG 1 - ENLARGED PLANS
BAJ 125RDC
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
M-401
SPUR #: 2207.00
1/4" = 1'-0" 1/ M-101
B1 - GROUND LEVEL - 31A - DEMO11/4" = 1'-0" 1/ M-101
B1 - GROUND LEVEL - 31A - NEW21/4" = 1'-0" 2/ M-101
B1 - LEVEL 1 - 147A - DEMO31/4" = 1'-0" 2/ M-101
B1 - LEVEL 1 - 147A - NEW4
1/4" = 1'-0" 3/ M-101
B1 - LEVEL 2 - 229 - DEMO51/4" = 1'-0" 3/ M-101
B1 - LEVEL 2 - 229 - NEW61/4" = 1'-0" 4/ M-101
B1 - LEVEL 3 - 331 - DEMO71/4" = 1'-0" 4/ M-101
B1 - LEVEL 3 - 331 - NEW8
1/4" = 1'-0" 5/ M-101
B1 - LEVEL 4 - 419 - DEMO91/4" = 1'-0" 5/ M-101
B1 - LEVEL 4 - 419 - NEW10
BLDG 1
DEMOLITION KEYNOTES
D2 CONTRACTOR SHALL DEMOLISH EXISTING CEILING-MOUNTED FAN COIL UNIT, ASSOCIATED PIPING, AND
ACCESSORIES. PREPARE SPACE FOR INSTALLATION OF NEW INDOOR MINI SPLIT UNIT(S).
D5 EXISTING DUCT(S) AND GRILLE(S) TO BE DEMOLISHED BACK TO NEAREST BRANCH/MAIN TAKEOFF AND
CAPPED. PREPARE SPACE FOR INSTALLATION OF NEW INDOOR MINI SPLIT UNIT(S).
D6 EXISTING HYDRONIC LINE(S) TO BE DEMOLISHED BACK TO NEAREST BRANCH/MAIN TAKEOFF AND CAPPED.
PREPARE SPACE FOR INSTALLATION OF NEW INDOOR MINI SPLIT UNIT(S).
D21 CONTRACTOR SHALL DEMOLISH EXISTING RADIATOR, ASSOCIATED PIPING, AND ACCESSORIES. PROVIDE PATCH AND REPAIR PENETRATIONS LEFT IN PLACE. PREPARE SPACE FOR INSTALLATION OF NEW
COOLING-ONLY DIRECT-EXPANSION DUCTLESS SPLIT-SYSTEM.
KEYNOTES
2 CONTRACTOR SHALL INSTALL NEW DUCTLESS SPLIT INDOOR UNIT, CONTROLS, AND ACCESSORIES IN THE LOCATION SHOWN. MOUNT UNIT AS HIGH AS POSSIBLE TO AVOID OBSTRUCTIONS.
This is the start of the file's text. The full file is on GovTribe.