13 - 596-22-700 Drawings 09_Security.pdf

PDF 46 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction Lexington - Leestown, KY 596-22-700
Solicitation number
36C77625B0040
Issued by

About this file

These are electronic security system design drawings for the Electronic Health Record Modernization (EHRM) Infrastructure Upgrades project at the Lexington VA Health Care System located at 2250 Leestown Road in Lexington, Kentucky. The comprehensive set of architectural and engineering drawings details a multi-building security infrastructure upgrade involving Buildings 1, 2, 3, 4, 12, 16, 17, 25, 27, 28, 29, 37, 47, and 48, with a focus on modernizing telecommunications rooms, security camera placements, access control systems, and electronic security infrastructure.

The drawings specify detailed requirements for installing new security cameras (multiple types including 90-degree, 270-degree, and motion-activated models), card readers with dual authentication capabilities, electric strikes, magnetic locks, request-to-exit devices, and associated cabling and conduit systems. Key design specifications include compatibility with existing VA campus security systems, mounting heights for devices, integration with existing telecommunications infrastructure, and adherence to VA Office of Information & Technology standards and physical security design manuals. The project involves both new installations and strategic replacements/upgrades of existing security equipment across multiple campus buildings.

View the file

Other files

File Type Posted
36C77625B0040 0006.pdf PDF
0006 - 596-22-700 DBA Wages - Fayette County - 08-22-2025.pdf PDF
36C77625B0040 0005.pdf PDF
0004 - 596-22-700 Responses to Tech Questions - 8-19-25.pdf PDF
0004 - 596-22-700 Spec Section 23 07 11.pdf PDF
0004 - 596-22-700 Spec Section 02 82 13.13 Revisions.pdf PDF
0004 - 596-22-700 Drawings 00_General Revisions.pdf PDF
0004 - 596-22-700 TR Photos - Question 58.pdf PDF
0004 - 596-22-700 Lexington TR Notes-MASTER.pdf PDF
0004 - 596-22-700 Spec Section 00 01 10 Revisions.pdf PDF
0004 - 596-22-700 Spec Section 01 00 00 Revisions.pdf PDF
0004 - 596-22-700 Drawings 02_Civil Revisions.pdf PDF
36C77625B0040 0004.pdf PDF
0004 - 596-22-700 Spec Section 08 11 13 Revisions.pdf PDF
0004 - 596-22-700 Spec Section 08 71 00 Revisions.pdf PDF
0004 - 596-22-700 Drawings 01_Environmental Revisions.pdf PDF
36C77625B0040 0003.pdf PDF
0003 - 596-22-700 Responses to Tech Questions - 8-12-25.pdf PDF
0003 - 596-22-700 DBA Wages - Fayette County - 08-08-2025.pdf PDF
0002 - 596-22-700 DBA Wages - Fayette County - 07-18-2025.pdf PDF
36C77625B0040 0002.pdf PDF
36C77625B0040 0001.pdf PDF
0001 - 596-22-700 Site Visit Sign-in Sheet - 7-8-25.pdf PDF
IFB 36C77625B0040 - 6-25-25.pdf PDF
02 - 596-22-700 Specs 2.pdf PDF
10 - 596-22-700 Drawings 06_Mechanical.pdf PDF
12 - 596-22-700 Drawings 08_Telecom.pdf PDF
16 - 596-22-700 PCRA.pdf PDF
07 - 596-22-700 Drawings 03_Structural.pdf PDF
09 - 596-22-700 Drawings 05_Fire Protection.pdf PDF
15 - 596-22-700 ICRA III.pdf PDF
17 - 596-22-700 Brand Name Justification.pdf PDF
18 - 596-22-700 DBA Wages - Fayette County - 06-06-2025.pdf PDF
19 - 596-22-700 VAAR 852.219-75 LOS - Construction.docx DOCX document
01 - 596-22-700 Specs 1.pdf PDF
03 - 596-22-700 Spec Section 01 31 00.01.pdf PDF
04 - 596-22-700 Drawings 00_General.pdf PDF
08 - 596-22-700 Drawings 04_Architectural.pdf PDF
11 - 596-22-700 Drawings 07_Electrical.pdf PDF
05 - 596-22-700 Drawings 01_Environmental.pdf PDF
06 - 596-22-700 Drawings 02_Civil.pdf PDF
14 - 596-22-700 ICRA II.pdf PDF
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

L

LIGHT EMITTING DIODE

LINEAR FEET (FOOT)

LIGHT HAZARD

LOCAL OPERATING CONSOLE

LED

LF

LH

LOC

LOW VOLTAGELV

M

MASTER ANTENNA TELEVISION SYSTEMMATV

MAXIMUMMAX

METAL-CLADMC

MAIN DISTRIBUTION FRAMEMDF

MANHOLEMH

MINIMUMMIN

MOUNTEDMTD

MOUNTINGMTG

N

NOT APPLICABLENA

NATIONAL ELECTRICAL CODENEC

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NEMA

NATIONAL FIRE PROTECTION ASSOCIATIONNFPA

NOT IN CONTRACTNIC

NOT TO SCALENTS

O

ON CENTEROC

OUTSIDE DIAMETEROD

ORDINARY HAZARDOH

P

PUBLIC ADDRESSPA

PULL CORDPC

POWER OVER ETHERNETPOE

PATCH PANELPP

POWERPWR

R

RCDD REGISTERED COMMUNICATIONS DISTRIBUTION DESIGNER

REFLECTED CEILING PLANRCP

RECEPTACLERCPT

RECESSEDREC

REQUIREDREQD

RIGID GALVANIZED STEELRGS

ROOMRM

ROOT MEAN SQUARERMS

RACK UNITRU

S

SUPPLYS

SCHEDULESCHED

SMOKE DETECTORSD

SIMILARSIM

SPEAKERSP

SPECIFICATIONSPEC

SPEAKER/ STROBESP/ST

SQUARESQ

STROBEST

SHIELDED TWISTED PAIRSTP

SURFACESURF

SYSTEMSYST

T

TELECOMMUNICATIONS ENCLOSURETE

TELECOMMUNICATIONS ENCLOSURE FACILITYTEF

TELEPHONETEL

TEMPERATURETEMP

TELECOMMUNICATIONS EQUIPMENT ROOMTER

TELECOMMUNICATIONS GROUNDING BUSSBARTGB

TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION

TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSSBAR

TR TELECOMMUNICATIONS ROOM

TP TWISTED PAIR

TTB TELEPHONE TERMINAL BOARD

TYP TYPICAL

U

UNDERFLOOR DUCTUFD

UNDERGROUNDUGND

UNDERWRITERS LABORATORYUL

UNLESS NOTED OTHERWISEUNO

UNINTERRUPTIBLE POWER SUPPLYUPS

UTILITYUTIL

V

VERTICAL CABLE MANAGERVCM

W

WITHW/

WALL MOUNTEDWM

WITHOUTW/O

X

EXPLOSION PROOFXP

GENERAL NOTES

1. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED

AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST

WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.

2. FINAL LOCATION OF ALL DEVICES SHALL BE COORDINATED WITH FINAL

ROOM FURNITURE CONFIGURATIONS, ACCESSORIES, SPACE INDICATED

FOR SPECIFIC DUTY.

3. ELECTRICAL OUTLETS INDICATED FOR REFERENCE PURPOSES ONLY;

REFER TO ELECTRICAL PLANS FOR ELECTRICAL REQUIREMENTS.

4. MOUNTING HEIGHTS FOR DEVICES SHALL BE MEASURED FROM FINAL

FINISH FLOOR TO CENTER OF BOX UNLESS NOTED OTHERWISE.

5. VERIFY THE LOCATIONS OF ALL FIREPROOFING PRIOR TO THE

INSTALLATION OF CONDUIT AND BACKBOXES.

6. IF FIELD CONDITIONS VARY FROM THE DRAWINGS, THE CONTRACTOR

SHALL DOCUMENT THE VARIATION AND REPORT IT TO THE GENERAL

CONTRACTOR FOR RESOLUTION WITH THE ENGINEER OF RECORD.

7. COORDINATE THE INSTALLATION REQUIREMENTS OF SYSTEM DEVICES,

EQUIPMENT, PATHWAYS, AND OTHER COMPONENTS WITH THE GENERAL

CONTRACTOR AND OTHER BUILDING TRADES PRIOR TO INSTALLATION.

8. COORDINATE GROUNDING REQUIREMENTS WITH THE ELECTRICAL

CONTRACTOR AND ENSURE THE COMMUNICATIONS GROUNDING MEETS

SYSTEM REQUIREMENTS AND TIA J-STD-607A STANDARDS PRIOR TO

ENERGIZING AND SYSTEMS EQUIPMENT.

9. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT

BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS

SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-DAYS

PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED

OTHERWISE.

ABBREVIATIONS

EIGHT POSITION, EIGHT CONTACT

ALARM ANNUNCIATOR PANEL

ABOVE FINISHED GRADE

ABOVE FINISHED FLOOR

AUTHORITY HAVING JURISDICTION

THE AMERICAN NATIONAL STANDARDS INSTITUTE

ARCHITECT

BATTERY

BOTTOM OF CABLE TRAY

BUILDING INDUSTRY CONSULTING SERVICE

INTERNATIONAL

8P8C

A

AAP

AFG

AFF

AHJ

ANSI

ARCH

B

BATT

BOCT

BICSI

CONDUIT

COMMUNITY ANTENNA TELEVISION

CLOSED CIRCUIT TELEVISION

CEILING

CEILING MOUNTED

COMPUTER MACHINE ROOM

COAXIAL CABLE

C

C

CATV

CCTV

CLG

CM

CMR

COAX

COMMUNICATIONCOMM

CONTINUE/ CONTINUOUSCONT

CENTERCTR

COPPERCU

D

DECIBEL OR DIRECT BURIALDB

DATA CENTERDC

DEMOLISH/ DEMOLITIONDEMO

DIAMETERDIA

DIMENSIONDIM

DOME LIGHTDL

DRAWINGDWG

E

EACHEA

EXTRA HAZARDEH

ELEVATIONEL

ELEVATORELEV

EMERGENCYEMER

ELECTROMAGNETIC INTERFERENCEEMI

ELECTRICAL METALLIC TUBINGEMT

EQUIPMENTEQUIP

EQUIPMENTEQPM

EXISTING TO REMAINETR

EXISTINGEX

F

FIRE ALARMFA

FINISHED FLOOR ELEVATIONFFE

FLEXIBLE METALLIC CONDUITFLEX

FLOORFLR

FEETFT

FIBER-OPTICFO

G

GAUGEGA

GENERAL CONTRACTORGC

GROUNDGND

H

HORIZONTAL CABLE MANAGERHCM

HEIGHTHGT

HANDHOLEHH

HERTZHZ

I

INSIDE DIAMETERID

INTERMEDIATE DISTRIBUTION FRAMEIDF

INFRAREDIR

J

JUNCTION BOXJB

K

KILOWATTKW

PROJECT CODES AND STANDARDS

A. VA OFFICE OF INFORMATION & TECHNOLOGY (OIT) INFRASTRUCTURE

STANDARDS FOR TELECOMMUNICATIONS SPACES, 1 JUNE 2023

B. VA PG-18-10 TELECOMMUNICATIONS AND SPECIAL

TELECOMMUNICATIONS SYSTEMS DESIGN MANUAL, FEBRUARY 2016

C. BICSI AND EIA/TIA STANDARDS AS DEFINED IN VA-18-10

D. VA-PSRDM - PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL,

1 JUNE 2023

PLAN LEGEND

DESCRIPTIONSYMBOL

OUT OF SCOPE AREA

UNSHIELDED TWISTED PAIRUTP

VIDEO SURVEILLANCE SYSTEMVSS

SINGLE-MODESM

SECURITY CONTROL CENTERSCC

SECURITY OPERATION CENTERSOC

OUTSIDE PLANTOSP

NETWORK OPERATION CENTERNOC

MULTI-MODEMM

INSIDE PLANTISP

DEMARCATION POINT OR ROOMDEMARC

ELECTRONIC SECURITY SYMBOLS

DESCRIPTIONSYMBOL

DOOR AUTO-CLOSER

PANIC/DURESS BUTTON MOUNTED AT 48" A.F.F. UNLESS

NOTED OTHERWISE

ACCESS CONTROL CARD READER/KEYPAD COMBINATION

DEVICE

DOOR POSITION SWITCH

INTRUSION DETECTION PASSIVE INFRARED MOTION

DETECTOR - WALL MOUNTED

DOOR AUTO-OPENER

ANTI-PROP DEVICE

REQUEST FOR EXIT PUSHBUTTON

DOORBELL PUSHBUTTON

BALANCED MAGNETIC SWITCH - WIRED TO ACCESS

CONTROL SYSTEM ONLY UNLESS OTHERWISE NOTED

DELAYED EGRESS

GLASS BREAK DETECTOR

GATE OPENER

INTRUSION DETECTION SYSTEM KEYPAD

MAGNETIC LOCKING DEVICE

AD

AC

AP

CR

RE

EL

GB

GO

DB

DE

DM

KP

MD

ML

PB

LOCAL ALARMLA

ELECTRIC STRIKE LOCK

SINGLE VIEW SECURITY CAMERA

XX:XX:XX = BUILDING ID:TYPE:SEQUENTIAL NUMBERXX:XX:XX

SECURITY SURVEILLANCE TELEVISION LINE, MIN. 1"

RACEWAY

VIDEO SURVEILLANCE MONITOR STATION

SSTV

M

WM WINDOW POSITION MONITOR/CONTACT SENSOR

BS

REQUEST FOR EXIT PASSIVE

INFRARED MOTION SENSOR

RE

IR

PB

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:3 :1

P

M

ELECTRONIC SECURITY SYSTEM COVER

SHEET

MDT Drawing # 237 OF 258KGH

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

T-000

SPUR #: 2207

No. REVISION DESCRIPTION DATE

ENGG

EQUIP

RM

STAIR

MED

RESEARCH

RM

PIPE

SPACE

CORRIDOR

SPRINKLER

PIPECORRIDOR

PODIATRY

STOR

WOMENS

TOILET

SOCIAL

WORKER

OFFICE

FIRE

CABINET

MED FOSTER

CARE OFFICE

P TOILET

CODING

COMPLIANCE

MGR

OFFICE

ELEVATOR

ELEVATOR

LOBBYPODIATRY

EXAM

ELEVATOR

STAIR

PODIATRY

SECTION

CHIEF

TOILET

PODIATRY

EXAM

SPD

CLOSET

MENS

TOILET

PIPE

SPACE

STAIR

FOYER

PODIATRIST

OFFICE

CODING

OFFICE

BREAK

RM

EXAMINATION

SOCIAL

WORKER

OFFICE

SOCIAL

WORK

SUPV

OFFICE

OFFICE

OFFICECOMPLIANCE

ANALYST

WAITING

RM

RECEPTIONIST

TEL/DATA

CLOSET IT

CLOSET

PODIATRY

RM

PODIATRY

RM

PODIATRY

RM

PODIATRY

RM

PODIATRY

RM

PODIATRY

CONFERENCE

RM

CODING

TY401

TY401

TR

147A-1

TY401

TY401

EXISTING

PHONE

ROOM

TR

31A

TY401

TY401

TR

229-1

TY402

TY402

TR

331-1

TY402

TY402

TR

419-1

A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED

AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST

WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.

B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD

NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR

REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD

VERIFY ALL CONDITIONS.

C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT

BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS

SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-

DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED

OTHERWISE.

D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS

DEFINITION:

1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR

INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.

2. SYMBOLS DASHED OR SPECIFICALLY KEYED NOTED: INDICATES

DEMOLITION WORK.

E. OWNER SHALL HAVE FIRST SALVAGE RIGHTS FOR ANY DEMOLISHED

DEVICES OR MATERIAL.

F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS

ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.

G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE

EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"

CONDUIT.

H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL

BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR

SHALL PROVIDE NEW WALL-BOX.

ELECTRONIC SECURITY SYSTEM GENERAL NOTES

KEY PLAN

LEESTOWN ROAD

N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:3 :1

P

M

BUILDING 1 - REFERENCE PLANS

MDT Drawing # 238 OF 258KGH

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

TY101

SPUR #: 2207

N

1" = 20'-0"

B1 - LEVEL 12

N

1" = 20'-0"

B1 - GROUND LEVEL1

N

1" = 20'-0"

B1 - LEVEL 23

N

1" = 20'-0"

B1 - LEVEL 34

N

1" = 20'-0"

B1 - LEVEL 45

TY402

TY402

TR

220-2

TY403

TY403

TR

24A-3

TY402

TY402

TY403

TY403

TR

131A-3

TR

122-2

TY403

TY403

TR

222A-3

A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED

AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST

WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.

B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD

NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR

REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD

VERIFY ALL CONDITIONS.

C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT

BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS

SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-

DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED

OTHERWISE.

D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS

DEFINITION:

1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR

INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.

F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS

ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.

G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE

EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"

CONDUIT.

H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL

BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR

SHALL PROVIDE NEW WALL-BOX.

ELECTRONIC SECURITY SYSTEM GENERAL NOTES

KEY PLAN

LEESTOWN ROAD

N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:3 :2

P

M

BUILDINGS 2 & 3 - REFERENCE PLANS

MDT Drawing # 239 OF 258KGH

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

TY102

2 & 3

SPUR #: 2207

N

1" = 20'-0"

B2 - LEVEL 22

N

1" = 20'-0"

B2, B3 - GROUND LEVEL1

N

1" = 20'-0"

B2, B3 - LEVEL 13

N

1" = 20'-0"

B3 - LEVEL 24

TY404

TY404

TY404

TR

102-4

A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED

AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST

WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.

B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD

NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR

REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD

VERIFY ALL CONDITIONS.

C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT

BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS

SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-

DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED

OTHERWISE.

D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS

DEFINITION:

1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR

INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.

F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS

ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.

G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE

EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"

CONDUIT.

H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL

BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR

SHALL PROVIDE NEW WALL-BOX.

ELECTRONIC SECURITY SYSTEM GENERAL NOTES

KEY PLAN

LEESTOWN ROAD

N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:3 :2

P

M

BUILDINGS 4 & 12 - REFERENCE PLANS

MDT Drawing # 240 OF 258KGH

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

TY103

4 & 12

SPUR #: 2207

N

1" = 20'-0"

B12 - LEVEL 12

N

1" = 20'-0"

B4 - LEVEL 11

TY404

TY404

TY405

TY405

TR

15-16

CLOSET

6B-16

TY405

TY405

TY405

TY405

TR

102-16

CLOSET

115B-16

TY405

TY405

TY406

TR

207A-16

CLOSET

222A-16

TY406

TY406

TY408

TY408

NEW

MCR

22-17

TR

13C-17

TY407

TY407

TRAINING

ROOM

125-17

TR

125A-17

CLOSET

126-17

TY407

TY407

CLOSET

TR

217A-17

A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED

AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST

WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.

B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD

NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR

REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD

VERIFY ALL CONDITIONS.

C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT

BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS

SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-

DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED

OTHERWISE.

D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS

DEFINITION:

1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR

INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.

F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS

ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.

G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE

EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"

CONDUIT.

H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL

BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR

SHALL PROVIDE NEW WALL-BOX.

ELECTRONIC SECURITY SYSTEM GENERAL NOTES

KEY PLAN

LEESTOWN ROAD

N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:3 :2

P

M

BUILDINGS 16 & 17 - REFERENCE PLANS

MDT Drawing # 241 OF 258KGH

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

TY104

16 & 17

SPUR #: 2207

N

1" = 20'-0"

B16 - GROUND LEVEL1

N

1" = 20'-0"

B16 - LEVEL 12

N

1" = 20'-0"

B16 - LEVEL 23

N

1" = 20'-0"

B17 - GROUND LEVEL4

N

1" = 20'-0"

B17 - LEVEL 15

N

1" = 20'-0"

B17 - LEVEL 26

TY409

TY409

TR

19-25

TY409

TY409

TY409

TR

112-25

TY409

TY409

TR

214-25

A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED

AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST

WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.

B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD

NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR

REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD

VERIFY ALL CONDITIONS.

C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT

BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS

SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-

DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED

OTHERWISE.

D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS

DEFINITION:

1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR

INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.

F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS

ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.

G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE

EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"

CONDUIT.

H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL

BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR

SHALL PROVIDE NEW WALL-BOX.

ELECTRONIC SECURITY SYSTEM GENERAL NOTES

KEY PLAN

LEESTOWN ROAD

N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:3 :2

P

M

BUILDING 25 - REFERENCE PLANS

MDT Drawing # 242 OF 258KGH

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

TY105

SPUR #: 2207

N

1" = 20'-0"

B25 - GROUND LEVEL1

N

1" = 20'-0"

B25 - LEVEL 12

N

1" = 20'-0"

B25 - LEVEL 23

TY410

TY410

TR

1A-28

A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED

AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST

WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.

B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD

NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR

REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD

VERIFY ALL CONDITIONS.

C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT

BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS

SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-

DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED

OTHERWISE.

D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS

DEFINITION:

1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR

INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.

F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS

ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.

G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE

EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"

CONDUIT.

H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL

BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR

SHALL PROVIDE NEW WALL-BOX.

ELECTRONIC SECURITY SYSTEM GENERAL NOTES

KEY PLAN

LEESTOWN ROAD

N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:3 :2

P

M

BUILDINGS 27 & 28 - REFERENCE PLANS

MDT Drawing # 243 OF 258KGH

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

TY106

27 & 28

SPUR #: 2207

N

1" = 20'-0"

B28 - GROUND LEVEL1

TY411

TY411

TR

19B-29

TY411

TY411

TR

135A-29

TY412

WORK

SHOP

8-37

TY412

TY412

SERVICE

2-48

A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED

AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST

WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.

B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD

NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR

REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD

VERIFY ALL CONDITIONS.

C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT

BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS

SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-

DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED

OTHERWISE.

D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS

DEFINITION:

1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR

INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.

F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS

ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.

G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE

EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"

CONDUIT.

H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL

BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR

SHALL PROVIDE NEW WALL-BOX.

ELECTRONIC SECURITY SYSTEM GENERAL NOTES

KEY PLAN

LEESTOWN ROAD

N

TR

239A-29 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:3 :2

P

M

BUILDINGS 29, 37, 47 & 48 - REFERENCE

PLANS

MDT Drawing # 244 OF 258KGH

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

TY107

29, 37, 47 & 48

SPUR #: 2207

N

1" = 20'-0"

B29 - GROUND LEVEL1

N

1" = 20'-0"

B29 - LEVEL 12

N

1" = 20'-0"

B37 - LEVEL 13

N

1" = 20'-0"

B47 - LEVEL 14

N

1" = 20'-0"

B48 - LEVEL 15

N

1" = 20'-0"

B29 - LEVEL 26

CR

EL

BSEL

CR

BS

RE

BSEL

RE

CR

RE

CR

BS EL

RE

CR

EL

CR

EL

CR

BSEL

RE

CR

EL

EXISTING PHONE

ROOM

TR

31A

TY500

A

-1

CR-1

BLDG1:C-01:1

TY500

-1

31B-1

TY500

CR-1

IR

IR

IR

TR

147A-1

TY500

A

-1

BLDG1:C-01:2

IR

TR

229-1

EXISTING PHONE

ROOM

TR

31A

TR

229-1

TY500

-1

BLDG1:C-01:3

IR

TR

147A-1

A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED

AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST

WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.

B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD

NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR

REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD

VERIFY ALL CONDITIONS.

C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT

BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS

SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-

DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED

OTHERWISE.

D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS

DEFINITION:

1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR

INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.

F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS

ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.

G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE

EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"

CONDUIT.

H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL

BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR

SHALL PROVIDE NEW WALL-BOX.

ELECTRONIC SECURITY SYSTEM GENERAL NOTES

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:3 :2

P

M

BUILDING 1 - ENLARGED PLANS

MDT Drawing # 245 OF 258KGH

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

TY401

SPUR #: 2207

1/4" = 1'-0"

B1 - GROUND LEVEL - 31 - PHONE ROOM - NEW TR2

1/4" = 1'-0"

B1 - LEVEL 1 - 147A - NEW TR41/4" = 1'-0"

B1 - LEVEL 2 - 229-1 - DEMO5

1/4" = 1'-0"

B1 - GROUND LEVEL - 31 - PHONE ROOM - DEMO1

1/4" = 1'-0"

B1 - LEVEL 2 - 229-1 - NEW TR6 1/4" = 1'-0"

B1 - LEVEL 1 - 147A - DEMO3

ELECTRONIC SECURITY SYSTEM KEYNOTES

1 REMOVE AND RETAIN SECURITY CAMERA IN GOOD WORKING CONDITION TO BE

REINSTALLED.

2 REINSTALL EXISTING FIXED, MOTION ACTIVATED CAMERA. IF EXISTING CAMERA

IS DAMAGED OR INOPERABLE, CONTRACTOR TO PROVIDE NEW FIXED, MOTION

ACTIVATED CAMERA COMPATIBLE WITH EXISTING VA CAMPUS SURVEILLANCE

SYSTEM. EXTEND CABLING AS REQUIRED AND TIE INTO SECURITY CONTROL

CENTER (SCC), NOTIFYING SCC IMMEDIATELY WHEN ROOM IS ENTERED AND

RECORDING TO NVR WHEN ACTIVATED.

CR

BS

EL

RE

CR

EL

BS

CR

EL

RE

CR

EL

CR

BSEL

RE

CR

BSEL

RE

CR

EL

TR

220-2

TR

220-2

TY500

220-2

BLDG2:C-01:2

IR

TR

122-2

TR

122-2

TY500

122-2

BLDG2:C-01:1

IR

TR

331-1

TR

331-1

TY500

-1

BLDG1:C-01:4

TR

419-1

TY500

-1

BLDG1:C-01:5

IR

TR

419-1

A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED

AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST

WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.

B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD

NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR

REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD

VERIFY ALL CONDITIONS.

C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT

BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS

SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-

DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED

OTHERWISE.

D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS

DEFINITION:

1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR

INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.

F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS

ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.

G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE

EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"

CONDUIT.

H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL

BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR

SHALL PROVIDE NEW WALL-BOX.

ELECTRONIC SECURITY SYSTEM GENERAL NOTES

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:3 :2

P

M

BUILDINGS 1 & 2 - ENLARGED PLANS

MDT Drawing # 246 OF 258KGH

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

TY402

1 & 2

SPUR #: 2207

1/4" = 1'-0"

B2 - LEVEL 2 - 220-2 - DEMO71/4" = 1'-0"

B2 - LEVEL 2 - 220-2 - NEW TR8

1/4" = 1'-0"

B2 - LEVEL 1 - 122-2 - DEMO51/4" = 1'-0"

B2 - LEVEL 1 - 122-2 - NEW TR6

1/4" = 1'-0"

B1 - LEVEL 3 - 331-1 - DEMO11/4" = 1'-0"

B1 - LEVEL 3 - 331-1 - NEW TR21/4" = 1'-0"

B1 - LEVEL 4 - 419 - NEW TR4 1/4" = 1'-0"

B1 - LEVEL 4 - 419 - DEMO3

ELECTRONIC SECURITY SYSTEM KEYNOTES

1 REMOVE AND RETAIN SECURITY CAMERA IN GOOD WORKING CONDITION TO BE

REINSTALLED.

2 REINSTALL EXISTING FIXED, MOTION ACTIVATED CAMERA. IF EXISTING CAMERA

IS DAMAGED OR INOPERABLE, CONTRACTOR TO PROVIDE NEW FIXED, MOTION

ACTIVATED CAMERA COMPATIBLE WITH EXISTING VA CAMPUS SURVEILLANCE

SYSTEM. EXTEND CABLING AS REQUIRED AND TIE INTO SECURITY CONTROL

CENTER (SCC), NOTIFYING SCC IMMEDIATELY WHEN ROOM IS ENTERED AND

RECORDING TO NVR WHEN ACTIVATED.

3 EXISTING CARD READER TO BE REMOVED IN WORKING ORDER, TO BE

REINSTALLED ON NEW BACKBOX.

4 PROVIDE NEW BACKBOX AND REINSTALL EXISTING CARD READER.

CR

BS

EL

RE

CR

EL

CR

BS

EL RE

CR

BS

EL

RE

CR

EL

TR

131A-3

TR

131A-3

TY500

131A-3

BLDG3:C-01:2

IR

TR

222A-3 222A-3

TY500

3 2

BLDG3:C-01:3

IR

TR

24A-3

TY500

24A-3

BLDG3:C-01:1

IR

TR

24A-3

A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED

AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST

WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.

B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD

NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR

REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD

VERIFY ALL CONDITIONS.

C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT

BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS

SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-

DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED

OTHERWISE.

D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS

DEFINITION:

1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR

INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.

F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS

ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.

G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE

EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"

CONDUIT.

H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL

BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR

SHALL PROVIDE NEW WALL-BOX.

ELECTRONIC SECURITY SYSTEM GENERAL NOTES

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:3 :2

P

M

BUILDING 3 - ENLARGED PLANS

MDT Drawing # 247 OF 258KGH

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

TY403

SPUR #: 2207

1/4" = 1'-0"

B3 - LEVEL 1 - 131A-3 - DEMO31/4" = 1'-0"

B3 - LEVEL 1 - 131A-3 - NEW TR4

1/4" = 1'-0"

B3 - LEVEL 2 - 222A-3 - DEMO51/4" = 1'-0"

B3 - LEVEL 2 - 222A-3 - NEW TR6

1/4" = 1'-0"

B3 - GROUND LEVEL - 24A-3 - NEW TR2 1/4" = 1'-0"

B3 - GROUND LEVEL - 24A-3 - DEMO1

ELECTRONIC SECURITY SYSTEM KEYNOTES

1 REMOVE AND RETAIN SECURITY CAMERA IN GOOD WORKING CONDITION TO BE

REINSTALLED.

2 REINSTALL EXISTING FIXED, MOTION ACTIVATED CAMERA. IF EXISTING CAMERA

IS DAMAGED OR INOPERABLE, CONTRACTOR TO PROVIDE NEW FIXED, MOTION

ACTIVATED CAMERA COMPATIBLE WITH EXISTING VA CAMPUS SURVEILLANCE

SYSTEM. EXTEND CABLING AS REQUIRED AND TIE INTO SECURITY CONTROL

CENTER (SCC), NOTIFYING SCC IMMEDIATELY WHEN ROOM IS ENTERED AND

RECORDING TO NVR WHEN ACTIVATED.

RE CR

BS

EL

CR

EL

BSCR

EL

RE

CR

EL

CR

BS

EL

RE

ELEC.

6C-12

BLDG12:C-05:1

TY500

6-12

CR-1PB

TR

102-4

TR

102-4

TY500

BLDG4:C-01:1

CR-1

-4

IR

CLOSET

6B-16

CLOSET

6B-16

TY500

6B-16

BLDG16:C-01:1

A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED

AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST

WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.

B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD

NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR

REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD

VERIFY ALL CONDITIONS.

C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT

BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS

SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-

DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED

OTHERWISE.

D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS

DEFINITION:

1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR

INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.

F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS

ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.

G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE

EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"

CONDUIT.

H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL

BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR

SHALL PROVIDE NEW WALL-BOX.

ELECTRONIC SECURITY SYSTEM GENERAL NOTES

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:3 :2

P

M

BUILDINGS 4, 12 & 16 - ENLARGED PLANS

MDT Drawing # 248 OF 258KGH

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

TY404

4, 12 & 16

SPUR #: 2207

1/4" = 1'-0"

B12 - LEVEL 1 - 6C - NEW TE3 1/4" = 1'-0"

B4 - LEVEL 1 - 102A-4 - DEMO11/4" = 1'-0"

B4 - LEVEL 1 - 102A-4 - NEW TR2

1/4" = 1'-0"

B16 - GROUND LEVEL - 6B-16 - DEMO41/4" = 1'-0"

B16 - GROUND LEVEL - 6B-16 - NEW5

ELECTRONIC SECURITY SYSTEM KEYNOTES

1 REMOVE AND RETAIN SECURITY CAMERA IN GOOD WORKING CONDITION TO BE

REINSTALLED.

2 REINSTALL EXISTING FIXED, MOTION ACTIVATED CAMERA. IF EXISTING CAMERA

IS DAMAGED OR INOPERABLE, CONTRACTOR TO PROVIDE NEW FIXED, MOTION

ACTIVATED CAMERA COMPATIBLE WITH EXISTING VA CAMPUS SURVEILLANCE

SYSTEM. EXTEND CABLING AS REQUIRED AND TIE INTO SECURITY CONTROL

CENTER (SCC), NOTIFYING SCC IMMEDIATELY WHEN ROOM IS ENTERED AND

RECORDING TO NVR WHEN ACTIVATED.

3 PROVIDE NEW FIXED, MOTION ACTIVATED CAMERA. TIE INTO SECURITY

CONTROL CENTER (SCC), NOTIFYING SCC IMMEDIATELY WHEN ROOM IS

ENTERED AND RECORDING TO NVR WHEN ACTIVATED.

EL

RE

CRBS

EL

RE

CR

EL

CR

BS EL

RE

CR

ELBS

CR

EL

RE

TR

15-16

ELEVATOR

NO-1

-1

TY500

BLDG16:C-01:2

CR-1

IR

TR

15-16

ELEVATOR

NO-1

SOCIAL

WORKER

OFFICE

102-16

TR

102-16

TY500

BLDG16:C-01:4

CR-1

-1

IR

TR

222A-16

CLOSET

222A-16

TY500

A

-1

BLDG16:C-01:5

TR

115B-16

CLOSET

115B-16

B

-1

TY500

BLDG16:C-01:3

IR

A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED

AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST

WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.

B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD

NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR

REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD

VERIFY ALL CONDITIONS.

C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT

BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS

SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-

DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED

OTHERWISE.

D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS

DEFINITION:

1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR

INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.

F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS

ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.

G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE

EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"

CONDUIT.

H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL

BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR

SHALL PROVIDE NEW WALL-BOX.

ELECTRONIC SECURITY SYSTEM GENERAL NOTES

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

/1

/2

:3 :3

P

M

BUILDING 16 - ENLARGED PLANS

MDT Drawing # 249 OF 258KGH

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511

TY405

SPUR #: 2207

1/4" = 1'-0"

B16 - GROUND LEVEL - 15 - NEW TR2 1/4" = 1'-0"

B16 - GROUND LEVEL - 15 - DEMO1

1/4" = 1'-0"

B16 - LEVEL 1 - 102 - DEMO51/4" = 1'-0"

B16 - LEVEL 1 - 102 - NEW TR6

1/4" = 1'-0"

B16 - LEVEL 2 - 222A-16 - DEMO71/4" = 1'-0"

B16 - LEVEL 2 - 222A-16 - NEW WORK8

1/4" = 1'-0"

B16 - LEVEL 1 - 115B - DEMO31/4" = 1'-0"

B16 - LEVEL 1 - 115B - NEW WORK4

ELECTRONIC SECURITY SYSTEM KEYNOTES

1 REMOVE AND RETAIN SECURITY CAMERA IN GOOD WORKING CONDITION TO BE

REINSTALLED.

2 REINSTALL EXISTING FIXED, MOTION ACTIVATED CAMERA. IF EXISTING CAMERA

IS DAMAGED OR INOPERABLE, CONTRACTOR TO PROVIDE NEW FIXED, MOTION

ACTIVATED CAMERA COMPATIBLE WITH EXISTING VA CAMPUS SURVEILLANCE

SYSTEM. EXTEND CABLING AS REQUIRED AND TIE INTO SECURITY CONTROL

CENTER (SCC), NOTIFYING SCC IMMEDIATELY WHEN ROOM IS ENTERED AND

RECORDING TO NVR WHEN ACTIVATED.

3 PROVIDE NEW FIXED, MOTION ACTIVATED CAMERA. TIE INTO SECURITY

CONTROL CENTER (SCC), NOTIFYING SCC IMMEDIATELY WHEN ROOM IS

EL

RE

CR

BS

EL

RE

BS

EL

CR

RE

CR

EL

CONFERENCE

ROOM

207-16

TR

207A-16

A

-1

TY500

BLDG16:C-01:6

CR-1

IR

TR

13C-17

TY500

13B-17

BLDG17:C-01:1

IR

CR-1

IR

TY500

TR

13C-17

A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED

AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST

WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.

B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD

NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR

REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD

VERIFY ALL CONDITIONS.

C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT

BE SHUTDOWN WITHOUT…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .