13 - 596-22-700 Drawings 09_Security.pdf
PDF 46 MB Posted
- Solicitation number
- 36C77625B0040
About this file
These are electronic security system design drawings for the Electronic Health Record Modernization (EHRM) Infrastructure Upgrades project at the Lexington VA Health Care System located at 2250 Leestown Road in Lexington, Kentucky. The comprehensive set of architectural and engineering drawings details a multi-building security infrastructure upgrade involving Buildings 1, 2, 3, 4, 12, 16, 17, 25, 27, 28, 29, 37, 47, and 48, with a focus on modernizing telecommunications rooms, security camera placements, access control systems, and electronic security infrastructure.
The drawings specify detailed requirements for installing new security cameras (multiple types including 90-degree, 270-degree, and motion-activated models), card readers with dual authentication capabilities, electric strikes, magnetic locks, request-to-exit devices, and associated cabling and conduit systems. Key design specifications include compatibility with existing VA campus security systems, mounting heights for devices, integration with existing telecommunications infrastructure, and adherence to VA Office of Information & Technology standards and physical security design manuals. The project involves both new installations and strategic replacements/upgrades of existing security equipment across multiple campus buildings.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
L
LIGHT EMITTING DIODE
LINEAR FEET (FOOT)
LIGHT HAZARD
LOCAL OPERATING CONSOLE
LED
LF
LH
LOC
LOW VOLTAGELV
M
MASTER ANTENNA TELEVISION SYSTEMMATV
MAXIMUMMAX
METAL-CLADMC
MAIN DISTRIBUTION FRAMEMDF
MANHOLEMH
MINIMUMMIN
MOUNTEDMTD
MOUNTINGMTG
N
NOT APPLICABLENA
NATIONAL ELECTRICAL CODENEC
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NEMA
NATIONAL FIRE PROTECTION ASSOCIATIONNFPA
NOT IN CONTRACTNIC
NOT TO SCALENTS
O
ON CENTEROC
OUTSIDE DIAMETEROD
ORDINARY HAZARDOH
P
PUBLIC ADDRESSPA
PULL CORDPC
POWER OVER ETHERNETPOE
PATCH PANELPP
POWERPWR
R
RCDD REGISTERED COMMUNICATIONS DISTRIBUTION DESIGNER
REFLECTED CEILING PLANRCP
RECEPTACLERCPT
RECESSEDREC
REQUIREDREQD
RIGID GALVANIZED STEELRGS
ROOMRM
ROOT MEAN SQUARERMS
RACK UNITRU
S
SUPPLYS
SCHEDULESCHED
SMOKE DETECTORSD
SIMILARSIM
SPEAKERSP
SPECIFICATIONSPEC
SPEAKER/ STROBESP/ST
SQUARESQ
STROBEST
SHIELDED TWISTED PAIRSTP
SURFACESURF
SYSTEMSYST
T
TELECOMMUNICATIONS ENCLOSURETE
TELECOMMUNICATIONS ENCLOSURE FACILITYTEF
TELEPHONETEL
TEMPERATURETEMP
TELECOMMUNICATIONS EQUIPMENT ROOMTER
TELECOMMUNICATIONS GROUNDING BUSSBARTGB
TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION
TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSSBAR
TR TELECOMMUNICATIONS ROOM
TP TWISTED PAIR
TTB TELEPHONE TERMINAL BOARD
TYP TYPICAL
U
UNDERFLOOR DUCTUFD
UNDERGROUNDUGND
UNDERWRITERS LABORATORYUL
UNLESS NOTED OTHERWISEUNO
UNINTERRUPTIBLE POWER SUPPLYUPS
UTILITYUTIL
V
VERTICAL CABLE MANAGERVCM
W
WITHW/
WALL MOUNTEDWM
WITHOUTW/O
X
EXPLOSION PROOFXP
GENERAL NOTES
1. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
2. FINAL LOCATION OF ALL DEVICES SHALL BE COORDINATED WITH FINAL
ROOM FURNITURE CONFIGURATIONS, ACCESSORIES, SPACE INDICATED
FOR SPECIFIC DUTY.
3. ELECTRICAL OUTLETS INDICATED FOR REFERENCE PURPOSES ONLY;
REFER TO ELECTRICAL PLANS FOR ELECTRICAL REQUIREMENTS.
4. MOUNTING HEIGHTS FOR DEVICES SHALL BE MEASURED FROM FINAL
FINISH FLOOR TO CENTER OF BOX UNLESS NOTED OTHERWISE.
5. VERIFY THE LOCATIONS OF ALL FIREPROOFING PRIOR TO THE
INSTALLATION OF CONDUIT AND BACKBOXES.
6. IF FIELD CONDITIONS VARY FROM THE DRAWINGS, THE CONTRACTOR
SHALL DOCUMENT THE VARIATION AND REPORT IT TO THE GENERAL
CONTRACTOR FOR RESOLUTION WITH THE ENGINEER OF RECORD.
7. COORDINATE THE INSTALLATION REQUIREMENTS OF SYSTEM DEVICES,
EQUIPMENT, PATHWAYS, AND OTHER COMPONENTS WITH THE GENERAL
CONTRACTOR AND OTHER BUILDING TRADES PRIOR TO INSTALLATION.
8. COORDINATE GROUNDING REQUIREMENTS WITH THE ELECTRICAL
CONTRACTOR AND ENSURE THE COMMUNICATIONS GROUNDING MEETS
SYSTEM REQUIREMENTS AND TIA J-STD-607A STANDARDS PRIOR TO
ENERGIZING AND SYSTEMS EQUIPMENT.
9. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-DAYS
PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
ABBREVIATIONS
EIGHT POSITION, EIGHT CONTACT
ALARM ANNUNCIATOR PANEL
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
AUTHORITY HAVING JURISDICTION
THE AMERICAN NATIONAL STANDARDS INSTITUTE
ARCHITECT
BATTERY
BOTTOM OF CABLE TRAY
BUILDING INDUSTRY CONSULTING SERVICE
INTERNATIONAL
8P8C
A
AAP
AFG
AFF
AHJ
ANSI
ARCH
B
BATT
BOCT
BICSI
CONDUIT
COMMUNITY ANTENNA TELEVISION
CLOSED CIRCUIT TELEVISION
CEILING
CEILING MOUNTED
COMPUTER MACHINE ROOM
COAXIAL CABLE
C
C
CATV
CCTV
CLG
CM
CMR
COAX
COMMUNICATIONCOMM
CONTINUE/ CONTINUOUSCONT
CENTERCTR
COPPERCU
D
DECIBEL OR DIRECT BURIALDB
DATA CENTERDC
DEMOLISH/ DEMOLITIONDEMO
DIAMETERDIA
DIMENSIONDIM
DOME LIGHTDL
DRAWINGDWG
E
EACHEA
EXTRA HAZARDEH
ELEVATIONEL
ELEVATORELEV
EMERGENCYEMER
ELECTROMAGNETIC INTERFERENCEEMI
ELECTRICAL METALLIC TUBINGEMT
EQUIPMENTEQUIP
EQUIPMENTEQPM
EXISTING TO REMAINETR
EXISTINGEX
F
FIRE ALARMFA
FINISHED FLOOR ELEVATIONFFE
FLEXIBLE METALLIC CONDUITFLEX
FLOORFLR
FEETFT
FIBER-OPTICFO
G
GAUGEGA
GENERAL CONTRACTORGC
GROUNDGND
H
HORIZONTAL CABLE MANAGERHCM
HEIGHTHGT
HANDHOLEHH
HERTZHZ
I
INSIDE DIAMETERID
INTERMEDIATE DISTRIBUTION FRAMEIDF
INFRAREDIR
J
JUNCTION BOXJB
K
KILOWATTKW
PROJECT CODES AND STANDARDS
A. VA OFFICE OF INFORMATION & TECHNOLOGY (OIT) INFRASTRUCTURE
STANDARDS FOR TELECOMMUNICATIONS SPACES, 1 JUNE 2023
B. VA PG-18-10 TELECOMMUNICATIONS AND SPECIAL
TELECOMMUNICATIONS SYSTEMS DESIGN MANUAL, FEBRUARY 2016
C. BICSI AND EIA/TIA STANDARDS AS DEFINED IN VA-18-10
D. VA-PSRDM - PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL,
1 JUNE 2023
PLAN LEGEND
DESCRIPTIONSYMBOL
OUT OF SCOPE AREA
UNSHIELDED TWISTED PAIRUTP
VIDEO SURVEILLANCE SYSTEMVSS
SINGLE-MODESM
SECURITY CONTROL CENTERSCC
SECURITY OPERATION CENTERSOC
OUTSIDE PLANTOSP
NETWORK OPERATION CENTERNOC
MULTI-MODEMM
INSIDE PLANTISP
DEMARCATION POINT OR ROOMDEMARC
ELECTRONIC SECURITY SYMBOLS
DESCRIPTIONSYMBOL
DOOR AUTO-CLOSER
PANIC/DURESS BUTTON MOUNTED AT 48" A.F.F. UNLESS
NOTED OTHERWISE
ACCESS CONTROL CARD READER/KEYPAD COMBINATION
DEVICE
DOOR POSITION SWITCH
INTRUSION DETECTION PASSIVE INFRARED MOTION
DETECTOR - WALL MOUNTED
DOOR AUTO-OPENER
ANTI-PROP DEVICE
REQUEST FOR EXIT PUSHBUTTON
DOORBELL PUSHBUTTON
BALANCED MAGNETIC SWITCH - WIRED TO ACCESS
CONTROL SYSTEM ONLY UNLESS OTHERWISE NOTED
DELAYED EGRESS
GLASS BREAK DETECTOR
GATE OPENER
INTRUSION DETECTION SYSTEM KEYPAD
MAGNETIC LOCKING DEVICE
AD
AC
AP
CR
RE
EL
GB
GO
DB
DE
DM
KP
MD
ML
PB
LOCAL ALARMLA
ELECTRIC STRIKE LOCK
SINGLE VIEW SECURITY CAMERA
XX:XX:XX = BUILDING ID:TYPE:SEQUENTIAL NUMBERXX:XX:XX
SECURITY SURVEILLANCE TELEVISION LINE, MIN. 1"
RACEWAY
VIDEO SURVEILLANCE MONITOR STATION
SSTV
M
WM WINDOW POSITION MONITOR/CONTACT SENSOR
BS
REQUEST FOR EXIT PASSIVE
INFRARED MOTION SENSOR
RE
IR
PB
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:3 :1
P
M
ELECTRONIC SECURITY SYSTEM COVER
SHEET
MDT Drawing # 237 OF 258KGH
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
T-000
SPUR #: 2207
No. REVISION DESCRIPTION DATE
ENGG
EQUIP
RM
STAIR
MED
RESEARCH
RM
PIPE
SPACE
CORRIDOR
SPRINKLER
PIPECORRIDOR
PODIATRY
STOR
WOMENS
TOILET
SOCIAL
WORKER
OFFICE
FIRE
CABINET
MED FOSTER
CARE OFFICE
P TOILET
CODING
COMPLIANCE
MGR
OFFICE
ELEVATOR
ELEVATOR
LOBBYPODIATRY
EXAM
ELEVATOR
STAIR
PODIATRY
SECTION
CHIEF
TOILET
PODIATRY
EXAM
SPD
CLOSET
MENS
TOILET
PIPE
SPACE
STAIR
FOYER
PODIATRIST
OFFICE
CODING
OFFICE
BREAK
RM
EXAMINATION
SOCIAL
WORKER
OFFICE
SOCIAL
WORK
SUPV
OFFICE
OFFICE
OFFICECOMPLIANCE
ANALYST
WAITING
RM
RECEPTIONIST
TEL/DATA
CLOSET IT
CLOSET
PODIATRY
RM
PODIATRY
RM
PODIATRY
RM
PODIATRY
RM
PODIATRY
RM
PODIATRY
CONFERENCE
RM
CODING
TY401
TY401
TR
147A-1
TY401
TY401
EXISTING
PHONE
ROOM
TR
31A
TY401
TY401
TR
229-1
TY402
TY402
TR
331-1
TY402
TY402
TR
419-1
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS
DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR
INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.
2. SYMBOLS DASHED OR SPECIFICALLY KEYED NOTED: INDICATES
DEMOLITION WORK.
E. OWNER SHALL HAVE FIRST SALVAGE RIGHTS FOR ANY DEMOLISHED
DEVICES OR MATERIAL.
F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS
ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.
G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE
EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"
CONDUIT.
H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL
BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR
SHALL PROVIDE NEW WALL-BOX.
ELECTRONIC SECURITY SYSTEM GENERAL NOTES
KEY PLAN
LEESTOWN ROAD
N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:3 :1
P
M
BUILDING 1 - REFERENCE PLANS
MDT Drawing # 238 OF 258KGH
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
TY101
SPUR #: 2207
N
1" = 20'-0"
B1 - LEVEL 12
N
1" = 20'-0"
B1 - GROUND LEVEL1
N
1" = 20'-0"
B1 - LEVEL 23
N
1" = 20'-0"
B1 - LEVEL 34
N
1" = 20'-0"
B1 - LEVEL 45
TY402
TY402
TR
220-2
TY403
TY403
TR
24A-3
TY402
TY402
TY403
TY403
TR
131A-3
TR
122-2
TY403
TY403
TR
222A-3
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS
DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR
INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.
F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS
ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.
G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE
EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"
CONDUIT.
H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL
BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR
SHALL PROVIDE NEW WALL-BOX.
ELECTRONIC SECURITY SYSTEM GENERAL NOTES
KEY PLAN
LEESTOWN ROAD
N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:3 :2
P
M
BUILDINGS 2 & 3 - REFERENCE PLANS
MDT Drawing # 239 OF 258KGH
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
TY102
2 & 3
SPUR #: 2207
N
1" = 20'-0"
B2 - LEVEL 22
N
1" = 20'-0"
B2, B3 - GROUND LEVEL1
N
1" = 20'-0"
B2, B3 - LEVEL 13
N
1" = 20'-0"
B3 - LEVEL 24
TY404
TY404
TY404
TR
102-4
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS
DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR
INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.
F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS
ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.
G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE
EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"
CONDUIT.
H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL
BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR
SHALL PROVIDE NEW WALL-BOX.
ELECTRONIC SECURITY SYSTEM GENERAL NOTES
KEY PLAN
LEESTOWN ROAD
N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:3 :2
P
M
BUILDINGS 4 & 12 - REFERENCE PLANS
MDT Drawing # 240 OF 258KGH
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
TY103
4 & 12
SPUR #: 2207
N
1" = 20'-0"
B12 - LEVEL 12
N
1" = 20'-0"
B4 - LEVEL 11
TY404
TY404
TY405
TY405
TR
15-16
CLOSET
6B-16
TY405
TY405
TY405
TY405
TR
102-16
CLOSET
115B-16
TY405
TY405
TY406
TR
207A-16
CLOSET
222A-16
TY406
TY406
TY408
TY408
NEW
MCR
22-17
TR
13C-17
TY407
TY407
TRAINING
ROOM
125-17
TR
125A-17
CLOSET
126-17
TY407
TY407
CLOSET
TR
217A-17
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS
DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR
INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.
F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS
ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.
G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE
EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"
CONDUIT.
H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL
BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR
SHALL PROVIDE NEW WALL-BOX.
ELECTRONIC SECURITY SYSTEM GENERAL NOTES
KEY PLAN
LEESTOWN ROAD
N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:3 :2
P
M
BUILDINGS 16 & 17 - REFERENCE PLANS
MDT Drawing # 241 OF 258KGH
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
TY104
16 & 17
SPUR #: 2207
N
1" = 20'-0"
B16 - GROUND LEVEL1
N
1" = 20'-0"
B16 - LEVEL 12
N
1" = 20'-0"
B16 - LEVEL 23
N
1" = 20'-0"
B17 - GROUND LEVEL4
N
1" = 20'-0"
B17 - LEVEL 15
N
1" = 20'-0"
B17 - LEVEL 26
TY409
TY409
TR
19-25
TY409
TY409
TY409
TR
112-25
TY409
TY409
TR
214-25
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS
DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR
INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.
F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS
ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.
G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE
EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"
CONDUIT.
H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL
BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR
SHALL PROVIDE NEW WALL-BOX.
ELECTRONIC SECURITY SYSTEM GENERAL NOTES
KEY PLAN
LEESTOWN ROAD
N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:3 :2
P
M
BUILDING 25 - REFERENCE PLANS
MDT Drawing # 242 OF 258KGH
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
TY105
SPUR #: 2207
N
1" = 20'-0"
B25 - GROUND LEVEL1
N
1" = 20'-0"
B25 - LEVEL 12
N
1" = 20'-0"
B25 - LEVEL 23
TY410
TY410
TR
1A-28
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS
DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR
INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.
F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS
ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.
G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE
EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"
CONDUIT.
H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL
BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR
SHALL PROVIDE NEW WALL-BOX.
ELECTRONIC SECURITY SYSTEM GENERAL NOTES
KEY PLAN
LEESTOWN ROAD
N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:3 :2
P
M
BUILDINGS 27 & 28 - REFERENCE PLANS
MDT Drawing # 243 OF 258KGH
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
TY106
27 & 28
SPUR #: 2207
N
1" = 20'-0"
B28 - GROUND LEVEL1
TY411
TY411
TR
19B-29
TY411
TY411
TR
135A-29
TY412
WORK
SHOP
8-37
TY412
TY412
SERVICE
2-48
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS
DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR
INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.
F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS
ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.
G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE
EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"
CONDUIT.
H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL
BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR
SHALL PROVIDE NEW WALL-BOX.
ELECTRONIC SECURITY SYSTEM GENERAL NOTES
KEY PLAN
LEESTOWN ROAD
N
TR
239A-29 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:3 :2
P
M
BUILDINGS 29, 37, 47 & 48 - REFERENCE
PLANS
MDT Drawing # 244 OF 258KGH
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
TY107
29, 37, 47 & 48
SPUR #: 2207
N
1" = 20'-0"
B29 - GROUND LEVEL1
N
1" = 20'-0"
B29 - LEVEL 12
N
1" = 20'-0"
B37 - LEVEL 13
N
1" = 20'-0"
B47 - LEVEL 14
N
1" = 20'-0"
B48 - LEVEL 15
N
1" = 20'-0"
B29 - LEVEL 26
CR
EL
BSEL
CR
BS
RE
BSEL
RE
CR
RE
CR
BS EL
RE
CR
EL
CR
EL
CR
BSEL
RE
CR
EL
EXISTING PHONE
ROOM
TR
31A
TY500
A
-1
CR-1
BLDG1:C-01:1
TY500
-1
31B-1
TY500
CR-1
IR
IR
IR
TR
147A-1
TY500
A
-1
BLDG1:C-01:2
IR
TR
229-1
EXISTING PHONE
ROOM
TR
31A
TR
229-1
TY500
-1
BLDG1:C-01:3
IR
TR
147A-1
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS
DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR
INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.
F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS
ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.
G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE
EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"
CONDUIT.
H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL
BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR
SHALL PROVIDE NEW WALL-BOX.
ELECTRONIC SECURITY SYSTEM GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:3 :2
P
M
BUILDING 1 - ENLARGED PLANS
MDT Drawing # 245 OF 258KGH
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
TY401
SPUR #: 2207
1/4" = 1'-0"
B1 - GROUND LEVEL - 31 - PHONE ROOM - NEW TR2
1/4" = 1'-0"
B1 - LEVEL 1 - 147A - NEW TR41/4" = 1'-0"
B1 - LEVEL 2 - 229-1 - DEMO5
1/4" = 1'-0"
B1 - GROUND LEVEL - 31 - PHONE ROOM - DEMO1
1/4" = 1'-0"
B1 - LEVEL 2 - 229-1 - NEW TR6 1/4" = 1'-0"
B1 - LEVEL 1 - 147A - DEMO3
ELECTRONIC SECURITY SYSTEM KEYNOTES
1 REMOVE AND RETAIN SECURITY CAMERA IN GOOD WORKING CONDITION TO BE
REINSTALLED.
2 REINSTALL EXISTING FIXED, MOTION ACTIVATED CAMERA. IF EXISTING CAMERA
IS DAMAGED OR INOPERABLE, CONTRACTOR TO PROVIDE NEW FIXED, MOTION
ACTIVATED CAMERA COMPATIBLE WITH EXISTING VA CAMPUS SURVEILLANCE
SYSTEM. EXTEND CABLING AS REQUIRED AND TIE INTO SECURITY CONTROL
CENTER (SCC), NOTIFYING SCC IMMEDIATELY WHEN ROOM IS ENTERED AND
RECORDING TO NVR WHEN ACTIVATED.
CR
BS
EL
RE
CR
EL
BS
CR
EL
RE
CR
EL
CR
BSEL
RE
CR
BSEL
RE
CR
EL
TR
220-2
TR
220-2
TY500
220-2
BLDG2:C-01:2
IR
TR
122-2
TR
122-2
TY500
122-2
BLDG2:C-01:1
IR
TR
331-1
TR
331-1
TY500
-1
BLDG1:C-01:4
TR
419-1
TY500
-1
BLDG1:C-01:5
IR
TR
419-1
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS
DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR
INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.
F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS
ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.
G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE
EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"
CONDUIT.
H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL
BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR
SHALL PROVIDE NEW WALL-BOX.
ELECTRONIC SECURITY SYSTEM GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:3 :2
P
M
BUILDINGS 1 & 2 - ENLARGED PLANS
MDT Drawing # 246 OF 258KGH
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
TY402
1 & 2
SPUR #: 2207
1/4" = 1'-0"
B2 - LEVEL 2 - 220-2 - DEMO71/4" = 1'-0"
B2 - LEVEL 2 - 220-2 - NEW TR8
1/4" = 1'-0"
B2 - LEVEL 1 - 122-2 - DEMO51/4" = 1'-0"
B2 - LEVEL 1 - 122-2 - NEW TR6
1/4" = 1'-0"
B1 - LEVEL 3 - 331-1 - DEMO11/4" = 1'-0"
B1 - LEVEL 3 - 331-1 - NEW TR21/4" = 1'-0"
B1 - LEVEL 4 - 419 - NEW TR4 1/4" = 1'-0"
B1 - LEVEL 4 - 419 - DEMO3
ELECTRONIC SECURITY SYSTEM KEYNOTES
1 REMOVE AND RETAIN SECURITY CAMERA IN GOOD WORKING CONDITION TO BE
REINSTALLED.
2 REINSTALL EXISTING FIXED, MOTION ACTIVATED CAMERA. IF EXISTING CAMERA
IS DAMAGED OR INOPERABLE, CONTRACTOR TO PROVIDE NEW FIXED, MOTION
ACTIVATED CAMERA COMPATIBLE WITH EXISTING VA CAMPUS SURVEILLANCE
SYSTEM. EXTEND CABLING AS REQUIRED AND TIE INTO SECURITY CONTROL
CENTER (SCC), NOTIFYING SCC IMMEDIATELY WHEN ROOM IS ENTERED AND
RECORDING TO NVR WHEN ACTIVATED.
3 EXISTING CARD READER TO BE REMOVED IN WORKING ORDER, TO BE
REINSTALLED ON NEW BACKBOX.
4 PROVIDE NEW BACKBOX AND REINSTALL EXISTING CARD READER.
CR
BS
EL
RE
CR
EL
CR
BS
EL RE
CR
BS
EL
RE
CR
EL
TR
131A-3
TR
131A-3
TY500
131A-3
BLDG3:C-01:2
IR
TR
222A-3 222A-3
TY500
3 2
BLDG3:C-01:3
IR
TR
24A-3
TY500
24A-3
BLDG3:C-01:1
IR
TR
24A-3
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS
DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR
INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.
F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS
ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.
G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE
EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"
CONDUIT.
H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL
BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR
SHALL PROVIDE NEW WALL-BOX.
ELECTRONIC SECURITY SYSTEM GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:3 :2
P
M
BUILDING 3 - ENLARGED PLANS
MDT Drawing # 247 OF 258KGH
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
TY403
SPUR #: 2207
1/4" = 1'-0"
B3 - LEVEL 1 - 131A-3 - DEMO31/4" = 1'-0"
B3 - LEVEL 1 - 131A-3 - NEW TR4
1/4" = 1'-0"
B3 - LEVEL 2 - 222A-3 - DEMO51/4" = 1'-0"
B3 - LEVEL 2 - 222A-3 - NEW TR6
1/4" = 1'-0"
B3 - GROUND LEVEL - 24A-3 - NEW TR2 1/4" = 1'-0"
B3 - GROUND LEVEL - 24A-3 - DEMO1
ELECTRONIC SECURITY SYSTEM KEYNOTES
1 REMOVE AND RETAIN SECURITY CAMERA IN GOOD WORKING CONDITION TO BE
REINSTALLED.
2 REINSTALL EXISTING FIXED, MOTION ACTIVATED CAMERA. IF EXISTING CAMERA
IS DAMAGED OR INOPERABLE, CONTRACTOR TO PROVIDE NEW FIXED, MOTION
ACTIVATED CAMERA COMPATIBLE WITH EXISTING VA CAMPUS SURVEILLANCE
SYSTEM. EXTEND CABLING AS REQUIRED AND TIE INTO SECURITY CONTROL
CENTER (SCC), NOTIFYING SCC IMMEDIATELY WHEN ROOM IS ENTERED AND
RECORDING TO NVR WHEN ACTIVATED.
RE CR
BS
EL
CR
EL
BSCR
EL
RE
CR
EL
CR
BS
EL
RE
ELEC.
6C-12
BLDG12:C-05:1
TY500
6-12
CR-1PB
TR
102-4
TR
102-4
TY500
BLDG4:C-01:1
CR-1
-4
IR
CLOSET
6B-16
CLOSET
6B-16
TY500
6B-16
BLDG16:C-01:1
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS
DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR
INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.
F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS
ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.
G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE
EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"
CONDUIT.
H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL
BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR
SHALL PROVIDE NEW WALL-BOX.
ELECTRONIC SECURITY SYSTEM GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:3 :2
P
M
BUILDINGS 4, 12 & 16 - ENLARGED PLANS
MDT Drawing # 248 OF 258KGH
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
TY404
4, 12 & 16
SPUR #: 2207
1/4" = 1'-0"
B12 - LEVEL 1 - 6C - NEW TE3 1/4" = 1'-0"
B4 - LEVEL 1 - 102A-4 - DEMO11/4" = 1'-0"
B4 - LEVEL 1 - 102A-4 - NEW TR2
1/4" = 1'-0"
B16 - GROUND LEVEL - 6B-16 - DEMO41/4" = 1'-0"
B16 - GROUND LEVEL - 6B-16 - NEW5
ELECTRONIC SECURITY SYSTEM KEYNOTES
1 REMOVE AND RETAIN SECURITY CAMERA IN GOOD WORKING CONDITION TO BE
REINSTALLED.
2 REINSTALL EXISTING FIXED, MOTION ACTIVATED CAMERA. IF EXISTING CAMERA
IS DAMAGED OR INOPERABLE, CONTRACTOR TO PROVIDE NEW FIXED, MOTION
ACTIVATED CAMERA COMPATIBLE WITH EXISTING VA CAMPUS SURVEILLANCE
SYSTEM. EXTEND CABLING AS REQUIRED AND TIE INTO SECURITY CONTROL
CENTER (SCC), NOTIFYING SCC IMMEDIATELY WHEN ROOM IS ENTERED AND
RECORDING TO NVR WHEN ACTIVATED.
3 PROVIDE NEW FIXED, MOTION ACTIVATED CAMERA. TIE INTO SECURITY
CONTROL CENTER (SCC), NOTIFYING SCC IMMEDIATELY WHEN ROOM IS
ENTERED AND RECORDING TO NVR WHEN ACTIVATED.
EL
RE
CRBS
EL
RE
CR
EL
CR
BS EL
RE
CR
ELBS
CR
EL
RE
TR
15-16
ELEVATOR
NO-1
-1
TY500
BLDG16:C-01:2
CR-1
IR
TR
15-16
ELEVATOR
NO-1
SOCIAL
WORKER
OFFICE
102-16
TR
102-16
TY500
BLDG16:C-01:4
CR-1
-1
IR
TR
222A-16
CLOSET
222A-16
TY500
A
-1
BLDG16:C-01:5
TR
115B-16
CLOSET
115B-16
B
-1
TY500
BLDG16:C-01:3
IR
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF TEN (10) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE T-000 ELECTRONIC SECURITY SYSTEM COVER SHEET FOR SYMBOLS
DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE AND/OR
INDICATING EXISTING UNLESS SPECIFICALLY NOTED OTHERWISE.
F. SECURITY CONTRACTOR SHALL PROVIDE ALL POWER REQUIREMENTS
ASSOCIATED WITH ELECTRONIC SECURITY SYSTEMS.
G. ALL EXISTING ESS CABLING SHALL BE INSTALLED IN CONDUIT, WHERE
EXPOSED CABLING IS FOUND CONTRACTOR SHALL PROVIDE NEW 1-1/4"
CONDUIT.
H. ALL CARD READERS WITHIN SCOPE SHALL BE MOUNTED ON WALL
BOXES. WHERE INSUFFICIENT MOUNTING IS FOUND, CONTRACTOR
SHALL PROVIDE NEW WALL-BOX.
ELECTRONIC SECURITY SYSTEM GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
STRUCTURAL
STAND
8234 ROBINSON
OVERLAND PARK, KS 66204
(913) 214-2169
/1
/2
:3 :3
P
M
BUILDING 16 - ENLARGED PLANS
MDT Drawing # 249 OF 258KGH
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES LEXINGTON, KY
03/15/2024
596-22-700
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
TY405
SPUR #: 2207
1/4" = 1'-0"
B16 - GROUND LEVEL - 15 - NEW TR2 1/4" = 1'-0"
B16 - GROUND LEVEL - 15 - DEMO1
1/4" = 1'-0"
B16 - LEVEL 1 - 102 - DEMO51/4" = 1'-0"
B16 - LEVEL 1 - 102 - NEW TR6
1/4" = 1'-0"
B16 - LEVEL 2 - 222A-16 - DEMO71/4" = 1'-0"
B16 - LEVEL 2 - 222A-16 - NEW WORK8
1/4" = 1'-0"
B16 - LEVEL 1 - 115B - DEMO31/4" = 1'-0"
B16 - LEVEL 1 - 115B - NEW WORK4
ELECTRONIC SECURITY SYSTEM KEYNOTES
1 REMOVE AND RETAIN SECURITY CAMERA IN GOOD WORKING CONDITION TO BE
REINSTALLED.
2 REINSTALL EXISTING FIXED, MOTION ACTIVATED CAMERA. IF EXISTING CAMERA
IS DAMAGED OR INOPERABLE, CONTRACTOR TO PROVIDE NEW FIXED, MOTION
ACTIVATED CAMERA COMPATIBLE WITH EXISTING VA CAMPUS SURVEILLANCE
SYSTEM. EXTEND CABLING AS REQUIRED AND TIE INTO SECURITY CONTROL
CENTER (SCC), NOTIFYING SCC IMMEDIATELY WHEN ROOM IS ENTERED AND
RECORDING TO NVR WHEN ACTIVATED.
3 PROVIDE NEW FIXED, MOTION ACTIVATED CAMERA. TIE INTO SECURITY
CONTROL CENTER (SCC), NOTIFYING SCC IMMEDIATELY WHEN ROOM IS
EL
RE
CR
BS
EL
RE
BS
EL
CR
RE
CR
EL
CONFERENCE
ROOM
207-16
TR
207A-16
A
-1
TY500
BLDG16:C-01:6
CR-1
IR
TR
13C-17
TY500
13B-17
BLDG17:C-01:1
IR
CR-1
IR
TY500
TR
13C-17
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT…