This document is a detailed telecommunications infrastructure survey spreadsheet tracking network infrastructure across multiple buildings and floors. The spreadsheet provides comprehensive data on 42 separate telecommunications rooms (TR), including room locations, cable types (primarily Cat 5e and Cat 6/6A), physical dimensions, port configurations, fiber optic details, and equipment/system notes. Key technical specifications include area measurements, rack configurations, cable types, port populations, fiber optic strand counts, and connector types. The data reveals varying network infrastructure conditions across different building areas, with port utilization ranging from 34.52% to 100%, cable categories including 5e, 6, and 6A, and additional systems noted such as coax TV, iStar Edge, fire alarms, and phone systems. The total infrastructure includes 6,960 total ports with 2,656 populated ports, and requires 56 48-port patch panels and 145 total patch panels to support the network infrastructure.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Area Pass/Fail
Buliding # TR # FT-L IN-L FT-W IN-W FT-H IN-H FT^2 Area # of Racks Type of Cat Cable 96 port 48 port 36 port 24 port Populated Ports Total Ports % Fill OM OS OM.2 OS.2 OM.3 OS.3 Notes
"Example" "Example" 10 0 8 4 10 0 83.34 Green 1 5/5e/6/6A 0 2 1 1 132 156 15.38% 62.5/50 9um 24 12 LC ST Wifi & Patient TV systems present
1 Grnd / 31 15 9 40 7 8 10 639.19 Green 1 5e 5 1 101 264 61.74% 62.5
1 1st Flr/ 147A 11 3 11 11 8 11 134.07 Green 1 5e 4 1 109 216 49.54% 62.5 12 SC 110 Blocks, Coax TV, iStar Edge, Fire Alarm
1 2nd Flr/ 229 11 5 8 7 8 7 98.00 Green 1 5e 4 1 89 216 58.80% 62.5 12 SC 110 Blocks, Coax TV, iStar Edge, Fire Alarm
1 3rd Flr/ 331 11 1 8 2 8 9 90.52 Green 1 5e 4 3 105 264 60.23% 62.5 12 SC 110 Blocks, Coax TV, iStar Edge, Fire Alarm, Fiber Termination & connected equipment.
1 4th Flr/ 419 11 0 8 6 7 6 93.50 Height 1 5e/ 6 2 3 90 168 46.43% 62.5 12 SC 110 blocks, Coax TV, iStar Edge, Fire Alarm, WiFi/Cellular
2 1st Flr/ 122 12 11 10 3 9 11 132.40 Green 1 5e 5 135 240 43.75% 62.5 12 SC 110 Blocks, iStar Edge, Fiber Termination, Wall mount Enclosure, Cat3 Cross Connects, Fire Alarm
2 2nd Flr/ 220 13 7 10 3 7 11 139.23 Height 1 5e 3 1 57 168 66.07% 62.5 12 SC 110 Blocks, Coax TV, iStar Edge, 3 Grnd / 24A 6 6 9 3 9 2 60.13 Red 1 5e 2 60 96 37.50% 62.5 12 SC 110 Blocks, iStar Edge, Fiber Termination, Wall mount Enclosure, Coax or Antenna system.
3 1st Flr/ 131A 6 10 9 3 12 7 63.21 Red 1 5e 3 1 103 168 38.69% 62.5 12 SC 110 Blocks, iStar Edge, Fire Alarm
3 2nd Flr/ 222A 6 4 9 4 8 8 59.12 Red 1 5e 4 64 192 66.67% 62.5 12 SC 110 Blocks, iStar Edge, Fire Alarm
4 1st Flr/ 102 7 10 5 10 12 0 45.70 Red 1 5e/ 6 1 4 58 144 59.72% 62.5 9 6 SC LC 110 Blocks, iStar Edge
12 1st Flr/ Cabinet 14 3 0.00 Green TE 5e 2 24 48 50.00% 62.5 6 SC 110 Blocks, iStar Edge, Cat3 Cross Connects, Fiber Termination Panel (8 Strand ST)
16 grnd/ 6B 7 3 11 0 9 8 79.75 Red 1 5e/ 6 6 1 121 312 61.22% 62.5 9 12 SC LC 110 Blocks, iStar Edge, Fiber Termination, Wall mount Enclosure, Cat3 Cross Connects, FOTP (2)
16 1st Flr/ 115B 11 2 7 1 8 11 79.10 Red 2 5e/ 6 7 1 121 360 66.39% 62.5 12 SC 110 Blocks, Coax TV, iStar Ultra
16 2nd/ 222A 11 2 7 3 8 3 80.96 Red 2 5e 5 1 129 264 51.14% 62.5 8 SC 110 Blocks, Coax TV, iStar Ultra
17 Basement/ 13B 11 4 26 6 9 3 300.34 Green 4 5e/ 6 4 3 126 264 52.27% 62.5/50 9 SC/LC LC SR/MCR/DC, 110 Blocks, Coax TV, iStar Edge, Phone Systems, Cat3 Cross Connects, FOTP (3)
17 1st Flr/ 126 12 7 5 11 8 6 74.46 Red 2 5e/ 6 4 1 107 216 50.46% 62.5 9 8 SC LC 110 Blocks, Coax TV, iStar Edge, Alarm systems
17 2nd Flr/ 218 12 9 6 4 8 3 80.75 Red 2 5e 5 1 122 264 53.79% 62.5 8 SC 110 Blocks, Coax TV, iStar Edge, Fire Alarm
20 2 13 10 18 6 7 6 255.92 Height 1/TE 5e 1 6 48 87.50% 62.5 FOTP (1), Fire Alarm, In Cabinet in Plans Room.
22 101A 33 4 7 4 10 1 244.45 Green TE 5e 1 9 24 62.50% 62.5 8 SC In Wall Panels, 110 Blocks
25 ground/ 19 12 11 6 11 8 3 89.35 Green 1 5e/ 6 4 109 192 43.23% 62.5 9 6 LC 66 Block, 110 Blocks, iStar Edge, Cat3 Cross Connect, FOTP (2) Wall mount Enclosure
25 1st Flr/ 112 12 9 6 6 8 11 82.88 Green 1 5e/6 /6A 4 1 113 216 47.69% 62.5 6 SC 110 Blocks, iStar Edge, 25 2nd Flr/ 214 12 10 6 10 8 6 87.70 Green 1 5e 4 1 131 216 39.35% 62.5 12 110 Blocks, iStar Edge, Service Provider Cabling Enclosure (T1)
27 ground/ 002F 16 2 8 3 9 11 133.38 Green 1 5e/ 6 2 1 47 120 60.83% 62.5 Coax TV, iStar Edge, FOTP (3), 27 ground/ 016D 16 1 8 3 10 3 132.69 Green 1 5e 1 1 42 72 41.67% 62.5 9 SC LC 110 Blocks, Coax TV, iStar Edge, Cat3 Cross Connect, Wall mount Enclosure
27 1st Flr/ 117A 16 3 8 4 9 7 135.42 Green 1 5e/ 6 2 29 96 69.79% 62.5 66 Block, Coax TV, iStar Edge
27 1st Flr/ 136A 16 3 8 3 10 3 134.07 Green 1 5e 2 29 96 69.79% 62.5 6 SC 110 Blocks, Coax TV, iStar Edge
27 2nd Flr/ 217A 16 3 8 4 10 9 135.42 Green 1 5e/ 6 2 1 29 120 75.83% 62.5 SC Coax TV, iStar Edge
27 2nd Flr/ 236A 16 4 8 3 9 4 134.75 Green 1 5e/ 6 2 26 96 72.92% 62.5 110 Blocks, Coax TV, iStar Edge
28 ground/ 1A 10 7 15 1 9 6 159.64 Green 1 5e/ 6/ 6A 2 1 62 120 48.33% 62.5 4 ST 110 Blocks, iStar Edge, Cat3 Cross Connects, Wall mount Enclosure, FOTP (2), Fire Alarm
28 1st Flr/ A156 9 3 12 2 9 3 112.55 Green 2 6A 9 1 0 456 100.00% 62.6/50 Newly Renovated see pics
28 2nd Flr/ A247 9 0 12 3 9 9 110.25 Green 2 6A 6 2 0 336 100.00% 62.5/50 Newly Renovated see pics
29 ground/ 21 9 7 5 11 8 11 56.71 Red 1 5e/ 6 4 3 80 264 69.70% 62.5 8 SC 110 Blocks, Coax TV, iStar Edge, Cat3 Cross Connect, FOTP (2), Amplifier
29 1st floor/ 134A 9 9 5 11 8 11 57.69 Red 1 5e/ 6 1 1 1 63 168 62.50% 62.5/50
29 2nd floor/ 239A 9 9 5 11 7 7 57.69 Height 1 5e/ 6 3 1 110 168 34.52% 62.5 8 SC 66 Blocks, 110 Blocks, Phone System, iStar Edge
37 8 80 0 27 2 9 11 2173.34 Green 1/TE 5e 1 1 14 72 80.56% 62.5 6 ST In Cabinet in Wood Shop
39 3 0.00 0 Under Construction
46 3 15 2 20 10 7 11 315.98 Height TE 5e 1 3 24 87.50% 62.5 In Cabinet in Air hadling room
47 8 45 1 13 0 8 3 586.09 Green TE 5e 2 18 96 81.25% 62.5 In Cabinet in Tool Room
48 2 8 0 15 11 7 5 127.34 Height TE 5e 1 9 48 81.25% 62.5 In Cabinet in Office/Locker Space
67 Chill Plant 12 0 12 6 7 11 150.00 Height 0 5e 0 62.5 12 ST No rack or cabinet see pics, Cat3 Cross Connect, FOTP Cross Connect
T112 3 34 1 21 2 12 11 721.44 Green 1/TE 5e 1 6 48 87.50% 62.5 6 ST In Cabinet in warehouse/storage space
Total 42 41 1 122 0 42 2656 6960 250 0
56 14548 Port Patch Panels Needed
# of patch panels Copper Ports Length width Height
TR Area Fiber Optic
Type Strands Connectors
File details come from the government source that posted it. Updated .