0004 - 596-22-700 Lexington TR Notes-MASTER.pdf

PDF 53 KB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction Lexington - Leestown, KY 596-22-700
Solicitation number
36C77625B0040
Issued by

About this file

This document is a detailed telecommunications infrastructure survey spreadsheet tracking network infrastructure across multiple buildings and floors. The spreadsheet provides comprehensive data on 42 separate telecommunications rooms (TR), including room locations, cable types (primarily Cat 5e and Cat 6/6A), physical dimensions, port configurations, fiber optic details, and equipment/system notes. Key technical specifications include area measurements, rack configurations, cable types, port populations, fiber optic strand counts, and connector types. The data reveals varying network infrastructure conditions across different building areas, with port utilization ranging from 34.52% to 100%, cable categories including 5e, 6, and 6A, and additional systems noted such as coax TV, iStar Edge, fire alarms, and phone systems. The total infrastructure includes 6,960 total ports with 2,656 populated ports, and requires 56 48-port patch panels and 145 total patch panels to support the network infrastructure.

View the file

Other files

File Type Posted
36C77625B0040 0006.pdf PDF
0006 - 596-22-700 DBA Wages - Fayette County - 08-22-2025.pdf PDF
36C77625B0040 0005.pdf PDF
0004 - 596-22-700 Spec Section 02 82 13.13 Revisions.pdf PDF
0004 - 596-22-700 Drawings 00_General Revisions.pdf PDF
0004 - 596-22-700 TR Photos - Question 58.pdf PDF
0004 - 596-22-700 Responses to Tech Questions - 8-19-25.pdf PDF
0004 - 596-22-700 Spec Section 23 07 11.pdf PDF
0004 - 596-22-700 Spec Section 00 01 10 Revisions.pdf PDF
0004 - 596-22-700 Spec Section 01 00 00 Revisions.pdf PDF
0004 - 596-22-700 Drawings 02_Civil Revisions.pdf PDF
36C77625B0040 0004.pdf PDF
0004 - 596-22-700 Spec Section 08 11 13 Revisions.pdf PDF
0004 - 596-22-700 Spec Section 08 71 00 Revisions.pdf PDF
0004 - 596-22-700 Drawings 01_Environmental Revisions.pdf PDF
36C77625B0040 0003.pdf PDF
0003 - 596-22-700 Responses to Tech Questions - 8-12-25.pdf PDF
0003 - 596-22-700 DBA Wages - Fayette County - 08-08-2025.pdf PDF
0002 - 596-22-700 DBA Wages - Fayette County - 07-18-2025.pdf PDF
36C77625B0040 0002.pdf PDF
36C77625B0040 0001.pdf PDF
0001 - 596-22-700 Site Visit Sign-in Sheet - 7-8-25.pdf PDF
07 - 596-22-700 Drawings 03_Structural.pdf PDF
09 - 596-22-700 Drawings 05_Fire Protection.pdf PDF
15 - 596-22-700 ICRA III.pdf PDF
17 - 596-22-700 Brand Name Justification.pdf PDF
18 - 596-22-700 DBA Wages - Fayette County - 06-06-2025.pdf PDF
19 - 596-22-700 VAAR 852.219-75 LOS - Construction.docx DOCX document
IFB 36C77625B0040 - 6-25-25.pdf PDF
02 - 596-22-700 Specs 2.pdf PDF
10 - 596-22-700 Drawings 06_Mechanical.pdf PDF
12 - 596-22-700 Drawings 08_Telecom.pdf PDF
16 - 596-22-700 PCRA.pdf PDF
01 - 596-22-700 Specs 1.pdf PDF
03 - 596-22-700 Spec Section 01 31 00.01.pdf PDF
04 - 596-22-700 Drawings 00_General.pdf PDF
08 - 596-22-700 Drawings 04_Architectural.pdf PDF
11 - 596-22-700 Drawings 07_Electrical.pdf PDF
05 - 596-22-700 Drawings 01_Environmental.pdf PDF
06 - 596-22-700 Drawings 02_Civil.pdf PDF
13 - 596-22-700 Drawings 09_Security.pdf PDF
14 - 596-22-700 ICRA II.pdf PDF
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Area Pass/Fail

Buliding # TR # FT-L IN-L FT-W IN-W FT-H IN-H FT^2 Area # of Racks Type of Cat Cable 96 port 48 port 36 port 24 port Populated Ports Total Ports % Fill OM OS OM.2 OS.2 OM.3 OS.3 Notes

"Example" "Example" 10 0 8 4 10 0 83.34 Green 1 5/5e/6/6A 0 2 1 1 132 156 15.38% 62.5/50 9um 24 12 LC ST Wifi & Patient TV systems present

1 Grnd / 31 15 9 40 7 8 10 639.19 Green 1 5e 5 1 101 264 61.74% 62.5

1 1st Flr/ 147A 11 3 11 11 8 11 134.07 Green 1 5e 4 1 109 216 49.54% 62.5 12 SC 110 Blocks, Coax TV, iStar Edge, Fire Alarm

1 2nd Flr/ 229 11 5 8 7 8 7 98.00 Green 1 5e 4 1 89 216 58.80% 62.5 12 SC 110 Blocks, Coax TV, iStar Edge, Fire Alarm

1 3rd Flr/ 331 11 1 8 2 8 9 90.52 Green 1 5e 4 3 105 264 60.23% 62.5 12 SC 110 Blocks, Coax TV, iStar Edge, Fire Alarm, Fiber Termination & connected equipment.

1 4th Flr/ 419 11 0 8 6 7 6 93.50 Height 1 5e/ 6 2 3 90 168 46.43% 62.5 12 SC 110 blocks, Coax TV, iStar Edge, Fire Alarm, WiFi/Cellular

2 1st Flr/ 122 12 11 10 3 9 11 132.40 Green 1 5e 5 135 240 43.75% 62.5 12 SC 110 Blocks, iStar Edge, Fiber Termination, Wall mount Enclosure, Cat3 Cross Connects, Fire Alarm

2 2nd Flr/ 220 13 7 10 3 7 11 139.23 Height 1 5e 3 1 57 168 66.07% 62.5 12 SC 110 Blocks, Coax TV, iStar Edge, 3 Grnd / 24A 6 6 9 3 9 2 60.13 Red 1 5e 2 60 96 37.50% 62.5 12 SC 110 Blocks, iStar Edge, Fiber Termination, Wall mount Enclosure, Coax or Antenna system.

3 1st Flr/ 131A 6 10 9 3 12 7 63.21 Red 1 5e 3 1 103 168 38.69% 62.5 12 SC 110 Blocks, iStar Edge, Fire Alarm

3 2nd Flr/ 222A 6 4 9 4 8 8 59.12 Red 1 5e 4 64 192 66.67% 62.5 12 SC 110 Blocks, iStar Edge, Fire Alarm

4 1st Flr/ 102 7 10 5 10 12 0 45.70 Red 1 5e/ 6 1 4 58 144 59.72% 62.5 9 6 SC LC 110 Blocks, iStar Edge

12 1st Flr/ Cabinet 14 3 0.00 Green TE 5e 2 24 48 50.00% 62.5 6 SC 110 Blocks, iStar Edge, Cat3 Cross Connects, Fiber Termination Panel (8 Strand ST)

16 grnd/ 6B 7 3 11 0 9 8 79.75 Red 1 5e/ 6 6 1 121 312 61.22% 62.5 9 12 SC LC 110 Blocks, iStar Edge, Fiber Termination, Wall mount Enclosure, Cat3 Cross Connects, FOTP (2)

16 1st Flr/ 115B 11 2 7 1 8 11 79.10 Red 2 5e/ 6 7 1 121 360 66.39% 62.5 12 SC 110 Blocks, Coax TV, iStar Ultra

16 2nd/ 222A 11 2 7 3 8 3 80.96 Red 2 5e 5 1 129 264 51.14% 62.5 8 SC 110 Blocks, Coax TV, iStar Ultra

17 Basement/ 13B 11 4 26 6 9 3 300.34 Green 4 5e/ 6 4 3 126 264 52.27% 62.5/50 9 SC/LC LC SR/MCR/DC, 110 Blocks, Coax TV, iStar Edge, Phone Systems, Cat3 Cross Connects, FOTP (3)

17 1st Flr/ 126 12 7 5 11 8 6 74.46 Red 2 5e/ 6 4 1 107 216 50.46% 62.5 9 8 SC LC 110 Blocks, Coax TV, iStar Edge, Alarm systems

17 2nd Flr/ 218 12 9 6 4 8 3 80.75 Red 2 5e 5 1 122 264 53.79% 62.5 8 SC 110 Blocks, Coax TV, iStar Edge, Fire Alarm

20 2 13 10 18 6 7 6 255.92 Height 1/TE 5e 1 6 48 87.50% 62.5 FOTP (1), Fire Alarm, In Cabinet in Plans Room.

22 101A 33 4 7 4 10 1 244.45 Green TE 5e 1 9 24 62.50% 62.5 8 SC In Wall Panels, 110 Blocks

25 ground/ 19 12 11 6 11 8 3 89.35 Green 1 5e/ 6 4 109 192 43.23% 62.5 9 6 LC 66 Block, 110 Blocks, iStar Edge, Cat3 Cross Connect, FOTP (2) Wall mount Enclosure

25 1st Flr/ 112 12 9 6 6 8 11 82.88 Green 1 5e/6 /6A 4 1 113 216 47.69% 62.5 6 SC 110 Blocks, iStar Edge, 25 2nd Flr/ 214 12 10 6 10 8 6 87.70 Green 1 5e 4 1 131 216 39.35% 62.5 12 110 Blocks, iStar Edge, Service Provider Cabling Enclosure (T1)

27 ground/ 002F 16 2 8 3 9 11 133.38 Green 1 5e/ 6 2 1 47 120 60.83% 62.5 Coax TV, iStar Edge, FOTP (3), 27 ground/ 016D 16 1 8 3 10 3 132.69 Green 1 5e 1 1 42 72 41.67% 62.5 9 SC LC 110 Blocks, Coax TV, iStar Edge, Cat3 Cross Connect, Wall mount Enclosure

27 1st Flr/ 117A 16 3 8 4 9 7 135.42 Green 1 5e/ 6 2 29 96 69.79% 62.5 66 Block, Coax TV, iStar Edge

27 1st Flr/ 136A 16 3 8 3 10 3 134.07 Green 1 5e 2 29 96 69.79% 62.5 6 SC 110 Blocks, Coax TV, iStar Edge

27 2nd Flr/ 217A 16 3 8 4 10 9 135.42 Green 1 5e/ 6 2 1 29 120 75.83% 62.5 SC Coax TV, iStar Edge

27 2nd Flr/ 236A 16 4 8 3 9 4 134.75 Green 1 5e/ 6 2 26 96 72.92% 62.5 110 Blocks, Coax TV, iStar Edge

28 ground/ 1A 10 7 15 1 9 6 159.64 Green 1 5e/ 6/ 6A 2 1 62 120 48.33% 62.5 4 ST 110 Blocks, iStar Edge, Cat3 Cross Connects, Wall mount Enclosure, FOTP (2), Fire Alarm

28 1st Flr/ A156 9 3 12 2 9 3 112.55 Green 2 6A 9 1 0 456 100.00% 62.6/50 Newly Renovated see pics

28 2nd Flr/ A247 9 0 12 3 9 9 110.25 Green 2 6A 6 2 0 336 100.00% 62.5/50 Newly Renovated see pics

29 ground/ 21 9 7 5 11 8 11 56.71 Red 1 5e/ 6 4 3 80 264 69.70% 62.5 8 SC 110 Blocks, Coax TV, iStar Edge, Cat3 Cross Connect, FOTP (2), Amplifier

29 1st floor/ 134A 9 9 5 11 8 11 57.69 Red 1 5e/ 6 1 1 1 63 168 62.50% 62.5/50

29 2nd floor/ 239A 9 9 5 11 7 7 57.69 Height 1 5e/ 6 3 1 110 168 34.52% 62.5 8 SC 66 Blocks, 110 Blocks, Phone System, iStar Edge

37 8 80 0 27 2 9 11 2173.34 Green 1/TE 5e 1 1 14 72 80.56% 62.5 6 ST In Cabinet in Wood Shop

39 3 0.00 0 Under Construction

46 3 15 2 20 10 7 11 315.98 Height TE 5e 1 3 24 87.50% 62.5 In Cabinet in Air hadling room

47 8 45 1 13 0 8 3 586.09 Green TE 5e 2 18 96 81.25% 62.5 In Cabinet in Tool Room

48 2 8 0 15 11 7 5 127.34 Height TE 5e 1 9 48 81.25% 62.5 In Cabinet in Office/Locker Space

67 Chill Plant 12 0 12 6 7 11 150.00 Height 0 5e 0 62.5 12 ST No rack or cabinet see pics, Cat3 Cross Connect, FOTP Cross Connect

T112 3 34 1 21 2 12 11 721.44 Green 1/TE 5e 1 6 48 87.50% 62.5 6 ST In Cabinet in warehouse/storage space

Total 42 41 1 122 0 42 2656 6960 250 0

56 14548 Port Patch Panels Needed

# of patch panels Copper Ports Length width Height

TR Area Fiber Optic

Type Strands Connectors