These structural drawings are for the Electronic Health Record Modernization (EHRM) Infrastructure Upgrades Construction Project at the Lexington VA Health Care System's Franklin R. Sousley Campus. The documents (specifically sheets SE001, SE101, and SE102) provide comprehensive structural details for Building 17 and Building 25, including ground level and basement floor plans, reinforcement schedules, concrete and masonry specifications, and general structural design criteria. Key technical specifications include concrete compressive strength requirements (4500 PSI for footings and slabs), seismic design category D, wind design parameters (118 MPH basic wind speed), and detailed reinforcement guidelines for concrete and masonry elements.
The structural drawings specify precise construction requirements such as minimum footing depths (3'-0" below grade), slab reinforcement (6x6-W2.1xW2.1 welded wire reinforcement), and specific reinforcement techniques for walls, bond beams, and penetrations. Design criteria follow the 2021 International Building Code and ASCE 7-16 standards, with an occupancy risk category of IV and specific requirements for concrete mix designs, reinforcement placement, and structural element connections. The project involves infrastructure upgrades at the Lexington, Kentucky VA Health Care System, with detailed engineering specifications to ensure structural integrity and compliance with federal building standards.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTES (GENERAL):
A. STAGGER ALL SPLICES 12 db MIN, BUT NOT LESS THAN 12"
B. ALL DIMENSIONS INDICATED IN TABLE ARE IN INCHES
C. BARS GREATER THAN #11 SHALL BE MECHANICALLY SPLICED
D. ALL SPLICES SHALL BE WIRED IN CONTACT STACKED VERTICAL
MULTIPLIERS:
ALL EMBEDMENT AND LAP SPLICE LENGTHS SHALL BE INCREASED
AS REQ'D BY THE MULIPLIERS BELOW. APPLY MULTIPLE
MULTIPLIERS IF APPLICABLE
1.3 -- IF CONC CONTAINS LIGHT WEIGHT AGGREGATES
1.3 -- IF EPOXY COATED REBAR USED
NOTES (PERTAINING TO TABLE):
A. TOP BARS ARE HORIZONTAL BARS THAT HAVE MORE THAN 12" OF FRESH CONCRETE
CAST BELOW THEM.
B. ALL BARS THAT ARE NOT "TOP BARS" ARE "OTHER" BARS
C. ABBREVIATIONS:
- LCE - COMPRESSION EMBEDMENT LENGTH
- LTE - TENSION EMBEDMENT LENGTH
- LCS - COMPRESSION LAP SPLICE LENGTH
- LTS - TENSION LAP SPLICE LENGTH
- LDH - HOOKED BAR TENSION EMBEDMENT LENGTH
DEVELOPMENT AND LAP SPLICE SCHEDULE
EMBEDMENT
F'c=3000 psi F'c=4000 psi
EMBEDMENTLAP SPLICE LAP SPLICE
COMPRESSION
BAR
COMPRESSION COMPRESSION COMPRESSIONTENSION (LTE) TENSION (LTS) TENSION (LTE) TENSION (LTS)HOOK HOOK
#3
#4
#5
#6
#7
#8
#9
#10
#11
(LCE) TOP OTHER (LCS) TOP OTHER (LDH) (LCS) TOP OTHER (LDH)(LCE) TOP OTHER
12 12 16 16
15 24
19 35
23 48
26 78
30 96
34 116
38 140
42 164
2'-0" MIN
40 BAR DIA
DETAIL NOTES:
CMU WALL BOND BEAM
(4) VERT BARS @
INTERSECTION. MATCH TYP
WALL REINF
BOND BEAM BARS TYP
VERT BARS, RE: PLAN & WALL
SECTION
(3) VERT BARS AT CORNER.
MATCH TYP WALL REINF
BOND BEAM CORNERS BOND BEAM INTERSECTION
2 3
4 56
DETAIL NOTES:
PAD SIZE: 1'-0" EACH WAY LARGER THAN
EQUIPMENT BASE OR SEE PLAN FOR SIZE
CHAMFER ALL 3/4" TYP
6x6-W2.9 WWR, 1" CLEAR OF TOP
#3 TIE AT 12" OC AROUND PERIMETER AND ALL
OPENINGS
CONSTRUCTION JOINT, ROUGHEN SURFACE TO
1/4 AMPLITUDE AND APPLY BONDING AGENT
#3 CONT AROUND PERIMETER
6" TYPICAL UNLESS NOTED OTHERWISE ON PLAN
SEE GENERAL NOTES FOR UNDERSLAB
REQUIREMENTS.
4" THICK SOG MINIMUM ON 4” OF GRANULAR FILL.
REINF SLAB WITH 6 X 6-W2.1xW2.1 WWR
T/SLAB
RE: PLAN
T/MEP SLAB
100'-6"
LARGER OF ADJACENT
PENETRATION DIAMETERS
D1 & D2 OR 6",
WHICHEVER IS GREATER
2" TYP
2" T
Y P
NOTES:
A. DETAIL DOES NOT APPLY FOR PENETRATIONS LARGER THAN 12" IN
DIAMETER. SEE TYP SLAB OPENING DETAIL FOR SUCH PENETRATIONS
DETAIL NOTES:
ARRANGE PRIMARY SLAB BARS
TO PASS BY PENETRATIONS.
DO NOT TERMINATE SLAB
BARS AT PENETRATIONS
(1) #5 x 5'-0" T&B @
ENDS & IN BTWN ALL
PENETRATIONS
(1)#5 x 5'-0" T&B EA SIDE
ALIGN PENETRATIONS WHERE
POSSIBLE
CORNERSINTERSECTIONSENDS
WALLS WITH 2 LAYERS OF REINF (10" OR GREATER)
WALLS WITH 1 LAYER OF REINF (< 10")
LTS
LT
S
DETAIL NOTES:
DWLS TO MATCH HORIZ REINF SIZE AND
SPACING. ALT HOOK DIRECTIONS (TYP)
CORNER BARS. MATCH HORIZ REINF SIZE AND
SPACING
HORIZONTAL BARS
STD HOOK
U-BARS TO MATCH SIZE AND SPACING OF
HORIZ BARS (TYP) @ WALLS 16" OR THICKER
DWLS TO MATCH HORIZ REINF SIZE AND
SPACING (TYP)
25 3
6 4
LTS
CORNERSINTERSECTIONS
3 4
5/16" CONT
BENT PL
1/4" CONT
BENT PL
5/16
5/16
DETAIL A
NOTES:
A. HEIGHT OF MASONRY ABOVE LINTEL MUST
BE MIN OF 1/2 THE OPENING WIDTH
B. PROVIDE ONE STEEL LINTEL FOR EA 4"
THICKNESS OF MASONRY. (FOR EXAMPLE: 3
ANGLES FOR 12" OF WALL)
C. LINTELS SPECIFICALLY CALLED OUT ON
DRAWINGS SHALL GOVERN OVER THIS
SCHEDULE
D. ALL STEEL ANGLES SHALL BE GALV AND
SHALL HAVE SHORT LEG HORIZONTAL (SLH)
E. L6 REQUIRES A 2" MIN AIR GAP TO FIT IN
WALL CAVITY.
5"
9"
LOOSE LINTEL SCHEDULE
L1
MARK
L2
L3
L4
L5
L6
UP TO 1'-8"
OPENING SIZE
1'-9" TO 3'-0"
3'-1" TO 4'-5"
4'-6" TO 6'-3"
6'-4" TO 8'-0"
8'-1" TO 12'-0"
1/4" PL x WALL WIDTH - 1/2"
OPENING SIZE
5/16" & 1/4" BENT PL (SEE DETAIL A) 8"
BRG LENGTH
L3 1/2" x 3 1/2" x 1/4"
L4" x 3 1/2" x 5/16"
L5" x 3 1/2" x 3/8"
L6" x 3 1/2" x 3/8" 8"
4"
4"
4"
4"
NOTES:
ROOF STRUCTURE, RE: PLAN.
POST-INSTALLED ANCHOR TO ROOF STRUCTURE.
STRUT CHANNEL BRACE
ATTACHMENT TO EQUIPMENT / CABINET.
POST-INSTALLED ANCHOR INTO FLOOR SLAB, TYP
CONCRETE FLOOR SLAB, RE: PLAN. AVOID
DAMAGING REINFORCEMENT.
ANCHORAGE BRACKET PER EQUIPMENT
MANUFACTURER
EQUIPMENT / CABINET
1 2
5 6
CONTRACTOR SHALL PROVIDE
FINAL DESIGN IN COMPLIANCE
WITH SEISMIC REQUIREMENTS
OUTLINED IN THE SPECIFICATIONS
Veterans Health
Administration
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
FULLY SPRINKLERED
STAMP:
Drawing Number
Building Number th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t 0 o n e q u a rt e r in c h o n e fo o t 0 o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
VA FORM 08-6231
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 E. ST. LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE., SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
STRUCTURAL ENGINEER
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST., STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS LLC
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
FIRE PROTECTION ENGRINEER
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
/1
/2
:4
:3
P
M
OF
SPUR #: 2207
BID DOCUMENTS
No. REVISION DESCRIPTION DATE
596-22-700
SE001
STRUCTURAL GENERAL NOTES AND
DETAILS
MDMPWS
EHRM INFRASTRUCTURE
UPGRADES, LEXINGTON, KY
03/15/2024
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
03_Abbreviation Schedule
Abbreviation Abbreviation Name
+/- PLUS OR MINUS
ADDNL ADDITIONAL
ADJ ADJACENT
AESS ARCHITECTURALLY EXPOSED
STRUCTURAL STEEL
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE
AR ANCHOR ROD
ARCH ARCHITECT OR ARCHITECTURAL
B/ BOTTOM OF
B/W BETWEEN
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BOT BOTTOM
BRG BEARING
BWP BRACED WALL PANEL
CFS COLD FORMED STEEL
CHKD CHECKED
CIP CAST IN PLACE
CJ CONTROL JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEAR
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
CTR CENTER
db DIA OF REINF BAR, DIA OF BOLT
DBA DEFORMED BAR ANCHOR
DIA or Ø DIAMETER
DIAG DIAGONAL
DIR DIRECTION
DWL DOWEL
EA EACH
EE EXTENDED END
EJ EXPANSION JOINT
ELEV ELEVATION
EN EDGE NAILING
ENGR ENGINEER
EOD EDGE OF DECK
EOS EDGE OF SLAB
EQ EQUAL
EW EACH WAY
EXIST EXISTING
EXT EXTERIOR
FDN FOUNDATION
FLG FLANGE
FLR FLOOR
FS FAR SIDE
FTG FOOTING
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZED
GB GRADE BEAM
GC GENERAL CONTRACTOR
HORIZ HORIZONTAL
HSA HEADED STUD ANCHOR
HSS HOLLOW STRUCTURAL SECTION
IF INSIDE FACE
INT INTERIOR
JST JOIST
K KIPS (1000 LBS)
LCE COMPRESSION EMBEDMENT LENGTH
LCS COMPRESSION LAP SPLICE LENGTH
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LSH LONG SLOTTED HOLE
LTE TENSION EMBEDMENT LENGTH
LTS TENSION LAP SLICE LENGTH
LW LIGHTWEIGHT
MFCR MANUFACTURER
MTL METAL
NIC NOT IN CONTRACT
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OF OUTSIDE FACE
OPP OPPOSITE
OVS OVERSIZED
P/C PRECAST
PAF POWDER ACTUATED FASTENER
PAR PARALLEL
PEMB PRE-ENGINEERED METAL BUILDING
PEN PENETRATION
PERP PERPENDICULAR
PL PLATE
PLF POUNDS PER LINEAR FOOT
PREFAB PREFABRICATED
PRELIM PRELIMINARY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
RC REINFORCED CONCRETE
RE: REFER TO
REINF REINFORCING
REQD REQUIRED
RF RIGID FRAME
SC SLIP CRITICAL
SDS SELF DRILLING SCREW
SIM SIMILAR
SLV SHORT LEG VERTICAL
SOG SLAB ON GRADE
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STIR STIRRUPS
STL STEEL
SW SHEAR WALL
SYM SYMMETRIC
T&B TOP AND BOTTOM
T/ TOP OF
TRANS TRANSVERSE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
W/ WITH
W/O WITHOUT
WF WIDE FLANGE
WP WORK POINT
WWR WELDED WIRE REINFORCEMENT
STRUCTURAL DESIGN CRITERIA (2021 IBC AND ASCE 7-16):
1. BUILDING OCCUPANCY RISK CATEGORY IV.
2. LIVE LOADS [UNIFORM (PSF) / POINT LOADS (KIPS)]:
-- GROUND LEVEL SLAB ........................................100 PSF / 2.0 K
3. WIND DESIGN DATA:
-- BASIC WIND SPEED (3 SEC GUST):……………...118 MPH
– ASD WIND SPEED, V(ASD)....................................92 MPH
-- WIND EXPOSURE:…………………………………..C
-- GROUND ELEVATION ABOVE SEA LEVEL……..1,000 FT
-- DIRECTIONALITY FACTOR (Kd) ..........................0.85
-- INTERNAL PRESSURE COEFF:………….……….0.18
4. EARTHQUAKE DESIGN DATA:
-- SEISMIC IMPORTANCE FACTOR (Ie):………......1.5 -- MAPPED SPECTRAL RESP ACCEL (Ss / S1):…..0.25 / 0.099
-- SITE CLASS:………………………………………….D
-- SPECTRAL RESPONSE COEFF (Sds / Sd1):……0.21 / 0.14
-- SEISMIC DESIGN CATEGORY:……………………D
-- SEISMIC FORCE RESISTING SYSTEM:…………R=3, CONCRETE
STRUCTURAL GENERAL NOTES:
1. DESIGN AND CONSTRUCTION SHALL CONFORM TO THE "INTERNATIONAL
BUILDING CODE, 2021 EDITION" AND ALL APPLICABLE VA DOCUMENTS, INCLUDING
HANDBOOK 18-8. REFER TO THE SPECIAL STRUCTURAL INSPECTION NOTES FOR
ADDITIONAL REQUIREMENTS.
2. CONTRACTOR TO VERIFY ALL DIMENSIONS, ELEVATIONS AND EXISTING
CONDITIONS AND REPORT ANY DISCREPANCIES TO THE ARCHITECT PRIOR TO
COMMENCING WORK.
3. IF DISCREPANCIES EXIST BETWEEN STRUCTURAL PLANS, ARCHITECTURAL
PLANS, OTHER PLANS, OR SPECIFICATIONS, THE CONTRACTOR OR
SUBCONTRACTOR SHALL PROVIDE A WRITTEN REQUEST FOR CLARIFICATION FROM
THE ARCHITECT AND/OR ENGINEER PRIOR TO PROCEEDING WITH THE WORK.
4. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER
THE BUILDING IS FULLY COMPLETED. IT IS SOLELY THE CONTRACTOR'S
RESPONSIBILITY TO EXECUTE AND DETERMINE FINAL ERECTION PROCEDURES,
SEQUENCING AND TO ENSURE THE SAFETY OF THE BUILDING AND ITS COMPONENT
PARTS DURING ERECTION. THIS INCLUDES WHATEVER SHORING, SHEETING,
TEMPORARY BRACING, GUYING OR TIE DOWNS WHICH MIGHT BE NECESSARY.
5. THE STRUCTURE AND FOUNDATIONS ARE NOT DESIGNED FOR FUTURE
EXPANSION.
6. FABRICATORS AND SUPPLIERS SHALL CLEARLY NOTE AND HIGHLIGHT CHANGES
MADE IN SHOP DRAWINGS, WHICH DO NOT COMPLY WITH THE CONTRACT
DOCUMENTS.
7. COLUMNS, BEAMS, JOISTS, OR TRUSSES SHALL NOT BE FIELD CUT OR TRIMMED
FOR ANY REASON WITHOUT THE WRITTEN APPROVAL OF THE
ARCHITECT/ENGINEER.
8. HOLES, PIPES, SLEEVES, ETC. NOT SHOWN ON THE DRAWINGS MUST BE
REVIEWED BY THE ARCHITECT/ENGINEER BEFORE PLACEMENT THROUGH
STRUCTURAL MEMBERS.
9. IF MECHANICAL AND ELECTRICAL EQUIPMENT SIZES, WEIGHTS, OR LOCATIONS
DO NOT COINCIDE WITH EQUIPMENT SHOWN ON THE PLANS, COORDINATE
ADJUSTMENTS WITH THE ARCHITECT.
10. NO AREA OF THE STRUCTURE SHALL BE LOADED WITH CONSTRUCTION
MATERIALS OR EQUIPMENT THAT EXCEEDS FINAL DESIGN CRITERIA.
11. BEAMS, COLUMNS, WALLS AND FOOTING CENTERS SHALL BE CENTERED UNDER
SUPPORTING MEMBERS (TYPICAL UNLESS NOTED OTHERWISE).
12. TYPICAL DETAILS ARE SHOWN ON SHEETS DESIGNATED "S0XX". THE INCLUDED
TYPICAL DETAILS MAY OR MAY NOT BE CUT / REFERENCED ON PLANS OR
SECTIONS, BUT ARE TO BE USED AS APPLICABLE
CONCRETE AND MASONRY REINFORCING STEEL:
1. SUBMIT SHOP DRAWINGS FOR REBAR. ALL REINFORCING BARS SHALL MEET
ASTM A615 GRADE 60.
2. ALL MESH SHALL MEET ASTM A-185: LAP A MINIMUM OF 8” OR ONE FULL MESH,
WHICHEVER IS GREATER.
3. REINFORCING BAR QUANTITIES SHOWN ARE FOR ESTIMATING PURPOSES ONLY.
4. PROVIDE AN ADDITIONAL ALLOWANCE OF 1% OF THE TOTAL REINFORCING
SHOWN ON THE FINAL DRAWINGS TO BE FABRICATED AND ERECTED DURING THE
PROGRESS OF THE WORK AT THE DIRECTION OF THE STRUCTURAL ENGINEER.
FOR THE ADDITIONAL REINFORCING ALLOWANCE, INCLUDE BOTH THE COST OF THE
REINFORCING AND THE LABOR TO PLACE IT.
5. CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE ¾” CLEAR FOR SLABS,
2” CLEAR FOR FORMED SURFACES AND 3” CLEAR FOR FOOTINGS (TYPICAL UNLESS
NOTED).
6. CONTRACTOR SHALL VERIFY THAT ALL REINFORCEMENT, SLAB DOWELS,
INSERTS, SLEEVES AND EMBEDDED ITEMS ARE PROPERLY LOCATED AND RIGIDLY
SECURED PRIOR TO CONCRETE PLACEMENT, “WET STICKING” DOWELS WILL NOT
BE ALLOWED.
7. REINFORCEMENT SHALL BE DETAILED IN ACCORDANCE WITH THE LATEST A.C.I.
DETAILING MANUAL BY A QUALIFIED AND EXPERIENCED FIRM AND PERSON. PLACE
AND SUPPORT REINFORCEMENT WITH ACCESSORIES: MAXIMUM SPACING - 48”
CENTERS (PLASTIC-TIPPED LEGS FOR EXPOSED SURFACES). USE 3” SBP
SUPPORTS AT ALL FOOTINGS.
8. ALL STRUCTURAL ADHESIVE SHALL BE SIMPSON SET 3G OR HILTI HY-200 R OR
EQUIVALENT. ALL STRUCTURAL ADHESIVE SHALL BE INSTALLED PER THE
MANUFACTURER'S REQUIREMENTS. SUBSTITUTIONS SHALL BE SUBMITTED FOR
REVIEW AND APPROVAL WITH APPROPRIATE ICBO EVALUATION REPORTS.
CONCRETE MASONRY UNITS:
1. ALL MASONRY SHALL BE IN ACCORDANCE WITH ACI 530 / TMS 402. REFER TO
ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR NON-STRUCTURAL BRICK
REQUIREMENTS. INDIVIDUAL CMU'S SHALL BE PER ASTM C90 (2650 PSI), GROUT
SHALL BE PER ASTM C476, MORTAR SHALL BE PER ASTM C270.
A. USE OF MASONRY CEMENT IS PROHIBITED.
B. USE OF AIR-ENTRAINING ADMIXTURES IS PROHIBITED.
2. MASONRY MATERIALS SHALL BE AS FOLLOWS:
A. f'm = 2,000 PSI MINIMUM. ALL UNITS SHALL BE NORMAL-WEIGHT BLOCK.
B. GROUT STRENGTH NOT LESS THAN 2,000 PSI.
C. MORTAR TYPE S. (USE TYPE M OR S, OR BETTER FOR PORTIONS
BELOW-GRADE).
4. WHERE NOT OTHERWISE SHOWN, MINIMUM WALL REINFORCEMENT SHALL BE (1)
#4 VERT AT 48" OC MAX. PROVIDE NOT LESS THAN 9-GAUGE HORIZONTAL LADDER-
TYPE REINFORCEMENT AT NOT MORE THAN 16" OC VERTICALLY, LAPPED 8"
MINIMUM. DISCONTINUE HORIZ REINF AT CONTROL JOINT LOCATIONS. REBAR
POSITIONERS SHALL BE USED FOR ALL VERTICAL BARS SUCH THAT A MINIMUM 3"
OF SPACE IS MAINTAINED CLEAR FOR PLACEMENT OF GROUT.
5. ALL BLOCKS SHALL BE LAID IN RUNNING BOND.
6. GROUT ALL BLOCK CORES CONTAINING VERTICAL BARS, HORIZONTAL BOND
BEAMS, AND/OR ANCHOR RODS. IN ADDITION:
-- GROUT SOLID ALL UNITS LOCATED BELOW GRADE AND/OR LOCATED IN CONTACT
WITH SOIL.
-- GROUT POUR HEIGHTS SHALL NOT EXCEED 5'-0" UNLESS CLEAN-OUTS ARE
PROVIDED AND INSPECTED. THE MAXIMUM GROUT POUR HEIGHT WITH CLEANOUTS
SHALL NOT EXCEED 12'-8". STOP GROUT POURS AT 1-1/2" BELOW THE TOP OF THE
CMU COURSE. CONSOLIDATE GROUT WITH VIBRATOR.
7. ALL OPENINGS IN NEW CONCRETE MASONRY WORK REQUIRE A BOND-BEAM
LINTEL PER TYPICAL DETAILS AND PLANS.
A. GALVANIZED LOOSE-ANGLE STEEL LINTELS SHALL BE UTILIZED TO
SUPPORT BRICK VENEER, AND WHERE CUTTING IN NEW OPENINGS IN EXISTING
BRICK AND TILE WALLS.
8. PROVIDE CONTROL JOINTS AS SHOWN ON ARCHITECTURAL AND/OR
STRUCTURAL DRAWINGS. WHERE NOT SHOWN OR OTHERWISE DENOTED,
PROVIDE CONTROL JOINTS AT NOT MORE THAN 25'-0" OC, LOCATED AT OPENINGS,
AND NEAR CORNERS, AS SHOWN ON TYPICAL DETAILS. PROVIDE VERTICAL
REINFORCEMENT ON EACH SIDE OF CONTROL JOINTS.
9. PLACEMENT OF REINFORCEMENT SHALL OCCUR PRIOR TO PLACEMENT OF
GROUT. ALL REINFORCEMENT IN STRUCTURAL AND SHEAR WALLS SHALL BE
INSPECTED PRIOR TO GROUTING, AND ALL MATERIALS AND MATERIAL PLACEMENT
INSPECTED AND TESTED.
10. EXTEND HORIZONTAL REINFORCEMENT IN BOND BEAMS, LINTELS AND SILLS
NOT LESS THAN 2'-0" PAST ENDS OF ALL OPENINGS. REINFORCEMENT IN BOND
BEAMS IN LINTELS SHALL BE CONTINUOUS BARS AND SHALL NOT BE LAP SPLICED
CAST IN PLACE CONCRETE:
1. SUBMIT PROPOSED MIXED DESIGNS OF EACH TYPE FOR REVIEW.
REQUIRED MINIMUM CONCRETE COMPRESSIVE STRENGTHS AT 28 DAYS:
a. FOOTING AND GRADE BEAM CONCRETE..…...4500 PSI (AIR-ENTRAINED)
b. SLAB ON GRADE…..............................................4500 PSI (AIR-ENTRAINED)
2. ALL CONCRETE MIX DESIGNS SHALL HAVE WATER TO CEMENT RATIOS LESS
THAN 0.52 (0.45 FOR MOISTURE SENSITIVE FLOORING), WITH A MAXIMUM 60/40 FINE
TO COARSE AGGREGATE RATIO. CONCRETE MIX DESIGNS THAT DO NOT CONFORM
TO THE ABOVE STANDARD AND/OR CONTAIN WATER REDUCING ADMIXTURES SHALL
BE SUBMITTED WITH APPROPRIATE TEST DATA PER A.C.I.. ALL CONCRETE SHALL BE
IN CONFORMANCE WITH THE A.C.I. 301 STANDARD THAT IS REFERENCED IN THE
BUILDING CODE AT THE TIME OF PERMITTING THE PROJECT..
3. EXTERIOR CONCRETE (FLOOR SLABS, WALLS, ETC) SHALL HAVE 6.5%
(PLUS/MINUS 1.5%) ENTRAINED AIR.
4. CHAMFER ALL EXPOSED CONCRETE EDGES 3/4”.
5. NO ALUMINUM SHALL BE EMBEDDED IN ANY CONCRETE.
6. NO CALCIUM CHLORIDE SHALL BE USED IN CONCRETE
7. THE DESIGN, CONSTRUCTION, AND SAFETY OF ALL FORMWORK IS THE
RESPONSIBILITY OF THE CONTRACTOR
8. ALL CONCRETE IS REINFORCED UNLESS SPECIFICALLY NOTED AS
UNREINFORCED. REINFORCE ALL CONCRETE NOT OTHERWISE SHOWN WITH THE
SAME REINFORCING AS SIMILAR SECTIONS OR AREAS.
9. CONSTRUCTION JOINTS IN GRADE BEAMS, CONTINUOUS FOOTINGS, AND WALLS
THAT DO NOT CHANGE DIRECTION SHALL BE SPACED NO GREATER THAN 60’-0”.
INTERMEDIATE CONTROL JOINTS SHALL BE SPACED AT 25’-0” MAX FOR WALLS.
CONTROL JOINTS IN WALLS SHALL ALSO BE LOCATED 15’-0” FROM CORNERS AND AT
CHANGES IN WALL THICKNESS
10. WHERE FRESH CONCRETE IS DEPOSITED AGAINST HARDENED CONCRETE
(GREATER THAN 8 HRS OLD), CLEAN EXISTING SURFACE OF LAITANCE AND
FOREIGN MATERIAL AND DAMPEN THE EXISTING SURFACE. IF REQUIRED,
ROUGHEN EXISTING CONCRETE TO ¼” AMPLITUDE.
11. SLABS ON GRADE SHALL BE 4” THICK MINIMUM ON 4” OF GRANULAR FILL. REINF
SLAB WITH 6 X 6-W2.1xW2.1 WWR. PLACE REINF IN UPPER 1/3 OF SLAB THICKNESS.
THIS NOTE SHALL BE TYPICAL UNLESS NOTED OTHERWISE
12. SAW CUT JOINTS OR KEYED CONSTRUCTION JOINTS IN SLABS ON GRADE SHALL
BE SPACED TO DIVIDE THE SLAB INTO PANELS NOT TO EXCEED 225 SQUARE FEET.
THE LONGER DIMENSION OF EACH PANEL SHALL NOT EXCEED THE SHORTER
DIMENSIONS BY MORE THAN 40%. JOINTS SHALL BE LOCATED AT COLUMN
CENTERLINES WHERE POSSIBLE. SPACING BETWEEN JOINTS SHALL NOT EXCEED 15
FEET. CONTRACTOR SHALL SUBMIT JOINT LAYOUT TO ARCHITECT FOR APPROVAL.
REFER TO TYPICAL DETAILS.
13. REINFORCEMENT SHALL BE CONTINUOUS AND LAPPED PER TYPICAL DETAIL
(2’ -6” MIN) EXCEPT AS NOTED AND PROVIDE CORNER BARS OF SAME SIZE AND
SPACING.
14. AGGREGATES AND/OR CONCRETE MIXES SHALL BE CERTIFIED TO BE FREE OF
AND ELIMINATE DAMAGE OF CONCRETE DUE TO ALKALI-SILICA REACTION OR
ALKALI-AGGREGATE REACTIONS WHEN EXPOSED TO SOILS AND/OR AN EXTERIOR
ENVIRONMENT.
SUBMITTALS:
1. GENERAL CONTRACTOR TO PROVIDE A SHOP DRAWING SUBMITTAL LOG AND
SUBMITTAL SCHEDULE ITEMIZING ALL PROPOSED SUBMITTALS FOR APPROVAL BY
STRUCTURAL ENGINEER OF RECORD.
2. ALL SHOP DRAWINGS SHALL BE CHECKED BY THE FABRICATOR AND APPROVED
BY THE GENERAL CONTRACTOR PRIOR TO SUBMITTAL TO THE STRUCTURAL
ENGINEER OF RECORD. SHOP DRAWING REVIEW BY ENGINEER IS LIMITED TO
VERIFYING GENERAL CONFORMANCE TO THE CONTRACT DOCUMENTS.
CONTRACTOR IS RESPONSIBLE FOR ANY CHANGES FROM THE CONTRACT
DOCUMENTS, DIMENSIONAL ERRORS, COORDINATION ERRORS, OR OMISSIONS IN
SHOP DRAWINGS. EOR IS NOT RESPONSIBLE FOR ANY DELAYS CAUSED BY THESE
REQUIREMENTS NOT BEING MET.
3. SHOP DRAWINGS SHALL INCLUDE CONNECTIONS AS WELL AS SIZE, SPACING,
AND GRADE OF ALL MEMBERS AND MATERIALS. PLANS AND ANY DETAILING
NECESSARY FOR DETERMINING FIT AND PLACEMENT SHALL ALSO BE INCLUDED.
4. ANY CHANGES TO THE STRUCTURAL DRAWINGS SHALL BE SUBMITTED TO THE
ARCHITECT AND ARE SUBJECT TO REVIEW AND APPROVAL OF THE STRUCTURAL
ENGINEER OF RECORD PRIOR TO RELEASE FOR FABRICATION AND
CONSTRUCTION.
5. DESIGN DRAWINGS, SHOP DRAWINGS, AND CALCULATIONS FOR THE DESIGN
AND FABRICATION OF ITEMS THAT ARE DESIGNED BY THE CONTRACTOR SHALL
BEAR THE SEAL AND SIGNATURE OF AN ENGINEER REGISTERED IN THE
APPROPRIATE STATE AND SHALL BE SUBMITTED TO THE ARCHITECT / ENGINEER
PRIOR TO FABRICATION AND CONSTRUCTION. CALCULATIONS SHALL BE INCLUDED
FOR ALL CONNECTIONS TO THE STRUCTURE, CONSIDERING LOCALIZED EFFECTS
ON STRUCTURAL ELEMENTS INDUCED BY THE CONNECTION LOADS. ITEMS THAT
ARE DESIGNED BY THE CONTRACTOR SHALL BE DESIGNED TO RESIST THE LIVE
LOADS INDICATED IN STRUCTURAL NOTES, DEAD LOAD, SELF WEIGHT, ANY
ADDITIONAL LOADING INDICATED ON PLANS AND DETAILS, SNOW DRIFT, AND A NET
WIND UPLIFT. THESE ITEMS DESIGNED BY THE CONTRACTOR SHALL INCLUDE ANY
RELEVANT TECHNICAL LITERATURE FROM THE MANUFACTURER , SUCH AS ICC-ES
REPORTS DEMONSTRATING CODE COMPLIANCE.
6. FIELD ENGINEERED DETAILS DEVELOPED BY THE CONTRACTOR THAT DIFFER
FROM OR ADD TO THE STRUCTURAL DRAWINGS SHALL BE SUBMITTED TO THE
ARCHITECT AND ARE SUBJECT TO REVIEW AND APPROVAL OF THE STRUCTURAL
ENGINEER OF RECORD PRIOR TO RELEASE FOR FABRICATION AND
CONSTRUCTION.
7. UNLESS DICTATED OTHERWISE BY THE CONTRACT DOCUMENTS, THE ENGINEER
SHALL HAVE A MINIMUM OF 10 WORKING DAYS FROM RECEIPT OF SHOP DRAWINGS
FOR REVIEW AND SHALL HAVE A MINIMUM OF 3 WORKING DAYS FOR RFI
RESPONSES.
8. SEE MATERIAL SPECIFIC SECTIONS IN THE GENERAL NOTES FOR REQUIRED
SHOP DRAWINGS AND CALCULATIONS TO BE SUBMITTED.
9. THE CONTRACTOR SHALL COORDINATE SEISMIC RESTRAINTS AND BRACING OF
ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL EQUIPMENT,
MACHINERY, AND ASSOCIATED PIPING WITH THE STRUCTURE. ANY CONNECTIONS
TO STRUCTURE SHALL CONFORM TO ASCE 7, CHAPTER 13 AND SHALL BE DESIGNED
BY AN ENGINEER REGISTERED IN THE APPROPRIATE STATE AND SHALL BE
SUBMITTED TO THE ARCHITECT PRIOR TO FABRICATION.
EARTHWORK AND FOUNDATIONS:
1. PERIMETER AND EXTERIOR FOOTINGS SHALL BEAR AT A MINIMUM OF 3’-0”
BELOW ADJACENT GRADE.
2. ALL FOOTINGS SHALL BEAR ON FIRM NATIVE MATERIALS, COMPACTED OR
ENGINEERED FILL CAPABLE OF SUPPORTING AN ALLOWABLE BEARING PRESSURE
OF 1,500 PSF PER THE IBC. DEEPEN FOOTINGS, AND REMOVE AND REPLACE
UNACCEPTABLE SOILS WITH ENGINEERED FILL AS REQUIRED TO PROVIDE THIS
MINIMUM DEPTH AND SUITABLE BEARING.
3. UNDERCUT THE PAD TO A DEPTH OF 24-INCHES BELOW BOTTOM OF FLOOR SLAB
ELEVATION AND REPLACE WITH LOW-VOLUME-CHANGE MATERIALS PER THE
GEOTECHNICAL REPORT.
3/4" = 1'-0"
SPLICE & DEVELOPMENT SCHEDULE1
3/4" = 1'-0"
MASONRY BOND BEAM2
1 1/2" = 1'-0"
EQUIP PAD @ NEW SLAB ON GRADE3
3/4" = 1'-0"
REINF @ SLAB PENETRATIONS4
3/4" = 1'-0"
CONC WALL CORNERS5
1 1/2" = 1'-0"
LOOSE LINTEL SCHEDULE7
4. FILL PLACEMENT, COMPACTION, AND SOIL BEARING TESTS SHALL BE
PERFORMED BY A GEOTECHNICAL ENGINEER PRIOR TO INSTALLING FOOTINGS TO
ENSURE DESIGN ALLOWABLE BEARING VALUES AND SLAB SUBGRADE
REQUIREMENTS ARE SATISFIED. IF ACTUAL SITE CONDITIONS DO NOT SATISFY
THESE REQUIREMENTS, COORDINATE ADJUSTMENTS WITH ARCHITECT/ENGINEER/
GEOTECHNICAL ENGINEER
5. SURFACE WATER SHALL NOT BE ALLOWED TO STAND ADJACENT TO OR DRAIN
TOWARDS THE FOUNDATION AND SLAB SUBGRADES UNDER ANY CIRCUMSTANCES.
PAVEMENTS OR GRADED SOILS AT THE PERIMETER OF THE BUILDING, EXCEPT AS
REQUIRED AT EXITS OR AS NOTED, SHALL BE SLOPED AWAY AT 5% OR 6” MIN FOR
THE FIRST TEN FEET AND AS REQUIRED TO PROVIDE POSITIVE DRAINAGE.
6. FOOTINGS MAY BE POURED TO NEAT LINES OF EXCAVATIONS PROVIDING
VERTICAL LINES OF EXCAVATIONS CAN BE MAINTAINED DURING CONCRETE
PLACEMENT.
7. DO NOT PLACE CONCRETE UNLESS FOOTING EXCAVATIONS ARE FREE OF ALL
WATER, FROST, ICE AND LOOSE SOIL. CONCRETE SHALL BE PLACED AS SOON AS
POSSIBLE AFTER EXCAVATION SO THAT EXCESSIVE DRYING OF BEARING
MATERIALS DOES NOT OCCUR. BEARING MATERIAL SHALL BE INSPECTED BY A
QUALIFIED INDEPENDENT TESTING LAB PRIOR TO PLACEMENT OF CONCRETE.
3/4" = 1'-0"
CONCEPTUAL EQUIPMENT BRACING AND ANCHORAGE DETAILS6
mmasilionis Snapshot mmasilionis Typewritten Text 03/15/2024
PLAN NOTES:
EXISTING 5"X8" PAN JOIST SLAB W/ 2" SLAB
12" CMU REINF W/ (2) #5 @ 16" OC, DWLS TO MATCH. GROUT ALL CELLS SOLID
4" THICK SOG MINIMUM ON 4” OF GRANULAR FILL. REINF SLAB WITH 6 X 6-
W2.1xW2.1 WWR
48" x 16" TRENCH FTG REINF W/ (4) #5 TOP & BOT & #6 TRANSVERSE @ 12" OC
TOP & BOT
MECHANICAL SLAB RE:3/SE001, RE:MEP FOR LOCATION OF PADS
16" DEEP CMU LINTEL REINF W/ (2) #5 BARS
@ JAMBS PROVIDE (2) #5 IN THE FIRST TWO CELLS ON EACH SIDE OF THE
OPENING
PROVIDE (3) 5/8" EXPANSION BOLTS FOR THE ATTACHMENT OF THE DOOR TO
THE CMU
EXPANSION JOINT, RE: ARCH
SHEET NOTES:
A. SEE ARCHITECTURAL DRAWING FOR DETAILS & DIMENSIONS NOT SHOWN.
A. REFERENCE SHEET S001 FOR STRUCTURAL GENERAL NOTES AND TYPICAL STRUCTURAL
DETAILS. REVIEW NOTES & DETAILS FOR APPLICABILITY.
C. FINISH MEP SLAB ELEVATION = 100'-0" UNO.
D. THE BOTTOM OF ALL EXTERIOR FOOTING SHALL BE 3'-0" MIN. BELOW GRADE (UNLESS
NOTED OTHERWISE), DEEPEN FOOTINGS AS REQUIRED. GRADE IS GENERALLY 4" BELOW
FINISH FLOOR ELEVATION (COORDINATE WITH CIVIL)
2 3 41
B
C
D
A
EXISTING 10"X16" CONC BM TO REMAIN
F V
/2
F V
9'
F V
/2
FV
11' - 1 1/2"
FV
10' - 8"
FV
15' - 0"
EXISTING
14"X14" COL
TO REMAIN
EXISTING
14"X14" COL
TO REMAIN
EXISTING
14"X14" COL
TO REMAIN
EXISTING
14"X14" COL
TO REMAIN
EXISTING
12"X14" COL
TO REMAIN
EXISTING
12"X14" COL
TO REMAIN
EXISTING
14"X16" COL
TO REMAIN
EXISTING
14"X16" COL
TO REMAIN
EXISTING
14"X14" COL
EXISTING
14"X14" COL
TO REMAIN
EXISTING 10"X16" CONC BM TO REMAIN
EXISTING 10"X16" CONC BM TO REMAIN
EXISTING 10"X16" CONC BM TO REMAINEXISTING 10"X16" CONC BM TO REMAINEXISTING 10"X16" CONC BM TO REMAIN
2 4
2 4 4 2
SE101
26' - 8 1/16"
SE101
SE101
7 8
3' - 11 1/4"
5/
1/
L4
S
LO
P E
P E
R A
R C
H
SE101
2 3
B
C
D
A
T O
M E
L
'-0
M
A X
IM
U
M
DETAIL NOTES:
CMU WALL, RE: PLAN
FACE BRICK, RE: ARCH
SOG RE: PLAN
TRENCH FTG, RE: PLAN
BOND BM W/ (2) #5 CONT,
PROVIDE A BOND BM EVERY
4'-0"
PRECAST CAP RE: ARCH
PROVIDE FLASHING BETWEEN
CAP AND CMU
#4 DWLS@ 4'-0" OC
#4 CONT
4" CMU BLOCK, BEHIND CMU
GROUT SOLID
BEARING SURFACE RE:
GENERAL NOTES FOR
COMPACTION AND MATERIAL
REQUIRMENTS
FLASHING, RE: ARCH
4" SCH 40 PIPE THROUGH
DRAINS @ 32" OC, SET @
GRADE ELEVATION, GROUT
SOLID AROUND PIPE INTO
GROUTED CELLS. AVOID REINF.
T/ SOG
RE:CIVIL
1' -0
2'-6"
T/ FTG
-2' - 0"
R E
: P
LA
N
RE: PLAN
NOTES:
REFER TO VA COR FOR SPLIT
FACE CMU BLOCKS OR
COLORED BLOCKS AND
MORTAR TO MATCH VA CAMPUS
DETAIL NOTES:
WALL OPENING WHERE EITHER DIMENSION IS 4'-0"
OR MORE, RE: TYPICAL MASONRY LINTEL
SCHEDULE
DOOR OPENING RE: PLAN
WALL OPENING WITH 2'-0" OR MORE BUT LESS
THAN 4'-0" IN EITHER DIRECTION RE: TYPICAL
MASONRY LINTEL SCHEDULE
MASONRY CONTROL JOINT
END OF WALL
TOP OF WALL OR FLOOR LINE
BAR RE: PLAN FOR SIZE
LINTEL PER PLAN
SHEAR DWL RE: PLAN
HORIZ BOND BEAM, RE: STRUCT GENERAL NOTES
NOTES:
A. SIZE OF VERT & HORIZ BARS TO MATCH WALL VERT
& HORIZ BARS MIN #4 BARS, RE: GENERAL NOTES FOR
TYPICAL WALL REINFORCING
B. BOND BEAMS AT ROOF CEILING & FLOOR JOIST
BEARING SHALL BE CONT THRU CONTROL JOINTS
24" MIN
DETAIL NOTES:
12" SOG REINF W/ #5 @ 14"
OC TOP & BOT, EA WAY
Veterans Health
Administration
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
FULLY SPRINKLERED
STAMP:
Drawing Number
Building Number th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t 0 o n e q u a rt e r in c h o n e fo o t 0 o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
VA FORM 08-6231
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 E. ST. LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE., SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
STRUCTURAL ENGINEER
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST., STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS LLC
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
FIRE PROTECTION ENGRINEER
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
/1
/2
:4
:3
P
M
OF
SPUR #: 2207
BID DOCUMENTS
No. REVISION DESCRIPTION DATE
596-22-700
SE101
BUILDING 17 - ENLARGED PLANS
MDMPWS
EHRM INFRASTRUCTURE
UPGRADES, LEXINGTON, KY
03/15/2024
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
N
1/4" = 1'-0"
B17 - GROUND LEVEL - 22-17- FLOOR PLAN2
N
1" = 20'-0"
B17 - GROUND LEVEL1
3/4" = 1'-0" 2/ SE101
CMU SCREEN WALL3
1/2" = 1'-0"
NON-LOAD BEARING MASONRY WALL REINF4
3/4" = 1'-0"
EQUIPMENT PAD ON GRADE5
mmasilionis Snapshot mmasilionis
SE102
FV
12' - 1 7/8" +/-
F V
3/
F V
1/ 8"
FV
28' - 0 9/16" +/-
PLAN NOTES:
12" CMU REINF W/ (2) #5 @ 16" OC, DWLS TO MATCH. GROUT
ALL CELLS SOLID
4" THICK SOG MINIMUM ON 4” OF GRANULAR FILL. REINF
SLAB WITH 6 X 6-W2.1xW2.1 WWR
48" x 16" TRENCH FTG REINF W/ (4) #5 TOP & BOT & #6
TRANSVERSE @ 12" OC TOP & BOT
MECHANICAL SLAB RE:3/SE001, RE:MEP FOR LOCATION OF
PADS
16" DEEP CMU LINTEL REINF W/ (2) #5 BARS
@ JAMBS PROVIDE (2) #5 IN THE FIRST TWO CELLS ON
EACH SIDE OF THE OPENING
PROVIDE (3) 5/8" EXPANSION BOLTS FOR THE ATTACHMENT
OF THE DOOR TO THE CMU
DRAIN PER ARCH
SE101
SE101
SE101
SE101
SHEET NOTES:
A. SEE ARCHITECTURAL DRAWING FOR DETAILS & DIMENSIONS NOT SHOWN.
A. REFERENCE SHEET S001 FOR STRUCTURAL GENERAL NOTES AND TYPICAL STRUCTURAL
DETAILS. REVIEW NOTES & DETAILS FOR APPLICABILITY.
C. FINISH MEP SLAB ELEVATION = 100'-0" UNO.
D. THE BOTTOM OF ALL EXTERIOR FOOTING SHALL BE 3'-0" MIN. BELOW GRADE (UNLESS
NOTED OTHERWISE), DEEPEN FOOTINGS AS REQUIRED. GRADE IS GENERALLY 4" BELOW
FINISH FLOOR ELEVATION (COORDINATE WITH CIVIL)
Veterans Health
Administration
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
FULLY SPRINKLERED
STAMP:
Drawing Number
Building Number th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t 0 o n e q u a rt e r in c h o n e fo o t 0 o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
VA FORM 08-6231
ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024
ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025
CIVIL ENGINEER
OLSSON
550 E. ST. LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENG.
SPUR DESIGN
2519 MADISON AVE., SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
STRUCTURAL ENGINEER
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST., STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS LLC
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, #1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
FIRE PROTECTION ENGRINEER
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 856-2965
/1
/2
:4
:3
P
M
OF
SPUR #: 2207
BID DOCUMENTS
No. REVISION DESCRIPTION DATE
596-22-700
SE102
BUILDING 25 - ENLARGED PLANS
AuthorChecker
EHRM INFRASTRUCTURE
UPGRADES, LEXINGTON, KY
03/15/2024
LEXINGTON VA HEALTH CARE
2250 LEESTOWN RD
LEXINGTON, KY 40511
N
1" = 20'-0"
B25 - GROUND LEVEL1
N
1/4" = 1'-0"
OVERALL BASEMENT PLAN Copy 1 - Callout 12 mmasilionis Snapshot mmasilionis
| Sheets |
| SE001 - STRUCTURAL GENERAL NOTES AND DETAILS |
| SE101 - BUILDING 17 - ENLARGED PLANS |
| SE102 - BUILDING 25 - ENLARGED PLANS |