0004 - 596-22-700 Drawings 01_Environmental Revisions.pdf

PDF 2 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction Lexington - Leestown, KY 596-22-700
Solicitation number
36C77625B0040
Issued by

About this file

These are Bid Documents for the Veterans Health Administration's Environmental Hazards Infrastructure Upgrades project at the Lexington VA Health Care facility in Lexington, Kentucky. The documents detail environmental remediation work across multiple floors of Buildings 1 and 25, specifically focusing on asbestos and lead-based material abatement. Key scope elements include removing asbestos-containing materials such as pipe insulation, floor tiles, ceiling tiles, and mastic, as well as performing lead-based paint spot removal, all within carefully controlled negative pressure enclosures. The project involves manual removal methods, disposal of hazardous materials, and coordinating work to minimize disruption to VA healthcare operations. The bid documents are dated 03/15/2024, prepared by SPUR Design, LLC, and are fully sprinklered construction documents intended for bidding purposes.

View the file

Other files

File Type Posted
36C77625B0040 0006.pdf PDF
0006 - 596-22-700 DBA Wages - Fayette County - 08-22-2025.pdf PDF
36C77625B0040 0005.pdf PDF
0004 - 596-22-700 Spec Section 01 00 00 Revisions.pdf PDF
0004 - 596-22-700 Spec Section 00 01 10 Revisions.pdf PDF
36C77625B0040 0004.pdf PDF
0004 - 596-22-700 Spec Section 08 11 13 Revisions.pdf PDF
0004 - 596-22-700 Spec Section 08 71 00 Revisions.pdf PDF
0004 - 596-22-700 TR Photos - Question 58.pdf PDF
0004 - 596-22-700 Responses to Tech Questions - 8-19-25.pdf PDF
0004 - 596-22-700 Drawings 00_General Revisions.pdf PDF
0004 - 596-22-700 Spec Section 23 07 11.pdf PDF
0004 - 596-22-700 Lexington TR Notes-MASTER.pdf PDF
0004 - 596-22-700 Spec Section 02 82 13.13 Revisions.pdf PDF
0004 - 596-22-700 Drawings 02_Civil Revisions.pdf PDF
36C77625B0040 0003.pdf PDF
0003 - 596-22-700 Responses to Tech Questions - 8-12-25.pdf PDF
0003 - 596-22-700 DBA Wages - Fayette County - 08-08-2025.pdf PDF
0002 - 596-22-700 DBA Wages - Fayette County - 07-18-2025.pdf PDF
36C77625B0040 0002.pdf PDF
0001 - 596-22-700 Site Visit Sign-in Sheet - 7-8-25.pdf PDF
36C77625B0040 0001.pdf PDF
18 - 596-22-700 DBA Wages - Fayette County - 06-06-2025.pdf PDF
17 - 596-22-700 Brand Name Justification.pdf PDF
IFB 36C77625B0040 - 6-25-25.pdf PDF
16 - 596-22-700 PCRA.pdf PDF
13 - 596-22-700 Drawings 09_Security.pdf PDF
14 - 596-22-700 ICRA II.pdf PDF
05 - 596-22-700 Drawings 01_Environmental.pdf PDF
02 - 596-22-700 Specs 2.pdf PDF
19 - 596-22-700 VAAR 852.219-75 LOS - Construction.docx DOCX document
15 - 596-22-700 ICRA III.pdf PDF
09 - 596-22-700 Drawings 05_Fire Protection.pdf PDF
10 - 596-22-700 Drawings 06_Mechanical.pdf PDF
07 - 596-22-700 Drawings 03_Structural.pdf PDF
06 - 596-22-700 Drawings 02_Civil.pdf PDF
12 - 596-22-700 Drawings 08_Telecom.pdf PDF
01 - 596-22-700 Specs 1.pdf PDF
03 - 596-22-700 Spec Section 01 31 00.01.pdf PDF
04 - 596-22-700 Drawings 00_General.pdf PDF
11 - 596-22-700 Drawings 07_Electrical.pdf PDF
08 - 596-22-700 Drawings 04_Architectural.pdf PDF
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

FULLY SPRINKLERED

1 2 � 4 � 6 � 8 �

1 2 � 4 � 6 � 8 �

STAMP:

Drawing Number

Building Number

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

/2

2/

:2 3:

A

M

BUILDING 1 - GROUND FLOOR -

ENVIRONMENTAL HAZARDS

CD 06 258JR

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511 HA010

SPUR #: 2207.00

No. REVISION DESCRIPTION DATE

NOT TO SCALE

BUILDING 1 - GROUND FLOOR

HAZARDOUS MATERIALS KEYNOTES

AN ASBESTOS-CONTAINING GRAY MASTIC EXISTS ON FIBERGLASS LINES AND FITTINGS THROUGHOUT BUILDING. UNLESS OTHERWISE SPECIFIED AVOID DISTURBANCE. ANY WORK IMPACTING THIS MATERIAL MUST BE PERFORMED BY LICENSED ASBESTOS ABATEMENT CONTRACTORS.

AN ASBESTOS-CONTAINING WHITE SINK SOUNDPROOFING MATERIAL IS KNOWN TO EXIST WITHIN BUILDING 1. AVOID ANY WORK LIKELY TO IMPACT SINKS COVERED IN THIS

WHITE SINK SOUNDPROOFING MATERIAL. SINKS LOCATED THROUGHOUT

AREA OF KNOWN AND/OR PRESUMED ASBESTOS CONTAINING BLACK COATING ON INSIDE OF EXTERIOR WALL, AND WATERPROOFING BELOW GRADE. WITHIN A NPE (NEGATIVE PRESSURE ENCLOSURE) , USING MANUAL MEANS, PROVIDE WALL PENETRATION(S). REFERENCE MECHANICAL, ELECTRICAL, AND TELECOMMUNICATION DRAWING SETS FOR DETAILS. NOTE - TELECOMMUNICATION PATHWAYS TO BE LOCATED WITHIN NEW DUCT BANKS HAVE A SLIGHTLY DIFFERENT ENTRY/EXIT POINT THAN THOSE INDICATED WITHIN THE CIVIL DRAWING SET. COORDINATE EXACT LOCATIONS AND QUANTITIES WITH COR, GC (GENERAL CONTRACTOR), AND OTHER IMPACTED PROFESSIONS AND

TRADES. ESTIMATED 3 SF EACH AT 3 LOCATIONS

WITHIN AN NPE, USING MANUAL MEANS, REMOVE, TO THE EXTENTS INDICATED BY ARCH (ARCHITECTURAL DRAWING SET), ACM (ASBESTOS-CONTAINING MATERIAL) 12" TAN W/ WHITE/GRAY/BROWN FLECK AND UNDERLYING ACM FLOOR TILE AND ACM BLACK MASTIC, 120 SF

WITHIN AN NPE, USING MANUAL AND GLOVEBAG METHODS, REMOVE, TO THE EXTENTS INDICATED BY ARCH. NON-ACM, LEAD BASED PAINTED PLASTER CEILING AND DAMAGED ACM PIPE/FITTING INSULATION ABOVE. REMOVE PIPE/FITTING INSULATION AT LEAST 3 LF INTO SPACE OVER REMAINING PLASTER TO ALLOW FOR BUFFER ZONE FOR NEW WALL CONSTRUCTION. HEPA VACUUM REMAINING ACM CONTAMINATED PLASTER CEILING AND ENCAPSULATE. .COORDINATE DATA AND UTILITY SHUTDOWN WITH COR, GC, AND OTHER IMPACTED PROFESSIONS AND TRADES, 120 SF OF PLASTER AND ESTIMATED 25 LF OF PIPE/FITTING INSULATION

LBP (LEAD-BASED PAINT) ON PLASTER CEILINGS. DO NOT DISTURB. ANY WORK LIKELY TO DISTURB THESE MATERIALS MUST BE PERFORMED BY A LICENSED ABATEMENT

CONTRACTOR. THROUGHOUT

LBP ON METAL STEAM LINES. DO NOT DISTURB. ANY WORK LIKELY TO DISTURB THESE MATERIALS MUST BE PERFORMED BY A LICENSED ABATEMENT CONTRACTOR.

THROUGHOUT

HAZARDOUS MATERIALS ALONG LIKELY ROUTING PATHWAYS ABOVE CEILING TILE. LEAD BASED PAINT ON CONCRETE &/OR PLASTER CEILING. WITHIN A NEGATIVE PRESSURE ENCLOSURE, USING CHEMICAL AND MANUAL METHODS, PERFORM SPOT REMOVAL OF LEAD BASED PAINT AT ANCHOR POINTS. 1 SF EACH LOCATION AT APPROXIMATELY 50 LOCATIONS. COORDINATE EXACT LOCATIONS AND QUANTITIES WITH GC AND OTHER AFFECTED TRADES.

USING GLOVEBAG METHODS WITHIN A NEGATIVE PRESSURE ENCLOSURE, REMOVE OUT OF CHASE FIBERGLASS PIPE INSULATION AND RELATED FITTINGS. PIPE INSUALTION SYSTEMS HAVE INTERMITTENT APPLIED ASBESTOS GRAY MASTIC IN THE APPROXIMATE FOLLOWING QUANTITIES; 25 LF OF PIPE INSULATION AND FITTINGS IN ROOM.

REFERENCE DRAWING M-401 FOR LOCATIONS OF PIPE TO BE REMOVED

A1

A2

A3

A4

A5

L1

L2

L3

3131A

A3

PARTITION LEGEND

1 HOUR FIRE RATED

2 HOUR FIRE RATED

3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

EXISTING WALL TO REMAIN

NEW NON-RATED WALLS

EXISTING 1 HOUR FIRE

EXISTING 2 HOUR FIRE

NOTE: NOT ALL SYMBOLS MAY BE USED

N

BID DOCUMENTS

1 ADDENDUM 1 7/29/2025

A6

A2 L2L1 L3A1

A4 A5

A3 A6

VISUAL KEY

LIMITS OF NEGATIVE PRESSURE ENCLOSURE(S) WITH APPROPRIATE

THREE STAGE DECON, TWO STAGE LOADOUT, AND NEGATIVE AIR

MACHINES WITH THREE STAGE HEPA FILTRATION ALL IN ACCORDANCE

WITH SPECIFICATIONS. TUBING SHALL BE VENTED TO THE BUILDING

EXTERIOR. EXHAUST TUBING AND OUTFLOW SHALL BE LOCATED SO AS

TO AVOID DISRUPTION TO VA OPERATIONS. COORDINATE EXHAUST

LOCATIONS WITH COR. REFER TO PHASING SHEETS FOR SPECIFIC

PROJECT-WIDE PHASING.

MAINTAIN A MINIMUM OF ½ THE WIDTH OF THE HALLWAYS FOR FREE

ACCESS TO MOVE PATIENTS. COORDINATE WITH THE VA-COR TO ALLOW

FOR ADEQUATE PASSAGE OF PATIENTS WHERE ASPECTS OF THE NPE

MAY RESTRICT PATIENT MOVEMENTS ON ROLLING TRANSPORTS.

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

FULLY SPRINKLERED

1 2 � 4 � 6 � 8 �

1 2 � 4 � 6 � 8 �

STAMP:

Drawing Number

Building Number

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

/2

2/

:2 3:

A

M

BUILDING 1 - FIRST FLOOR -

ENVIRONMENTAL HAZARDS

CD 07 258JR

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511 HA011

SPUR #: 2207.00

No. REVISION DESCRIPTION DATE

NOT TO SCALE

BUILDING 1 - FIRST FLOOR

HAZARDOUS MATERIALS KEYNOTES

AN ASBESTOS-CONTAINING GRAY MASTIC EXISTS ON FIBERGLASS LINES AND FITTINGS THROUGHOUT BUILDING. UNLESS OTHERWISE SPECIFIED AVOID DISTURBANCE. ANY WORK IMPACTING THIS MATERIAL MUST BE PERFORMED BY LICENSED ASBESTOS ABATEMENT CONTRACTORS.

AN ASBESTOS-CONTAINING WHITE SINK SOUNDPROOFING MATERIAL IS KNOWN TO EXIST WITHIN BUILDING 1. AVOID ANY WORK LIKELY TO IMPACT SINKS COVERED IN THIS

WHITE SINK SOUNDPROOFING MATERIAL.

LBP ON PLASTER CEILINGS. DO NOT DISTURB. ANY WORK LIKELY TO DISTURB THESE MATERIALS MUST BE PERFORMED BY A LICENSED ABATEMENT CONTRACTOR.

LBP ON METAL STEAM LINES. DO NOT DISTURB. ANY WORK LIKELY TO DISTURB THESE MATERIALS MUST BE PERFORMED BY A LICENSED ABATEMENT CONTRACTOR.

HAZARDOUS MATERIALS ALONG LIKELY ROUTING PATHWAYS ABOVE CEILING TILE. LEAD BASED PAINT ON CONCRETE &/OR PLASTER CEILING. WITHIN A NEGATIVE PRESSURE ENCLOSURE, USING CHEMICAL AND MANUAL METHODS, PERFORM SPOT REMOVAL OF LEAD BASED PAINT AT ANCHOR POINTS. 1 SF EACH LOCATION AT APPROXIMATELY 50 LOCATIONS. COORDINATE EXACT LOCATIONS AND QUANTITIES WITH GC AND OTHER AFFECTED TRADES.

USING GLOVEBAG METHODS WITHIN A NEGATIVE PRESSURE ENCLOSURE, REMOVE OUT OF CHASE FIBERGLASS PIPE INSULATION AND RELATED FITTINGS. PIPE INSUALTION SYSTEMS HAVE INTERMITTENT APPLIED ASBESTOS GRAY MASTIC IN THE APPROXIMATE FOLLOWING QUANTITIES; 55 LF OF PIPE INSULATION AND FITTINGS IN ROOM AND 12 LF OF PIPE INSULATION RELATED TO DEMOLITION OF CFU. REFERENCE DRAWING M-401 FOR LOCATIONS OF PIPE TO BE REMOVED

A1

A2

L1

L2

L3

147A-1

PARTITION LEGEND

1 HOUR FIRE RATED

2 HOUR FIRE RATED

3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

EXISTING WALL TO REMAIN

NEW NON-RATED WALLS

EXISTING 1 HOUR FIRE

EXISTING 2 HOUR FIRE

NOTE: NOT ALL SYMBOLS MAY BE USED

A2 L2L1 L3A1

BID DOCUMENTS

1 ADDENDUM 1 7/29/2025

A3

A3

VISUAL KEY

LIMITS OF NEGATIVE PRESSURE ENCLOSURE(S) WITH APPROPRIATE

THREE STAGE DECON, TWO STAGE LOADOUT, AND NEGATIVE AIR

MACHINES WITH THREE STAGE HEPA FILTRATION ALL IN ACCORDANCE

WITH SPECIFICATIONS. TUBING SHALL BE VENTED TO THE BUILDING

EXTERIOR. EXHAUST TUBING AND OUTFLOW SHALL BE LOCATED SO AS

TO AVOID DISRUPTION TO VA OPERATIONS. COORDINATE EXHAUST

LOCATIONS WITH COR. REFER TO PHASING SHEETS FOR SPECIFIC

PROJECT-WIDE PHASING.

MAINTAIN A MINIMUM OF ½ THE WIDTH OF THE HALLWAYS FOR FREE

ACCESS TO MOVE PATIENTS. COORDINATE WITH THE VA-COR TO ALLOW

FOR ADEQUATE PASSAGE OF PATIENTS WHERE ASPECTS OF THE NPE

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

FULLY SPRINKLERED

1 2 � 4 � 6 � 8 �

1 2 � 4 � 6 � 8 �

STAMP:

Drawing Number

Building Number

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

/2

2/

:2 3:

A

M

BUILDING 1 - SECOND FLOOR -

ENVIRONMENTAL HAZARDS

CD 08 258JR

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511 HA012

SPUR #: 2207.00

No. REVISION DESCRIPTION DATE

NOT TO SCALE

BUILDING 1 - SECOND FLOOR

HAZARDOUS MATERIALS KEYNOTES

AN ASBESTOS-CONTAINING GRAY MASTIC EXISTS ON FIBERGLASS LINES AND FITTINGS THROUGHOUT BUILDING. UNLESS OTHERWISE SPECIFIED AVOID DISTURBANCE. ANY WORK IMPACTING THIS MATERIAL MUST BE PERFORMED BY LICENSED ASBESTOS ABATEMENT CONTRACTORS.

AN ASBESTOS-CONTAINING WHITE SINK SOUNDPROOFING MATERIAL IS KNOWN TO EXIST WITHIN BUILDING 1. AVOID ANY WORK LIKELY TO IMPACT SINKS COVERED IN THIS

WHITE SINK SOUNDPROOFING MATERIAL.

WITHIN A NPE, USING MANUAL MEANS, REMOVE NON-ACM 12" CREAM W/ TAN FLECK AND UNDERLYING ACM BLACK MASTIC, 94 SF

LBP ON PLASTER CEILINGS. DO NOT DISTURB.ANY WORK LIKELY TO DISTURB THESE MATERIALS MUST BE PERFORMED BY A LICENSED ABATEMENT CONTRACTOR.

LBP ON METAL STEAM LINES. DO NOT DISTURB.ANY WORK LIKELY TO DISTURB THESE MATERIALS MUST BE PERFORMED BY A LICENSED ABATEMENT CONTRACTOR.

HAZARDOUS MATERIALS ALONG LIKELY ROUTING PATHWAYS ABOVE CEILING TILE. LEAD BASED PAINT ON CONCRETE &/OR PLASTER CEILING. WITHIN A NEGATIVE PRESSURE ENCLOSURE, USING CHEMICAL AND MANUAL METHODS, PERFORM SPOT REMOVAL OF LEAD BASED PAINT AT ANCHOR POINTS. 1 SF EACH LOCATION AT APPROXIMATELY 50 LOCATIONS. COORDINATE EXACT LOCATIONS AND QUANTITIES WITH GC AND OTHER AFFECTED TRADES.

USING GLOVEBAG METHODS WITHIN A NEGATIVE PRESSURE ENCLOSURE, REMOVE OUT OF CHASE FIBERGLASS PIPE INSULATION AND RELATED FITTINGS. PIPE INSUALTION SYSTEMS HAVE INTERMITTENT APPLIED ASBESTOS GRAY MASTIC IN THE APPROXIMATE FOLLOWING QUANTITIES; 46 LF OF PIPE INSULATION AND FITTINGS IN ROOM AND 12 LF OF PIPE INSULATION RELATED TO DEMOLITION OF CFU. REFERENCE DRAWING M-401 FOR LOCATIONS OF PIPE TO BE REMOVED

A1

A2

A3

L1

L2

L3

229-1

PARTITION LEGEND

1 HOUR FIRE RATED

2 HOUR FIRE RATED

3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

EXISTING WALL TO REMAIN

NEW NON-RATED WALLS

EXISTING 1 HOUR FIRE

EXISTING 2 HOUR FIRE

NOTE: NOT ALL SYMBOLS MAY BE USED

A2 L2L1 L3A1

BID DOCUMENTS

A3

1 ADDENDUM 1 7/29/2025

A4

A4

VISUAL KEY

LIMITS OF NEGATIVE PRESSURE ENCLOSURE(S) WITH APPROPRIATE

THREE STAGE DECON, TWO STAGE LOADOUT, AND NEGATIVE AIR

MACHINES WITH THREE STAGE HEPA FILTRATION ALL IN ACCORDANCE

WITH SPECIFICATIONS. TUBING SHALL BE VENTED TO THE BUILDING

EXTERIOR. EXHAUST TUBING AND OUTFLOW SHALL BE LOCATED SO AS

TO AVOID DISRUPTION TO VA OPERATIONS. COORDINATE EXHAUST

LOCATIONS WITH COR. REFER TO PHASING SHEETS FOR SPECIFIC

PROJECT-WIDE PHASING.

MAINTAIN A MINIMUM OF ½ THE WIDTH OF THE HALLWAYS FOR FREE

ACCESS TO MOVE PATIENTS. COORDINATE WITH THE VA-COR TO ALLOW

FOR ADEQUATE PASSAGE OF PATIENTS WHERE ASPECTS OF THE NPE

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

FULLY SPRINKLERED

1 2 � 4 � 6 � 8 �

1 2 � 4 � 6 � 8 �

STAMP:

Drawing Number

Building Number

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

/2

2/

:2 3:

A

M

BUILDING 1 - THIRD FLOOR -

ENVIRONMENTAL HAZARDS

CD 09 258JR

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511 HA013

SPUR #: 2207.00

No. REVISION DESCRIPTION DATE

NOT TO SCALE

BUILDING 1 - THIRD FLOOR

HAZARDOUS MATERIALS KEYNOTES

AN ASBESTOS-CONTAINING GRAY MASTIC EXISTS ON FIBERGLASS LINES AND FITTINGS THROUGHOUT BUILDING. UNLESS OTHERWISE SPECIFIED AVOID DISTURBANCE. ANY WORK IMPACTING THIS MATERIAL MUST BE PERFORMED BY LICENSED ASBESTOS ABATEMENT CONTRACTORS.

AN ASBESTOS-CONTAINING WHITE SINK SOUNDPROOFING MATERIAL IS KNOWN TO EXIST WITHIN BUILDING 1. AVOID ANY WORK LIKELY TO IMPACT SINKS COVERED IN THIS WHITE SINK

SOUNDPROOFING MATERIAL.

WITHIN A NPE, USING MM's, REMOVE NON-ACM 12" BEIGE WITH LONG BROWN STREAK, NON-ACM MASTIC, LEVELING COMPOUND, AND UNDERLYING RESIDUAL ACM BLACK MASTIC. ~87 SF

LBP ON PLASTER CEILINGS. DO NOT DISTURB.ANY WORK LIKELY TO DISTURB THESE MATERIALS MUST BE PERFORMED BY A LICENSED ABATEMENT CONTRACTOR.

LBP ON METAL STEAM LINES. DO NOT DISTURB.ANY WORK LIKELY TO DISTURB THESE MATERIALS MUST BE PERFORMED BY A LICENSED ABATEMENT CONTRACTOR.

HAZARDOUS MATERIALS ALONG LIKELY ROUTING PATHWAYS ABOVE CEILING TILE. LEAD BASED PAINT ON CONCRETE &/OR PLASTER CEILING. WITHIN A NEGATIVE PRESSURE ENCLOSURE, USING CHEMICAL AND MANUAL METHODS, PERFORM SPOT REMOVAL OF LEAD BASED PAINT AT ANCHOR POINTS. 1 SF EACH LOCATION AT APPROXIMATELY 50 LOCATIONS.

COORDINATE EXACT LOCATIONS AND QUANTITIES WITH GC AND OTHER AFFECTED TRADES.

USING GLOVEBAG METHODS WITHIN A NEGATIVE PRESSURE ENCLOSURE, REMOVE OUT OF CHASE FIBERGLASS PIPE INSULATION AND RELATED FITTINGS. PIPE INSUALTION SYSTEMS HAVE INTERMITTENT APPLIED ASBESTOS GRAY MASTIC IN THE APPROXIMATE FOLLOWING QUANTITIES; 26 LF OF PIPE INSULATION AND FITTINGS IN ROOM AND 12 LF OF PIPE INSULATION RELATED TO DEMOLITION OF CFU. REFERENCE DRAWING M-401 FOR LOCATIONS OF PIPE TO BE REMOVED

A1

A2

A3

L1

L2

L3

331-1

PARTITION LEGEND

1 HOUR FIRE RATED

2 HOUR FIRE RATED

3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

EXISTING WALL TO REMAIN

NEW NON-RATED WALLS

EXISTING 1 HOUR FIRE

EXISTING 2 HOUR FIRE

NOTE: NOT ALL SYMBOLS MAY BE USED

BID DOCUMENTS

A4

1 ADDENDUM 1 7/29/2025

A4

A3

A2 L2L1 L3A1

VISUAL KEY

LIMITS OF NEGATIVE PRESSURE ENCLOSURE(S) WITH APPROPRIATE

THREE STAGE DECON, TWO STAGE LOADOUT, AND NEGATIVE AIR

MACHINES WITH THREE STAGE HEPA FILTRATION ALL IN ACCORDANCE

WITH SPECIFICATIONS. TUBING SHALL BE VENTED TO THE BUILDING

EXTERIOR. EXHAUST TUBING AND OUTFLOW SHALL BE LOCATED SO AS

TO AVOID DISRUPTION TO VA OPERATIONS. COORDINATE EXHAUST

LOCATIONS WITH COR. REFER TO PHASING SHEETS FOR SPECIFIC

PROJECT-WIDE PHASING.

MAINTAIN A MINIMUM OF ½ THE WIDTH OF THE HALLWAYS FOR FREE

ACCESS TO MOVE PATIENTS. COORDINATE WITH THE VA-COR TO ALLOW

FOR ADEQUATE PASSAGE OF PATIENTS WHERE ASPECTS OF THE NPE

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

FULLY SPRINKLERED

1 2 � 4 � 6 � 8 �

1 2 � 4 � 6 � 8 �

STAMP:

Drawing Number

Building Number

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

/2

2/

:2 3:

A

M

BUILDING 1 - THIRD FLOOR -

ENVIRONMENTAL HAZARDS

CD 10 258JR

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511 HA014

SPUR #: 2207.00

No. REVISION DESCRIPTION DATE

NOT TO SCALE

BUILDING 1 - FOURTH FLOOR

HAZARDOUS MATERIALS KEYNOTES

AN ASBESTOS-CONTAINING GRAY MASTIC EXISTS ON FIBERGLASS LINES AND FITTINGS THROUGHOUT BUILDING. UNLESS OTHERWISE SPECIFIED AVOID DISTURBANCE. ANY WORK IMPACTING THIS MATERIAL MUST BE PERFORMED BY LICENSED ASBESTOS ABATEMENT CONTRACTORS.

AN ASBESTOS-CONTAINING WHITE SINK SOUNDPROOFING MATERIAL IS KNOWN TO EXIST WITHIN BUILDING 1. AVOID ANY WORK LIKELY TO IMPACT SINKS COVERED IN THIS WHITE SINK

SOUNDPROOFING MATERIAL.

WITHIN A NPE, USING MM's, REMOVE NON-ACM 12" BEIGE WITH LONG BROWN STREAK, NON-ACM MASTIC, LEVELING COMPOUND, AND UNDERLYING RESIDUAL ACM BLACK MASTIC. ~97 SF

LBP ON PLASTER CEILINGS. DO NOT DISTURB.ANY WORK LIKELY TO DISTURB THESE MATERIALS MUST BE PERFORMED BY A LICENSED ABATEMENT CONTRACTOR.

LBP ON METAL STEAM LINES. DO NOT DISTURB.ANY WORK LIKELY TO DISTURB THESE MATERIALS MUST BE PERFORMED BY A LICENSED ABATEMENT CONTRACTOR.

HAZARDOUS MATERIALS ALONG LIKELY ROUTING PATHWAYS ABOVE CEILING TILE. LEAD BASED PAINT ON CONCRETE &/OR PLASTER CEILING. WITHIN A NEGATIVE PRESSURE ENCLOSURE, USING CHEMICAL AND MANUAL METHODS, PERFORM SPOT REMOVAL OF LEAD BASED PAINT AT ANCHOR POINTS. 1 SF EACH LOCATION AT APPROXIMATELY 50 LOCATIONS.

COORDINATE EXACT LOCATIONS AND QUANTITIES WITH GC AND OTHER AFFECTED TRADES.

USING GLOVEBAG METHODS WITHIN A NEGATIVE PRESSURE ENCLOSURE, REMOVE OUT OF CHASE FIBERGLASS PIPE INSULATION AND RELATED FITTINGS. PIPE INSUALTION SYSTEMS HAVE INTERMITTENT APPLIED ASBESTOS GRAY MASTIC IN THE APPROXIMATE FOLLOWING QUANTITIES; 42 LF OF PIPE INSULATION AND FITTINGS IN ROOM AND 12 LF OF PIPE INSULATION RELATED TO DEMOLITION OF CFU. REFERENCE DRAWING M-401 FOR LOCATIONS OF PIPE TO BE REMOVED

A1

A2

A3

L1

L2

L3

PARTITION LEGEND

1 HOUR FIRE RATED

2 HOUR FIRE RATED

3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

EXISTING WALL TO REMAIN

NEW NON-RATED WALLS

EXISTING 1 HOUR FIRE

EXISTING 2 HOUR FIRE

NOTE: NOT ALL SYMBOLS MAY BE USED

BID DOCUMENTS

1 ADDENDUM 1 7/29/2025

A4

419-1 A4 A3

VISUAL KEY

LIMITS OF NEGATIVE PRESSURE ENCLOSURE(S) WITH APPROPRIATE

THREE STAGE DECON, TWO STAGE LOADOUT, AND NEGATIVE AIR

MACHINES WITH THREE STAGE HEPA FILTRATION ALL IN ACCORDANCE

WITH SPECIFICATIONS. TUBING SHALL BE VENTED TO THE BUILDING

EXTERIOR. EXHAUST TUBING AND OUTFLOW SHALL BE LOCATED SO AS

TO AVOID DISRUPTION TO VA OPERATIONS. COORDINATE EXHAUST

LOCATIONS WITH COR. REFER TO PHASING SHEETS FOR SPECIFIC

PROJECT-WIDE PHASING.

MAINTAIN A MINIMUM OF ½ THE WIDTH OF THE HALLWAYS FOR FREE

ACCESS TO MOVE PATIENTS. COORDINATE WITH THE VA-COR TO ALLOW

FOR ADEQUATE PASSAGE OF PATIENTS WHERE ASPECTS OF THE NPE

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

FULLY SPRINKLERED

1 2 � 4 � 6 � 8 �

1 2 � 4 � 6 � 8 �

STAMP:

Drawing Number

Building Number

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

/2

2/

:2 3:

A

M

BUILDING 25 - GROUND FLOOR -

ENVIRONMENTAL HAZARDS

CD 25 258JR

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511 HA250

SPUR #: 2207.00

No. REVISION DESCRIPTION DATE

HAZARDOUS MATERIALS KEYNOTES

KEYNOTE DELETED

AREA OF KNOWN DAMAGED ASBESTOS CONTAINING PIPE INSULATION ABOVE

CEILING TILE. WITHIN A NEGATIVE PRESSURE ENCLOSURE, USING MANUAL

MEANS, REMOVE CONTAMINATED NON-ACM CEILING TILE AND GLOVEBAG

METHOD REMOVE DAMAGED ASBESTOS CONTAINING PIPE/PIPE FITTING

INSULATION. DISPOSE OF CEILING TILE AS ACM WASTE, 32 SF CEILING TILE AND 10

LF OF ACM INSULATION.

WITHIN A NEGATIVE PRESSURE ENCLOSURE, USING MANUAL MEANS, REMOVE

ASBESTOS CONTAINING 12" BEIGE FLOOR TILE AND UNDERLYING ASBESTOS

CONTAINING BLACK MASTIC, 90 SF

AREA OF KNOWN AND/OR PRESUMED ASBESTOS CONTAINING BLACK COATING

ON INSIDE OF EXTERIOR WALL, AND WATERPROOFING BELOW GRADE. WITHIN A

NPE, USING MANUAL MEANS, PROVIDE WALL PENETRATION(S). REFERENCE

MECHANICAL, ELECTRICAL, AND TELECOMMUNICATION DRAWING SETS FOR

DETAILS. NOTE - TELECOMMUNICATION PATHWAYS TO BE LOCATED WITHIN NEW

DUCT BANKS HAVE A SLIGHTLY DIFFERENT ENTRY/EXIT POINT THAN THOSE

INDICATED WITHIN THE CIVIL DRAWING SET. COORDINATE EXACT LOCATIONS AND

QUANTITIES WITH COR, GC, AND OTHER IMPACTED PROFESSIONS AND TRADES.

ESTIMATED 3 SF EACH AT 3 LOCATIONS

WITHIN A NEGATIVE PRESSURE ENCLOSURE, USING MANUAL MEANS, DEMOLISH

EXISTING NON-ACM PLASTER &/OR DRYWALL CHASE WALL TO EXPOSE

UNDERLYING ACM PIPE/FITTING INSULATION. THEN, USING GLOVE BAG METHODS,

REMOVE ACM PIPE/FITTING INSULATION, 120 SF OF NON-ACM PLASTER &/OR

DRYWALL, 25 LF PIPE/FITTING INSULATION

WITHIN A NEGATIVE PRESSURE MINI-ENCLOSURE, USING MANUAL MEANS,

PROVIDE FLOOR PENETRATIONS THROUGH 16" NON-ACM VINYL FLOOR TILE, ACM

GREEN TERRAZZO FLOORING, AND UNDERLYING CONCRETE TO FACILITATE

INSTALLATION OF TELECOM CONDUIT AND CABLE FOR B-PATH RISERS AND

FLOOR PLATE FOR METAL WALL FRAMING. COORDINATE EXACT SIZE AND

PLACEMENT WITH GC, TC, AND OTHER IMPACTED TRADES, 2 SF EACH AT 3

LOCATIONS

DO NOT DISTURB ASBESTOS-CONTAIING 12”X12” CEILING TILE MASTIC DURING

REMOVAL/REPLACEMENT OF EXISTING CABLE TRAY. REUSE OF EXISTING CABLE

TRAY ATTACHMENT POINTS IS REQUIRED IN THIS AREA.

A1

A2

A3

A4

19-25

NOT TO SCALE

BUILDING 25 - GROUND FLOOR

A3

A4

A2

PARTITION LEGEND

1 HOUR FIRE RATED

2 HOUR FIRE RATED

3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

EXISTING WALL TO REMAIN

NEW NON-RATED WALLS

EXISTING 1 HOUR FIRE

EXISTING 2 HOUR FIRE

NOTE: NOT ALL SYMBOLS MAY BE USED

N

BID DOCUMENTS

A5

A6

A6A5

A7

1 ADDENDUM 1 7/29/2025

A7

VISUAL KEY

LIMITS OF NEGATIVE PRESSURE ENCLOSURE(S) WITH APPROPRIATE

THREE STAGE DECON, TWO STAGE LOADOUT, AND NEGATIVE AIR

MACHINES WITH THREE STAGE HEPA FILTRATION ALL IN ACCORDANCE

WITH SPECIFICATIONS. TUBING SHALL BE VENTED TO THE BUILDING

EXTERIOR. EXHAUST TUBING AND OUTFLOW SHALL BE LOCATED SO AS

TO AVOID DISRUPTION TO VA OPERATIONS. COORDINATE EXHAUST

LOCATIONS WITH COR. REFER TO PHASING SHEETS FOR SPECIFIC

PROJECT-WIDE PHASING.

MAINTAIN A MINIMUM OF ½ THE WIDTH OF THE HALLWAYS FOR FREE

ACCESS TO MOVE PATIENTS. COORDINATE WITH THE VA-COR TO ALLOW

FOR ADEQUATE PASSAGE OF PATIENTS WHERE ASPECTS OF THE NPE

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

FULLY SPRINKLERED

1 2 � 4 � 6 � 8 �

1 2 � 4 � 6 � 8 �

STAMP:

Drawing Number

Building Number

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

/2

2/

:2 3:

A

M

BUILDING 25 - FIRST FLOOR -

ENVIRONMENTAL HAZARDS

CD 26 258JR

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511 HA251

SPUR #: 2207.00

No. REVISION DESCRIPTION DATE

HAZARDOUS MATERIALS KEYNOTES

KEYNOTE DELETED

WITHIN A NEGATIVE PRESSURE MINI-ENCLOSURE, USING MANUAL MEANS,

PROVIDE FLOOR PENETRATIONS THROUGH 16" NON-ACM VINYL FLOOR TILE, ACM

GREEN TERRAZZO FLOORING, AND UNDERLYING CONCRETE TO FACILITATE

INSTALLATION OF TELECOM CONDUIT AND CABLE FOR B-PATH RISERS AND

FLOOR PLATE FOR METAL WALL FRAMING. COORDINATE EXACT SIZE AND

PLACEMENT WITH GC, TC, AND OTHER IMPACTED TRADES, 2 SF EACH AT 3

LOCATIONS

A1

NOT TO SCALE

BUILDING 25 - FIRST FLOOR

214-25

PARTITION LEGEND

1 HOUR FIRE RATED

2 HOUR FIRE RATED

3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

EXISTING WALL TO REMAIN

NEW NON-RATED WALLS

EXISTING 1 HOUR FIRE

EXISTING 2 HOUR FIRE

NOTE: NOT ALL SYMBOLS MAY BE USED

N

BID DOCUMENTS

A2

A2

1 ADDENDUM 1 7/29/2025

VISUAL KEY

LIMITS OF NEGATIVE PRESSURE ENCLOSURE(S) WITH APPROPRIATE

THREE STAGE DECON, TWO STAGE LOADOUT, AND NEGATIVE AIR

MACHINES WITH THREE STAGE HEPA FILTRATION ALL IN ACCORDANCE

WITH SPECIFICATIONS. TUBING SHALL BE VENTED TO THE BUILDING

EXTERIOR. EXHAUST TUBING AND OUTFLOW SHALL BE LOCATED SO AS

TO AVOID DISRUPTION TO VA OPERATIONS. COORDINATE EXHAUST

LOCATIONS WITH COR. REFER TO PHASING SHEETS FOR SPECIFIC

PROJECT-WIDE PHASING.

MAINTAIN A MINIMUM OF ½ THE WIDTH OF THE HALLWAYS FOR FREE

ACCESS TO MOVE PATIENTS. COORDINATE WITH THE VA-COR TO ALLOW

FOR ADEQUATE PASSAGE OF PATIENTS WHERE ASPECTS OF THE NPE

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

FULLY SPRINKLERED

1 2 � 4 � 6 � 8 �

1 2 � 4 � 6 � 8 �

STAMP:

Drawing Number

Building Number

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENG.

SPUR DESIGN

2519 MADISON AVE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, #1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 856-2965

STRUCTURAL

STAND

8234 ROBINSON

OVERLAND PARK, KS 66204

(913) 214-2169

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH: SETH CAVIN, LICENSE #8468 EXP. 06/30/2024

ENGR: SPUR DESIGN, LLC COA #5197 EXP. 12/31/2025

/2

2/

:2 3:

A

M

BUILDING 25 - SECOND FLOOR -

ENVIRONMENTAL HAZARDS

CD 27 258JR

EHRM INFRASTRUCTURE

UPGRADES LEXINGTON, KY

03/15/2024

596-22-700

LEXINGTON VA HEALTH CARE

2250 LEESTOWN RD

LEXINGTON, KY 40511 HA252

SPUR #: 2207.00

No. REVISION DESCRIPTION DATE

NOT TO SCALE

BUILDING 25 - SECOND FLOOR

HAZARDOUS MATERIALS KEYNOTES

KEYNOTE DELETED

WITHIN A NEGATIVE PRESSURE MINI-ENCLOSURE, USING MANUAL MEANS,

PROVIDE FLOOR PENETRATIONS THROUGH 16" NON-ACM VINYL FLOOR TILE, ACM

GREEN TERRAZZO FLOORING, AND UNDERLYING CONCRETE TO FACILITATE

INSTALLATION OF TELECOM CONDUIT AND CABLE FOR B-PATH RISERS AND

FLOOR PLATE FOR METAL WALL FRAMING. COORDINATE EXACT SIZE AND

PLACEMENT WITH GC, TC, AND OTHER IMPACTED TRADES, 2 SF EACH AT 3

LOCATIONS

A1

112-25

PARTITION LEGEND

1 HOUR FIRE RATED

2 HOUR FIRE RATED

3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

EXISTING WALL TO REMAIN

NEW NON-RATED WALLS

EXISTING 1 HOUR FIRE

EXISTING 2 HOUR FIRE

NOTE: NOT ALL SYMBOLS MAY BE USED

N

BID DOCUMENTS

A2

A2

1 ADDENDUM 1 7/29/2025

VISUAL KEY

LIMITS OF NEGATIVE PRESSURE ENCLOSURE(S) WITH APPROPRIATE

THREE STAGE DECON, TWO STAGE LOADOUT, AND NEGATIVE AIR

MACHINES WITH THREE STAGE HEPA FILTRATION ALL IN ACCORDANCE

WITH SPECIFICATIONS. TUBING SHALL BE VENTED TO THE BUILDING

EXTERIOR. EXHAUST TUBING AND OUTFLOW SHALL BE LOCATED SO AS

TO AVOID DISRUPTION TO VA OPERATIONS. COORDINATE EXHAUST

LOCATIONS WITH COR. REFER TO PHASING SHEETS FOR SPECIFIC

PROJECT-WIDE PHASING.

MAINTAIN A MINIMUM OF ½ THE WIDTH OF THE HALLWAYS FOR FREE

ACCESS TO MOVE PATIENTS. COORDINATE WITH THE VA-COR TO ALLOW

FOR ADEQUATE PASSAGE OF PATIENTS WHERE ASPECTS OF THE NPE

1-HA010
Sheets and Views
Model
2-HA011
Sheets and Views
Model
3-HA012
Sheets and Views
Model
4-HA013
Sheets and Views
Model
5-HA014
Sheets and Views
Model
20-HA250
Sheets and Views
Model
21-HA251
Sheets and Views
Model
22-HA252
Sheets and Views
Model