These are architectural engineering drawings for telecommunications room enlargements at the VA Medical Center in Grand Junction, Colorado. The documents detail two specific telecommunications rooms (TR Room 106 and TR Room 150) with detailed rack elevation diagrams showing equipment configurations. Key components include VA-provided 1U 48-port switches, 144-strand fiber distribution panels, CAT6A data patch panels, vertical rack PDUs, rack-mount UPS systems, and cable management infrastructure. The drawings specify notes requiring contractor coordination with the VA's IS/IT representative for final rack component layout, with estimated existing cable counts ranging from 20 to 252 CAT5e cables. The project is part of the EHRM IU (Electronic Health Record Modernization Integrated Utility) initiative, with 100% construction documents prepared by HFG Architecture and Specialized Engineering Solutions, marked as fully sprinklered and dated for completion in December 2024 with subsequent addendums in June and August 2025.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CR AC
C
AC
TR
ROOM
B44-TN400
GROUND BAR
2D
2D
12"x4"
AC
C1 126"
2' - 6"
KEYPAD
1U CABLE MANAGEMENT
1U BONDING BUS BAR (BACK) 1U BLANKING PANEL (FRONT)
1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL
2U CABLE MANAGEMENT
2U CABLE MANAGEMENT
1U 48 PORT CAT6A DATA PATCH PANEL
2U CABLE MANAGEMENT
1U 48 PORT VA PROVIDED SWITCH
1U CABLE MANAGEMENT
5U SPACE FOR OIT PROVIDED
EQUIPMENT. PROVIDE BLANKING
PANELS FOR UNUSED SPACES
2U RACK MOUNT UPS
D
PROVIDE DATA CABLE TO RACK
MOUNTED UPS FOR CONNECTION
TO MONITORING SYSTEM
NOTES:
1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.
2. COORDINATE EXACT RACK LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.
3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.
4. RACK ELEVATION SHOWS A FULLY CONFIGURED SAMPLE RACK. CONTRACTOR TO PROVIDE REQUIRED EQUIPMENT TO
SUPPORT THE FINAL DATA COUNT FROM THE ENLARGED NEW SHEET.
5. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.
6. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, TR PATCH CABLES, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.
2U CABLE MANAGEMENT
1U 48 PORT VA PROVIDED SWITCH
2U CABLE MANAGEMENT
1U 48 PORT CAT6A DATA PATCH PANEL
1U 48 PORT CAT6A DATA PATCH PANEL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7100 E BELLEVIEW AVE,
STE 107
GREENWOOD VILLAGE,
CO 80111
Phone: (720) 200-5955 www.specializedeng.com
SES Project : 22295
330 N. Mead St, Suite 100 Wichita, KS 67202
Phone: (316) 262-2500 www.hfgarchitecture.com
A u to d e s k D o c s /2
V
A G ra n d J u n c ti o n
E H
R M
/5
-7
.B
.E
T .R
.r v t
/2
/2
:0
:1
P
M
B44-TN400
ENLARGED PLANS - TELECOM - TR ROOM 106 EHRM IU AT THE GRAND JUNCTION,
CO VA MEDICAL CENTER
2121 North Ave, Grand Junction, CO 81501
575-21-700
12/17/2024 RJA CMW
02' 2' 4'
04' 4' 8'
1/2" = 1'-0"
FIRST LEVEL FLOOR PLAN - ENLARGED TELECOM - TR ROOM 106
1/4" = 1'-0"
TR ROOM 106 - A
1/4" = 1'-0"
TR ROOM 106 - B
1/4" = 1'-0"
TR ROOM 106 - C
1/4" = 1'-0"
TR ROOM 106 - D
NO SCALE
COMMUNICATIONS - TYPICAL WALL CABINET ELEVATION - TE
Revisions: Date:
Addendum 1 06/27/2025
Addendum 2 08/22/2025
A. THE ESTIMATED CABLE COUNTS BELOW REPRESENT ESTIMATED EXISTING CABLES IN THE SPACE OR EXISTING ROOM BEING REPLACED. THESE ARE THE ESTIMATED CABLES THAT WILL BE PRESENT IN THE
SPACE AT THE COMPLETION OF THE PROJECT.
a. EXISTING CABLE COUNT:
• DATA (CAT6):
• DATA (CAT5e): 20
• DATA (CAT5):
• DATA (CAT3):
B. CONTRACTOR IS RESPONSIBLE TO VERIFY FINAL COUNTS IN AREAS SERVED BY TR.
(REFER TO GENERAL NOTES ON SHEET TN000 FOR ADDITIONAL DETAILS)
CABLING NOTES
Revisions: Date:
Addendum 1 06/27/2025
Addendum 2 08/22/2025
CRAC
C
AC
IT /
SECURITY
TELECOM
B45-TN400
GROUND BAR
2D
2D
12"x4"
AC
45TR
C2 126"
C2 126"
12"x4" 12"x4"
12"x4"
KEYPAD
FUTURE
NEMA L21-20R (TYP)
RACK 1
RACK 1
V E
R T
IC
A
L R
A C
K P
D U
V E
R T
IC
A
L R
A C
K P
D U
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
SPACE FOR FUTURE USE.
PROVIDE BLANK PANELS FOR UNUSED SPACES.
6U 5KW RACK MOUNT UPS
D
PROVIDE DATA CABLE TO RACK
MOUNTED UPS FOR CONNECTION
TO MONITORING SYSTEM
VERTICAL CABLE
MANAGEMENT (TYP)
NEMA L21-20R (TYP)
RACK 2
RACK 2
V E
R T
IC
A
L R
A C
K P
D U
V E
R T
IC
A
L R
A C
K P
D U
6U 5KW RACK MOUNT UPS
D
1U BONDING BUS BAR (BACK) 1U ANGLED BLANKING PANEL (FRONT)
NOTES:
1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.
2. COORDINATE EXACT RACK LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.
3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.
4. RACK ELEVATION SHOWS A FULLY CONFIGURED SAMPLE RACK. CONTRACTOR TO PROVIDE REQUIRED EQUIPMENT TO
SUPPORT THE FINAL DATA COUNT FROM THE ENLARGED NEW SHEET.
5. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.
6. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, TR PATCH CABLES, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.
4 POST CHANNEL
RACK (TYP)
1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL
SPACE FOR FUTURE HORIZONTAL CABLE
DISTRIBUTION. PROVIDE ANGLED BLANKING PANELS
FOR UNUSED SPACES.
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
SPACE FOR FUTURE BUILDING EXPANSION
A. THE ESTIMATED CABLE COUNTS BELOW REPRESENT ESTIMATED EXISTING CABLES IN THE SPACE OR EXISTING ROOM BEING REPLACED. THESE ARE THE ESTIMATED CABLES THAT WILL BE PRESENT IN THE
SPACE AT THE COMPLETION OF THE PROJECT.
a. EXISTING CABLE COUNT:
• DATA (CAT6):
• DATA (CAT5e): 252
• DATA (CAT5):
• DATA (CAT3):
B. CONTRACTOR IS RESPONSIBLE TO VERIFY FINAL COUNTS IN AREAS SERVED BY TR.
(REFER TO GENERAL NOTES ON SHEET TN000 FOR ADDITIONAL DETAILS)
CABLING NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7100 E BELLEVIEW AVE,
STE 107
GREENWOOD VILLAGE,
CO 80111
Phone: (720) 200-5955 www.specializedeng.com
SES Project : 22295
330 N. Mead St, Suite 100 Wichita, KS 67202
Phone: (316) 262-2500 www.hfgarchitecture.com
A u to d e s k D o c s /2
V
A G ra n d J u n c ti o n
E H
R M
/5
-7
.B
.E
T .R
.r v t
/2
/2
:0
:4
P
M
B45-TN400
TELECOMMUNICATIONS ROOM
ENLARGEMENTS
EHRM IU AT THE GRAND JUNCTION,
CO VA MEDICAL CENTER
2121 North Ave, Grand Junction, CO 81501
575-21-700
12/17/2024 RJA CMW
1/2" = 1'-0"
FIRST LEVEL FLOOR PLAN - ENLARGED TELECOM - IT/SECUIRTY/TELECOM 150
1/4" = 1'-0"
TR ROOM - 1 - A
1/4" = 1'-0"
TR ROOM - 1 - B
1/4" = 1'-0"
TR ROOM - 1 - C
1/4" = 1'-0"
TR ROOM - 1 - D
04' 4' 8'
02' 2' 4'
NO SCALE
COMMUNICATIONS - TYPICAL TWO RACK ELEVATION WITH RACK MOUNT UPS