575-700.VA Mechanical Grand Junction EHRM Addendum 2 - Changed Sheets Only.pdf

PDF 1 MB Posted

Attached to
Y1DA--575-21-700 | Construction| EHRM Infrastructure Upgrades | Grand Junction, CO
Solicitation number
36C77625B0039
Issued by

About this file

These mechanical engineering drawings detail the EHRM (Electronic Health Records Modernization) renovation project for the U.S. Department of Veterans Affairs Medical Center located in Grand Junction, Colorado. The documents are 100% Construction Documents prepared by IMEG Corp. and Specialized Engineering Solutions (SES), with the project number 22007411.00 and SES project number 22295. The drawings cover mechanical system modifications across multiple building sections (B01, B05, B06, B08, B09, B35, B36, B37, and B45), focusing on replacing and routing new mechanical infrastructure including:

Key mechanical system modifications include installing new condensing units with 24" elevation stands, routing refrigerant and chilled water piping, removing existing diffusers and ductwork, installing new fan and filter sections, and implementing condensate pumping systems. The project is fully sprinklered and involves extensive mechanical system updates in various rooms such as IT/security rooms, telecommunications rooms, mechanical spaces, and office areas. The drawings are dated December 17, 2024, with the most recent revision (Addendum 2) on August 22, 2025.

View the file

Other files

File Type Posted
S05 - 575-21-700 Tech Questions responses updated - GJ CO - 8-28-25.docx DOCX document
575-700.VA Archtitectural Grand Junction EHRM Addendum 2 - Changed Sheets Only.pdf PDF
For Information Only - B44_2013_TERRACON_41013_Parking_Garage.pdf PDF
575-700.VA Civil Grand Junction EHRM Addendum 2 - Fiber Optic Manhole Detail.pdf PDF
575-700.VA Telecom Grand Junction EHRM Addendum 2 - Changed Sheets Only.pdf PDF
For Information Only - B9_2019_Geotech_Report_HB_Boiler_Plant.pdf PDF
S06- Amendment 0009.pdf PDF
S06 - Amendment 0008.pdf PDF
S06- Amendment 0007.pdf PDF
32 05 23 Cement and Concrete for Exterior Improvements.pdf PDF
32 12 16 Asphalt Paving.pdf PDF
CIP concrete short form.pdf PDF
S06- Amendment 0006- Bid due date extended 08-28-25.pdf PDF
S06- Amendment 0005- Bid due date extended.pdf PDF
S06- Amendment 0005- Bid due date extended.pdf PDF
B12 Roof 20250730.pdf PDF
S06- Amendment 0004- Bid opening info and all tech questions responses.pdf PDF
4 Utility Plan.pdf PDF
B7 Roof 20250730.pdf PDF
S05 - 575-21-700 All Tech Questions Responses - CO.docx DOCX document
S06- Amendment 0003 - DB Wages updated - Bid extension - RFI answers.pdf PDF
S05 - 575-21-700 Tech Questions Responses- GJ CO 07-28-25.docx DOCX document
P07- Updated Wages Determination - Grand Junction CO 07-25-2025.pdf PDF
S04- Signed site visit sign in sheet - 57521700 CO.pdf PDF
S06- Amendment 0002- Signed site visit sheet.pdf PDF
ATT 12- Drawings - EHRM - Grand Junction - CO.pdf PDF
ATT 13- Specifications-Combined- EHRM - Grand Junction CO.pdf PDF
ATT 4- Grand Junction CO - SPECS 07-03-25- Addendum.pdf PDF
ATT 11 - Site Visit Instructions.pdf PDF
ATT 1- Grand Junction EHRM - Drawings 07-03-25 - Addendum.pdf PDF
S06 - Amendment 0001.pdf PDF
ATT 7 - Spec 01 31 00.01 Project Management and Coordination.pdf PDF
ATT 3- Estimated Construction Schedule- EHRM- Grand Junction CO.pdf PDF
ATT 10 - GEO Reports B20.pdf PDF
ATT 6 - Wages Determination - Grand Junction CO.pdf PDF
ATT 5- 100 CD Basis of Design -Combined- Grand Junction CO.pdf PDF
ATT 1- Grand Junction EHRM - Drawings 07-03-25.pdf PDF
ATT 8 - Limitations on Subcontracting.docx DOCX document
36C77625B0039.pdf PDF
ATT 11- Site Visit Instructions.pdf PDF
ATT 4- Grand Junction CO - SPECS 07-03-25.pdf PDF
ATT 2- Parking Guidelines Grand Junction VAMC.pdf PDF
ATT 9- Hazardous Materials Report.pdf PDF
Show all 43

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

6"CWS

6"CWR 4"CWS

4"CWR

2 1/2"CWS

2 1/2"CWR

2"CWR

2"CWS

2 1/2"CWR

2 1/2"CWS

"S A N

3"CWS

3"CWR

SANSAN

1207 1104

3"CW 3"CW

"C

W

2"SAN

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2023 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

7600 E ORCHARD ROAD

SUITE 250-S

GREENWOOD VILLAGE, CO 80111

P: 303.796.6000 www.imegcorp.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

KEYPLAN N

A

B C

D

PROJECT #22007411.00

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

100% CONSTRUCTION

DOCUMENTS

A u to d e s k D o c s /2

V

A G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.M .R

.r v t

/2

/2

:5

:1

P

M

B01-M200

BASEMENT - OVERALL MECHANICAL PLAN EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

2121 North Ave, Grand Junction, CO 81501

575-21-700

12/17/2024 BRE WLJ

N

1" = 20'-0"

BASEMENT - OVERALL MECHANICAL PLAN

1" = 20'

0' 10' 20' 40'

KEYNOTES

201 CONNECT TO EXISTING 6" CW MAINS IN CRAWL SPACE

DOWNSTREAM OF EXISTING BTU METER.

204 FLUSH AND FILL EXISTING CHILLED WATER SYSTEM.

902 ROUTE NEW PIPING UP THROUGH NEW CHASE ON 2ND FLOOR.

REFER TO MECHANICAL RISER DIAGRAM.

1104 ROUTE NEW CW PIPING AND CONNECT TO EXISTING CW PIPE.

1207 CONNECT NEW 2" SANITARY PIPING FROM RISER TO EXISTING

SANITARY PIPE.

Revisions: Date:

Addendum 2 08/22/2025

AIAI

THS

FACTORY MOUNTED CONTROL PANEL

WALL/FLOOR MOUNTED CONSOLE

COMPUTER ROOM UNIT AIR

CONDITIONING UNIT.

THERE ARE BOTH DX SPLIT AND CW

UNITS.

N.T.S. #2

WALL MTD

SPACE TEMP

SENSOR

RETURN AIR

SUPPLY AIR

CRU SEQUENCE OF OPERATION GENERAL: (CONTROLS PROVIDED WITH UNIT)

THERE ARE BOTH CHILLED WATER AND SPLIT DX BASED SYSTEMS FOR THIS PROJECT. BOTH

MODELS SHALL BE FACTORY CONTROLLED WITH THE CW BASED UNITS CONTROLLING THE CW

CONTROL VALVE AND THE SPLIT DX BASED UNITS CONTROLLING THE SPLIT CONDENSING UNITS.

PROVIDE NECESSARY LOW VOLT CONTROL WIRING AND STARTUP AS REQUIRED BY

MANUFACTURER'S INSTRUCTIONS.

THE CRU IS CONTROLLED BY A FACTORY ASSEMBLED AND MOUNTED MICROPROCESSOR BASED

CONTROL SYSTEM AND CONNECTED TO THE FACILITY MANAGEMENT CONTROL SYSTEM (FMCS) FOR

MONITORING PURPOSES.

THE MICROPROCESSOR CONTROL SYSTEM SHALL MONITOR THE RETURN AIR TEMPERATURE AND

HUMIDITY. THE MICROPROCESSOR CONTROL SYSTEM SHALL AUTOMATICALLY HEAT, COOL, REHEAT, HUMIDIFY, AND DEHUMIDIFY AS REQUIRED TO MAINTAIN THE SPACE TEMPERATURE AND HUMIDITY

SETPOINTS.

THE ALLOWABLE VA SPACE SETPOINT RANGES ARE 72°F TO 80°F SPACE/RACK INLET TEMPERATURE AND 10% TO 60% RELATIVE HUMIDITY (ADJ.). SET SPACE COOLING SETPOINT INITIALLY AT 72°F (ADJ.).

SET SPACE HUMIDIFICAITON SETPOINT AT 25% RH (ADJ.) AND SET SPACE DEHUMIDIFICAITON

SETPIONT AT 50% RH (ADJ.).

MICROPROCESSOR CONTROL SYSTEM SHALL BE CAPABLE OF DISABLING ANY ALARM IF REQUIRED.

FMCS SEQUENCE OF OPERATION (CONTROLS PROVIDED BY TCC)

THE TCC SHALL EXTEND THE FMCS NETWORK TO THE CRU MICROPROCESSOR CONTROLLER PER

THE PROTOCOL SPECIFIED IN SECTION 23 09 00. THE FMCS SHALL MONITOR THE OPERATING

PARAMETERS AND ALARM CONDITIONS INDICATED BY THE CRU.

ALARMS, INTERLOCKS AND SAFETIES AT FMCS:

SEND AN ALARM TO THE FMCS OPERATOR INTERFACE UPON THE OCCURRENCE OF ANY OF THE

FOLLOWING MICROPROCESSOR CONTROL SYSTEM ALARM CONDITIONS:

• LOSS OF POWER TO CRU

• HIGH TEMPERATURE

• LOW TEMPERATURE

• HIGH HUMIDITY

• LOW HUMIDITY

• WATER FLOOR SENSOR

TO/FROM FMCS THROUGH MAU BACNET

GATEWAY:

• RETURN AIR TEMPERATURE

• RETURN AIR HUMIDITY CRU LOSS OF POWER

• HIGH TEMPERATURE ALARM

• LOW TEMERATURE ALARM

• HIGH HUMIDITY ALARM

• LOW HUMIDITY ALARM

• WATER FLOOR SENSOR

BACNET

INTERFACE TO

FMCS

WALL MTD

SPACE

HUMIDITY

SENSOR

SUPPLY

AIR

SEQUENCE OF OPERATION:

FAN SHALL RUN CONTINUOUSLY, AND SHALL BE ENABLED/DISBLED VIA

THE DISCONNECT SWITCH.

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2023 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

7600 E ORCHARD ROAD

SUITE 250-S

GREENWOOD VILLAGE, CO 80111

P: 303.796.6000 www.imegcorp.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

PROJECT #22007411.00

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

100% CONSTRUCTION

DOCUMENTS

A u to d e s k D o c s /2

G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.M .R

.r v t

/2

/2

:5

:5

P

M

M501

MECHANICAL CONTROLS EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

2121 North Ave, Grand Junction, CO 81501

575-21-700

12/17/2024 BRE WLJ

NO SCALE

COMPUTER ROOM UNIT CONTROL

M_CRU.2.01

Revisions: Date:

Addendum 2 08/22/2025

NO SCALE

FAN - RUN CONTINUOUSLY

M_EF.2.19

TH

TELEPHONE CLOSET

CU-5-1

CU-5-2

<varies>

B05-M300

ELECTRICAL CLOSET

TR

CLOSET

12011101

SD-1

8ø

14x8 SA

ELECTRICAL CLOSET

TR

CLOSET

FCU-5-1

FCU-5-2

CP-1

F-1

/4

"C W

/4

"D

SUC

LIQ

SUC

LIQ

14x8 SA ø

SG-1

6x6/50

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2023 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

7600 E ORCHARD ROAD

SUITE 250-S

GREENWOOD VILLAGE, CO 80111

P: 303.796.6000 www.imegcorp.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

PROJECT #22007411.00

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

100% CONSTRUCTION

DOCUMENTS

A u to d e s k D o c s /2

G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.M .R

.r v t

/2

/2

:5

:3

P

M

B05-M300

ENLARGED MECHANICAL DEMO AND NEW

PLANS

EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

2121 North Ave, Grand Junction, CO 81501

575-21-700

12/17/2024 BRE WLJ

KEYNOTES

006 REMOVE EXISTING DIFFUSER AND ASSOCIATED DUCTWORK

BACK TO THE MAIN BRANCH AND CAP.

203 ROUTE AND SIZE REFRIGERANT PIPIING FROM CONDENSING

UNIT TO INDOOR UNIT PER MANUFACTURES INSTRUCTIONS.

703 INSTALL CONDENSING UNIT ON PREMANUFACTURED

CONDENSING UNIT PAD. CONDENSING UNIT TO BE PROVIDED

WITH 24" STAND TO ELEVATE UNIT ABOVE GRADE.

900 RELOCATE EXISTING PLUMBING AND MECHANICAL

INFRASTRUCTURE TO AVOID NEW TR. FIELD VERIFY EXISTING

INFRASTRUCTURE AND NOTIFY ENGINEER IN WRITING IF

FURTHER CLARIFICATION IS NEEDED FOR RELOCATION OF

EXISTING INFRASTRUCTURE PRIOR TO BIDDING.

1101 ROUTE NEW 1/2" CW PIPE FROM RESTROOM GROUP TO TR

ROOM FOR HUMIDIFICATION.

1102 ROUTE CW PIPING TO NEW WATER FILTER AND CONNECT TO

NEW CRAC UNIT.

1200 PROVIDE WITH EXTERNAL CONDENSATE PUMP. ROUTE DRAIN

FROM ADJACENT CRAC UNIT TO TERMINATE INTO CONDENSATE

PUMP. REFER TO OVERALL PLAN FOR CONDENSATE PIPE

TERMINATION.

1201 ROUTE NEW 3/4" PUMPED CONDENSATE PIPING TO RESTROOM

AND TERMINATE INTO SINK TAILPIECE WITH AIR GAP.

N

1/8" = 1'-0"

FIRST FLOOR - OVERALL MECHANICAL PLAN

N

1/8" = 1'-0"

SECOND FLOOR - OVERALL MECHANICAL PLAN

N

1/2" = 1'-0"

ENLARGED SECOND FLOOR IT ROOM - MECHANICAL DEMOLITION PLAN

N

1/2" = 1'-0"

ENLARGED SECOND FLOOR IT ROOM - MECHANICAL NEW PLAN

4' 8' 16'

1/8" = 1'-0"

0' 4' 8' 16'

1/8" = 1'-0"

0'

1' 2' 4'

1/2" = 1'-0"

0' 1' 2' 4'

1/2" = 1'-0"

0'

Revisions: Date:

H T

ELEC.

RR-1

110-1

RR-2

110-2

INNOVATION/COMPUTER

KITCHEN

NURSE EDUCATOR

TE

106HOUSEKEEPING CLOSET

111A

PROGRAM SPECIALIST

QUALITY MANAGER

CHIEF OF EDUCATION

CHIEF QUALITY

ED/STORAGE

VESTIBULE

114A

STORAGE CLOSET

116B

CLOSET

116A

DIRECTOR, CONFERENCE

COMPUTER LAB

101/101A

MECH ROOM

STAIRS

CONFERENCE ROOM

CORRIDOR

CORR.

CORRIDOR

LOBBY

B06-M300

CU-6-1

SUC

LIQ

3/4"D

3/4"CW

900 011 TE

FCU-6-1CP-1F-1

12001102

F-1

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2023 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

7600 E ORCHARD ROAD

SUITE 250-S

GREENWOOD VILLAGE, CO 80111

P: 303.796.6000 www.imegcorp.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

PROJECT #22007411.00

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

100% CONSTRUCTION

DOCUMENTS

A u to d e s k D o c s /2

G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.M .R

.r v t

/2

/2

:0

:2

P

M

B06-M300

ENLARGED MECHANICAL DEMO AND NEW

PLANS

EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

2121 North Ave, Grand Junction, CO 81501

575-21-700

12/17/2024 BRE WLJ

KEYNOTES

011 REMOVE EXISTING MINI-SPLIT AND ASSOCIATED CONDENSING

UNIT, POWER, CONTROLS, AND APPURTENANCES.

203 ROUTE AND SIZE REFRIGERANT PIPIING FROM CONDENSING

UNIT TO INDOOR UNIT PER MANUFACTURES INSTRUCTIONS.

703 INSTALL CONDENSING UNIT ON PREMANUFACTURED

CONDENSING UNIT PAD. CONDENSING UNIT TO BE PROVIDED

WITH 24" STAND TO ELEVATE UNIT ABOVE GRADE.

705 PROVIDE NEW IN-LINE FAN WITH FILTER SECTION, INLET OF FAN

TO BE OPEN TO CEILING PLENUM.

900 RELOCATE EXISTING PLUMBING AND MECHANICAL

INFRASTRUCTURE TO AVOID NEW TR. FIELD VERIFY EXISTING

INFRASTRUCTURE AND NOTIFY ENGINEER IN WRITING IF

FURTHER CLARIFICATION IS NEEDED FOR RELOCATION OF

EXISTING INFRASTRUCTURE PRIOR TO BIDDING.

1101 ROUTE NEW 1/2" CW PIPE FROM RESTROOM GROUP TO TR

ROOM FOR HUMIDIFICATION.

1102 ROUTE CW PIPING TO NEW WATER FILTER AND CONNECT TO

NEW CRAC UNIT.

1200 PROVIDE WITH EXTERNAL CONDENSATE PUMP. ROUTE DRAIN

FROM ADJACENT CRAC UNIT TO TERMINATE INTO CONDENSATE

PUMP. REFER TO OVERALL PLAN FOR CONDENSATE PIPE

TERMINATION.

1201 ROUTE NEW 3/4" PUMPED CONDENSATE PIPING TO RESTROOM

AND TERMINATE INTO SINK TAILPIECE WITH AIR GAP.

N

1/4" = 1'-0"

OVERALL MECHANICAL PLAN

N

1/2" = 1'-0"

ENLARGED IT ROOM - MECHANICAL DEMOLITION PLAN

N

1/2" = 1'-0"

ENLARGED IT ROOM - MECHANICAL NEW PLAN

2' 4' 8'0'

1/4" = 1'-0"

2' 4' 8'0'

1/4" = 1'-0"

2' 4' 8'0'

1/4" = 1'-0"

Revisions: Date:

B08-M300

TE ROOM

PLUMB SHOP

STORAGE

TOILET

XXX

OFFICE

BREAK ROOM

CORR

STORAGE

OFFICE

GENERAL ENG.

114C

TOILET

XXXA

TOILET

XXXB

OFFICE SPACE

CORR

OFFICE ENTRY

CHIEF ENGINEER

CONF. ROOM

JAN

CORR

/4

"D

FCU-8-1

CU-8-1

CP-1

TE ROOM

CORR

/4

"D

LIQ

SUC

SG-1

6x6/50 ø

CORR

RG-E

SD-E

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2023 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

7600 E ORCHARD ROAD

SUITE 250-S

GREENWOOD VILLAGE, CO 80111

P: 303.796.6000 www.imegcorp.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

PROJECT #22007411.00

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

100% CONSTRUCTION

DOCUMENTS

A u to d e s k D o c s /2

G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.M .R

.r v t

/2

/2

:2

:3

P

M

B08-M300

OVERALL AND ENLARGED MECHANICAL

DEMO AND NEW PLANS

EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

2121 North Ave, Grand Junction, CO 81501

575-21-700

12/17/2024 BRE WLJ

N

1/8" = 1'-0"

OVERALL MECHANICAL PLAN

N

1/2" = 1'-0"

ENLARGED IT ROOM - MECHANICAL NEW PLAN

KEYNOTES

006 REMOVE EXISTING DIFFUSER AND ASSOCIATED DUCTWORK BACK

TO THE MAIN BRANCH AND CAP.

010 REMOVE EXISTING RETURN GRILLE.

111 PROVIDE PRE-TAB ON ALL EXISTING AIR TERMINALS ASSOCIATED

WITH SUPPLY DUCTWORK.

112 PROVIDE POST-TAB ON ALL EXISTING TERMINALS ASSOCIATED

WITH SUPPLY DUCTWORK. BALANCE AIR TERMINALS TO PRE-TAB

MEASURMENT.

203 ROUTE AND SIZE REFRIGERANT PIPIING FROM CONDENSING UNIT

TO INDOOR UNIT PER MANUFACTURES INSTRUCTIONS.

703 INSTALL CONDENSING UNIT ON PREMANUFACTURED CONDENSING

UNIT PAD. CONDENSING UNIT TO BE PROVIDED WITH 24" STAND

TO ELEVATE UNIT ABOVE GRADE.

900 RELOCATE EXISTING PLUMBING AND MECHANICAL

INFRASTRUCTURE TO AVOID NEW TR. FIELD VERIFY EXISTING

INFRASTRUCTURE AND NOTIFY ENGINEER IN WRITING IF FURTHER

CLARIFICATION IS NEEDED FOR RELOCATION OF EXISTING

INFRASTRUCTURE PRIOR TO BIDDING.

1200 PROVIDE WITH EXTERNAL CONDENSATE PUMP. ROUTE DRAIN

FROM ADJACENT CRAC UNIT TO TERMINATE INTO CONDENSATE

PUMP. REFER TO OVERALL PLAN FOR CONDENSATE PIPE

TERMINATION.

1201 ROUTE NEW 3/4" PUMPED CONDENSATE PIPING TO RESTROOM

AND TERMINATE INTO SINK TAILPIECE WITH AIR GAP.

N

1/2" = 1'-0"

ENLARGED IT ROOM - MECHANICAL DEMOLITION PLAN

1' 2' 4'

1/2" = 1'-0"

0'4' 8' 16'

1/8" = 1'-0"

0'

1' 2' 4'

1/2" = 1'-0"

0'

Revisions: Date:

T H

B09-M300

MECHANICAL

MECHANICAL

OFFICE, STAFF

BOILER PLANT

MECHANICAL

OFFICE, STAFF

MECHANICAL

B100

MECHANICAL

TEMPORARY ELEC.

107A

CU-9-1

1"LIQ

1"SUC

FCU-9-1

CP-11206

L

IQ

S U

C

SG-1

6x6/50 6ø

F-1

3/4"D

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2023 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

7600 E ORCHARD ROAD

SUITE 250-S

GREENWOOD VILLAGE, CO 80111

P: 303.796.6000 www.imegcorp.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

PROJECT #22007411.00

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

100% CONSTRUCTION

DOCUMENTS

A u to d e s k D o c s /2

G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.M .R

.r v t

/2

/2

:3

:0

P

M

B09-M300

ENLARGED MECHANICAL DEMO AND NEW

PLANS

EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

2121 North Ave, Grand Junction, CO 81501

575-21-700

12/17/2024 BRE WLJ

KEYNOTES

203 ROUTE AND SIZE REFRIGERANT PIPIING FROM CONDENSING

UNIT TO INDOOR UNIT PER MANUFACTURES INSTRUCTIONS.

703 INSTALL CONDENSING UNIT ON PREMANUFACTURED

CONDENSING UNIT PAD. CONDENSING UNIT TO BE PROVIDED

WITH 24" STAND TO ELEVATE UNIT ABOVE GRADE.

706 PROVIDE NEW IN-LINE FAN WITH FILTER SECTION, INLET OF FAN

TO BE OPEN TO ADJACENT SPACE.

900 RELOCATE EXISTING PLUMBING AND MECHANICAL

INFRASTRUCTURE TO AVOID NEW TR. FIELD VERIFY EXISTING

INFRASTRUCTURE AND NOTIFY ENGINEER IN WRITING IF

FURTHER CLARIFICATION IS NEEDED FOR RELOCATION OF

EXISTING INFRASTRUCTURE PRIOR TO BIDDING.

1206 PROVIDE WITH EXTERNAL CONDENSATE PUMP AND ROUTE

CONDENSATE PIPING TO NEAREST IN-DIRECT DRAIN.

N

1/8" = 1'-0"

OVERALL MECHANICAL PLAN

N

1/2" = 1'-0"

ENLARGED IT ROOM - MECHANICAL DEMOLITION PLAN

N

1/2" = 1'-0"

ENLARGED IT ROOM - MECHANICAL NEW PLAN

4' 8' 16'

1/8" = 1'-0"

0'

1" = 20'

1' 2' 4'

1/2" = 1'-0"

0' 10' 20' 40'

1" = 20'

1' 2' 4'

1/2" = 1'-0"

0' 10' 20' 40'

Revisions: Date:

B35-M300

CORR

TR ROOM

GROUP THERAPY

CU-35-1

SG-1

6x6/50

14x14

6ø

TR ROOM

CORR

GROUP THERAPY

FCU-35-1

CP-13/4"D 1200

1/2"CW

F-11102

LIQ

SUC

SG-1

6x6/50

6ø

1/2"CW

3/4"D

SG-1

8x16/50

8ø

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2023 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

7600 E ORCHARD ROAD

SUITE 250-S

GREENWOOD VILLAGE, CO 80111

P: 303.796.6000 www.imegcorp.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

PROJECT #22007411.00

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

100% CONSTRUCTION

DOCUMENTS

A u to d e s k D o c s /2

G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.M .R

.r v t

/2

/2

:4

:2

P

M

B35-M300

OVERALL AND ENLARGED MECHANICAL

DEMO AND NEW PLANS

EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

2121 North Ave, Grand Junction, CO 81501

575-21-700

12/17/2024 BRE WLJ

N

1/8" = 1'-0"

OVERALL MECHANICAL PLAN

N

1/2" = 1'-0"

ENLARGED IT ROOM - MECHANICAL NEW PLAN

KEYNOTES

116 CONNECT TO EXISTING VERTICAL MAIN SUPPLY PLENUM IN

CORRIDOR.

203 ROUTE AND SIZE REFRIGERANT PIPIING FROM CONDENSING UNIT

TO INDOOR UNIT PER MANUFACTURES INSTRUCTIONS.

703 INSTALL CONDENSING UNIT ON PREMANUFACTURED CONDENSING

UNIT PAD. CONDENSING UNIT TO BE PROVIDED WITH 24" STAND

TO ELEVATE UNIT ABOVE GRADE.

900 RELOCATE EXISTING PLUMBING AND MECHANICAL

INFRASTRUCTURE TO AVOID NEW TR. FIELD VERIFY EXISTING

INFRASTRUCTURE AND NOTIFY ENGINEER IN WRITING IF FURTHER

CLARIFICATION IS NEEDED FOR RELOCATION OF EXISTING

INFRASTRUCTURE PRIOR TO BIDDING.

1101 ROUTE NEW 1/2" CW PIPE FROM RESTROOM GROUP TO TR ROOM

FOR HUMIDIFICATION.

1102 ROUTE CW PIPING TO NEW WATER FILTER AND CONNECT TO NEW

CRAC UNIT.

1200 PROVIDE WITH EXTERNAL CONDENSATE PUMP. ROUTE DRAIN

FROM ADJACENT CRAC UNIT TO TERMINATE INTO CONDENSATE

PUMP. REFER TO OVERALL PLAN FOR CONDENSATE PIPE

TERMINATION.

1201 ROUTE NEW 3/4" PUMPED CONDENSATE PIPING TO RESTROOM

AND TERMINATE INTO SINK TAILPIECE WITH AIR GAP.

N

1/2" = 1'-0"

ENLARGED IT ROOM - MECHANICAL DEMOLITION PLAN

4' 8' 16'

1/8" = 1'-0"

0' 1' 2' 4'

1/2" = 1'-0"

0'

1' 2' 4'

1/2" = 1'-0"

0'

Revisions: Date:

B36-M300

TR ROOM

ENTRY

VESTIBULE

FCU-36-1

CU-36-1

FCU-36-2

CU-36-2

CP-1

TR ROOM

/4

"D

/2

"C W

F-11102

SG-1

6x6/55

6ø x1

1"SUC

1"LIQ

TR ROOM

SD SD

ø ø x1

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2023 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

7600 E ORCHARD ROAD

SUITE 250-S

GREENWOOD VILLAGE, CO 80111

P: 303.796.6000 www.imegcorp.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

PROJECT #22007411.00

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

100% CONSTRUCTION

DOCUMENTS

A u to d e s k D o c s /2

G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.M .R

.r v t

/2

/2

:1

:1

P

M

B36-M300

B36 - OVERALL AND ENLARGED MECHANICAL

DEMO AND NEW PLANS

EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

2121 North Ave, Grand Junction, CO 81501

575-21-700

12/17/2024 BRE WLJ

N

1" = 10'-0"

B36 - OVERALL MECHANICAL PLAN

N

1/2" = 1'-0"

ENLARGED IT ROOM - MECHANICAL NEW PLAN

KEYNOTES

006 REMOVE EXISTING DIFFUSER AND ASSOCIATED DUCTWORK BACK

TO THE MAIN BRANCH AND CAP.

010 REMOVE EXISTING RETURN GRILLE.

203 ROUTE AND SIZE REFRIGERANT PIPIING FROM CONDENSING UNIT

TO INDOOR UNIT PER MANUFACTURES INSTRUCTIONS.

703 INSTALL CONDENSING UNIT ON PREMANUFACTURED CONDENSING

UNIT PAD. CONDENSING UNIT TO BE PROVIDED WITH 24" STAND

TO ELEVATE UNIT ABOVE GRADE.

900 RELOCATE EXISTING PLUMBING AND MECHANICAL

INFRASTRUCTURE TO AVOID NEW TR. FIELD VERIFY EXISTING

INFRASTRUCTURE AND NOTIFY ENGINEER IN WRITING IF FURTHER

CLARIFICATION IS NEEDED FOR RELOCATION OF EXISTING

INFRASTRUCTURE PRIOR TO BIDDING.

1101 ROUTE NEW 1/2" CW PIPE FROM RESTROOM GROUP TO TR ROOM

FOR HUMIDIFICATION.

1102 ROUTE CW PIPING TO NEW WATER FILTER AND CONNECT TO NEW

CRAC UNIT.

1200 PROVIDE WITH EXTERNAL CONDENSATE PUMP. ROUTE DRAIN

FROM ADJACENT CRAC UNIT TO TERMINATE INTO CONDENSATE

PUMP. REFER TO OVERALL PLAN FOR CONDENSATE PIPE

TERMINATION.

1201 ROUTE NEW 3/4" PUMPED CONDENSATE PIPING TO RESTROOM

AND TERMINATE INTO SINK TAILPIECE WITH AIR GAP.

N

1/2" = 1'-0"

ENLARGED IT ROOM - MECHANICAL DEMOLITION PLAN

1" = 10'

5' 10' 20'0'

1' 2' 4'

1/2" = 1'-0"

0'

1' 2' 4'

1/2" = 1'-0"

0'

Revisions: Date:

H T

B37-M300

PROPOSED STORAGE

A108A

PROPOSED TR ROOM

A108B

PROPOSED STORAGE

A108C

MANAGERS OFFICE

A109

RR.

A110

OPEN OFFICE

67TR ROOM

A112

CU-37-1 CU-37-2

FCU-37-1

CP-1

FCU-37-2

/4

"D

/4

"C W

F-1

S U

C

L

IQ

S U

C

L

IQ

6ø

SG-1

6x6/50

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2023 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

7600 E ORCHARD ROAD

SUITE 250-S

GREENWOOD VILLAGE, CO 80111

P: 303.796.6000 www.imegcorp.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

PROJECT #22007411.00

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

100% CONSTRUCTION

DOCUMENTS

A u to d e s k D o c s /2

G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.M .R

.r v t

/2

/2

:1

:2

P

M

B37-M300

OVERALL AND ENLARGED MECHANICAL

DEMO AND NEW PLANS

EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

2121 North Ave, Grand Junction, CO 81501

575-21-700

12/17/2024 BRE WLJ

N

1" = 10'-0"

OVERALL MECHANICAL PLAN

N

1/2" = 1'-0"

ENLARGED IT ROOM - MECHANICAL NEW PLAN

N

1/2" = 1'-0"

ENLARGED IT ROOM - MECHANICAL DEMOLITION PLAN

KEYNOTES

117 CONNECT TO EXISTING VERTICAL MAIN SUPPLY PLENUM.

203 ROUTE AND SIZE REFRIGERANT PIPIING FROM CONDENSING UNIT

TO INDOOR UNIT PER MANUFACTURES INSTRUCTIONS.

703 INSTALL CONDENSING UNIT ON PREMANUFACTURED CONDENSING

UNIT PAD. CONDENSING UNIT TO BE PROVIDED WITH 24" STAND

TO ELEVATE UNIT ABOVE GRADE.

1101 ROUTE NEW 1/2" CW PIPE FROM RESTROOM GROUP TO TR ROOM

FOR HUMIDIFICATION.

1102 ROUTE CW PIPING TO NEW WATER FILTER AND CONNECT TO NEW

CRAC UNIT.

1200 PROVIDE WITH EXTERNAL CONDENSATE PUMP. ROUTE DRAIN

FROM ADJACENT CRAC UNIT TO TERMINATE INTO CONDENSATE

PUMP. REFER TO OVERALL PLAN FOR CONDENSATE PIPE

TERMINATION.

1201 ROUTE NEW 3/4" PUMPED CONDENSATE PIPING TO RESTROOM

AND TERMINATE INTO SINK TAILPIECE WITH AIR GAP.

1" = 10'

5' 10' 20'0'

1' 2' 4'

1/2" = 1'-0"

0'

1' 2' 4'

1/2" = 1'-0"

0'

Revisions: Date:

B45-M300

IT / SECURITY / TELECOM

CU-45-1

CU-45-2

IT / SECURITY / TELECOM

FCU-45-1

FCU-45-2

CP-1

3/4"D

3/4"CW

1102F-1

S U

C

L

IQ

S U

C

L

IQ

SG-1

6x6/70 ø

SG-E

24x12

SS-1 SS-1

011 011

SG-E

24x12

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2023 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

7600 E ORCHARD ROAD

SUITE 250-S

GREENWOOD VILLAGE, CO 80111

P: 303.796.6000 www.imegcorp.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

PROJECT #22007411.00

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

100% CONSTRUCTION

DOCUMENTS

A u to d e s k D o c s /2

G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.M .R

.r v t

/2

/2

:2

:1

P

M

B45-M300

OVERALL AND ENLARGED MECHANICAL

DEMO AND NEW PLANS

EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

2121 North Ave, Grand Junction, CO 81501

575-21-700

12/17/2024 BRE WLJ

N

1/16" = 1'-0"

OVERALL MECHANICAL PLAN

N

1/2" = 1'-0"

ENLARGED IT ROOM - MECHANICAL NEW PLAN

KEYNOTES

011 REMOVE EXISTING MINI-SPLIT AND ASSOCIATED CONDENSING

UNIT, POWER, CONTROLS, AND APPURTENANCES.

203 ROUTE AND SIZE REFRIGERANT PIPIING FROM CONDENSING UNIT

TO INDOOR UNIT PER MANUFACTURES INSTRUCTIONS.

703 INSTALL CONDENSING UNIT ON PREMANUFACTURED CONDENSING

UNIT PAD. CONDENSING UNIT TO BE PROVIDED WITH 24" STAND

TO ELEVATE UNIT ABOVE GRADE.

1101 ROUTE NEW 1/2" CW PIPE FROM RESTROOM GROUP TO TR ROOM

FOR HUMIDIFICATION.

1102 ROUTE CW PIPING TO NEW WATER FILTER AND CONNECT TO NEW

CRAC UNIT.

1200 PROVIDE WITH EXTERNAL CONDENSATE PUMP. ROUTE DRAIN

FROM ADJACENT CRAC UNIT TO TERMINATE INTO CONDENSATE

PUMP. REFER TO OVERALL PLAN FOR CONDENSATE PIPE

TERMINATION.

1201 ROUTE NEW 3/4" PUMPED CONDENSATE PIPING TO RESTROOM

AND TERMINATE INTO SINK TAILPIECE WITH AIR GAP.

N

1/2" = 1'-0"

ENLARGED IT ROOM - MECHANICAL DEMOLITION PLAN

8' 16' 32'

1/16" = 1'-0"

0' 1' 2' 4'

1/2" = 1'-0"

0'

1' 2' 4'

1/2" = 1'-0"

0'

Revisions: Date:

575-700.B01.M.R23 B01-M200 Addendum 2
575-700.B01.M.R23 M501 Addendum 2
575-700.B05.M.R23 B05-M300 Addendum 2
575-700.B06.M.R23 B06-M300 Addendum 2
575-700.B08.M.R23 B08-M300 Addendum 2
575-700.B09.M.R23 B09-M300 Addendum 2
575-700.B35.M.R23 B35-M300 Addendum 2
575-700.B36.M.R23 B36-M300 Addendum 2
575-700.B37.M.R23 B37-M300 Addendum 2
575-700.B45.M.R23 B45-M300 Addendum 2

File details come from the government source that posted it. Updated .