These architectural demolition and renovation documents detail the extensive interior modifications planned for multiple buildings at the Grand Junction VA Medical Center. The project involves selective demolition and reconstruction of various rooms and spaces across Buildings 1, 5, 6, 8, 9, 12, 20, 35, 36, and 37, with a focus on creating new Telecommunications (TR) rooms and upgrading interior finishes. Key renovation elements include installing new metal stud walls, replacing ceiling systems, installing fire-rated plywood panels, relocating fire extinguishers, and creating new room configurations while maintaining existing building structures. The documents specify detailed demolition schedules, plan notes for construction, and precise instructions for wall assemblies, ceiling modifications, and door replacements, with an emphasis on maintaining fire compartmentalization and meeting VA construction standards.

View the file

Other files

File Type Posted
S05 - 575-21-700 Tech Questions responses updated - GJ CO - 8-28-25.docx DOCX document
For Information Only - B44_2013_TERRACON_41013_Parking_Garage.pdf PDF
575-700.VA Civil Grand Junction EHRM Addendum 2 - Fiber Optic Manhole Detail.pdf PDF
575-700.VA Telecom Grand Junction EHRM Addendum 2 - Changed Sheets Only.pdf PDF
For Information Only - B9_2019_Geotech_Report_HB_Boiler_Plant.pdf PDF
575-700.VA Mechanical Grand Junction EHRM Addendum 2 - Changed Sheets Only.pdf PDF
S06- Amendment 0009.pdf PDF
S06 - Amendment 0008.pdf PDF
S06- Amendment 0007.pdf PDF
32 05 23 Cement and Concrete for Exterior Improvements.pdf PDF
32 12 16 Asphalt Paving.pdf PDF
CIP concrete short form.pdf PDF
S06- Amendment 0006- Bid due date extended 08-28-25.pdf PDF
S06- Amendment 0005- Bid due date extended.pdf PDF
S06- Amendment 0005- Bid due date extended.pdf PDF
B12 Roof 20250730.pdf PDF
S06- Amendment 0004- Bid opening info and all tech questions responses.pdf PDF
4 Utility Plan.pdf PDF
B7 Roof 20250730.pdf PDF
S05 - 575-21-700 All Tech Questions Responses - CO.docx DOCX document
S06- Amendment 0003 - DB Wages updated - Bid extension - RFI answers.pdf PDF
S05 - 575-21-700 Tech Questions Responses- GJ CO 07-28-25.docx DOCX document
P07- Updated Wages Determination - Grand Junction CO 07-25-2025.pdf PDF
S04- Signed site visit sign in sheet - 57521700 CO.pdf PDF
S06- Amendment 0002- Signed site visit sheet.pdf PDF
ATT 12- Drawings - EHRM - Grand Junction - CO.pdf PDF
ATT 13- Specifications-Combined- EHRM - Grand Junction CO.pdf PDF
ATT 4- Grand Junction CO - SPECS 07-03-25- Addendum.pdf PDF
ATT 11 - Site Visit Instructions.pdf PDF
ATT 1- Grand Junction EHRM - Drawings 07-03-25 - Addendum.pdf PDF
S06 - Amendment 0001.pdf PDF
ATT 7 - Spec 01 31 00.01 Project Management and Coordination.pdf PDF
ATT 3- Estimated Construction Schedule- EHRM- Grand Junction CO.pdf PDF
ATT 10 - GEO Reports B20.pdf PDF
ATT 6 - Wages Determination - Grand Junction CO.pdf PDF
ATT 5- 100 CD Basis of Design -Combined- Grand Junction CO.pdf PDF
ATT 1- Grand Junction EHRM - Drawings 07-03-25.pdf PDF
ATT 8 - Limitations on Subcontracting.docx DOCX document
36C77625B0039.pdf PDF
ATT 11- Site Visit Instructions.pdf PDF
ATT 4- Grand Junction CO - SPECS 07-03-25.pdf PDF
ATT 2- Parking Guidelines Grand Junction VAMC.pdf PDF
ATT 9- Hazardous Materials Report.pdf PDF
Show all 43

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

3 4

15' - 0"

2" 3' - 4"

1 8

15' - 0"

129 SF

TR ROOM

3' - 0"

NEW PIPING

CHASE

6" 3' - 4"

OPEN TO DECK

TR ROOM

3 4

3' - 4" 2"

8 1

8 1

12' - 2"

158 SF

TR ROOM

3' - 0"

NEW PIPING

CHASE

3' - 4" 4"

3' - 1 1/2" 4' - 7"

14 12' - 6"

TR ROOM

OPEN TO DECK

WALL

DOOR

CEILING

AND GRID

DEMO LEGEND

RATED WALL

WALL TYPES

SMOKE BARRIER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

KEYPLAN N

A

B C

D

B C

D

330 N. Mead St, Suite 100 Wichita, KS 67202

Phone: (316) 262-2500 www.hfgarchitecture.com

EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

575-21-700

12/17/2024

2121 North Ave, Grand Junction, CO 81501

JW JS

A u to d e s k D o c s /2

V

A G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.A

R

.r v t

/9 /2

:1

:1

P

M

B01-A101

FIRST FLOOR ENLARGED PLANS

1/4" = 1'-0"

BLDG. 1 - FIRST FLOOR DEMO PLAN 1684

1/4" = 1'-0"

BLDG. 1 - FIRST FLOOR DEMO RCP 1684

1/4" = 1'-0"

BLDG. 1 - FIRST FLOOR PLAN ENLARGED 1684

1/4" = 1'-0"

BLDG. 1 - FIRST FLOOR RCP 1684

1/4" = 1'-0"

BLDG. 1 - FIRST FLOOR DEMO PLAN 1402

1/4" = 1'-0"

BLDG. 1 - FIRST FLOOR DEMO RCP 1402

1/4" = 1'-0"

BLDG. 1 - FIRST FLOOR PLAN ENLARGED 1402

1/4" = 1'-0"

BLDG. 1 - FIRST FLOOR RCP 1402

DEMO SCHEDULE

1 REMOVE WALL PARTITIONS INCLUDING DOORS, FRAMES, COUNTERS, CABINETS AND SHELVING TO

EXTENTS SHOWN.

2 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR OWNER.

3 REMOVE ALL FLOORING AND WALL FINISHES INCLUDING WALL PROTECTION AND CORNER GUARDS.

EXISTING GYP. BD. TO REMAIN.

4 REMOVE CEILING IN ITS ENTIRETY. SEE DEMOLITION REFLECTED CEILING PLAN FOR EXTENTS.

5 REMOVE PORTION OF WALL TO PREPARE FOR INSTALLATION OF NEW DOOR.

6 REMOVE MILLWORK IN ITS ENTIRETY.

7 REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED PIPING AS APPLICABLE. SEE PLUMBING PLANS.

PREPARE/ LEVEL SURFACES TO RECEIVE NEW FINISHES.

8 REMOVE EXISTING FURNITURE, EQUIPMENT, BASE, CHAIR RAIL & SHELVING - VERIFY/SALVAGE FOR

OWNER.

9 REMOVE HEADER/ WALL ABOVE EXISTING DOOR TO ACCOMMODATE NEW DOOR.

11 REMOVE FLOORING TO EXTENTS SHOWN - PREP FOR NEW FLOORING.

12 SALVAGE & RE-USE EXISTING GLASS DECORATIVE PANELS. SALVAGE & RE-USE EXISTING WALL

STANDOFFS 12 TOTAL.

13 DEMO PORTION OF EXISTING WALL. PREPARE FOR NEW 6" RATED WALL ASSEMBLY AND FEC.

14 REMOVE EXISTING WOOD CABINET AND TRIM. SALVAGE FOR OWNER

15 REMOVE EXISTING OMNICELL UNIT. REF 2/B20-A101 FOR NEW LOCATION. VERIFY WITH VA

16 REMOVE EXISTING GLASS PANE. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS GLASS PANEL. G.C. TO VERIFY PANEL THICKNESS PRIOR TO BIDDING.

ALUMINUM FINISH SHALL MATCH EXISTING WINDOW FRAME. REFER TO SPEC 07 43 00

17 EXISTING FAN COIL UNIT. REF. MECHANICAL FOR DEMO/REMOVAL

18 REMOVE EXISTING BED DOCKER. SALVAGE FOR OWNER.

19 REMOVE EXISTING SIDEWALL LOUVER. G.C. TO VERIFY WITH OWNER PRIOR TO REMOVAL.

20 VERIFY WITH MECHANICAL AND ELECTRICAL FOR ANY REQ'D. RECEPTACLE & MED GAS

REMOVAL/DEMO/ABANDONMENT.

DEMO RCP SCHEDULE

1 EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED - SALVAGE FOR

OWNER.

2 PORTION OF EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED TO

EXTENTS SHOWN - SALVAGE FOR OWNER.

3 EXISTING GYP. BOARD SOFFIT AND ALL OF ITS COMPONENTS TO BE REMOVED.

4 EXISTING GYP. BOARD CEILING AND ALL OF ITS COMPONENTS TO BE REMOVED.

5 EXISTING PIPING - REFERENCE PLUMBING DRAWINGS.

6 EXISTING SPRINKLER HEAD/ LINE - REFERENCE PLUMBING DRAWINGS.

7 EXISTING DIFFUSER - REFERENCE MECHANICAL DRAWINGS. SALVAGE FOR OWNER.

8 NON-RATED ICRA/CONSTRUCTION BARRIERS ARE PERMITTED ONLY WHERE THE

SPRINKLERS IN THE CONSTRUCTION AREA REMAIN IN SERVICE. REPLACE THE

EXISTING SPRINKLER(S) IN THE TR WITH NEW UPRIGHT SPRINKLERS AT THE TIME THE

CEILING IS REMOVED IN ORDER TO MAINTAIN SPRINKLER PROTECTION IN THE

CONSTRUCTION AREA. - REFERENCE PLUMBING.

9 EXISTING CEILING LIGHTS TO BE REMOVED - SALVAGE FOR OWNER.

10 DEMO/MODIFY PORTION OF CEILING TILE TO ACCOMODATE STUDS THAT EXTEND TO

STRUCTURE ABOVE.

11 REMOVE EXISTING CURTAIN TRACK. SALVAGE FOR OWNER.

2' 4' 8'0'

1/4" = 1'-0"

N

PLAN NOTES - FLOOR PLAN

1 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. CONNECTED TO STRUCTURE ABOVE W/ 5/8" GYP BD (BOTH SIDES)

PAINTED TO EXTEND TO DECK ABOVE.

2 INFILL EXISTING OPENING WITH CONSTRUCTION METHODS AND MATERIALS THAT MATCH EXISTING

CONSTRUCTION.

3 PROVIDE FULL HEIGHT PAINTED FIRE RATED, PRESSURE TREATED 3/4" PLYWOOD [8'-0" MIN. AFF.] OVER EXISTING OR NEW PAINTED GYP. BOARD WALL. VERIFY EXACT REQUIREMENTS WITH ELECTRICAL PLANS AND SPECIFICATIONS. CONTRACTOR TO SHOW PROOF OF PLYWOOD FIRE RATING BEFORE PLYWOOD IS PAINTED.

5 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (ONE SIDE) PAINTED TO

EXTEND TO DECK.

6 INSTALL SALVAGED GLASS DECORATIVE PANELS AND WALL STANDOFFS. PROVIDE NEW WALL STANDOFFS AS

REQUIRED TO MATCH EXISTING. REF ELEVATION 3-B01-A109 FOR MOUNTING HEIGHTS.

7 EXTEND METAL STUD WALL FROM EXISTING STUD WALL TO DECK ABOVE. EXTEND GYP BOARD TO DECK ABOVE

(BOTH SIDES) G.C. TO VERIFY PRIOR TO BIDDING.

8 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.

9 PATCH/FILL VOID HOLES IN GYP BOARD TO DECK (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.

10 G.C. TO PROVIDE AND INSTALL A 20" X 6" MIN. METAL TRANSFER DOOR GRILLE WITHIN EXISTING DOOR. TO BE

PAINTED THE SAME COLOR AS THE ADJACENT DOOR FRAME.

11 NEW 6" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (BOTH SIDES) PAINTED TO

EXTEND TO DECK. MATCH EXISTING WALL ASSEMBLY RATING.

12 PATCH, INFILL, PAINT AS REQ'D AT REMOVED SIDEWALL LOUVER.

13 AT REMOVED FAN COIL EXHAUST OPENING, INFILL WITH SAME WALL ASSEMBLY AND FINISH EA. SIDE.

14 ALL TR ROOM WALLS MUST BE SEALED TO MAINTAIN A COMPARTMENT PER NFPA 13.

2' 4' 8'0'

1/4" = 1'-0"

RCP NOTE SCHEDULE

1 INFILL CEILING WITH CONSTRUCTION METHODS AND MATERIALS

THAT MATCH EXISTING CEILING.

2 REFERENCE ELECTRICAL FOR NEW LIGHTING LAYOUT.

3 EXTEND GYP TO ABOVE CEILING AND EXTEND STUDS TO

STRUCTURE ABOVE.

Revisions: Date: 08/22/25 Addendum 2 08/22/25

EXAM

ROOM

8' - 2"

EXISTING

88 SF

EXAM

ROOM

EXIST.

7' - 4"

3 8

EXAM

ROOM

30 SF

SOILED

HOLDING

3' - 9"

EXIST.

3 8

SOILED

HOLDING

OPEN TO DECK

SOILED

HOLDING

WALL

DOOR

CEILING

AND GRID

DEMO LEGEND

EXAM

ROOM

SOILED

HOLDING

E01

E

E

E04

E

E

E

E

E03

E

E

E

E09

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

KEYPLAN N

A

B C

D

B C

D

330 N. Mead St, Suite 100 Wichita, KS 67202

Phone: (316) 262-2500 www.hfgarchitecture.com

EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

575-21-700

12/17/2024

2121 North Ave, Grand Junction, CO 81501

JW JS

A u to d e s k D o c s /2

G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.A

R

.r v t

/9 /2

:1

:2

P

M

B01-A102

FIRST FLOOR ENLARGED PLANS

1/4" = 1'-0"

BLDG. 1 - FIRST FLOOR RCP 1687

1/4" = 1'-0"

BLDG. 1 - FIRST FLOOR PLAN ENLARGED 1687

1/4" = 1'-0"

BLDG. 1 - FIRST FLOOR DEMO PLAN 1687

1/4" = 1'-0"

BLDG. 1 - FIRST FLOOR PLAN ENLARGED 1691

1/4" = 1'-0"

BLDG. 1 - FIRST FLOOR DEMO PLAN 1691

1/4" = 1'-0"

BLDG. 1 - FIRST FLOOR RCP 1691

DEMO SCHEDULE

1 REMOVE WALL PARTITIONS INCLUDING DOORS, FRAMES, COUNTERS, CABINETS AND SHELVING TO

EXTENTS SHOWN.

2 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR OWNER.

3 REMOVE ALL FLOORING AND WALL FINISHES INCLUDING WALL PROTECTION AND CORNER GUARDS.

EXISTING GYP. BD. TO REMAIN.

4 REMOVE CEILING IN ITS ENTIRETY. SEE DEMOLITION REFLECTED CEILING PLAN FOR EXTENTS.

5 REMOVE PORTION OF WALL TO PREPARE FOR INSTALLATION OF NEW DOOR.

6 REMOVE MILLWORK IN ITS ENTIRETY.

7 REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED PIPING AS APPLICABLE. SEE PLUMBING PLANS.

PREPARE/ LEVEL SURFACES TO RECEIVE NEW FINISHES.

8 REMOVE EXISTING FURNITURE, EQUIPMENT, BASE, CHAIR RAIL & SHELVING - VERIFY/SALVAGE FOR

OWNER.

9 REMOVE HEADER/ WALL ABOVE EXISTING DOOR TO ACCOMMODATE NEW DOOR.

11 REMOVE FLOORING TO EXTENTS SHOWN - PREP FOR NEW FLOORING.

12 SALVAGE & RE-USE EXISTING GLASS DECORATIVE PANELS. SALVAGE & RE-USE EXISTING WALL

STANDOFFS 12 TOTAL.

13 DEMO PORTION OF EXISTING WALL. PREPARE FOR NEW 6" RATED WALL ASSEMBLY AND FEC.

14 REMOVE EXISTING WOOD CABINET AND TRIM. SALVAGE FOR OWNER

15 REMOVE EXISTING OMNICELL UNIT. REF 2/B20-A101 FOR NEW LOCATION. VERIFY WITH VA

16 REMOVE EXISTING GLASS PANE. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS GLASS PANEL. G.C. TO VERIFY PANEL THICKNESS PRIOR TO BIDDING.

ALUMINUM FINISH SHALL MATCH EXISTING WINDOW FRAME. REFER TO SPEC 07 43 00

17 EXISTING FAN COIL UNIT. REF. MECHANICAL FOR DEMO/REMOVAL

18 REMOVE EXISTING BED DOCKER. SALVAGE FOR OWNER.

19 REMOVE EXISTING SIDEWALL LOUVER. G.C. TO VERIFY WITH OWNER PRIOR TO REMOVAL.

20 VERIFY WITH MECHANICAL AND ELECTRICAL FOR ANY REQ'D. RECEPTACLE & MED GAS

REMOVAL/DEMO/ABANDONMENT.

PLAN NOTES - FLOOR PLAN

1 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. CONNECTED TO STRUCTURE ABOVE W/ 5/8" GYP BD (BOTH SIDES)

PAINTED TO EXTEND TO DECK ABOVE.

2 INFILL EXISTING OPENING WITH CONSTRUCTION METHODS AND MATERIALS THAT MATCH EXISTING

CONSTRUCTION.

3 PROVIDE FULL HEIGHT PAINTED FIRE RATED, PRESSURE TREATED 3/4" PLYWOOD [8'-0" MIN. AFF.] OVER EXISTING OR NEW PAINTED GYP. BOARD WALL. VERIFY EXACT REQUIREMENTS WITH ELECTRICAL PLANS AND SPECIFICATIONS. CONTRACTOR TO SHOW PROOF OF PLYWOOD FIRE RATING BEFORE PLYWOOD IS PAINTED.

5 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (ONE SIDE) PAINTED TO

EXTEND TO DECK.

6 INSTALL SALVAGED GLASS DECORATIVE PANELS AND WALL STANDOFFS. PROVIDE NEW WALL STANDOFFS AS

REQUIRED TO MATCH EXISTING. REF ELEVATION 3-B01-A109 FOR MOUNTING HEIGHTS.

7 EXTEND METAL STUD WALL FROM EXISTING STUD WALL TO DECK ABOVE. EXTEND GYP BOARD TO DECK ABOVE

(BOTH SIDES) G.C. TO VERIFY PRIOR TO BIDDING.

8 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.

9 PATCH/FILL VOID HOLES IN GYP BOARD TO DECK (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.

10 G.C. TO PROVIDE AND INSTALL A 20" X 6" MIN. METAL TRANSFER DOOR GRILLE WITHIN EXISTING DOOR. TO BE

PAINTED THE SAME COLOR AS THE ADJACENT DOOR FRAME.

11 NEW 6" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (BOTH SIDES) PAINTED TO

EXTEND TO DECK. MATCH EXISTING WALL ASSEMBLY RATING.

12 PATCH, INFILL, PAINT AS REQ'D AT REMOVED SIDEWALL LOUVER.

13 AT REMOVED FAN COIL EXHAUST OPENING, INFILL WITH SAME WALL ASSEMBLY AND FINISH EA. SIDE.

14 ALL TR ROOM WALLS MUST BE SEALED TO MAINTAIN A COMPARTMENT PER NFPA 13.

RCP NOTE SCHEDULE

1 INFILL CEILING WITH CONSTRUCTION METHODS AND MATERIALS

THAT MATCH EXISTING CEILING.

2 REFERENCE ELECTRICAL FOR NEW LIGHTING LAYOUT.

3 EXTEND GYP TO ABOVE CEILING AND EXTEND STUDS TO

STRUCTURE ABOVE.

1/4" = 1'-0"

BLDG. 1 - EQUIPMENT - FIRST FLOOR

PLAN ENLARGED 1687 & 1691

EQUIPMENT SCHEDULE

Equipment Number Equipment Description

Provided By

Installed By Electrical Data Mechanical Plumbing COMMENTS

E01 HAND SANITIZER DISPENSER VA GC No No No No

E02 SOILED CART VA VA No No No No

E03 GUEST CHAIR VA VA No No No No

E04 CUBICLE CURTAIN AND

TRACK

GC GC No No No No

E05 TASK CHAIR VA VA No No No No

E06 SOAP DISPENSER VA GC No No No No

E07 PAPER TOWEL DISPENSER VA GC No No No No

E08 SHARPS VA GC No No No No

E09 EXAM TABLE VA VA Yes No No No

E10 48" WIDE DESK VA VA No No No No

E11 COMPUTER VA VA Yes Yes No No

E12 PHONE VA VA No Yes No No

N 2' 4' 8'0'

1/4" = 1'-0"

2' 4' 8'0'

1/4" = 1'-0"

2' 4' 8'0'

1/4" = 1'-0"

3' - 4" 5' - 9"

9' - 5"

1' - 5"

9' - 5"

1 8

EXISTING COLUMN

9' - 0"

147 SF

TR ROOM

1' - 0"

NEW PIPING CHASE

1 5

4" 3' - 4"

OPEN TO DECK

TR ROOM

3 4

8' - 7"

8' - 7"

1 8

104 SF

TR ROOM

8' - 2"

1' - 0"

NEW PIPING CHASE 3' - 0"

TR ROOM

OPEN TO DECK

WALL

DOOR

CEILING

AND GRID

DEMO LEGEND

1' - 0"

ROOM

NEW PIPING CHASE

ROOM

DEMO EXISTING PAPER

TOWEL DISPENSER -

SALVAGE FOR OWNER.

RATED WALL

WALL TYPES

SMOKE BARRIER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

KEYPLAN N

A

B C

D

B C

D

330 N. Mead St, Suite 100 Wichita, KS 67202

Phone: (316) 262-2500 www.hfgarchitecture.com

EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

575-21-700

12/17/2024

2121 North Ave, Grand Junction, CO 81501

JW JS

A u to d e s k D o c s /2

G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.A

R

.r v t

/9 /2

:1

:3

P

M

B01-A104

SECOND FLOOR ENLARGED PLANS

1/4" = 1'-0"

BLDG. 1 - SECOND FLOOR DEMO PLAN 2670

1/4" = 1'-0"

BLDG. 1 - SECOND FLOOR DEMO RCP 2670

1/4" = 1'-0"

BLDG. 1 - SECOND FLOOR PLAN ENLARGED 2670

1/4" = 1'-0"

BLDG. 1 - SECOND FLOOR RCP 2670

1/4" = 1'-0"

BLDG. 1 - SECOND FLOOR DEMO PLAN 2401

1/4" = 1'-0"

BLDG. 1 - SECOND FLOOR DEMO RCP 2401

1/4" = 1'-0"

BLDG. 1 - SECOND FLOOR PLAN ENLARGED 2401

1/4" = 1'-0"

BLDG. 1 - SECOND FLOOR RCP 2401

2' 4' 8'0'

1/4" = 1'-0"

N

DEMO SCHEDULE

1 REMOVE WALL PARTITIONS INCLUDING DOORS, FRAMES, COUNTERS, CABINETS AND SHELVING TO

EXTENTS SHOWN.

2 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR OWNER.

3 REMOVE ALL FLOORING AND WALL FINISHES INCLUDING WALL PROTECTION AND CORNER GUARDS.

EXISTING GYP. BD. TO REMAIN.

4 REMOVE CEILING IN ITS ENTIRETY. SEE DEMOLITION REFLECTED CEILING PLAN FOR EXTENTS.

5 REMOVE PORTION OF WALL TO PREPARE FOR INSTALLATION OF NEW DOOR.

6 REMOVE MILLWORK IN ITS ENTIRETY.

7 REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED PIPING AS APPLICABLE. SEE PLUMBING PLANS.

PREPARE/ LEVEL SURFACES TO RECEIVE NEW FINISHES.

8 REMOVE EXISTING FURNITURE, EQUIPMENT, BASE, CHAIR RAIL & SHELVING - VERIFY/SALVAGE FOR

OWNER.

9 REMOVE HEADER/ WALL ABOVE EXISTING DOOR TO ACCOMMODATE NEW DOOR.

11 REMOVE FLOORING TO EXTENTS SHOWN - PREP FOR NEW FLOORING.

12 SALVAGE & RE-USE EXISTING GLASS DECORATIVE PANELS. SALVAGE & RE-USE EXISTING WALL

STANDOFFS 12 TOTAL.

13 DEMO PORTION OF EXISTING WALL. PREPARE FOR NEW 6" RATED WALL ASSEMBLY AND FEC.

14 REMOVE EXISTING WOOD CABINET AND TRIM. SALVAGE FOR OWNER

15 REMOVE EXISTING OMNICELL UNIT. REF 2/B20-A101 FOR NEW LOCATION. VERIFY WITH VA

16 REMOVE EXISTING GLASS PANE. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS GLASS PANEL. G.C. TO VERIFY PANEL THICKNESS PRIOR TO BIDDING.

ALUMINUM FINISH SHALL MATCH EXISTING WINDOW FRAME. REFER TO SPEC 07 43 00

17 EXISTING FAN COIL UNIT. REF. MECHANICAL FOR DEMO/REMOVAL

18 REMOVE EXISTING BED DOCKER. SALVAGE FOR OWNER.

19 REMOVE EXISTING SIDEWALL LOUVER. G.C. TO VERIFY WITH OWNER PRIOR TO REMOVAL.

20 VERIFY WITH MECHANICAL AND ELECTRICAL FOR ANY REQ'D. RECEPTACLE & MED GAS

REMOVAL/DEMO/ABANDONMENT.

DEMO RCP SCHEDULE

1 EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED - SALVAGE FOR

OWNER.

2 PORTION OF EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED TO

EXTENTS SHOWN - SALVAGE FOR OWNER.

3 EXISTING GYP. BOARD SOFFIT AND ALL OF ITS COMPONENTS TO BE REMOVED.

4 EXISTING GYP. BOARD CEILING AND ALL OF ITS COMPONENTS TO BE REMOVED.

5 EXISTING PIPING - REFERENCE PLUMBING DRAWINGS.

6 EXISTING SPRINKLER HEAD/ LINE - REFERENCE PLUMBING DRAWINGS.

7 EXISTING DIFFUSER - REFERENCE MECHANICAL DRAWINGS. SALVAGE FOR OWNER.

8 NON-RATED ICRA/CONSTRUCTION BARRIERS ARE PERMITTED ONLY WHERE THE

SPRINKLERS IN THE CONSTRUCTION AREA REMAIN IN SERVICE. REPLACE THE

EXISTING SPRINKLER(S) IN THE TR WITH NEW UPRIGHT SPRINKLERS AT THE TIME THE

CEILING IS REMOVED IN ORDER TO MAINTAIN SPRINKLER PROTECTION IN THE

CONSTRUCTION AREA. - REFERENCE PLUMBING.

9 EXISTING CEILING LIGHTS TO BE REMOVED - SALVAGE FOR OWNER.

10 DEMO/MODIFY PORTION OF CEILING TILE TO ACCOMODATE STUDS THAT EXTEND TO

STRUCTURE ABOVE.

11 REMOVE EXISTING CURTAIN TRACK. SALVAGE FOR OWNER.

PLAN NOTES - FLOOR PLAN

1 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. CONNECTED TO STRUCTURE ABOVE W/ 5/8" GYP BD (BOTH SIDES)

PAINTED TO EXTEND TO DECK ABOVE.

2 INFILL EXISTING OPENING WITH CONSTRUCTION METHODS AND MATERIALS THAT MATCH EXISTING

CONSTRUCTION.

3 PROVIDE FULL HEIGHT PAINTED FIRE RATED, PRESSURE TREATED 3/4" PLYWOOD [8'-0" MIN. AFF.] OVER EXISTING OR NEW PAINTED GYP. BOARD WALL. VERIFY EXACT REQUIREMENTS WITH ELECTRICAL PLANS AND SPECIFICATIONS. CONTRACTOR TO SHOW PROOF OF PLYWOOD FIRE RATING BEFORE PLYWOOD IS PAINTED.

5 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (ONE SIDE) PAINTED TO

EXTEND TO DECK.

6 INSTALL SALVAGED GLASS DECORATIVE PANELS AND WALL STANDOFFS. PROVIDE NEW WALL STANDOFFS AS

REQUIRED TO MATCH EXISTING. REF ELEVATION 3-B01-A109 FOR MOUNTING HEIGHTS.

7 EXTEND METAL STUD WALL FROM EXISTING STUD WALL TO DECK ABOVE. EXTEND GYP BOARD TO DECK ABOVE

(BOTH SIDES) G.C. TO VERIFY PRIOR TO BIDDING.

8 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.

9 PATCH/FILL VOID HOLES IN GYP BOARD TO DECK (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.

10 G.C. TO PROVIDE AND INSTALL A 20" X 6" MIN. METAL TRANSFER DOOR GRILLE WITHIN EXISTING DOOR. TO BE

PAINTED THE SAME COLOR AS THE ADJACENT DOOR FRAME.

11 NEW 6" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (BOTH SIDES) PAINTED TO

EXTEND TO DECK. MATCH EXISTING WALL ASSEMBLY RATING.

12 PATCH, INFILL, PAINT AS REQ'D AT REMOVED SIDEWALL LOUVER.

13 AT REMOVED FAN COIL EXHAUST OPENING, INFILL WITH SAME WALL ASSEMBLY AND FINISH EA. SIDE.

14 ALL TR ROOM WALLS MUST BE SEALED TO MAINTAIN A COMPARTMENT PER NFPA 13.

2' 4' 8'0'

1/4" = 1'-0"

1/4" = 1'-0"

BLDG. 1 - SECOND FLOOR PLAN ENLARGED 2661

1/4" = 1'-0"

BLDG. 1 - SECOND FLOOR DEMO PLAN 2661

TR ROOM

4" 3' - 4"

TR ROOM

13' - 6"

97 SF

TR ROOM

3' - 0"

NEW PIPING CHASE

4" 3' - 4"

TR ROOM

15'-10"

OPEN TO DECK

CLEAN

SUPPLY

STORAGE

5' - 1" 7' - 3"

10"

2' - 1"

3 4 8

2 9

6' - 0"

3 4 8

2' - 1"

152 SF

CLEAN

SUPPLY

STORAGE

NEW PIPING CHASE

8' - 2"

4' - 0"

110 SF

TR ROOM

3420A

10' - 1"

EXIST.

3' - 4" 6"

3420A

CLEAN

SUPPLY

STORAGE

OPEN TO DECK

TR ROOM

3420A

WALL

DOOR

CEILING

AND GRID

DEMO LEGEND

RATED WALL

WALL TYPES

SMOKE BARRIER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

KEYPLAN N

A

B C

D

330 N. Mead St, Suite 100 Wichita, KS 67202

Phone: (316) 262-2500 www.hfgarchitecture.com

EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

575-21-700

12/17/2024

2121 North Ave, Grand Junction, CO 81501

JW JS

A u to d e s k D o c s /2

G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.A

R

.r v t

/9 /2

:1

:4

P

M

B01-A106

THIRD FLOOR ENLARGED PLANS

1/4" = 1'-0"

BLDG. 1 - THIRD FLOOR DEMO PLAN 3665

1/4" = 1'-0"

BLDG. 1 - THIRD FLOOR DEMO RCP 3665

1/4" = 1'-0"

BLDG. 1 - THIRD FLOOR PLAN ENLARGED 3665

1/4" = 1'-0"

BLDG. 1 - THIRD FLOOR RCP 3665

1/4" = 1'-0"

BLDG. 1 - THIRD FLOOR DEMO PLAN 3420, 3420A

1/4" = 1'-0"

BLDG. 1 - THIRD FLOOR DEMO RCP 3420, 3420A

1/4" = 1'-0"

BLDG. 1 - THIRD FLOOR PLAN ENLARGED 3420, 3420A

1/4" = 1'-0"

BLDG. 1 - THIRD FLOOR RCP 3420, 3420A

2' 4' 8'0'

1/4" = 1'-0"

N

DEMO SCHEDULE

1 REMOVE WALL PARTITIONS INCLUDING DOORS, FRAMES, COUNTERS, CABINETS AND SHELVING TO

EXTENTS SHOWN.

2 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR OWNER.

3 REMOVE ALL FLOORING AND WALL FINISHES INCLUDING WALL PROTECTION AND CORNER GUARDS.

EXISTING GYP. BD. TO REMAIN.

4 REMOVE CEILING IN ITS ENTIRETY. SEE DEMOLITION REFLECTED CEILING PLAN FOR EXTENTS.

5 REMOVE PORTION OF WALL TO PREPARE FOR INSTALLATION OF NEW DOOR.

6 REMOVE MILLWORK IN ITS ENTIRETY.

7 REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED PIPING AS APPLICABLE. SEE PLUMBING PLANS.

PREPARE/ LEVEL SURFACES TO RECEIVE NEW FINISHES.

8 REMOVE EXISTING FURNITURE, EQUIPMENT, BASE, CHAIR RAIL & SHELVING - VERIFY/SALVAGE FOR

OWNER.

9 REMOVE HEADER/ WALL ABOVE EXISTING DOOR TO ACCOMMODATE NEW DOOR.

11 REMOVE FLOORING TO EXTENTS SHOWN - PREP FOR NEW FLOORING.

12 SALVAGE & RE-USE EXISTING GLASS DECORATIVE PANELS. SALVAGE & RE-USE EXISTING WALL

STANDOFFS 12 TOTAL.

13 DEMO PORTION OF EXISTING WALL. PREPARE FOR NEW 6" RATED WALL ASSEMBLY AND FEC.

14 REMOVE EXISTING WOOD CABINET AND TRIM. SALVAGE FOR OWNER

15 REMOVE EXISTING OMNICELL UNIT. REF 2/B20-A101 FOR NEW LOCATION. VERIFY WITH VA

16 REMOVE EXISTING GLASS PANE. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS GLASS PANEL. G.C. TO VERIFY PANEL THICKNESS PRIOR TO BIDDING.

ALUMINUM FINISH SHALL MATCH EXISTING WINDOW FRAME. REFER TO SPEC 07 43 00

17 EXISTING FAN COIL UNIT. REF. MECHANICAL FOR DEMO/REMOVAL

18 REMOVE EXISTING BED DOCKER. SALVAGE FOR OWNER.

19 REMOVE EXISTING SIDEWALL LOUVER. G.C. TO VERIFY WITH OWNER PRIOR TO REMOVAL.

20 VERIFY WITH MECHANICAL AND ELECTRICAL FOR ANY REQ'D. RECEPTACLE & MED GAS

REMOVAL/DEMO/ABANDONMENT.

DEMO RCP SCHEDULE

1 EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED - SALVAGE FOR

OWNER.

2 PORTION OF EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED TO

EXTENTS SHOWN - SALVAGE FOR OWNER.

3 EXISTING GYP. BOARD SOFFIT AND ALL OF ITS COMPONENTS TO BE REMOVED.

4 EXISTING GYP. BOARD CEILING AND ALL OF ITS COMPONENTS TO BE REMOVED.

5 EXISTING PIPING - REFERENCE PLUMBING DRAWINGS.

6 EXISTING SPRINKLER HEAD/ LINE - REFERENCE PLUMBING DRAWINGS.

7 EXISTING DIFFUSER - REFERENCE MECHANICAL DRAWINGS. SALVAGE FOR OWNER.

8 NON-RATED ICRA/CONSTRUCTION BARRIERS ARE PERMITTED ONLY WHERE THE

SPRINKLERS IN THE CONSTRUCTION AREA REMAIN IN SERVICE. REPLACE THE

EXISTING SPRINKLER(S) IN THE TR WITH NEW UPRIGHT SPRINKLERS AT THE TIME THE

CEILING IS REMOVED IN ORDER TO MAINTAIN SPRINKLER PROTECTION IN THE

CONSTRUCTION AREA. - REFERENCE PLUMBING.

9 EXISTING CEILING LIGHTS TO BE REMOVED - SALVAGE FOR OWNER.

10 DEMO/MODIFY PORTION OF CEILING TILE TO ACCOMODATE STUDS THAT EXTEND TO

STRUCTURE ABOVE.

11 REMOVE EXISTING CURTAIN TRACK. SALVAGE FOR OWNER.

PLAN NOTES - FLOOR PLAN

1 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. CONNECTED TO STRUCTURE ABOVE W/ 5/8" GYP BD (BOTH SIDES)

PAINTED TO EXTEND TO DECK ABOVE.

2 INFILL EXISTING OPENING WITH CONSTRUCTION METHODS AND MATERIALS THAT MATCH EXISTING

CONSTRUCTION.

3 PROVIDE FULL HEIGHT PAINTED FIRE RATED, PRESSURE TREATED 3/4" PLYWOOD [8'-0" MIN. AFF.] OVER EXISTING OR NEW PAINTED GYP. BOARD WALL. VERIFY EXACT REQUIREMENTS WITH ELECTRICAL PLANS AND SPECIFICATIONS. CONTRACTOR TO SHOW PROOF OF PLYWOOD FIRE RATING BEFORE PLYWOOD IS PAINTED.

5 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (ONE SIDE) PAINTED TO

EXTEND TO DECK.

6 INSTALL SALVAGED GLASS DECORATIVE PANELS AND WALL STANDOFFS. PROVIDE NEW WALL STANDOFFS AS

REQUIRED TO MATCH EXISTING. REF ELEVATION 3-B01-A109 FOR MOUNTING HEIGHTS.

7 EXTEND METAL STUD WALL FROM EXISTING STUD WALL TO DECK ABOVE. EXTEND GYP BOARD TO DECK ABOVE

(BOTH SIDES) G.C. TO VERIFY PRIOR TO BIDDING.

8 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.

9 PATCH/FILL VOID HOLES IN GYP BOARD TO DECK (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.

10 G.C. TO PROVIDE AND INSTALL A 20" X 6" MIN. METAL TRANSFER DOOR GRILLE WITHIN EXISTING DOOR. TO BE

PAINTED THE SAME COLOR AS THE ADJACENT DOOR FRAME.

11 NEW 6" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (BOTH SIDES) PAINTED TO

EXTEND TO DECK. MATCH EXISTING WALL ASSEMBLY RATING.

12 PATCH, INFILL, PAINT AS REQ'D AT REMOVED SIDEWALL LOUVER.

13 AT REMOVED FAN COIL EXHAUST OPENING, INFILL WITH SAME WALL ASSEMBLY AND FINISH EA. SIDE.

14 ALL TR ROOM WALLS MUST BE SEALED TO MAINTAIN A COMPARTMENT PER NFPA 13.

2' 4' 8'0'

1/4" = 1'-0"

Room

Room

Room

Room 4420 Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room .... Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room 4207 Room

Room

Room

Room

Room

Room

Room

Room .... Room

Room

Room

Room

Room

Room

Room

Room

Room 4025 Room

4027 Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

B01-A107

FEC

INSTALL NEW FULLY RECESSED RATED

FIRE EXTINGUISHER CABINET W/ CLASS

C CARBON DIOXIDE FIRE EXTINGUISHER.

G.C. TO VERIFY REQ'D. CANISTER SIZE

WITH VA.

3 4

1' - 6"

14400 6

7 8

124 SF

TR ROOM

NEW PIPING CHASE3' - 0"

12' - 7 1/2"

EXIST.

1' - 6"

INSTALL NEW FULLY RECESSED RATED

FIRE EXTINGUISHER CABINET W/ CLASS C

CARBON DIOXIDE FIRE EXTINGUISHER.

G.C. TO VERIFY WITH VA.

B01-A107

11' - 7"

TR ROOM

OPEN TO DECK

WALL

DOOR

CEILING

AND GRID

DEMO LEGEND

R E

F S

P E

C

REF. SPEC.

A .F

.F

M A

X

FIRE EXTINGUISHER

HANDLE TO BE MOUNTED

AT 4' A.F.F. MAX.

PROVIDE RATED

CABINET WHEN

INSTALLED IN RATED

WALL. CABINET TO

MATCH RATING OF WALL

ASSEMBLY.

PER. MANUFACTURER

1' - 6" F.V.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

KEYPLAN N

B C

D

330 N. Mead St, Suite 100 Wichita, KS 67202

Phone: (316) 262-2500 www.hfgarchitecture.com

EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

575-21-700

12/17/2024

2121 North Ave, Grand Junction, CO 81501

JW JS

A u to d e s k D o c s /2

G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.A

R

.r v t

/9 /2

:1

:5

P

M

B01-A107

EXISTING FOURTH FLOOR OVERALL &

ENLARGED PLANS

1" = 20'-0"

FOURTH FLOOR PLAN OVERALL

1/4" = 1'-0"

BLDG. 1 - FOURTH FLOOR DEMO PLAN 4400

1/4" = 1'-0"

BLDG. 1 - FOURTH FLOOR DEMO RCP 4400

1/4" = 1'-0"

BLDG. 1 - FOURTH FLOOR PLAN ENLARGED 4400

1/4" = 1'-0"

BLDG. 1 - FOURTH FLOOR RCP 4400

N

1" = 20'

0' 10' 20' 40'

2' 4' 8'0'

1/4" = 1'-0"

DEMO SCHEDULE

1 REMOVE WALL PARTITIONS INCLUDING DOORS, FRAMES, COUNTERS, CABINETS AND SHELVING TO

EXTENTS SHOWN.

2 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR OWNER.

3 REMOVE ALL FLOORING AND WALL FINISHES INCLUDING WALL PROTECTION AND CORNER GUARDS.

EXISTING GYP. BD. TO REMAIN.

4 REMOVE CEILING IN ITS ENTIRETY. SEE DEMOLITION REFLECTED CEILING PLAN FOR EXTENTS.

5 REMOVE PORTION OF WALL TO PREPARE FOR INSTALLATION OF NEW DOOR.

6 REMOVE MILLWORK IN ITS ENTIRETY.

7 REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED PIPING AS APPLICABLE. SEE PLUMBING PLANS.

PREPARE/ LEVEL SURFACES TO RECEIVE NEW FINISHES.

8 REMOVE EXISTING FURNITURE, EQUIPMENT, BASE, CHAIR RAIL & SHELVING - VERIFY/SALVAGE FOR

OWNER.

9 REMOVE HEADER/ WALL ABOVE EXISTING DOOR TO ACCOMMODATE NEW DOOR.

11 REMOVE FLOORING TO EXTENTS SHOWN - PREP FOR NEW FLOORING.

12 SALVAGE & RE-USE EXISTING GLASS DECORATIVE PANELS. SALVAGE & RE-USE EXISTING WALL

STANDOFFS 12 TOTAL.

13 DEMO PORTION OF EXISTING WALL. PREPARE FOR NEW 6" RATED WALL ASSEMBLY AND FEC.

14 REMOVE EXISTING WOOD CABINET AND TRIM. SALVAGE FOR OWNER

15 REMOVE EXISTING OMNICELL UNIT. REF 2/B20-A101 FOR NEW LOCATION. VERIFY WITH VA

16 REMOVE EXISTING GLASS PANE. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS GLASS PANEL. G.C. TO VERIFY PANEL THICKNESS PRIOR TO BIDDING.

ALUMINUM FINISH SHALL MATCH EXISTING WINDOW FRAME. REFER TO SPEC 07 43 00

17 EXISTING FAN COIL UNIT. REF. MECHANICAL FOR DEMO/REMOVAL

18 REMOVE EXISTING BED DOCKER. SALVAGE FOR OWNER.

19 REMOVE EXISTING SIDEWALL LOUVER. G.C. TO VERIFY WITH OWNER PRIOR TO REMOVAL.

20 VERIFY WITH MECHANICAL AND ELECTRICAL FOR ANY REQ'D. RECEPTACLE & MED GAS

REMOVAL/DEMO/ABANDONMENT.

DEMO RCP SCHEDULE

1 EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED - SALVAGE FOR

OWNER.

2 PORTION OF EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED TO

EXTENTS SHOWN - SALVAGE FOR OWNER.

3 EXISTING GYP. BOARD SOFFIT AND ALL OF ITS COMPONENTS TO BE REMOVED.

4 EXISTING GYP. BOARD CEILING AND ALL OF ITS COMPONENTS TO BE REMOVED.

5 EXISTING PIPING - REFERENCE PLUMBING DRAWINGS.

6 EXISTING SPRINKLER HEAD/ LINE - REFERENCE PLUMBING DRAWINGS.

7 EXISTING DIFFUSER - REFERENCE MECHANICAL DRAWINGS. SALVAGE FOR OWNER.

8 NON-RATED ICRA/CONSTRUCTION BARRIERS ARE PERMITTED ONLY WHERE THE

SPRINKLERS IN THE CONSTRUCTION AREA REMAIN IN SERVICE. REPLACE THE

EXISTING SPRINKLER(S) IN THE TR WITH NEW UPRIGHT SPRINKLERS AT THE TIME THE

CEILING IS REMOVED IN ORDER TO MAINTAIN SPRINKLER PROTECTION IN THE

CONSTRUCTION AREA. - REFERENCE PLUMBING.

9 EXISTING CEILING LIGHTS TO BE REMOVED - SALVAGE FOR OWNER.

10 DEMO/MODIFY PORTION OF CEILING TILE TO ACCOMODATE STUDS THAT EXTEND TO

STRUCTURE ABOVE.

11 REMOVE EXISTING CURTAIN TRACK. SALVAGE FOR OWNER.

PLAN NOTES - FLOOR PLAN

1 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. CONNECTED TO STRUCTURE ABOVE W/ 5/8" GYP BD (BOTH SIDES)

PAINTED TO EXTEND TO DECK ABOVE.

2 INFILL EXISTING OPENING WITH CONSTRUCTION METHODS AND MATERIALS THAT MATCH EXISTING

CONSTRUCTION.

3 PROVIDE FULL HEIGHT PAINTED FIRE RATED, PRESSURE TREATED 3/4" PLYWOOD [8'-0" MIN. AFF.] OVER EXISTING OR NEW PAINTED GYP. BOARD WALL. VERIFY EXACT REQUIREMENTS WITH ELECTRICAL PLANS AND SPECIFICATIONS. CONTRACTOR TO SHOW PROOF OF PLYWOOD FIRE RATING BEFORE PLYWOOD IS PAINTED.

5 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (ONE SIDE) PAINTED TO

EXTEND TO DECK.

6 INSTALL SALVAGED GLASS DECORATIVE PANELS AND WALL STANDOFFS. PROVIDE NEW WALL STANDOFFS AS

REQUIRED TO MATCH EXISTING. REF ELEVATION 3-B01-A109 FOR MOUNTING HEIGHTS.

7 EXTEND METAL STUD WALL FROM EXISTING STUD WALL TO DECK ABOVE. EXTEND GYP BOARD TO DECK ABOVE

(BOTH SIDES) G.C. TO VERIFY PRIOR TO BIDDING.

8 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.

9 PATCH/FILL VOID HOLES IN GYP BOARD TO DECK (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.

10 G.C. TO PROVIDE AND INSTALL A 20" X 6" MIN. METAL TRANSFER DOOR GRILLE WITHIN EXISTING DOOR. TO BE

PAINTED THE SAME COLOR AS THE ADJACENT DOOR FRAME.

11 NEW 6" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (BOTH SIDES) PAINTED TO

EXTEND TO DECK. MATCH EXISTING WALL ASSEMBLY RATING.

12 PATCH, INFILL, PAINT AS REQ'D AT REMOVED SIDEWALL LOUVER.

13 AT REMOVED FAN COIL EXHAUST OPENING, INFILL WITH SAME WALL ASSEMBLY AND FINISH EA. SIDE.

14 ALL TR ROOM WALLS MUST BE SEALED TO MAINTAIN A COMPARTMENT PER NFPA 13.

Revisions: Date:

3/4" = 1'-0"

FEC CABINET MOUNTING HEIGHT

1 1/2" = 1'-0"

PLAN DETAIL - FULLY RECESSED FEC

PATCH, MUD, TAPE AND

PAINT GYP. BOARD

EXISTING WALL TO REMAIN

EXISTING WALL TO REMAIN

5/8" GYP. BOARD - PAINT

TO MATCH ADJACENT

WALL SURFACE

5/8" GYP. BOARD

6" METAL STUDS

FULLY RECESSED RATED FEC.

REF. MANUFACTURER FOR

CABINET DIMENSIONS

08/22/25

3 4

8 15' - 8"

172 SF

TR ROOM

3' - 0"

11' - 0"

OPEN TO DECK

TR ROOM

Room

Room 54..

Room

Room 541.

Room

Room

Room

Room

Room

Room

Room

Room 54..

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room 5403 Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room ....Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room .... Room

Room

Room

B01-A108

FE

REPLACE EXISTING FIRE EXTINGUISHER

WITH NEW CLASS C CARBON DIOXIDE FIRE

EXTINGUISHER. G.C. TO VERIFY REQ'D.

CANISTER SIZE WITH VA. FE APPROX. 18'

FROM NEW TR

WALL

DOOR

CEILING

AND GRID

DEMO LEGEND

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

KEYPLAN N

B C

D

330 N. Mead St, Suite 100 Wichita, KS 67202

Phone: (316) 262-2500 www.hfgarchitecture.com

EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

575-21-700

12/17/2024

2121 North Ave, Grand Junction, CO 81501

JW JS

A u to d e s k D o c s /2

G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.A

R

.r v t

/9 /2

:1

:0

P

M

B01-A108

EXISTING FIFTH FLOOR OVERALL &

ENLARGED PLANS

1/4" = 1'-0"

FIFTH FLOOR DEMO PLAN 5401

1/4" = 1'-0"

FIFTH FLOOR DEMO RCP 5401

1/4" = 1'-0"

NEW FIFTH FLOOR PLAN ENLARGED 5401

1/4" = 1'-0"

FIFTH FLOOR RCP 5401

1" = 20'-0"

FIFTH FLOOR PLAN OVERALL

N

1" = 20'

0' 10' 20' 40'

2' 4' 8'0'

1/4" = 1'-0"

DEMO SCHEDULE

1 REMOVE WALL PARTITIONS INCLUDING DOORS, FRAMES, COUNTERS, CABINETS AND SHELVING TO

EXTENTS SHOWN.

2 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR OWNER.

3 REMOVE ALL FLOORING AND WALL FINISHES INCLUDING WALL PROTECTION AND CORNER GUARDS.

EXISTING GYP. BD. TO REMAIN.

4 REMOVE CEILING IN ITS ENTIRETY. SEE DEMOLITION REFLECTED CEILING PLAN FOR EXTENTS.

5 REMOVE PORTION OF WALL TO PREPARE FOR INSTALLATION OF NEW DOOR.

6 REMOVE MILLWORK IN ITS ENTIRETY.

7 REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED PIPING AS APPLICABLE. SEE PLUMBING PLANS.

PREPARE/ LEVEL SURFACES TO RECEIVE NEW FINISHES.

8 REMOVE EXISTING FURNITURE, EQUIPMENT, BASE, CHAIR RAIL & SHELVING - VERIFY/SALVAGE FOR

OWNER.

9 REMOVE HEADER/ WALL ABOVE EXISTING DOOR TO ACCOMMODATE NEW DOOR.

11 REMOVE FLOORING TO EXTENTS SHOWN - PREP FOR NEW FLOORING.

12 SALVAGE & RE-USE EXISTING GLASS DECORATIVE PANELS. SALVAGE & RE-USE EXISTING WALL

STANDOFFS 12 TOTAL.

13 DEMO PORTION OF EXISTING WALL. PREPARE FOR NEW 6" RATED WALL ASSEMBLY AND FEC.

14 REMOVE EXISTING WOOD CABINET AND TRIM. SALVAGE FOR OWNER

15 REMOVE EXISTING OMNICELL UNIT. REF 2/B20-A101 FOR NEW LOCATION. VERIFY WITH VA

16 REMOVE EXISTING GLASS PANE. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS GLASS PANEL. G.C. TO VERIFY PANEL THICKNESS PRIOR TO BIDDING.

ALUMINUM FINISH SHALL MATCH EXISTING WINDOW FRAME. REFER TO SPEC 07 43 00

17 EXISTING FAN COIL UNIT. REF. MECHANICAL FOR DEMO/REMOVAL

18 REMOVE EXISTING BED DOCKER. SALVAGE FOR OWNER.

19 REMOVE EXISTING SIDEWALL LOUVER. G.C. TO VERIFY WITH OWNER PRIOR TO REMOVAL.

20 VERIFY WITH MECHANICAL AND ELECTRICAL FOR ANY REQ'D. RECEPTACLE & MED GAS

REMOVAL/DEMO/ABANDONMENT.

DEMO RCP SCHEDULE

1 EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED - SALVAGE FOR

OWNER.

2 PORTION OF EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED TO

EXTENTS SHOWN - SALVAGE FOR OWNER.

3 EXISTING GYP. BOARD SOFFIT AND ALL OF ITS COMPONENTS TO BE REMOVED.

4 EXISTING GYP. BOARD CEILING AND ALL OF ITS COMPONENTS TO BE REMOVED.

5 EXISTING PIPING - REFERENCE PLUMBING DRAWINGS.

6 EXISTING SPRINKLER HEAD/ LINE - REFERENCE PLUMBING DRAWINGS.

7 EXISTING DIFFUSER - REFERENCE MECHANICAL DRAWINGS. SALVAGE FOR OWNER.

8 NON-RATED ICRA/CONSTRUCTION BARRIERS ARE PERMITTED ONLY WHERE THE

SPRINKLERS IN THE CONSTRUCTION AREA REMAIN IN SERVICE. REPLACE THE

EXISTING SPRINKLER(S) IN THE TR WITH NEW UPRIGHT SPRINKLERS AT THE TIME THE

CEILING IS REMOVED IN ORDER TO MAINTAIN SPRINKLER PROTECTION IN THE

CONSTRUCTION AREA. - REFERENCE PLUMBING.

9 EXISTING CEILING LIGHTS TO BE REMOVED - SALVAGE FOR OWNER.

10 DEMO/MODIFY PORTION OF CEILING TILE TO ACCOMODATE STUDS THAT EXTEND TO

STRUCTURE ABOVE.

11 REMOVE EXISTING CURTAIN TRACK. SALVAGE FOR OWNER.

PLAN NOTES - FLOOR PLAN

1 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. CONNECTED TO STRUCTURE ABOVE W/ 5/8" GYP BD (BOTH SIDES)

PAINTED TO EXTEND TO DECK ABOVE.

2 INFILL EXISTING OPENING WITH CONSTRUCTION METHODS AND MATERIALS THAT MATCH EXISTING

CONSTRUCTION.

3 PROVIDE FULL HEIGHT PAINTED FIRE RATED, PRESSURE TREATED 3/4" PLYWOOD [8'-0" MIN. AFF.] OVER EXISTING OR NEW PAINTED GYP. BOARD WALL. VERIFY EXACT REQUIREMENTS WITH ELECTRICAL PLANS AND SPECIFICATIONS. CONTRACTOR TO SHOW PROOF OF PLYWOOD FIRE RATING BEFORE PLYWOOD IS PAINTED.

5 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (ONE SIDE) PAINTED TO

EXTEND TO DECK.

6 INSTALL SALVAGED GLASS DECORATIVE PANELS AND WALL STANDOFFS. PROVIDE NEW WALL STANDOFFS AS

REQUIRED TO MATCH EXISTING. REF ELEVATION 3-B01-A109 FOR MOUNTING HEIGHTS.

7 EXTEND METAL STUD WALL FROM EXISTING STUD WALL TO DECK ABOVE. EXTEND GYP BOARD TO DECK ABOVE

(BOTH SIDES) G.C. TO VERIFY PRIOR TO BIDDING.

8 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.

9 PATCH/FILL VOID HOLES IN GYP BOARD TO DECK (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.

10 G.C. TO PROVIDE AND INSTALL A 20" X 6" MIN. METAL TRANSFER DOOR GRILLE WITHIN EXISTING DOOR. TO BE

PAINTED THE SAME COLOR AS THE ADJACENT DOOR FRAME.

11 NEW 6" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (BOTH SIDES) PAINTED TO

EXTEND TO DECK. MATCH EXISTING WALL ASSEMBLY RATING.

12 PATCH, INFILL, PAINT AS REQ'D AT REMOVED SIDEWALL LOUVER.

13 AT REMOVED FAN COIL EXHAUST OPENING, INFILL WITH SAME WALL ASSEMBLY AND FINISH EA. SIDE.

14 ALL TR ROOM WALLS MUST BE SEALED TO MAINTAIN A COMPARTMENT PER NFPA 13.

1111 8

121212 12 12

96 SF

TR ROOM

NEW PIPING CHASE

1' - 8" 7' - 7" 6' - 0"

336 SF

CLERICAL/

RECEPTION

WAITING

163 SF

FILES +

PRINTER

12' - 1"

VESTIBULE

HALL

50 SF

ROOM

3' - 6"

4' - 5" 5"

6' - 6"

4' - 10"

2' - 2" 3' - 0" 4"

4" 3' - 4" 5' - 7"

PARTIAL HEIGHT WALL SHOWN DASHED WITH SS-1 WALL CAP

3' - 0"

B01-A109 2-

1' - 0"

CURVED SOFFIT

SHOWN DASHED

ABOVE

CURVED SOFFIT SHOWN

DASHED ABOVE

A1

A1

A1

A1

A1

A1

B01-A109

B01-A109

B01-A109

B01-A109

B01-A109

B01-A1103

A1

A1

B01-A109

B01-A109

Room

Room .... Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room 641.

Room

Room

Room

Room

Room

Room

Room

Room .... Room

Room

Room

Room

B01-A109

FE

REPLACE EXISTING FIRE EXTINGUISHER

WITH NEW CLASS C CARBON DIOXIDE FIRE

EXTINGUISHER. G.C. TO VERIFY REQ'D.

CANISTER SIZE WITH VA. FEC APPROX. 11'

FROM NEW TR

WALL

DOOR

CEILING

AND GRID

DEMO LEGEND

REF PLAN

B01-A109

SCHEDULED BASE

SS-1 WALL CAP

5/8" GYP BD PAINTED

SOLID SURFACE ON ONE

LAYER OF 3/4" PART.

BD.; EASED RADIUS

CORNERS.;1

/4

MTL. STUD

MAX

4" 5" 3 1/2"

REFERENCE ARCH

DTLS FOR WALL

CONSTRUCTION

BASE AS SCHEDULED

1' - 0"

RECEPTION SIDE

5/8" GYP BD PAINTED

(EACH SIDE)

3 5/8" MTL. STUD 16" O.C.

5"

BASE AS SCHEDULED

METAL RUNNER TRACK, (TYP)

3 5/8"

METAL RUNNER TRACK

J-MOLD (EACH SIDE)

TOP OF WALL BELOW

5/8" GYP BD PAINTED TO

EXTEND ABOVE CEILING

STUDS EXTENDED TO

STRUCTURE ABOVE

5"

WALL ASSEMBLY

STANDOFF CAP

GASKETS

PANEL

BARREL SPACER

SCREW

WALL ANCHOR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

KEYPLAN N

B C

D

330 N. Mead St, Suite 100 Wichita, KS 67202

Phone: (316) 262-2500 www.hfgarchitecture.com

EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

575-21-700

12/17/2024

2121 North Ave, Grand Junction, CO 81501

JW JS

A u to d e s k D o c s /2

G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.A

R

.r v t

/2

/2

:5

:0

P

M

B01-A109

EXISTING SIXTH FLOOR OVERALL &

ENLARGED PLANS

1/4" = 1'-0"

SIXTH FLOOR DEMO PLAN 6201, 6202, 6203, 6204

1/4" = 1'-0"

NEW SIXTH FLOOR PLAN ENLARGED 6201, 6202, 6203, 6204

1" = 20'-0"

SIXTH FLOOR PLAN OVERALL

N

1" = 20'

0' 10' 20' 40'

2' 4' 8'0'

1/4" = 1'-0"

DEMO SCHEDULE

1 REMOVE WALL PARTITIONS INCLUDING DOORS, FRAMES, COUNTERS, CABINETS AND SHELVING TO

EXTENTS SHOWN.

2 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR OWNER.

3 REMOVE ALL FLOORING AND WALL FINISHES INCLUDING WALL PROTECTION AND CORNER GUARDS.

EXISTING GYP. BD. TO REMAIN.

4 REMOVE CEILING IN ITS ENTIRETY. SEE DEMOLITION REFLECTED CEILING PLAN FOR EXTENTS.

5 REMOVE PORTION OF WALL TO PREPARE FOR INSTALLATION OF NEW DOOR.

6 REMOVE MILLWORK IN ITS ENTIRETY.

7 REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED PIPING AS APPLICABLE. SEE PLUMBING PLANS.

PREPARE/ LEVEL SURFACES TO RECEIVE NEW FINISHES.

8 REMOVE EXISTING FURNITURE, EQUIPMENT, BASE, CHAIR RAIL & SHELVING - VERIFY/SALVAGE FOR

OWNER.

9 REMOVE HEADER/ WALL ABOVE EXISTING DOOR TO ACCOMMODATE NEW DOOR.

11 REMOVE FLOORING TO EXTENTS SHOWN - PREP FOR NEW FLOORING.

12 SALVAGE & RE-USE EXISTING GLASS DECORATIVE PANELS. SALVAGE & RE-USE EXISTING WALL

STANDOFFS 12 TOTAL.

13 DEMO PORTION OF EXISTING WALL. PREPARE FOR NEW 6" RATED WALL ASSEMBLY AND FEC.

14 REMOVE EXISTING WOOD CABINET AND TRIM. SALVAGE FOR OWNER

15 REMOVE EXISTING OMNICELL UNIT. REF 2/B20-A101 FOR NEW LOCATION. VERIFY WITH VA

16 REMOVE EXISTING GLASS PANE. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS GLASS PANEL. G.C. TO VERIFY PANEL THICKNESS PRIOR TO BIDDING.

ALUMINUM FINISH SHALL MATCH EXISTING WINDOW FRAME. REFER TO SPEC 07 43 00

17 EXISTING FAN COIL UNIT. REF. MECHANICAL FOR DEMO/REMOVAL

18 REMOVE EXISTING BED DOCKER. SALVAGE FOR OWNER.

19 REMOVE EXISTING SIDEWALL LOUVER. G.C. TO VERIFY WITH OWNER PRIOR TO REMOVAL.

20 VERIFY WITH MECHANICAL AND ELECTRICAL FOR ANY REQ'D. RECEPTACLE & MED GAS

REMOVAL/DEMO/ABANDONMENT.

PLAN NOTES - FLOOR PLAN

1 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. CONNECTED TO STRUCTURE ABOVE W/ 5/8" GYP BD (BOTH SIDES) PAINTED TO EXTEND TO DECK ABOVE.

2 INFILL EXISTING OPENING WITH CONSTRUCTION METHODS AND MATERIALS THAT MATCH EXISTING CONSTRUCTION.

3 PROVIDE FULL HEIGHT PAINTED FIRE RATED, PRESSURE TREATED 3/4" PLYWOOD [8'-0" MIN. AFF.] OVER EXISTING OR NEW PAINTED GYP. BOARD WALL. VERIFY EXACT REQUIREMENTS WITH ELECTRICAL PLANS AND SPECIFICATIONS. CONTRACTOR TO SHOW PROOF OF PLYWOOD FIRE RATING

BEFORE PLYWOOD IS PAINTED.

5 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (ONE SIDE) PAINTED TO EXTEND TO DECK.

6 INSTALL SALVAGED GLASS DECORATIVE PANELS AND WALL STANDOFFS. PROVIDE NEW WALL STANDOFFS AS REQUIRED TO MATCH EXISTING. REF

ELEVATION 3-B01-A109 FOR MOUNTING HEIGHTS.

7 EXTEND METAL STUD WALL FROM EXISTING STUD WALL TO DECK ABOVE. EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES)

8 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES).

9 PATCH/FILL VOID HOLES IN GYP BOARD TO DECK (BOTH SIDES).

10 G.C. TO PROVIDE AND INSTALL A 20" X 6" MIN. METAL TRANSFER DOOR GRILLE WITHIN EXISTING DOOR. TO BE PAINTED THE SAME COLOR AS THE

ADJACENT DOOR FRAME.

11 NEW 6" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (BOTH SIDES) PAINTED TO EXTEND TO DECK. MATCH EXISTING

WALL ASSEMBLY RATING.

12 PATCH, INFILL, PAINT AS REQ'D AT REMOVED SIDEWALL LOUVER.

13 AT REMOVED FAN COIL EXHAUST OPENING, INFILL WITH SAME WALL ASSEMBLY AND FINISH EA. SIDE.

14 ALL TR ROOM WALLS MUST BE SEALED TO MAINTAIN A COMPARTMENT PER NFPA 13.

1/2" = 1'-0"

PARTIAL HEIGHT WALL

1" = 1'-0"

PARTIAL HEIGHT WALL SECTION

1" = 1'-0"

WALL PARTITION TYPE "A1"

1 1/2" = 1'-0"

PLAN DETAIL - BRACE STUDS

Revisions: Date:

Addendum 2 08/22/25

3" = 1'-0"

DETAIL - WALL STANDOFFS

OFFICE

CORRIDOR

200A

CORRIDOR

OFFICE

CONFERENCE

ROOM

STAIRS

COMPLIANCE

BUSINESS

INTEGRITY

OFFICER

MENS

RESTROOM

WOMENS

RESTROOM

PRIVACY

OFFICER

205204202

TELEPHONE

CLOSET

ELECTRICAL

CLOSET

ELEVATOR

HOISTWAY

ˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍ

B05-A100

FE

REPLACE EXISTING FIRE EXTINGUISHER

WITH NEW CLASS C CARBON DIOXIDE FIRE

EXTINGUISHER. G.C. TO VERIFY REQ'D.

CANISTER SIZE WITH VA. FE APPROX. 10'

FROM NEW TR

220 221

80 SF

TR

6' - 7" 4' - 8 1/2"

8' - 11" 2' - 4 1/2"

51 SF

CLOSET

ELECTRICAL

CLOSET

3' - 4" 4"

9'-9 1/4"

OPEN TO DECK

TR

CLOSET

202 8' - 0"

OFFICE

TELEPHONE

CLOSET

8' - 0"

8' - 0" 7' - 10 1/2"8' - 0"

ELECTRICAL

CLOSET

OFFICE

TELEPHONE

CLOSET

ELECTRICAL

CLOSET

DEP CHIEF

CORRIDOR

100A

POLICE

TRAINING &

CONFERENCE

RM

CORRIDOR

STAIRS

STAIRS

ELEVATOR

HOISTWAY

EVIDENCE

PROCESSING

/STORAGE

LT 2 WS

PHYSICAL

SECURITY

OFFICER,

COMPLIANCE

OFFICER,

STORAGE

SECURITY

ˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍ

B05-A100

POLICE

CHIEF

POLICE

FOUR

TOUCHDOWN

SPACES

PIV

TRAINING

OFFICER

TELEPHONE

CLOSET

EXIST.

WALL

DOOR

CEILING

AND GRID

DEMO LEGEND

2" 3' - 0"

2"

3' - 0"

A

CAULKING @ EA. SIDE

HEADER, REF. STRUCT.

H.M. FRAME W/ MIN. 3

ANCHORS EA. SIDE -

REF. SCHED.

DOOR PER SCHED.

GYP. BD. & MTL. STUD WALL

PER PART. SCHED.

CAULKING @ EA. SIDE

DOOR PER SCHED.

H.M. FRAME W/ MIN. 3

ANCHORS EA. SIDE -

REF. SCHED.

GYP. BD. & MTL. STUD WALL

PER PART. SCHED.

20 GA. DBL STUDS @

JAMBS, TYP.

U .N

.O

T Y

P

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

330 N. Mead St, Suite 100 Wichita, KS 67202

Phone: (316) 262-2500 www.hfgarchitecture.com

EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

575-21-700

12/17/2024

2121 North Ave, Grand Junction, CO 81501

JW JS

A u to d e s k D o c s /2

G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.A

R

.r v t

/9 /2

:5

:1

P

M

B05-A100

BUILDING 5 OVERALL & ENLARGED PLANS

1/8" = 1'-0"

BLDG. 5 - EXISTING SECOND FLOOR PLAN OVERALL

1/4" = 1'-0"

BLDG. 5 - SECOND FLOOR DEMO PLAN 201

1/4" = 1'-0"

BLDG. 5 - SECOND FLOOR PLAN ENLARGED 201

1/4" = 1'-0"

BLDG. 5 - SECOND FLOOR RCP 201

1/4" = 1'-0"

BLDG. 5 - SECOND FLOOR DEMO RCP 201

DEMO SCHEDULE

1 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR OWNER.

2 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR RE-USE

3 REMOVE PORTION OF WALL TO EXTENTS SHOWN.

4 REMOVE ALL FLOORING AND WALL FINISHES INCLUDING WALL

PROTECTION AND CORNER GUARDS TO EXTENTS SHOWN. EXISTING

GYP. BD. TO REMAIN.

5 REMOVE PORTION OF WALL TO PREPARE FOR INSTALLATION OF NEW

DOOR.

2' 4' 8'0'

1/4" = 1'-0"

1/8" = 1'-0"

BLDG. 5 - EXISTING FIRST FLOOR PLAN OVERALL

1/2" = 1'-0"

BLDG. 5 - FIRST FLOOR PLAN ENLARGED 120

4' 8' 16'

1/8" = 1'-0"

0'

DEMO RCP SCHEDULE

1 EXISTING GYP. BOARD CEILING AND ALL OF ITS COMPONENTS

TO BE REMOVED.

2 EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE

REMOVED - SALVAGE FOR OWNER.

3 NON-RATED ICRA/CONSTRUCTION BARRIERS ARE PERMITTED

ONLY WHERE THE SPRINKLERS IN THE CONSTRUCTION AREA

REMAIN IN SERVICE. REPLACE THE EXISTING SPRINKLER(S) IN

THE TR WITH NEW UPRIGHT SPRINKLERS AT THE TIME THE

CEILING IS REMOVED IN ORDER TO MAINTAIN SPRINKLER

PROTECTION IN THE CONSTRUCTION AREA. - REFERENCE

PLUMBING.

PLAN NOTES - FLOOR PLAN

1 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. CONNECTED TO STRUCTURE ABOVE W/ 5/8"

GYP BD (BOTH SIDES) PAINTED TO EXTEND TO DECK.

2 PROVIDE FULL HEIGHT PAINTED FIRE RATED, PRESSURE TREATED 3/4" PLYWOOD [8'-0"

MIN. AFF.] OVER EXISTING OR NEW PAINTED GYP. BOARD WALL. VERIFY EXACT

REQUIREMENTS WITH ELECTRICAL PLANS AND SPECIFICATIONS. CONTRACTOR TO

SHOW PROOF OF PLYWOOD FIRE RATING BEFORE PLYWOOD IS PAINTED.

3 EXTEND METAL STUD WALL FROM EXISTING STUD WALL TO DECK ABOVE. EXTEND GYP

BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY BEFORE BIDDING.

4 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY BEFORE BIDDING.

5 PATCH/FILL VOID HOLES IN GYP BOARD TO DECK (BOTH SIDES). G.C. TO VERIFY

BEFORE BIDDING.

6 ALL TR ROOM WALLS MUST BE SEALED TO MAINTAIN A COMPARTMENT PER NFPA 13.

N

DOOR SCHEDULE

DOOR

NO. SIZE HDWR SET FIRE RATING

DOOR FRAME DETAILS

REMARKSTYPE MAT'L GLASS TYPE MAT'L GLASS HEAD JAMB THRESHOLD

201 3'-0" x 7'-0" x 1 3/4" 1.0 20 MIN. A WD - 1 HM - 3/B05-A100 4/B05-A100 - BUILDING 5 - FLOOR 2

202 3'-0" x 7'-0" x 1 3/4" 2.0 - A WD - 1 HM - 3/B05-A100 4/B05-A100 - BUILDING 5 - FLOOR 2

1/2" = 1'-0"

DOOR FRAME TYPE ELEVATION

1/2" = 1'-0"

DOOR TYPE ELEVATION

1 1/2" = 1'-0"

HM DOOR (HEAD)

1 1/2" = 1'-0"

HM DOOR (JAMB)

PLAN NOTES - RCP

1 INFILL CEILING WITH CONSTRUCTION METHODS AND

MATERIALS THAT MATCH EXISTING CEILING.

1' 2' 4'

1/2" = 1'-0"

0'

QUALITY

MANAGER

CHIEF

QUALITY

CHIEF OF

EDUCATION

PROGRAM

SPECIALIST

CORRIDOR

ED/STORAGE

117 LOBBY

CONFERENCE

ROOM

CLOSET

116A

STORAGE

CLOSET

116B

VESTIBULE

114A

COMPUTER

LAB

101/101A 102 INNOVATION/COMPUTER

DIRECTOR,

CONFERENCE

KITCHEN

RR

RR

ELEC.

CORR.

MECH

ROOM

STAIRS

NURSE

EDUCATOR

TE

106A

HOUSEKEEPING

CLOSET

111A

CORRIDOR

ˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍ

B06-A100

42 SF

TE

106A

9' - 6 1/2"

EXIST.

OPEN TO DECK

TE

106A8'-0" 1 21

WALL

DOOR

CEILING

AND GRID

DEMO LEGEND

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

7100 E BELLEVIEW AVE,

STE 107

GREENWOOD VILLAGE,

CO 80111

Phone: (720) 200-5955 www.specializedeng.com

SES Project : 22295

330 N. Mead St, Suite 100 Wichita, KS 67202

Phone: (316) 262-2500 www.hfgarchitecture.com

EHRM IU AT THE GRAND JUNCTION,

CO VA MEDICAL CENTER

575-21-700

12/17/2024

2121 North Ave, Grand Junction, CO 81501

JW JS

A u to d e s k D o c s /2

G ra n d

J u n c ti o n

E H

R M

/5

-7

.B

.A

R

.r v t

/9 /2

:5

:4

P

M

B06-A100

BUILDING 6 OVERALL & ENLARGED PLANS

1/8" = 1'-0"

BLDG. 6 - EXISTING FIRST FLOOR PLAN OVERALL

1/4" = 1'-0"

BLDG. 6 - FIRST FLOOR PLAN ENLARGED 106

2' 4' 8'0'

1/4" = 1'-0"

1/4" = 1'-0"

BLDG. 6 - RCP 106

1/4" = 1'-0"

BLDG. 6 - DEMO RCP 106

1/4" = 1'-0"

BLDG. 6 - DEMO PLAN 106

DEMO SCHEDULE

1 EXISTING CONDITIONS TO REMAIN - NO DEMO

REQUIRED

PLAN NOTES - FLOOR PLAN

1 EXISTING CONDITIONS TO REMAIN.

2 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY

BEFORE BIDDING.

DEMO RCP SCHEDULE

1 EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED -

SALVAGE FOR OWNER.

2 NON-RATED ICRA/CONSTRUCTION BARRIERS ARE PERMITTED ONLY

WHERE THE SPRINKLERS IN THE CONSTRUCTION AREA REMAIN IN

SERVICE. REPLACE THE EXISTING SPRINKLER(S) IN THE TR WITH

NEW UPRIGHT SPRINKLERS AT THE TIME THE CEILING IS REMOVED

IN ORDER TO MAINTAIN SPRINKLER PROTECTION IN THE

CONSTRUCTION AREA. - REFERENCE PLUMBING.

4' 8' 16'

1/8" = 1'-0"

0'

N

PLUMB

SHOP

STORAGE

TOILET

XXX

OFFICE

BREAK

ROOM

CORR

STORAGE

OFFICE

GENERAL

ENG.

114C

TOILET

XXXA

TOILET

XXXB

OFFICE

SPACE

CORR

OFFICE

ENTRY

CHIEF

ENGINEER

CONF.

ROOM

JAN

B08-A100

CORR

(3) INSULATED PIPES

13' - 6"

CORR

74 SF

TE ROOM

13' - 1"

3' - 4" 4"

12' - 0"

TE ROOM

OPEN TO DECK

WALL

DOOR

CEILING

AND GRID

DEMO LEGEND

2" 3' - 0"

2"

3' - 0"

A

CAULKING @ EA. SIDE

HEADER, REF. STRUCT.

H.M. FRAME W/ MIN. 3

ANCHORS EA. SIDE -

REF. SCHED.

DOOR PER SCHED.

GYP. BD. & MTL. STUD WALL

PER PART. SCHED.

CAULKING @ EA. SIDE

DOOR PER SCHED.

H.M. FRAME W/ MIN. 3

ANCHORS EA. SIDE -

REF. SCHED.

GYP. BD. & MTL. STUD WALL

PER PART. SCHED.

20 GA. DBL STUDS @

JAMBS, TYP.

U .N

.O

T Y

P

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5…

This is the start of the file's text. The full file is on GovTribe.