575-700.VA Archtitectural Grand Junction EHRM Addendum 2 - Changed Sheets Only.pdf
PDF 3 MB Posted
- Solicitation number
- 36C77625B0039
About this file
These architectural demolition and renovation documents detail the extensive interior modifications planned for multiple buildings at the Grand Junction VA Medical Center. The project involves selective demolition and reconstruction of various rooms and spaces across Buildings 1, 5, 6, 8, 9, 12, 20, 35, 36, and 37, with a focus on creating new Telecommunications (TR) rooms and upgrading interior finishes. Key renovation elements include installing new metal stud walls, replacing ceiling systems, installing fire-rated plywood panels, relocating fire extinguishers, and creating new room configurations while maintaining existing building structures. The documents specify detailed demolition schedules, plan notes for construction, and precise instructions for wall assemblies, ceiling modifications, and door replacements, with an emphasis on maintaining fire compartmentalization and meeting VA construction standards.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
3 4
15' - 0"
2" 3' - 4"
1 8
15' - 0"
129 SF
TR ROOM
3' - 0"
NEW PIPING
CHASE
6" 3' - 4"
OPEN TO DECK
TR ROOM
3 4
3' - 4" 2"
8 1
8 1
12' - 2"
158 SF
TR ROOM
3' - 0"
NEW PIPING
CHASE
3' - 4" 4"
3' - 1 1/2" 4' - 7"
14 12' - 6"
TR ROOM
OPEN TO DECK
WALL
DOOR
CEILING
AND GRID
DEMO LEGEND
RATED WALL
WALL TYPES
SMOKE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7100 E BELLEVIEW AVE,
STE 107
GREENWOOD VILLAGE,
CO 80111
Phone: (720) 200-5955 www.specializedeng.com
SES Project : 22295
KEYPLAN N
A
B C
D
B C
D
330 N. Mead St, Suite 100 Wichita, KS 67202
Phone: (316) 262-2500 www.hfgarchitecture.com
EHRM IU AT THE GRAND JUNCTION,
CO VA MEDICAL CENTER
575-21-700
12/17/2024
2121 North Ave, Grand Junction, CO 81501
JW JS
A u to d e s k D o c s /2
V
A G ra n d
J u n c ti o n
E H
R M
/5
-7
.B
.A
R
.r v t
/9 /2
:1
:1
P
M
B01-A101
FIRST FLOOR ENLARGED PLANS
1/4" = 1'-0"
BLDG. 1 - FIRST FLOOR DEMO PLAN 1684
1/4" = 1'-0"
BLDG. 1 - FIRST FLOOR DEMO RCP 1684
1/4" = 1'-0"
BLDG. 1 - FIRST FLOOR PLAN ENLARGED 1684
1/4" = 1'-0"
BLDG. 1 - FIRST FLOOR RCP 1684
1/4" = 1'-0"
BLDG. 1 - FIRST FLOOR DEMO PLAN 1402
1/4" = 1'-0"
BLDG. 1 - FIRST FLOOR DEMO RCP 1402
1/4" = 1'-0"
BLDG. 1 - FIRST FLOOR PLAN ENLARGED 1402
1/4" = 1'-0"
BLDG. 1 - FIRST FLOOR RCP 1402
DEMO SCHEDULE
1 REMOVE WALL PARTITIONS INCLUDING DOORS, FRAMES, COUNTERS, CABINETS AND SHELVING TO
EXTENTS SHOWN.
2 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR OWNER.
3 REMOVE ALL FLOORING AND WALL FINISHES INCLUDING WALL PROTECTION AND CORNER GUARDS.
EXISTING GYP. BD. TO REMAIN.
4 REMOVE CEILING IN ITS ENTIRETY. SEE DEMOLITION REFLECTED CEILING PLAN FOR EXTENTS.
5 REMOVE PORTION OF WALL TO PREPARE FOR INSTALLATION OF NEW DOOR.
6 REMOVE MILLWORK IN ITS ENTIRETY.
7 REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED PIPING AS APPLICABLE. SEE PLUMBING PLANS.
PREPARE/ LEVEL SURFACES TO RECEIVE NEW FINISHES.
8 REMOVE EXISTING FURNITURE, EQUIPMENT, BASE, CHAIR RAIL & SHELVING - VERIFY/SALVAGE FOR
OWNER.
9 REMOVE HEADER/ WALL ABOVE EXISTING DOOR TO ACCOMMODATE NEW DOOR.
11 REMOVE FLOORING TO EXTENTS SHOWN - PREP FOR NEW FLOORING.
12 SALVAGE & RE-USE EXISTING GLASS DECORATIVE PANELS. SALVAGE & RE-USE EXISTING WALL
STANDOFFS 12 TOTAL.
13 DEMO PORTION OF EXISTING WALL. PREPARE FOR NEW 6" RATED WALL ASSEMBLY AND FEC.
14 REMOVE EXISTING WOOD CABINET AND TRIM. SALVAGE FOR OWNER
15 REMOVE EXISTING OMNICELL UNIT. REF 2/B20-A101 FOR NEW LOCATION. VERIFY WITH VA
16 REMOVE EXISTING GLASS PANE. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS GLASS PANEL. G.C. TO VERIFY PANEL THICKNESS PRIOR TO BIDDING.
ALUMINUM FINISH SHALL MATCH EXISTING WINDOW FRAME. REFER TO SPEC 07 43 00
17 EXISTING FAN COIL UNIT. REF. MECHANICAL FOR DEMO/REMOVAL
18 REMOVE EXISTING BED DOCKER. SALVAGE FOR OWNER.
19 REMOVE EXISTING SIDEWALL LOUVER. G.C. TO VERIFY WITH OWNER PRIOR TO REMOVAL.
20 VERIFY WITH MECHANICAL AND ELECTRICAL FOR ANY REQ'D. RECEPTACLE & MED GAS
REMOVAL/DEMO/ABANDONMENT.
DEMO RCP SCHEDULE
1 EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED - SALVAGE FOR
OWNER.
2 PORTION OF EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED TO
EXTENTS SHOWN - SALVAGE FOR OWNER.
3 EXISTING GYP. BOARD SOFFIT AND ALL OF ITS COMPONENTS TO BE REMOVED.
4 EXISTING GYP. BOARD CEILING AND ALL OF ITS COMPONENTS TO BE REMOVED.
5 EXISTING PIPING - REFERENCE PLUMBING DRAWINGS.
6 EXISTING SPRINKLER HEAD/ LINE - REFERENCE PLUMBING DRAWINGS.
7 EXISTING DIFFUSER - REFERENCE MECHANICAL DRAWINGS. SALVAGE FOR OWNER.
8 NON-RATED ICRA/CONSTRUCTION BARRIERS ARE PERMITTED ONLY WHERE THE
SPRINKLERS IN THE CONSTRUCTION AREA REMAIN IN SERVICE. REPLACE THE
EXISTING SPRINKLER(S) IN THE TR WITH NEW UPRIGHT SPRINKLERS AT THE TIME THE
CEILING IS REMOVED IN ORDER TO MAINTAIN SPRINKLER PROTECTION IN THE
CONSTRUCTION AREA. - REFERENCE PLUMBING.
9 EXISTING CEILING LIGHTS TO BE REMOVED - SALVAGE FOR OWNER.
10 DEMO/MODIFY PORTION OF CEILING TILE TO ACCOMODATE STUDS THAT EXTEND TO
STRUCTURE ABOVE.
11 REMOVE EXISTING CURTAIN TRACK. SALVAGE FOR OWNER.
2' 4' 8'0'
1/4" = 1'-0"
N
PLAN NOTES - FLOOR PLAN
1 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. CONNECTED TO STRUCTURE ABOVE W/ 5/8" GYP BD (BOTH SIDES)
PAINTED TO EXTEND TO DECK ABOVE.
2 INFILL EXISTING OPENING WITH CONSTRUCTION METHODS AND MATERIALS THAT MATCH EXISTING
CONSTRUCTION.
3 PROVIDE FULL HEIGHT PAINTED FIRE RATED, PRESSURE TREATED 3/4" PLYWOOD [8'-0" MIN. AFF.] OVER EXISTING OR NEW PAINTED GYP. BOARD WALL. VERIFY EXACT REQUIREMENTS WITH ELECTRICAL PLANS AND SPECIFICATIONS. CONTRACTOR TO SHOW PROOF OF PLYWOOD FIRE RATING BEFORE PLYWOOD IS PAINTED.
5 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (ONE SIDE) PAINTED TO
EXTEND TO DECK.
6 INSTALL SALVAGED GLASS DECORATIVE PANELS AND WALL STANDOFFS. PROVIDE NEW WALL STANDOFFS AS
REQUIRED TO MATCH EXISTING. REF ELEVATION 3-B01-A109 FOR MOUNTING HEIGHTS.
7 EXTEND METAL STUD WALL FROM EXISTING STUD WALL TO DECK ABOVE. EXTEND GYP BOARD TO DECK ABOVE
(BOTH SIDES) G.C. TO VERIFY PRIOR TO BIDDING.
8 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.
9 PATCH/FILL VOID HOLES IN GYP BOARD TO DECK (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.
10 G.C. TO PROVIDE AND INSTALL A 20" X 6" MIN. METAL TRANSFER DOOR GRILLE WITHIN EXISTING DOOR. TO BE
PAINTED THE SAME COLOR AS THE ADJACENT DOOR FRAME.
11 NEW 6" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (BOTH SIDES) PAINTED TO
EXTEND TO DECK. MATCH EXISTING WALL ASSEMBLY RATING.
12 PATCH, INFILL, PAINT AS REQ'D AT REMOVED SIDEWALL LOUVER.
13 AT REMOVED FAN COIL EXHAUST OPENING, INFILL WITH SAME WALL ASSEMBLY AND FINISH EA. SIDE.
14 ALL TR ROOM WALLS MUST BE SEALED TO MAINTAIN A COMPARTMENT PER NFPA 13.
2' 4' 8'0'
1/4" = 1'-0"
RCP NOTE SCHEDULE
1 INFILL CEILING WITH CONSTRUCTION METHODS AND MATERIALS
THAT MATCH EXISTING CEILING.
2 REFERENCE ELECTRICAL FOR NEW LIGHTING LAYOUT.
3 EXTEND GYP TO ABOVE CEILING AND EXTEND STUDS TO
STRUCTURE ABOVE.
Revisions: Date: 08/22/25 Addendum 2 08/22/25
EXAM
ROOM
8' - 2"
EXISTING
88 SF
EXAM
ROOM
EXIST.
7' - 4"
3 8
EXAM
ROOM
30 SF
SOILED
HOLDING
3' - 9"
EXIST.
3 8
SOILED
HOLDING
OPEN TO DECK
SOILED
HOLDING
WALL
DOOR
CEILING
AND GRID
DEMO LEGEND
EXAM
ROOM
SOILED
HOLDING
E01
E
E
E04
E
E
E
E
E03
E
E
E
E09
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7100 E BELLEVIEW AVE,
STE 107
GREENWOOD VILLAGE,
CO 80111
Phone: (720) 200-5955 www.specializedeng.com
SES Project : 22295
KEYPLAN N
A
B C
D
B C
D
330 N. Mead St, Suite 100 Wichita, KS 67202
Phone: (316) 262-2500 www.hfgarchitecture.com
EHRM IU AT THE GRAND JUNCTION,
CO VA MEDICAL CENTER
575-21-700
12/17/2024
2121 North Ave, Grand Junction, CO 81501
JW JS
A u to d e s k D o c s /2
G ra n d
J u n c ti o n
E H
R M
/5
-7
.B
.A
R
.r v t
/9 /2
:1
:2
P
M
B01-A102
FIRST FLOOR ENLARGED PLANS
1/4" = 1'-0"
BLDG. 1 - FIRST FLOOR RCP 1687
1/4" = 1'-0"
BLDG. 1 - FIRST FLOOR PLAN ENLARGED 1687
1/4" = 1'-0"
BLDG. 1 - FIRST FLOOR DEMO PLAN 1687
1/4" = 1'-0"
BLDG. 1 - FIRST FLOOR PLAN ENLARGED 1691
1/4" = 1'-0"
BLDG. 1 - FIRST FLOOR DEMO PLAN 1691
1/4" = 1'-0"
BLDG. 1 - FIRST FLOOR RCP 1691
DEMO SCHEDULE
1 REMOVE WALL PARTITIONS INCLUDING DOORS, FRAMES, COUNTERS, CABINETS AND SHELVING TO
EXTENTS SHOWN.
2 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR OWNER.
3 REMOVE ALL FLOORING AND WALL FINISHES INCLUDING WALL PROTECTION AND CORNER GUARDS.
EXISTING GYP. BD. TO REMAIN.
4 REMOVE CEILING IN ITS ENTIRETY. SEE DEMOLITION REFLECTED CEILING PLAN FOR EXTENTS.
5 REMOVE PORTION OF WALL TO PREPARE FOR INSTALLATION OF NEW DOOR.
6 REMOVE MILLWORK IN ITS ENTIRETY.
7 REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED PIPING AS APPLICABLE. SEE PLUMBING PLANS.
PREPARE/ LEVEL SURFACES TO RECEIVE NEW FINISHES.
8 REMOVE EXISTING FURNITURE, EQUIPMENT, BASE, CHAIR RAIL & SHELVING - VERIFY/SALVAGE FOR
OWNER.
9 REMOVE HEADER/ WALL ABOVE EXISTING DOOR TO ACCOMMODATE NEW DOOR.
11 REMOVE FLOORING TO EXTENTS SHOWN - PREP FOR NEW FLOORING.
12 SALVAGE & RE-USE EXISTING GLASS DECORATIVE PANELS. SALVAGE & RE-USE EXISTING WALL
STANDOFFS 12 TOTAL.
13 DEMO PORTION OF EXISTING WALL. PREPARE FOR NEW 6" RATED WALL ASSEMBLY AND FEC.
14 REMOVE EXISTING WOOD CABINET AND TRIM. SALVAGE FOR OWNER
15 REMOVE EXISTING OMNICELL UNIT. REF 2/B20-A101 FOR NEW LOCATION. VERIFY WITH VA
16 REMOVE EXISTING GLASS PANE. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS GLASS PANEL. G.C. TO VERIFY PANEL THICKNESS PRIOR TO BIDDING.
ALUMINUM FINISH SHALL MATCH EXISTING WINDOW FRAME. REFER TO SPEC 07 43 00
17 EXISTING FAN COIL UNIT. REF. MECHANICAL FOR DEMO/REMOVAL
18 REMOVE EXISTING BED DOCKER. SALVAGE FOR OWNER.
19 REMOVE EXISTING SIDEWALL LOUVER. G.C. TO VERIFY WITH OWNER PRIOR TO REMOVAL.
20 VERIFY WITH MECHANICAL AND ELECTRICAL FOR ANY REQ'D. RECEPTACLE & MED GAS
REMOVAL/DEMO/ABANDONMENT.
PLAN NOTES - FLOOR PLAN
1 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. CONNECTED TO STRUCTURE ABOVE W/ 5/8" GYP BD (BOTH SIDES)
PAINTED TO EXTEND TO DECK ABOVE.
2 INFILL EXISTING OPENING WITH CONSTRUCTION METHODS AND MATERIALS THAT MATCH EXISTING
CONSTRUCTION.
3 PROVIDE FULL HEIGHT PAINTED FIRE RATED, PRESSURE TREATED 3/4" PLYWOOD [8'-0" MIN. AFF.] OVER EXISTING OR NEW PAINTED GYP. BOARD WALL. VERIFY EXACT REQUIREMENTS WITH ELECTRICAL PLANS AND SPECIFICATIONS. CONTRACTOR TO SHOW PROOF OF PLYWOOD FIRE RATING BEFORE PLYWOOD IS PAINTED.
5 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (ONE SIDE) PAINTED TO
EXTEND TO DECK.
6 INSTALL SALVAGED GLASS DECORATIVE PANELS AND WALL STANDOFFS. PROVIDE NEW WALL STANDOFFS AS
REQUIRED TO MATCH EXISTING. REF ELEVATION 3-B01-A109 FOR MOUNTING HEIGHTS.
7 EXTEND METAL STUD WALL FROM EXISTING STUD WALL TO DECK ABOVE. EXTEND GYP BOARD TO DECK ABOVE
(BOTH SIDES) G.C. TO VERIFY PRIOR TO BIDDING.
8 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.
9 PATCH/FILL VOID HOLES IN GYP BOARD TO DECK (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.
10 G.C. TO PROVIDE AND INSTALL A 20" X 6" MIN. METAL TRANSFER DOOR GRILLE WITHIN EXISTING DOOR. TO BE
PAINTED THE SAME COLOR AS THE ADJACENT DOOR FRAME.
11 NEW 6" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (BOTH SIDES) PAINTED TO
EXTEND TO DECK. MATCH EXISTING WALL ASSEMBLY RATING.
12 PATCH, INFILL, PAINT AS REQ'D AT REMOVED SIDEWALL LOUVER.
13 AT REMOVED FAN COIL EXHAUST OPENING, INFILL WITH SAME WALL ASSEMBLY AND FINISH EA. SIDE.
14 ALL TR ROOM WALLS MUST BE SEALED TO MAINTAIN A COMPARTMENT PER NFPA 13.
RCP NOTE SCHEDULE
1 INFILL CEILING WITH CONSTRUCTION METHODS AND MATERIALS
THAT MATCH EXISTING CEILING.
2 REFERENCE ELECTRICAL FOR NEW LIGHTING LAYOUT.
3 EXTEND GYP TO ABOVE CEILING AND EXTEND STUDS TO
STRUCTURE ABOVE.
1/4" = 1'-0"
BLDG. 1 - EQUIPMENT - FIRST FLOOR
PLAN ENLARGED 1687 & 1691
EQUIPMENT SCHEDULE
Equipment Number Equipment Description
Provided By
Installed By Electrical Data Mechanical Plumbing COMMENTS
E01 HAND SANITIZER DISPENSER VA GC No No No No
E02 SOILED CART VA VA No No No No
E03 GUEST CHAIR VA VA No No No No
E04 CUBICLE CURTAIN AND
TRACK
GC GC No No No No
E05 TASK CHAIR VA VA No No No No
E06 SOAP DISPENSER VA GC No No No No
E07 PAPER TOWEL DISPENSER VA GC No No No No
E08 SHARPS VA GC No No No No
E09 EXAM TABLE VA VA Yes No No No
E10 48" WIDE DESK VA VA No No No No
E11 COMPUTER VA VA Yes Yes No No
E12 PHONE VA VA No Yes No No
N 2' 4' 8'0'
1/4" = 1'-0"
2' 4' 8'0'
1/4" = 1'-0"
2' 4' 8'0'
1/4" = 1'-0"
3' - 4" 5' - 9"
9' - 5"
1' - 5"
9' - 5"
1 8
EXISTING COLUMN
9' - 0"
147 SF
TR ROOM
1' - 0"
NEW PIPING CHASE
1 5
4" 3' - 4"
OPEN TO DECK
TR ROOM
3 4
8' - 7"
8' - 7"
1 8
104 SF
TR ROOM
8' - 2"
1' - 0"
NEW PIPING CHASE 3' - 0"
TR ROOM
OPEN TO DECK
WALL
DOOR
CEILING
AND GRID
DEMO LEGEND
1' - 0"
ROOM
NEW PIPING CHASE
ROOM
DEMO EXISTING PAPER
TOWEL DISPENSER -
SALVAGE FOR OWNER.
RATED WALL
WALL TYPES
SMOKE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7100 E BELLEVIEW AVE,
STE 107
GREENWOOD VILLAGE,
CO 80111
Phone: (720) 200-5955 www.specializedeng.com
SES Project : 22295
KEYPLAN N
A
B C
D
B C
D
330 N. Mead St, Suite 100 Wichita, KS 67202
Phone: (316) 262-2500 www.hfgarchitecture.com
EHRM IU AT THE GRAND JUNCTION,
CO VA MEDICAL CENTER
575-21-700
12/17/2024
2121 North Ave, Grand Junction, CO 81501
JW JS
A u to d e s k D o c s /2
G ra n d
J u n c ti o n
E H
R M
/5
-7
.B
.A
R
.r v t
/9 /2
:1
:3
P
M
B01-A104
SECOND FLOOR ENLARGED PLANS
1/4" = 1'-0"
BLDG. 1 - SECOND FLOOR DEMO PLAN 2670
1/4" = 1'-0"
BLDG. 1 - SECOND FLOOR DEMO RCP 2670
1/4" = 1'-0"
BLDG. 1 - SECOND FLOOR PLAN ENLARGED 2670
1/4" = 1'-0"
BLDG. 1 - SECOND FLOOR RCP 2670
1/4" = 1'-0"
BLDG. 1 - SECOND FLOOR DEMO PLAN 2401
1/4" = 1'-0"
BLDG. 1 - SECOND FLOOR DEMO RCP 2401
1/4" = 1'-0"
BLDG. 1 - SECOND FLOOR PLAN ENLARGED 2401
1/4" = 1'-0"
BLDG. 1 - SECOND FLOOR RCP 2401
2' 4' 8'0'
1/4" = 1'-0"
N
DEMO SCHEDULE
1 REMOVE WALL PARTITIONS INCLUDING DOORS, FRAMES, COUNTERS, CABINETS AND SHELVING TO
EXTENTS SHOWN.
2 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR OWNER.
3 REMOVE ALL FLOORING AND WALL FINISHES INCLUDING WALL PROTECTION AND CORNER GUARDS.
EXISTING GYP. BD. TO REMAIN.
4 REMOVE CEILING IN ITS ENTIRETY. SEE DEMOLITION REFLECTED CEILING PLAN FOR EXTENTS.
5 REMOVE PORTION OF WALL TO PREPARE FOR INSTALLATION OF NEW DOOR.
6 REMOVE MILLWORK IN ITS ENTIRETY.
7 REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED PIPING AS APPLICABLE. SEE PLUMBING PLANS.
PREPARE/ LEVEL SURFACES TO RECEIVE NEW FINISHES.
8 REMOVE EXISTING FURNITURE, EQUIPMENT, BASE, CHAIR RAIL & SHELVING - VERIFY/SALVAGE FOR
OWNER.
9 REMOVE HEADER/ WALL ABOVE EXISTING DOOR TO ACCOMMODATE NEW DOOR.
11 REMOVE FLOORING TO EXTENTS SHOWN - PREP FOR NEW FLOORING.
12 SALVAGE & RE-USE EXISTING GLASS DECORATIVE PANELS. SALVAGE & RE-USE EXISTING WALL
STANDOFFS 12 TOTAL.
13 DEMO PORTION OF EXISTING WALL. PREPARE FOR NEW 6" RATED WALL ASSEMBLY AND FEC.
14 REMOVE EXISTING WOOD CABINET AND TRIM. SALVAGE FOR OWNER
15 REMOVE EXISTING OMNICELL UNIT. REF 2/B20-A101 FOR NEW LOCATION. VERIFY WITH VA
16 REMOVE EXISTING GLASS PANE. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS GLASS PANEL. G.C. TO VERIFY PANEL THICKNESS PRIOR TO BIDDING.
ALUMINUM FINISH SHALL MATCH EXISTING WINDOW FRAME. REFER TO SPEC 07 43 00
17 EXISTING FAN COIL UNIT. REF. MECHANICAL FOR DEMO/REMOVAL
18 REMOVE EXISTING BED DOCKER. SALVAGE FOR OWNER.
19 REMOVE EXISTING SIDEWALL LOUVER. G.C. TO VERIFY WITH OWNER PRIOR TO REMOVAL.
20 VERIFY WITH MECHANICAL AND ELECTRICAL FOR ANY REQ'D. RECEPTACLE & MED GAS
REMOVAL/DEMO/ABANDONMENT.
DEMO RCP SCHEDULE
1 EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED - SALVAGE FOR
OWNER.
2 PORTION OF EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED TO
EXTENTS SHOWN - SALVAGE FOR OWNER.
3 EXISTING GYP. BOARD SOFFIT AND ALL OF ITS COMPONENTS TO BE REMOVED.
4 EXISTING GYP. BOARD CEILING AND ALL OF ITS COMPONENTS TO BE REMOVED.
5 EXISTING PIPING - REFERENCE PLUMBING DRAWINGS.
6 EXISTING SPRINKLER HEAD/ LINE - REFERENCE PLUMBING DRAWINGS.
7 EXISTING DIFFUSER - REFERENCE MECHANICAL DRAWINGS. SALVAGE FOR OWNER.
8 NON-RATED ICRA/CONSTRUCTION BARRIERS ARE PERMITTED ONLY WHERE THE
SPRINKLERS IN THE CONSTRUCTION AREA REMAIN IN SERVICE. REPLACE THE
EXISTING SPRINKLER(S) IN THE TR WITH NEW UPRIGHT SPRINKLERS AT THE TIME THE
CEILING IS REMOVED IN ORDER TO MAINTAIN SPRINKLER PROTECTION IN THE
CONSTRUCTION AREA. - REFERENCE PLUMBING.
9 EXISTING CEILING LIGHTS TO BE REMOVED - SALVAGE FOR OWNER.
10 DEMO/MODIFY PORTION OF CEILING TILE TO ACCOMODATE STUDS THAT EXTEND TO
STRUCTURE ABOVE.
11 REMOVE EXISTING CURTAIN TRACK. SALVAGE FOR OWNER.
PLAN NOTES - FLOOR PLAN
1 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. CONNECTED TO STRUCTURE ABOVE W/ 5/8" GYP BD (BOTH SIDES)
PAINTED TO EXTEND TO DECK ABOVE.
2 INFILL EXISTING OPENING WITH CONSTRUCTION METHODS AND MATERIALS THAT MATCH EXISTING
CONSTRUCTION.
3 PROVIDE FULL HEIGHT PAINTED FIRE RATED, PRESSURE TREATED 3/4" PLYWOOD [8'-0" MIN. AFF.] OVER EXISTING OR NEW PAINTED GYP. BOARD WALL. VERIFY EXACT REQUIREMENTS WITH ELECTRICAL PLANS AND SPECIFICATIONS. CONTRACTOR TO SHOW PROOF OF PLYWOOD FIRE RATING BEFORE PLYWOOD IS PAINTED.
5 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (ONE SIDE) PAINTED TO
EXTEND TO DECK.
6 INSTALL SALVAGED GLASS DECORATIVE PANELS AND WALL STANDOFFS. PROVIDE NEW WALL STANDOFFS AS
REQUIRED TO MATCH EXISTING. REF ELEVATION 3-B01-A109 FOR MOUNTING HEIGHTS.
7 EXTEND METAL STUD WALL FROM EXISTING STUD WALL TO DECK ABOVE. EXTEND GYP BOARD TO DECK ABOVE
(BOTH SIDES) G.C. TO VERIFY PRIOR TO BIDDING.
8 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.
9 PATCH/FILL VOID HOLES IN GYP BOARD TO DECK (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.
10 G.C. TO PROVIDE AND INSTALL A 20" X 6" MIN. METAL TRANSFER DOOR GRILLE WITHIN EXISTING DOOR. TO BE
PAINTED THE SAME COLOR AS THE ADJACENT DOOR FRAME.
11 NEW 6" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (BOTH SIDES) PAINTED TO
EXTEND TO DECK. MATCH EXISTING WALL ASSEMBLY RATING.
12 PATCH, INFILL, PAINT AS REQ'D AT REMOVED SIDEWALL LOUVER.
13 AT REMOVED FAN COIL EXHAUST OPENING, INFILL WITH SAME WALL ASSEMBLY AND FINISH EA. SIDE.
14 ALL TR ROOM WALLS MUST BE SEALED TO MAINTAIN A COMPARTMENT PER NFPA 13.
2' 4' 8'0'
1/4" = 1'-0"
1/4" = 1'-0"
BLDG. 1 - SECOND FLOOR PLAN ENLARGED 2661
1/4" = 1'-0"
BLDG. 1 - SECOND FLOOR DEMO PLAN 2661
TR ROOM
4" 3' - 4"
TR ROOM
13' - 6"
97 SF
TR ROOM
3' - 0"
NEW PIPING CHASE
4" 3' - 4"
TR ROOM
15'-10"
OPEN TO DECK
CLEAN
SUPPLY
STORAGE
5' - 1" 7' - 3"
10"
2' - 1"
3 4 8
2 9
6' - 0"
3 4 8
2' - 1"
152 SF
CLEAN
SUPPLY
STORAGE
NEW PIPING CHASE
8' - 2"
4' - 0"
110 SF
TR ROOM
3420A
10' - 1"
EXIST.
3' - 4" 6"
3420A
CLEAN
SUPPLY
STORAGE
OPEN TO DECK
TR ROOM
3420A
WALL
DOOR
CEILING
AND GRID
DEMO LEGEND
RATED WALL
WALL TYPES
SMOKE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7100 E BELLEVIEW AVE,
STE 107
GREENWOOD VILLAGE,
CO 80111
Phone: (720) 200-5955 www.specializedeng.com
SES Project : 22295
KEYPLAN N
A
B C
D
330 N. Mead St, Suite 100 Wichita, KS 67202
Phone: (316) 262-2500 www.hfgarchitecture.com
EHRM IU AT THE GRAND JUNCTION,
CO VA MEDICAL CENTER
575-21-700
12/17/2024
2121 North Ave, Grand Junction, CO 81501
JW JS
A u to d e s k D o c s /2
G ra n d
J u n c ti o n
E H
R M
/5
-7
.B
.A
R
.r v t
/9 /2
:1
:4
P
M
B01-A106
THIRD FLOOR ENLARGED PLANS
1/4" = 1'-0"
BLDG. 1 - THIRD FLOOR DEMO PLAN 3665
1/4" = 1'-0"
BLDG. 1 - THIRD FLOOR DEMO RCP 3665
1/4" = 1'-0"
BLDG. 1 - THIRD FLOOR PLAN ENLARGED 3665
1/4" = 1'-0"
BLDG. 1 - THIRD FLOOR RCP 3665
1/4" = 1'-0"
BLDG. 1 - THIRD FLOOR DEMO PLAN 3420, 3420A
1/4" = 1'-0"
BLDG. 1 - THIRD FLOOR DEMO RCP 3420, 3420A
1/4" = 1'-0"
BLDG. 1 - THIRD FLOOR PLAN ENLARGED 3420, 3420A
1/4" = 1'-0"
BLDG. 1 - THIRD FLOOR RCP 3420, 3420A
2' 4' 8'0'
1/4" = 1'-0"
N
DEMO SCHEDULE
1 REMOVE WALL PARTITIONS INCLUDING DOORS, FRAMES, COUNTERS, CABINETS AND SHELVING TO
EXTENTS SHOWN.
2 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR OWNER.
3 REMOVE ALL FLOORING AND WALL FINISHES INCLUDING WALL PROTECTION AND CORNER GUARDS.
EXISTING GYP. BD. TO REMAIN.
4 REMOVE CEILING IN ITS ENTIRETY. SEE DEMOLITION REFLECTED CEILING PLAN FOR EXTENTS.
5 REMOVE PORTION OF WALL TO PREPARE FOR INSTALLATION OF NEW DOOR.
6 REMOVE MILLWORK IN ITS ENTIRETY.
7 REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED PIPING AS APPLICABLE. SEE PLUMBING PLANS.
PREPARE/ LEVEL SURFACES TO RECEIVE NEW FINISHES.
8 REMOVE EXISTING FURNITURE, EQUIPMENT, BASE, CHAIR RAIL & SHELVING - VERIFY/SALVAGE FOR
OWNER.
9 REMOVE HEADER/ WALL ABOVE EXISTING DOOR TO ACCOMMODATE NEW DOOR.
11 REMOVE FLOORING TO EXTENTS SHOWN - PREP FOR NEW FLOORING.
12 SALVAGE & RE-USE EXISTING GLASS DECORATIVE PANELS. SALVAGE & RE-USE EXISTING WALL
STANDOFFS 12 TOTAL.
13 DEMO PORTION OF EXISTING WALL. PREPARE FOR NEW 6" RATED WALL ASSEMBLY AND FEC.
14 REMOVE EXISTING WOOD CABINET AND TRIM. SALVAGE FOR OWNER
15 REMOVE EXISTING OMNICELL UNIT. REF 2/B20-A101 FOR NEW LOCATION. VERIFY WITH VA
16 REMOVE EXISTING GLASS PANE. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS GLASS PANEL. G.C. TO VERIFY PANEL THICKNESS PRIOR TO BIDDING.
ALUMINUM FINISH SHALL MATCH EXISTING WINDOW FRAME. REFER TO SPEC 07 43 00
17 EXISTING FAN COIL UNIT. REF. MECHANICAL FOR DEMO/REMOVAL
18 REMOVE EXISTING BED DOCKER. SALVAGE FOR OWNER.
19 REMOVE EXISTING SIDEWALL LOUVER. G.C. TO VERIFY WITH OWNER PRIOR TO REMOVAL.
20 VERIFY WITH MECHANICAL AND ELECTRICAL FOR ANY REQ'D. RECEPTACLE & MED GAS
REMOVAL/DEMO/ABANDONMENT.
DEMO RCP SCHEDULE
1 EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED - SALVAGE FOR
OWNER.
2 PORTION OF EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED TO
EXTENTS SHOWN - SALVAGE FOR OWNER.
3 EXISTING GYP. BOARD SOFFIT AND ALL OF ITS COMPONENTS TO BE REMOVED.
4 EXISTING GYP. BOARD CEILING AND ALL OF ITS COMPONENTS TO BE REMOVED.
5 EXISTING PIPING - REFERENCE PLUMBING DRAWINGS.
6 EXISTING SPRINKLER HEAD/ LINE - REFERENCE PLUMBING DRAWINGS.
7 EXISTING DIFFUSER - REFERENCE MECHANICAL DRAWINGS. SALVAGE FOR OWNER.
8 NON-RATED ICRA/CONSTRUCTION BARRIERS ARE PERMITTED ONLY WHERE THE
SPRINKLERS IN THE CONSTRUCTION AREA REMAIN IN SERVICE. REPLACE THE
EXISTING SPRINKLER(S) IN THE TR WITH NEW UPRIGHT SPRINKLERS AT THE TIME THE
CEILING IS REMOVED IN ORDER TO MAINTAIN SPRINKLER PROTECTION IN THE
CONSTRUCTION AREA. - REFERENCE PLUMBING.
9 EXISTING CEILING LIGHTS TO BE REMOVED - SALVAGE FOR OWNER.
10 DEMO/MODIFY PORTION OF CEILING TILE TO ACCOMODATE STUDS THAT EXTEND TO
STRUCTURE ABOVE.
11 REMOVE EXISTING CURTAIN TRACK. SALVAGE FOR OWNER.
PLAN NOTES - FLOOR PLAN
1 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. CONNECTED TO STRUCTURE ABOVE W/ 5/8" GYP BD (BOTH SIDES)
PAINTED TO EXTEND TO DECK ABOVE.
2 INFILL EXISTING OPENING WITH CONSTRUCTION METHODS AND MATERIALS THAT MATCH EXISTING
CONSTRUCTION.
3 PROVIDE FULL HEIGHT PAINTED FIRE RATED, PRESSURE TREATED 3/4" PLYWOOD [8'-0" MIN. AFF.] OVER EXISTING OR NEW PAINTED GYP. BOARD WALL. VERIFY EXACT REQUIREMENTS WITH ELECTRICAL PLANS AND SPECIFICATIONS. CONTRACTOR TO SHOW PROOF OF PLYWOOD FIRE RATING BEFORE PLYWOOD IS PAINTED.
5 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (ONE SIDE) PAINTED TO
EXTEND TO DECK.
6 INSTALL SALVAGED GLASS DECORATIVE PANELS AND WALL STANDOFFS. PROVIDE NEW WALL STANDOFFS AS
REQUIRED TO MATCH EXISTING. REF ELEVATION 3-B01-A109 FOR MOUNTING HEIGHTS.
7 EXTEND METAL STUD WALL FROM EXISTING STUD WALL TO DECK ABOVE. EXTEND GYP BOARD TO DECK ABOVE
(BOTH SIDES) G.C. TO VERIFY PRIOR TO BIDDING.
8 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.
9 PATCH/FILL VOID HOLES IN GYP BOARD TO DECK (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.
10 G.C. TO PROVIDE AND INSTALL A 20" X 6" MIN. METAL TRANSFER DOOR GRILLE WITHIN EXISTING DOOR. TO BE
PAINTED THE SAME COLOR AS THE ADJACENT DOOR FRAME.
11 NEW 6" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (BOTH SIDES) PAINTED TO
EXTEND TO DECK. MATCH EXISTING WALL ASSEMBLY RATING.
12 PATCH, INFILL, PAINT AS REQ'D AT REMOVED SIDEWALL LOUVER.
13 AT REMOVED FAN COIL EXHAUST OPENING, INFILL WITH SAME WALL ASSEMBLY AND FINISH EA. SIDE.
14 ALL TR ROOM WALLS MUST BE SEALED TO MAINTAIN A COMPARTMENT PER NFPA 13.
2' 4' 8'0'
1/4" = 1'-0"
Room
Room
Room
Room 4420 Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room .... Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room 4207 Room
Room
Room
Room
Room
Room
Room
Room .... Room
Room
Room
Room
Room
Room
Room
Room
Room 4025 Room
4027 Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
B01-A107
FEC
INSTALL NEW FULLY RECESSED RATED
FIRE EXTINGUISHER CABINET W/ CLASS
C CARBON DIOXIDE FIRE EXTINGUISHER.
G.C. TO VERIFY REQ'D. CANISTER SIZE
WITH VA.
3 4
1' - 6"
14400 6
7 8
124 SF
TR ROOM
NEW PIPING CHASE3' - 0"
12' - 7 1/2"
EXIST.
1' - 6"
INSTALL NEW FULLY RECESSED RATED
FIRE EXTINGUISHER CABINET W/ CLASS C
CARBON DIOXIDE FIRE EXTINGUISHER.
G.C. TO VERIFY WITH VA.
B01-A107
11' - 7"
TR ROOM
OPEN TO DECK
WALL
DOOR
CEILING
AND GRID
DEMO LEGEND
R E
F S
P E
C
REF. SPEC.
A .F
.F
M A
X
FIRE EXTINGUISHER
HANDLE TO BE MOUNTED
AT 4' A.F.F. MAX.
PROVIDE RATED
CABINET WHEN
INSTALLED IN RATED
WALL. CABINET TO
MATCH RATING OF WALL
ASSEMBLY.
PER. MANUFACTURER
1' - 6" F.V.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7100 E BELLEVIEW AVE,
STE 107
GREENWOOD VILLAGE,
CO 80111
Phone: (720) 200-5955 www.specializedeng.com
SES Project : 22295
KEYPLAN N
B C
D
330 N. Mead St, Suite 100 Wichita, KS 67202
Phone: (316) 262-2500 www.hfgarchitecture.com
EHRM IU AT THE GRAND JUNCTION,
CO VA MEDICAL CENTER
575-21-700
12/17/2024
2121 North Ave, Grand Junction, CO 81501
JW JS
A u to d e s k D o c s /2
G ra n d
J u n c ti o n
E H
R M
/5
-7
.B
.A
R
.r v t
/9 /2
:1
:5
P
M
B01-A107
EXISTING FOURTH FLOOR OVERALL &
ENLARGED PLANS
1" = 20'-0"
FOURTH FLOOR PLAN OVERALL
1/4" = 1'-0"
BLDG. 1 - FOURTH FLOOR DEMO PLAN 4400
1/4" = 1'-0"
BLDG. 1 - FOURTH FLOOR DEMO RCP 4400
1/4" = 1'-0"
BLDG. 1 - FOURTH FLOOR PLAN ENLARGED 4400
1/4" = 1'-0"
BLDG. 1 - FOURTH FLOOR RCP 4400
N
1" = 20'
0' 10' 20' 40'
2' 4' 8'0'
1/4" = 1'-0"
DEMO SCHEDULE
1 REMOVE WALL PARTITIONS INCLUDING DOORS, FRAMES, COUNTERS, CABINETS AND SHELVING TO
EXTENTS SHOWN.
2 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR OWNER.
3 REMOVE ALL FLOORING AND WALL FINISHES INCLUDING WALL PROTECTION AND CORNER GUARDS.
EXISTING GYP. BD. TO REMAIN.
4 REMOVE CEILING IN ITS ENTIRETY. SEE DEMOLITION REFLECTED CEILING PLAN FOR EXTENTS.
5 REMOVE PORTION OF WALL TO PREPARE FOR INSTALLATION OF NEW DOOR.
6 REMOVE MILLWORK IN ITS ENTIRETY.
7 REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED PIPING AS APPLICABLE. SEE PLUMBING PLANS.
PREPARE/ LEVEL SURFACES TO RECEIVE NEW FINISHES.
8 REMOVE EXISTING FURNITURE, EQUIPMENT, BASE, CHAIR RAIL & SHELVING - VERIFY/SALVAGE FOR
OWNER.
9 REMOVE HEADER/ WALL ABOVE EXISTING DOOR TO ACCOMMODATE NEW DOOR.
11 REMOVE FLOORING TO EXTENTS SHOWN - PREP FOR NEW FLOORING.
12 SALVAGE & RE-USE EXISTING GLASS DECORATIVE PANELS. SALVAGE & RE-USE EXISTING WALL
STANDOFFS 12 TOTAL.
13 DEMO PORTION OF EXISTING WALL. PREPARE FOR NEW 6" RATED WALL ASSEMBLY AND FEC.
14 REMOVE EXISTING WOOD CABINET AND TRIM. SALVAGE FOR OWNER
15 REMOVE EXISTING OMNICELL UNIT. REF 2/B20-A101 FOR NEW LOCATION. VERIFY WITH VA
16 REMOVE EXISTING GLASS PANE. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS GLASS PANEL. G.C. TO VERIFY PANEL THICKNESS PRIOR TO BIDDING.
ALUMINUM FINISH SHALL MATCH EXISTING WINDOW FRAME. REFER TO SPEC 07 43 00
17 EXISTING FAN COIL UNIT. REF. MECHANICAL FOR DEMO/REMOVAL
18 REMOVE EXISTING BED DOCKER. SALVAGE FOR OWNER.
19 REMOVE EXISTING SIDEWALL LOUVER. G.C. TO VERIFY WITH OWNER PRIOR TO REMOVAL.
20 VERIFY WITH MECHANICAL AND ELECTRICAL FOR ANY REQ'D. RECEPTACLE & MED GAS
REMOVAL/DEMO/ABANDONMENT.
DEMO RCP SCHEDULE
1 EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED - SALVAGE FOR
OWNER.
2 PORTION OF EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED TO
EXTENTS SHOWN - SALVAGE FOR OWNER.
3 EXISTING GYP. BOARD SOFFIT AND ALL OF ITS COMPONENTS TO BE REMOVED.
4 EXISTING GYP. BOARD CEILING AND ALL OF ITS COMPONENTS TO BE REMOVED.
5 EXISTING PIPING - REFERENCE PLUMBING DRAWINGS.
6 EXISTING SPRINKLER HEAD/ LINE - REFERENCE PLUMBING DRAWINGS.
7 EXISTING DIFFUSER - REFERENCE MECHANICAL DRAWINGS. SALVAGE FOR OWNER.
8 NON-RATED ICRA/CONSTRUCTION BARRIERS ARE PERMITTED ONLY WHERE THE
SPRINKLERS IN THE CONSTRUCTION AREA REMAIN IN SERVICE. REPLACE THE
EXISTING SPRINKLER(S) IN THE TR WITH NEW UPRIGHT SPRINKLERS AT THE TIME THE
CEILING IS REMOVED IN ORDER TO MAINTAIN SPRINKLER PROTECTION IN THE
CONSTRUCTION AREA. - REFERENCE PLUMBING.
9 EXISTING CEILING LIGHTS TO BE REMOVED - SALVAGE FOR OWNER.
10 DEMO/MODIFY PORTION OF CEILING TILE TO ACCOMODATE STUDS THAT EXTEND TO
STRUCTURE ABOVE.
11 REMOVE EXISTING CURTAIN TRACK. SALVAGE FOR OWNER.
PLAN NOTES - FLOOR PLAN
1 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. CONNECTED TO STRUCTURE ABOVE W/ 5/8" GYP BD (BOTH SIDES)
PAINTED TO EXTEND TO DECK ABOVE.
2 INFILL EXISTING OPENING WITH CONSTRUCTION METHODS AND MATERIALS THAT MATCH EXISTING
CONSTRUCTION.
3 PROVIDE FULL HEIGHT PAINTED FIRE RATED, PRESSURE TREATED 3/4" PLYWOOD [8'-0" MIN. AFF.] OVER EXISTING OR NEW PAINTED GYP. BOARD WALL. VERIFY EXACT REQUIREMENTS WITH ELECTRICAL PLANS AND SPECIFICATIONS. CONTRACTOR TO SHOW PROOF OF PLYWOOD FIRE RATING BEFORE PLYWOOD IS PAINTED.
5 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (ONE SIDE) PAINTED TO
EXTEND TO DECK.
6 INSTALL SALVAGED GLASS DECORATIVE PANELS AND WALL STANDOFFS. PROVIDE NEW WALL STANDOFFS AS
REQUIRED TO MATCH EXISTING. REF ELEVATION 3-B01-A109 FOR MOUNTING HEIGHTS.
7 EXTEND METAL STUD WALL FROM EXISTING STUD WALL TO DECK ABOVE. EXTEND GYP BOARD TO DECK ABOVE
(BOTH SIDES) G.C. TO VERIFY PRIOR TO BIDDING.
8 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.
9 PATCH/FILL VOID HOLES IN GYP BOARD TO DECK (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.
10 G.C. TO PROVIDE AND INSTALL A 20" X 6" MIN. METAL TRANSFER DOOR GRILLE WITHIN EXISTING DOOR. TO BE
PAINTED THE SAME COLOR AS THE ADJACENT DOOR FRAME.
11 NEW 6" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (BOTH SIDES) PAINTED TO
EXTEND TO DECK. MATCH EXISTING WALL ASSEMBLY RATING.
12 PATCH, INFILL, PAINT AS REQ'D AT REMOVED SIDEWALL LOUVER.
13 AT REMOVED FAN COIL EXHAUST OPENING, INFILL WITH SAME WALL ASSEMBLY AND FINISH EA. SIDE.
14 ALL TR ROOM WALLS MUST BE SEALED TO MAINTAIN A COMPARTMENT PER NFPA 13.
Revisions: Date:
3/4" = 1'-0"
FEC CABINET MOUNTING HEIGHT
1 1/2" = 1'-0"
PLAN DETAIL - FULLY RECESSED FEC
PATCH, MUD, TAPE AND
PAINT GYP. BOARD
EXISTING WALL TO REMAIN
EXISTING WALL TO REMAIN
5/8" GYP. BOARD - PAINT
TO MATCH ADJACENT
WALL SURFACE
5/8" GYP. BOARD
6" METAL STUDS
FULLY RECESSED RATED FEC.
REF. MANUFACTURER FOR
CABINET DIMENSIONS
08/22/25
3 4
8 15' - 8"
172 SF
TR ROOM
3' - 0"
11' - 0"
OPEN TO DECK
TR ROOM
Room
Room 54..
Room
Room 541.
Room
Room
Room
Room
Room
Room
Room
Room 54..
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room 5403 Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room ....Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room .... Room
Room
Room
B01-A108
FE
REPLACE EXISTING FIRE EXTINGUISHER
WITH NEW CLASS C CARBON DIOXIDE FIRE
EXTINGUISHER. G.C. TO VERIFY REQ'D.
CANISTER SIZE WITH VA. FE APPROX. 18'
FROM NEW TR
WALL
DOOR
CEILING
AND GRID
DEMO LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7100 E BELLEVIEW AVE,
STE 107
GREENWOOD VILLAGE,
CO 80111
Phone: (720) 200-5955 www.specializedeng.com
SES Project : 22295
KEYPLAN N
B C
D
330 N. Mead St, Suite 100 Wichita, KS 67202
Phone: (316) 262-2500 www.hfgarchitecture.com
EHRM IU AT THE GRAND JUNCTION,
CO VA MEDICAL CENTER
575-21-700
12/17/2024
2121 North Ave, Grand Junction, CO 81501
JW JS
A u to d e s k D o c s /2
G ra n d
J u n c ti o n
E H
R M
/5
-7
.B
.A
R
.r v t
/9 /2
:1
:0
P
M
B01-A108
EXISTING FIFTH FLOOR OVERALL &
ENLARGED PLANS
1/4" = 1'-0"
FIFTH FLOOR DEMO PLAN 5401
1/4" = 1'-0"
FIFTH FLOOR DEMO RCP 5401
1/4" = 1'-0"
NEW FIFTH FLOOR PLAN ENLARGED 5401
1/4" = 1'-0"
FIFTH FLOOR RCP 5401
1" = 20'-0"
FIFTH FLOOR PLAN OVERALL
N
1" = 20'
0' 10' 20' 40'
2' 4' 8'0'
1/4" = 1'-0"
DEMO SCHEDULE
1 REMOVE WALL PARTITIONS INCLUDING DOORS, FRAMES, COUNTERS, CABINETS AND SHELVING TO
EXTENTS SHOWN.
2 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR OWNER.
3 REMOVE ALL FLOORING AND WALL FINISHES INCLUDING WALL PROTECTION AND CORNER GUARDS.
EXISTING GYP. BD. TO REMAIN.
4 REMOVE CEILING IN ITS ENTIRETY. SEE DEMOLITION REFLECTED CEILING PLAN FOR EXTENTS.
5 REMOVE PORTION OF WALL TO PREPARE FOR INSTALLATION OF NEW DOOR.
6 REMOVE MILLWORK IN ITS ENTIRETY.
7 REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED PIPING AS APPLICABLE. SEE PLUMBING PLANS.
PREPARE/ LEVEL SURFACES TO RECEIVE NEW FINISHES.
8 REMOVE EXISTING FURNITURE, EQUIPMENT, BASE, CHAIR RAIL & SHELVING - VERIFY/SALVAGE FOR
OWNER.
9 REMOVE HEADER/ WALL ABOVE EXISTING DOOR TO ACCOMMODATE NEW DOOR.
11 REMOVE FLOORING TO EXTENTS SHOWN - PREP FOR NEW FLOORING.
12 SALVAGE & RE-USE EXISTING GLASS DECORATIVE PANELS. SALVAGE & RE-USE EXISTING WALL
STANDOFFS 12 TOTAL.
13 DEMO PORTION OF EXISTING WALL. PREPARE FOR NEW 6" RATED WALL ASSEMBLY AND FEC.
14 REMOVE EXISTING WOOD CABINET AND TRIM. SALVAGE FOR OWNER
15 REMOVE EXISTING OMNICELL UNIT. REF 2/B20-A101 FOR NEW LOCATION. VERIFY WITH VA
16 REMOVE EXISTING GLASS PANE. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS GLASS PANEL. G.C. TO VERIFY PANEL THICKNESS PRIOR TO BIDDING.
ALUMINUM FINISH SHALL MATCH EXISTING WINDOW FRAME. REFER TO SPEC 07 43 00
17 EXISTING FAN COIL UNIT. REF. MECHANICAL FOR DEMO/REMOVAL
18 REMOVE EXISTING BED DOCKER. SALVAGE FOR OWNER.
19 REMOVE EXISTING SIDEWALL LOUVER. G.C. TO VERIFY WITH OWNER PRIOR TO REMOVAL.
20 VERIFY WITH MECHANICAL AND ELECTRICAL FOR ANY REQ'D. RECEPTACLE & MED GAS
REMOVAL/DEMO/ABANDONMENT.
DEMO RCP SCHEDULE
1 EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED - SALVAGE FOR
OWNER.
2 PORTION OF EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED TO
EXTENTS SHOWN - SALVAGE FOR OWNER.
3 EXISTING GYP. BOARD SOFFIT AND ALL OF ITS COMPONENTS TO BE REMOVED.
4 EXISTING GYP. BOARD CEILING AND ALL OF ITS COMPONENTS TO BE REMOVED.
5 EXISTING PIPING - REFERENCE PLUMBING DRAWINGS.
6 EXISTING SPRINKLER HEAD/ LINE - REFERENCE PLUMBING DRAWINGS.
7 EXISTING DIFFUSER - REFERENCE MECHANICAL DRAWINGS. SALVAGE FOR OWNER.
8 NON-RATED ICRA/CONSTRUCTION BARRIERS ARE PERMITTED ONLY WHERE THE
SPRINKLERS IN THE CONSTRUCTION AREA REMAIN IN SERVICE. REPLACE THE
EXISTING SPRINKLER(S) IN THE TR WITH NEW UPRIGHT SPRINKLERS AT THE TIME THE
CEILING IS REMOVED IN ORDER TO MAINTAIN SPRINKLER PROTECTION IN THE
CONSTRUCTION AREA. - REFERENCE PLUMBING.
9 EXISTING CEILING LIGHTS TO BE REMOVED - SALVAGE FOR OWNER.
10 DEMO/MODIFY PORTION OF CEILING TILE TO ACCOMODATE STUDS THAT EXTEND TO
STRUCTURE ABOVE.
11 REMOVE EXISTING CURTAIN TRACK. SALVAGE FOR OWNER.
PLAN NOTES - FLOOR PLAN
1 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. CONNECTED TO STRUCTURE ABOVE W/ 5/8" GYP BD (BOTH SIDES)
PAINTED TO EXTEND TO DECK ABOVE.
2 INFILL EXISTING OPENING WITH CONSTRUCTION METHODS AND MATERIALS THAT MATCH EXISTING
CONSTRUCTION.
3 PROVIDE FULL HEIGHT PAINTED FIRE RATED, PRESSURE TREATED 3/4" PLYWOOD [8'-0" MIN. AFF.] OVER EXISTING OR NEW PAINTED GYP. BOARD WALL. VERIFY EXACT REQUIREMENTS WITH ELECTRICAL PLANS AND SPECIFICATIONS. CONTRACTOR TO SHOW PROOF OF PLYWOOD FIRE RATING BEFORE PLYWOOD IS PAINTED.
5 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (ONE SIDE) PAINTED TO
EXTEND TO DECK.
6 INSTALL SALVAGED GLASS DECORATIVE PANELS AND WALL STANDOFFS. PROVIDE NEW WALL STANDOFFS AS
REQUIRED TO MATCH EXISTING. REF ELEVATION 3-B01-A109 FOR MOUNTING HEIGHTS.
7 EXTEND METAL STUD WALL FROM EXISTING STUD WALL TO DECK ABOVE. EXTEND GYP BOARD TO DECK ABOVE
(BOTH SIDES) G.C. TO VERIFY PRIOR TO BIDDING.
8 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.
9 PATCH/FILL VOID HOLES IN GYP BOARD TO DECK (BOTH SIDES). G.C. TO VERIFY PRIOR TO BIDDING.
10 G.C. TO PROVIDE AND INSTALL A 20" X 6" MIN. METAL TRANSFER DOOR GRILLE WITHIN EXISTING DOOR. TO BE
PAINTED THE SAME COLOR AS THE ADJACENT DOOR FRAME.
11 NEW 6" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (BOTH SIDES) PAINTED TO
EXTEND TO DECK. MATCH EXISTING WALL ASSEMBLY RATING.
12 PATCH, INFILL, PAINT AS REQ'D AT REMOVED SIDEWALL LOUVER.
13 AT REMOVED FAN COIL EXHAUST OPENING, INFILL WITH SAME WALL ASSEMBLY AND FINISH EA. SIDE.
14 ALL TR ROOM WALLS MUST BE SEALED TO MAINTAIN A COMPARTMENT PER NFPA 13.
1111 8
121212 12 12
96 SF
TR ROOM
NEW PIPING CHASE
1' - 8" 7' - 7" 6' - 0"
336 SF
CLERICAL/
RECEPTION
WAITING
163 SF
FILES +
PRINTER
12' - 1"
VESTIBULE
HALL
50 SF
ROOM
3' - 6"
4' - 5" 5"
6' - 6"
4' - 10"
2' - 2" 3' - 0" 4"
4" 3' - 4" 5' - 7"
PARTIAL HEIGHT WALL SHOWN DASHED WITH SS-1 WALL CAP
3' - 0"
B01-A109 2-
1' - 0"
CURVED SOFFIT
SHOWN DASHED
ABOVE
CURVED SOFFIT SHOWN
DASHED ABOVE
A1
A1
A1
A1
A1
A1
B01-A109
B01-A109
B01-A109
B01-A109
B01-A109
B01-A1103
A1
A1
B01-A109
B01-A109
Room
Room .... Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room 641.
Room
Room
Room
Room
Room
Room
Room
Room .... Room
Room
Room
Room
B01-A109
FE
REPLACE EXISTING FIRE EXTINGUISHER
WITH NEW CLASS C CARBON DIOXIDE FIRE
EXTINGUISHER. G.C. TO VERIFY REQ'D.
CANISTER SIZE WITH VA. FEC APPROX. 11'
FROM NEW TR
WALL
DOOR
CEILING
AND GRID
DEMO LEGEND
REF PLAN
B01-A109
SCHEDULED BASE
SS-1 WALL CAP
5/8" GYP BD PAINTED
SOLID SURFACE ON ONE
LAYER OF 3/4" PART.
BD.; EASED RADIUS
CORNERS.;1
/4
MTL. STUD
MAX
4" 5" 3 1/2"
REFERENCE ARCH
DTLS FOR WALL
CONSTRUCTION
BASE AS SCHEDULED
1' - 0"
RECEPTION SIDE
5/8" GYP BD PAINTED
(EACH SIDE)
3 5/8" MTL. STUD 16" O.C.
5"
BASE AS SCHEDULED
METAL RUNNER TRACK, (TYP)
3 5/8"
METAL RUNNER TRACK
J-MOLD (EACH SIDE)
TOP OF WALL BELOW
5/8" GYP BD PAINTED TO
EXTEND ABOVE CEILING
STUDS EXTENDED TO
STRUCTURE ABOVE
5"
WALL ASSEMBLY
STANDOFF CAP
GASKETS
PANEL
BARREL SPACER
SCREW
WALL ANCHOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7100 E BELLEVIEW AVE,
STE 107
GREENWOOD VILLAGE,
CO 80111
Phone: (720) 200-5955 www.specializedeng.com
SES Project : 22295
KEYPLAN N
B C
D
330 N. Mead St, Suite 100 Wichita, KS 67202
Phone: (316) 262-2500 www.hfgarchitecture.com
EHRM IU AT THE GRAND JUNCTION,
CO VA MEDICAL CENTER
575-21-700
12/17/2024
2121 North Ave, Grand Junction, CO 81501
JW JS
A u to d e s k D o c s /2
G ra n d
J u n c ti o n
E H
R M
/5
-7
.B
.A
R
.r v t
/2
/2
:5
:0
P
M
B01-A109
EXISTING SIXTH FLOOR OVERALL &
ENLARGED PLANS
1/4" = 1'-0"
SIXTH FLOOR DEMO PLAN 6201, 6202, 6203, 6204
1/4" = 1'-0"
NEW SIXTH FLOOR PLAN ENLARGED 6201, 6202, 6203, 6204
1" = 20'-0"
SIXTH FLOOR PLAN OVERALL
N
1" = 20'
0' 10' 20' 40'
2' 4' 8'0'
1/4" = 1'-0"
DEMO SCHEDULE
1 REMOVE WALL PARTITIONS INCLUDING DOORS, FRAMES, COUNTERS, CABINETS AND SHELVING TO
EXTENTS SHOWN.
2 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR OWNER.
3 REMOVE ALL FLOORING AND WALL FINISHES INCLUDING WALL PROTECTION AND CORNER GUARDS.
EXISTING GYP. BD. TO REMAIN.
4 REMOVE CEILING IN ITS ENTIRETY. SEE DEMOLITION REFLECTED CEILING PLAN FOR EXTENTS.
5 REMOVE PORTION OF WALL TO PREPARE FOR INSTALLATION OF NEW DOOR.
6 REMOVE MILLWORK IN ITS ENTIRETY.
7 REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED PIPING AS APPLICABLE. SEE PLUMBING PLANS.
PREPARE/ LEVEL SURFACES TO RECEIVE NEW FINISHES.
8 REMOVE EXISTING FURNITURE, EQUIPMENT, BASE, CHAIR RAIL & SHELVING - VERIFY/SALVAGE FOR
OWNER.
9 REMOVE HEADER/ WALL ABOVE EXISTING DOOR TO ACCOMMODATE NEW DOOR.
11 REMOVE FLOORING TO EXTENTS SHOWN - PREP FOR NEW FLOORING.
12 SALVAGE & RE-USE EXISTING GLASS DECORATIVE PANELS. SALVAGE & RE-USE EXISTING WALL
STANDOFFS 12 TOTAL.
13 DEMO PORTION OF EXISTING WALL. PREPARE FOR NEW 6" RATED WALL ASSEMBLY AND FEC.
14 REMOVE EXISTING WOOD CABINET AND TRIM. SALVAGE FOR OWNER
15 REMOVE EXISTING OMNICELL UNIT. REF 2/B20-A101 FOR NEW LOCATION. VERIFY WITH VA
16 REMOVE EXISTING GLASS PANE. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS GLASS PANEL. G.C. TO VERIFY PANEL THICKNESS PRIOR TO BIDDING.
ALUMINUM FINISH SHALL MATCH EXISTING WINDOW FRAME. REFER TO SPEC 07 43 00
17 EXISTING FAN COIL UNIT. REF. MECHANICAL FOR DEMO/REMOVAL
18 REMOVE EXISTING BED DOCKER. SALVAGE FOR OWNER.
19 REMOVE EXISTING SIDEWALL LOUVER. G.C. TO VERIFY WITH OWNER PRIOR TO REMOVAL.
20 VERIFY WITH MECHANICAL AND ELECTRICAL FOR ANY REQ'D. RECEPTACLE & MED GAS
REMOVAL/DEMO/ABANDONMENT.
PLAN NOTES - FLOOR PLAN
1 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. CONNECTED TO STRUCTURE ABOVE W/ 5/8" GYP BD (BOTH SIDES) PAINTED TO EXTEND TO DECK ABOVE.
2 INFILL EXISTING OPENING WITH CONSTRUCTION METHODS AND MATERIALS THAT MATCH EXISTING CONSTRUCTION.
3 PROVIDE FULL HEIGHT PAINTED FIRE RATED, PRESSURE TREATED 3/4" PLYWOOD [8'-0" MIN. AFF.] OVER EXISTING OR NEW PAINTED GYP. BOARD WALL. VERIFY EXACT REQUIREMENTS WITH ELECTRICAL PLANS AND SPECIFICATIONS. CONTRACTOR TO SHOW PROOF OF PLYWOOD FIRE RATING
BEFORE PLYWOOD IS PAINTED.
5 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (ONE SIDE) PAINTED TO EXTEND TO DECK.
6 INSTALL SALVAGED GLASS DECORATIVE PANELS AND WALL STANDOFFS. PROVIDE NEW WALL STANDOFFS AS REQUIRED TO MATCH EXISTING. REF
ELEVATION 3-B01-A109 FOR MOUNTING HEIGHTS.
7 EXTEND METAL STUD WALL FROM EXISTING STUD WALL TO DECK ABOVE. EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES)
8 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES).
9 PATCH/FILL VOID HOLES IN GYP BOARD TO DECK (BOTH SIDES).
10 G.C. TO PROVIDE AND INSTALL A 20" X 6" MIN. METAL TRANSFER DOOR GRILLE WITHIN EXISTING DOOR. TO BE PAINTED THE SAME COLOR AS THE
ADJACENT DOOR FRAME.
11 NEW 6" 20 GA. METAL STUDS AT 16" O.C. TO EXTEND TO DECK ABOVE W/ 5/8" GYP BD (BOTH SIDES) PAINTED TO EXTEND TO DECK. MATCH EXISTING
WALL ASSEMBLY RATING.
12 PATCH, INFILL, PAINT AS REQ'D AT REMOVED SIDEWALL LOUVER.
13 AT REMOVED FAN COIL EXHAUST OPENING, INFILL WITH SAME WALL ASSEMBLY AND FINISH EA. SIDE.
14 ALL TR ROOM WALLS MUST BE SEALED TO MAINTAIN A COMPARTMENT PER NFPA 13.
1/2" = 1'-0"
PARTIAL HEIGHT WALL
1" = 1'-0"
PARTIAL HEIGHT WALL SECTION
1" = 1'-0"
WALL PARTITION TYPE "A1"
1 1/2" = 1'-0"
PLAN DETAIL - BRACE STUDS
Revisions: Date:
Addendum 2 08/22/25
3" = 1'-0"
DETAIL - WALL STANDOFFS
OFFICE
CORRIDOR
200A
CORRIDOR
OFFICE
CONFERENCE
ROOM
STAIRS
COMPLIANCE
BUSINESS
INTEGRITY
OFFICER
MENS
RESTROOM
WOMENS
RESTROOM
PRIVACY
OFFICER
205204202
TELEPHONE
CLOSET
ELECTRICAL
CLOSET
ELEVATOR
HOISTWAY
ˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍ
B05-A100
FE
REPLACE EXISTING FIRE EXTINGUISHER
WITH NEW CLASS C CARBON DIOXIDE FIRE
EXTINGUISHER. G.C. TO VERIFY REQ'D.
CANISTER SIZE WITH VA. FE APPROX. 10'
FROM NEW TR
220 221
80 SF
TR
6' - 7" 4' - 8 1/2"
8' - 11" 2' - 4 1/2"
51 SF
CLOSET
ELECTRICAL
CLOSET
3' - 4" 4"
9'-9 1/4"
OPEN TO DECK
TR
CLOSET
202 8' - 0"
OFFICE
TELEPHONE
CLOSET
8' - 0"
8' - 0" 7' - 10 1/2"8' - 0"
ELECTRICAL
CLOSET
OFFICE
TELEPHONE
CLOSET
ELECTRICAL
CLOSET
DEP CHIEF
CORRIDOR
100A
POLICE
TRAINING &
CONFERENCE
RM
CORRIDOR
STAIRS
STAIRS
ELEVATOR
HOISTWAY
EVIDENCE
PROCESSING
/STORAGE
LT 2 WS
PHYSICAL
SECURITY
OFFICER,
COMPLIANCE
OFFICER,
STORAGE
SECURITY
ˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍ
B05-A100
POLICE
CHIEF
POLICE
FOUR
TOUCHDOWN
SPACES
PIV
TRAINING
OFFICER
TELEPHONE
CLOSET
EXIST.
WALL
DOOR
CEILING
AND GRID
DEMO LEGEND
2" 3' - 0"
2"
3' - 0"
A
CAULKING @ EA. SIDE
HEADER, REF. STRUCT.
H.M. FRAME W/ MIN. 3
ANCHORS EA. SIDE -
REF. SCHED.
DOOR PER SCHED.
GYP. BD. & MTL. STUD WALL
PER PART. SCHED.
CAULKING @ EA. SIDE
DOOR PER SCHED.
H.M. FRAME W/ MIN. 3
ANCHORS EA. SIDE -
REF. SCHED.
GYP. BD. & MTL. STUD WALL
PER PART. SCHED.
20 GA. DBL STUDS @
JAMBS, TYP.
U .N
.O
T Y
P
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7100 E BELLEVIEW AVE,
STE 107
GREENWOOD VILLAGE,
CO 80111
Phone: (720) 200-5955 www.specializedeng.com
SES Project : 22295
330 N. Mead St, Suite 100 Wichita, KS 67202
Phone: (316) 262-2500 www.hfgarchitecture.com
EHRM IU AT THE GRAND JUNCTION,
CO VA MEDICAL CENTER
575-21-700
12/17/2024
2121 North Ave, Grand Junction, CO 81501
JW JS
A u to d e s k D o c s /2
G ra n d
J u n c ti o n
E H
R M
/5
-7
.B
.A
R
.r v t
/9 /2
:5
:1
P
M
B05-A100
BUILDING 5 OVERALL & ENLARGED PLANS
1/8" = 1'-0"
BLDG. 5 - EXISTING SECOND FLOOR PLAN OVERALL
1/4" = 1'-0"
BLDG. 5 - SECOND FLOOR DEMO PLAN 201
1/4" = 1'-0"
BLDG. 5 - SECOND FLOOR PLAN ENLARGED 201
1/4" = 1'-0"
BLDG. 5 - SECOND FLOOR RCP 201
1/4" = 1'-0"
BLDG. 5 - SECOND FLOOR DEMO RCP 201
DEMO SCHEDULE
1 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR OWNER.
2 REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR RE-USE
3 REMOVE PORTION OF WALL TO EXTENTS SHOWN.
4 REMOVE ALL FLOORING AND WALL FINISHES INCLUDING WALL
PROTECTION AND CORNER GUARDS TO EXTENTS SHOWN. EXISTING
GYP. BD. TO REMAIN.
5 REMOVE PORTION OF WALL TO PREPARE FOR INSTALLATION OF NEW
DOOR.
2' 4' 8'0'
1/4" = 1'-0"
1/8" = 1'-0"
BLDG. 5 - EXISTING FIRST FLOOR PLAN OVERALL
1/2" = 1'-0"
BLDG. 5 - FIRST FLOOR PLAN ENLARGED 120
4' 8' 16'
1/8" = 1'-0"
0'
DEMO RCP SCHEDULE
1 EXISTING GYP. BOARD CEILING AND ALL OF ITS COMPONENTS
TO BE REMOVED.
2 EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE
REMOVED - SALVAGE FOR OWNER.
3 NON-RATED ICRA/CONSTRUCTION BARRIERS ARE PERMITTED
ONLY WHERE THE SPRINKLERS IN THE CONSTRUCTION AREA
REMAIN IN SERVICE. REPLACE THE EXISTING SPRINKLER(S) IN
THE TR WITH NEW UPRIGHT SPRINKLERS AT THE TIME THE
CEILING IS REMOVED IN ORDER TO MAINTAIN SPRINKLER
PROTECTION IN THE CONSTRUCTION AREA. - REFERENCE
PLUMBING.
PLAN NOTES - FLOOR PLAN
1 NEW 3 5/8" 20 GA. METAL STUDS AT 16" O.C. CONNECTED TO STRUCTURE ABOVE W/ 5/8"
GYP BD (BOTH SIDES) PAINTED TO EXTEND TO DECK.
2 PROVIDE FULL HEIGHT PAINTED FIRE RATED, PRESSURE TREATED 3/4" PLYWOOD [8'-0"
MIN. AFF.] OVER EXISTING OR NEW PAINTED GYP. BOARD WALL. VERIFY EXACT
REQUIREMENTS WITH ELECTRICAL PLANS AND SPECIFICATIONS. CONTRACTOR TO
SHOW PROOF OF PLYWOOD FIRE RATING BEFORE PLYWOOD IS PAINTED.
3 EXTEND METAL STUD WALL FROM EXISTING STUD WALL TO DECK ABOVE. EXTEND GYP
BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY BEFORE BIDDING.
4 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY BEFORE BIDDING.
5 PATCH/FILL VOID HOLES IN GYP BOARD TO DECK (BOTH SIDES). G.C. TO VERIFY
BEFORE BIDDING.
6 ALL TR ROOM WALLS MUST BE SEALED TO MAINTAIN A COMPARTMENT PER NFPA 13.
N
DOOR SCHEDULE
DOOR
NO. SIZE HDWR SET FIRE RATING
DOOR FRAME DETAILS
REMARKSTYPE MAT'L GLASS TYPE MAT'L GLASS HEAD JAMB THRESHOLD
201 3'-0" x 7'-0" x 1 3/4" 1.0 20 MIN. A WD - 1 HM - 3/B05-A100 4/B05-A100 - BUILDING 5 - FLOOR 2
202 3'-0" x 7'-0" x 1 3/4" 2.0 - A WD - 1 HM - 3/B05-A100 4/B05-A100 - BUILDING 5 - FLOOR 2
1/2" = 1'-0"
DOOR FRAME TYPE ELEVATION
1/2" = 1'-0"
DOOR TYPE ELEVATION
1 1/2" = 1'-0"
HM DOOR (HEAD)
1 1/2" = 1'-0"
HM DOOR (JAMB)
PLAN NOTES - RCP
1 INFILL CEILING WITH CONSTRUCTION METHODS AND
MATERIALS THAT MATCH EXISTING CEILING.
1' 2' 4'
1/2" = 1'-0"
0'
QUALITY
MANAGER
CHIEF
QUALITY
CHIEF OF
EDUCATION
PROGRAM
SPECIALIST
CORRIDOR
ED/STORAGE
117 LOBBY
CONFERENCE
ROOM
CLOSET
116A
STORAGE
CLOSET
116B
VESTIBULE
114A
COMPUTER
LAB
101/101A 102 INNOVATION/COMPUTER
DIRECTOR,
CONFERENCE
KITCHEN
RR
RR
ELEC.
CORR.
MECH
ROOM
STAIRS
NURSE
EDUCATOR
TE
106A
HOUSEKEEPING
CLOSET
111A
CORRIDOR
ˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍˍ ˍˍˍˍˍˍˍ
B06-A100
42 SF
TE
106A
9' - 6 1/2"
EXIST.
OPEN TO DECK
TE
106A8'-0" 1 21
WALL
DOOR
CEILING
AND GRID
DEMO LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
7100 E BELLEVIEW AVE,
STE 107
GREENWOOD VILLAGE,
CO 80111
Phone: (720) 200-5955 www.specializedeng.com
SES Project : 22295
330 N. Mead St, Suite 100 Wichita, KS 67202
Phone: (316) 262-2500 www.hfgarchitecture.com
EHRM IU AT THE GRAND JUNCTION,
CO VA MEDICAL CENTER
575-21-700
12/17/2024
2121 North Ave, Grand Junction, CO 81501
JW JS
A u to d e s k D o c s /2
G ra n d
J u n c ti o n
E H
R M
/5
-7
.B
.A
R
.r v t
/9 /2
:5
:4
P
M
B06-A100
BUILDING 6 OVERALL & ENLARGED PLANS
1/8" = 1'-0"
BLDG. 6 - EXISTING FIRST FLOOR PLAN OVERALL
1/4" = 1'-0"
BLDG. 6 - FIRST FLOOR PLAN ENLARGED 106
2' 4' 8'0'
1/4" = 1'-0"
1/4" = 1'-0"
BLDG. 6 - RCP 106
1/4" = 1'-0"
BLDG. 6 - DEMO RCP 106
1/4" = 1'-0"
BLDG. 6 - DEMO PLAN 106
DEMO SCHEDULE
1 EXISTING CONDITIONS TO REMAIN - NO DEMO
REQUIRED
PLAN NOTES - FLOOR PLAN
1 EXISTING CONDITIONS TO REMAIN.
2 EXTEND GYP BOARD TO DECK ABOVE (BOTH SIDES). G.C. TO VERIFY
BEFORE BIDDING.
DEMO RCP SCHEDULE
1 EXISTING CEILING TILE/ GRID/ LIGHTS/ DIFFUSERS TO BE REMOVED -
SALVAGE FOR OWNER.
2 NON-RATED ICRA/CONSTRUCTION BARRIERS ARE PERMITTED ONLY
WHERE THE SPRINKLERS IN THE CONSTRUCTION AREA REMAIN IN
SERVICE. REPLACE THE EXISTING SPRINKLER(S) IN THE TR WITH
NEW UPRIGHT SPRINKLERS AT THE TIME THE CEILING IS REMOVED
IN ORDER TO MAINTAIN SPRINKLER PROTECTION IN THE
CONSTRUCTION AREA. - REFERENCE PLUMBING.
4' 8' 16'
1/8" = 1'-0"
0'
N
PLUMB
SHOP
STORAGE
TOILET
XXX
OFFICE
BREAK
ROOM
CORR
STORAGE
OFFICE
GENERAL
ENG.
114C
TOILET
XXXA
TOILET
XXXB
OFFICE
SPACE
CORR
OFFICE
ENTRY
CHIEF
ENGINEER
CONF.
ROOM
JAN
B08-A100
CORR
(3) INSULATED PIPES
13' - 6"
CORR
74 SF
TE ROOM
13' - 1"
3' - 4" 4"
12' - 0"
TE ROOM
OPEN TO DECK
WALL
DOOR
CEILING
AND GRID
DEMO LEGEND
2" 3' - 0"
2"
3' - 0"
A
CAULKING @ EA. SIDE
HEADER, REF. STRUCT.
H.M. FRAME W/ MIN. 3
ANCHORS EA. SIDE -
REF. SCHED.
DOOR PER SCHED.
GYP. BD. & MTL. STUD WALL
PER PART. SCHED.
CAULKING @ EA. SIDE
DOOR PER SCHED.
H.M. FRAME W/ MIN. 3
ANCHORS EA. SIDE -
REF. SCHED.
GYP. BD. & MTL. STUD WALL
PER PART. SCHED.
20 GA. DBL STUDS @
JAMBS, TYP.
U .N
.O
T Y
P
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5…