90209 - 570-20-308 - VA CA Fresno CHW - ASI-01 Drawings- 20260724.pdf

PDF 21 MB Posted

Attached to
Z2DA--570-20-308 - Replace and Expand Chilled Water Infrastructure in Building 1 | Construction Services Procurement
Solicitation number
36C26126R0028
Issued by

About this file

This document is a set of architectural drawings for the Fresno VA Hospital's chilled water infrastructure replacement and expansion project. The drawings depict demolition and construction plans across multiple floors of Building 1, detailing infection control measures, wall modifications, and mechanical system installations necessary to support the project's objectives.

The demolition plans (sheets AD101-AD109) specify work across seven floors including the sub-basement through the seventh floor, organized into Unit A and Unit B sections. Key demolition requirements include removal of acoustical ceiling tiles and grid systems, gypsum board or plaster ceilings, floor slabs via saw-cut operations, and selective removal of mechanical equipment and casework. Infection Control Restriction Area (ICRA) classifications range from Class II for exterior work to Class IV for interior spaces, with specific requirements for containment barriers, pressure monitoring, and after-hours installation/removal between 5:30 PM and 6:00 AM PST. Critical notes emphasize maintaining life safety egress, temporary wall partition layout approval by the Contracting Officer's Representative (COR), and adherence to section 01 35 26 Safety Requirements. The construction floor plans (sheets AE101-AE104) illustrate new wall placements per wall type specifications, new door installations, and coordination requirements for owner-provided equipment blocking. General construction notes require UL-rated walls, cement board for tile-bearing surfaces, moisture-resistant gypsum board for plumbing fixture walls, and contractor responsibility for fireproofing and lead lining repairs to maintain required protection levels. The project is dated for a July 1, 2026 issue with ASI 01 revision dated July 24, 2026, and involves Seven Generations Architecture + Engineering and DavEnergy Solutions as design consultants.

View the file

Other files

File Type Posted
Wage Determinaton CA202600148 07.14.26.pdf PDF
36C26126R0028 0007.docx DOCX document
36C26126R0028 0006.docx DOCX document
RFI LOG UPDATE AMENDMENT 005.xlsx XLSX spreadsheet
90209 - 570-20-308 - Fresno CHW - ASI 01 - 20260724.pdf PDF
36C26126R0028 0005.docx DOCX document
36C26126R0028 0004.docx DOCX document
36C26126R0028 -0003.docx DOCX document
SECTION 01 91 00 GENERAL COMMISSIONING REQUIREMENTS.pdf PDF
Construction Clause 52.212-4.docx DOCX document
Attachment C - Key Personnel Evaluation 36C26126R0028.docx DOCX document
36C26126R0028-0002.docx DOCX document
RFI LOG UPDATE AMENDMENT 003.xlsx XLSX spreadsheet
90209 - 570-20-308 - Fresno Chilled Water Bid Set Combined Specs-20260504r1.pdf PDF
VA Specific Clause Payments Fixed Price Construction.docx DOCX document
36C26126R0028 0003.docx DOCX document
VA Specific Clause Payments under Fixed Price Construction.docx DOCX document
VA Fresno Chiller Plant MEP Record Drawings 11-15-24_Part1.pdf PDF
Construction 52.212-4.docx DOCX document
VA Fresno Chiller Plant MEP Record Drawings 11-15-24_Part2.pdf PDF
RFI LOG UPDATE AMENDMENT 002.xlsx XLSX spreadsheet
36C26126R0028 0002.docx DOCX document
36C26126R0028 Site Visit Log In Sheet.pdf PDF
90209 - 570-20-308 - Fresno CHW - Bulletin 01 Summary - 20260701.pdf PDF
90209 - 570-20-308 - Fresno CHW - Bulletin 01 Narrative - 20260701.pdf PDF
Question RFI No. 4 - Asbestos Abatement Scope and Allowance.docx DOCX document
RFI LOG.xlsx XLSX spreadsheet
Question RFI No. 7 - Buy American Domestic Materials.docx DOCX document
Question RFI No. 12 - Temporary Pumps Piping.docx DOCX document
90209 - 570-20-308 - Fresno CHW - Bulletin 01 Drawings - 20260701.pdf PDF
36C26126R0028 0001.docx DOCX document
VA NOTICE OF LIMITATIONS ON SUBCONTRACTING DEV 2023.docx DOCX document
90209 - 570-20-308 - Fresno CHW - Bid Set Basis Of Design - 20260504.pdf PDF
Attachment C - Key Personnel Evaluation.docx DOCX document
36C26126R0028_1.docx DOCX document
ID Me Information.docx DOCX document
Attachment E - Past Performance Questionnaire.docx DOCX document
90209 - 570-20-308 - Fresno Chilled Water Bid Set Combined Drawings-20260504_Part3.pdf PDF
Attachment A - Request for Information.docx DOCX document
Attachment D - Construction Experience Project Data Sheet.doc DOC document
90209 - 570-20-308 - Fresno Chilled Water Bid Set Combined Drawings-20260504_Part2.pdf PDF
Attachment B - EMR Sheet.docx DOCX document
90209 - 570-20-308 - Fresno Chilled Water Bid Set Combined Specs-20260504.pdf PDF
90209 - 570-20-308 - Fresno Chilled Water Bid Set Combined Drawings-20260504_Part1.pdf PDF
Attachment G - Supplemental Price Breakdown.xlsx XLSX spreadsheet
Site Visit Location Details.pdf PDF
852.219-75 Fillable.pdf PDF
Show all 47

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ICRA GENERAL NOTES

1. REFER TO 01 35 26 SAFETY REQUIREMENTS FOR ADDITIONAL

INFORMATION.

2. CONSTRUCT ICRA BARRIER PRIOR TO ANY DEMOLITION

WORK.

3. WHERE CLASS IV ICRA IS CALLED OUT ON THE DEMO PLANS,

EXISTING MECHANICAL ROOMS CAN BE PLANNED FOR

CLASS III.

4. ALL EXTERIOR WORK TO BE CLASS II ICRA.

5. THE INTENT OF INFECTION CONTROL ISOLATION IS TO

CONTAIN DUST AND PARTICULATE MATTER FROM THE

CONSTRUCTION AREA. PERIMETER TO BE SEALED

COMPLETELY WITH SHEET PLASTIC WHEN NO TEMPORARY

PARTITION IS CALLED OUT.

6. MAINTAIN PRESSURE MONITORS DRUING CONSTRUCTION

OPERATIONS.

7. CONTROL BARRIERS TO BE INSTALLED AND REMOVED ONLY

DURING AFTER HOURS (5:30 PM PST - 6:00 AM PST)

8. LIFE SAFETY EGRESS IS TO BE MAINTAINED AT ALL TIMES.

9. EXACT TEMPORARY WALL PARTITION LAYOUT TO BE

PROVIDED BY CONTRACTOR. DIMENSIONS AND EXACT

LAYOUT TO BE REVIEWED AT THE CONSTRUCTION SITE WITH

COR APPROVAL.

DEMO/ICRA LEGEND

TEMPORARY WALL (REFER TO WALL TYPES)

AREA OF SAWCUT FLOOR SLAB DEMOLITION

(REFER TO STRUCTURAL)

AREA NOT IN PROJECT SCOPE

NOTE: SEE SHEET AD001 FOR DEMOLITION GENERAL NOTES.

A D

B

B2A03

MECH EQUIP. ROOM

1B09

AIR INTAKE

FLOOR

SLAB

ABOVE

A

B architecture +engineering

SEVEN

GENERATIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID SET

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

570-20-308REPLACE AND EXPAND CHILLED

WATER INFRASTRUCTURE,

BUILDING 1 N/A

TCMH07/01/2026

FRESNO VA HOSPITAL

2615 E. CLINTON AVE, FRESNO, CA 93703

SEVEN GENERATIONS ARCHITECTURE + ENGINEERING

600 E. MICHIGAN AVE., SUITE B

KALAMAZOO, MI 49007

269-927-0144

DAVENERGY SOLUTIONS

2207 GARNET AVE, SUITE 1

SAN DIEGO, CA 22108

612-770-8552

A/E:

A u to d e s k D o c s /2

V A

F re s n o C h ill e d

W a te r

In fr a s tr u c tu re /2

V

A F re s n o

C h ill e d

W a te r

In fr a s tr u c tu re

A R

C H

-R

.r v t

/2

/2

:5

:5

P

M

SCALE: As indicated

AD101A

SUB-BASEMENT DEMO PLAN -

AREA A

NORTH

SCALE: 1/8" = 1'-0"

SUB-BASEMENT DEMOLITION

FLOOR PLAN - UNIT A

DEMOLITION KEY NOTES

NO. DESCRIPTION

12 SAW-CUT AND REMOVE FLOOR DECK AND SLAB. REFER TO STRUCTURAL DRAWINGS FOR STRUCTURAL

SUPPORT MODIFICATIONS REQUIRED AND EXACT SAW-CUT DIMENSIONS AND PLACEMENT.

NOTE: THIS AREA TO BE CLASS III ICRA

Revisions: Date:

BID SET 05/04/2026

BULLETIN 1 07/01/2026

ASI 01 07/24/2026

F

1. REFER TO 01 35 26 SAFETY REQUIREMENTS FOR ADDITIONAL

INFORMATION.

2. CONSTRUCT ICRA BARRIER PRIOR TO ANY DEMOLITION

WORK.

3. WHERE CLASS IV ICRA IS CALLED OUT ON THE DEMO PLANS,

EXISTING MECHANICAL ROOMS CAN BE PLANNED FOR

CLASS III.

4. ALL EXTERIOR WORK TO BE CLASS II ICRA.

5. THE INTENT OF INFECTION CONTROL ISOLATION IS TO

CONTAIN DUST AND PARTICULATE MATTER FROM THE

CONSTRUCTION AREA. PERIMETER TO BE SEALED

COMPLETELY WITH SHEET PLASTIC WHEN NO TEMPORARY

PARTITION IS CALLED OUT.

6. MAINTAIN PRESSURE MONITORS DRUING CONSTRUCTION

OPERATIONS.

7. CONTROL BARRIERS TO BE INSTALLED AND REMOVED ONLY

DURING AFTER HOURS (5:30 PM PST - 6:00 AM PST)

8. LIFE SAFETY EGRESS IS TO BE MAINTAINED AT ALL TIMES.

9. EXACT TEMPORARY WALL PARTITION LAYOUT TO BE

PROVIDED BY CONTRACTOR. DIMENSIONS AND EXACT

LAYOUT TO BE REVIEWED AT THE CONSTRUCTION SITE WITH

COR APPROVAL.

DEMO/ICRA LEGEND

TEMPORARY WALL (REFER TO WALL TYPES)

AREA OF SAWCUT FLOOR SLAB DEMOLITION

(REFER TO STRUCTURAL)

AREA NOT IN PROJECT SCOPE

NOTE: SEE SHEET AD001 FOR DEMOLITION GENERAL NOTES.

A D

A

A D

A

B2A08A

BATTERY CHARGING

ROOM

B2A08

EMS STORAGE

B2A07

EMS SUPERVISOR'S

B2A03

MECH EQUIP. ROOM

B2A08

EMS STORAGE

B2A04

POLICE VAULT

B2A03

MECH EQUIP. ROOM

1B09

AIR INTAKE

SB-5

ELECTRIC SHOP

B2A01A

HVAC/ELECTRICAL

OFFICE

B2A01

ENGINEERING SHOP

B2A03

MECH EQUIP. ROOM

B2A01B

STORAGE

B2A11

CORRIDOR

FLOOR

SLAB

ABOVE

B2A02

EMS LOCKER ROOM

A

B architecture +engineering

SEVEN

GENERATIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID SET

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

570-20-308REPLACE AND EXPAND CHILLED

WATER INFRASTRUCTURE,

BUILDING 1 N/A

TCMH07/01/2026

FRESNO VA HOSPITAL

2615 E. CLINTON AVE, FRESNO, CA 93703

SEVEN GENERATIONS ARCHITECTURE + ENGINEERING

600 E. MICHIGAN AVE., SUITE B

KALAMAZOO, MI 49007

269-927-0144

DAVENERGY SOLUTIONS

2207 GARNET AVE, SUITE 1

SAN DIEGO, CA 22108

612-770-8552

A/E:

A u to d e s k D o c s /2

V A

F re s n o C h ill e d

W a te r

In fr a s tr u c tu re /2

V

A F re s n o

C h ill e d

W a te r

In fr a s tr u c tu re

A R

C H

-R

.r v t

/2

/2

:5

:5

P

M

SCALE: As indicated

AD101B

SUB-BASEMENT DEMO PLAN -

AREA B

DEMOLITION KEY NOTES

NO. DESCRIPTION

12 SAW-CUT AND REMOVE FLOOR DECK AND SLAB. REFER TO STRUCTURAL DRAWINGS FOR STRUCTURAL

SUPPORT MODIFICATIONS REQUIRED AND EXACT SAW-CUT DIMENSIONS AND PLACEMENT.

14 REMOVE A PORTION OF EXISTING ROOF MEMBRANE, COVER BOARD, RIGID INSULATION, AND ALL

EXISTING MATERIALS DOWN TO EXISTING DECK.

NORTH

SCALE: 1/8" = 1'-0"

SUB-BASEMENT DEMOLITION

FLOOR PLAN - UNIT B

NOTE: THIS AREA TO BE CLASS III ICRA

Revisions: Date:

BID SET 05/04/2026

BULLETIN 1 07/01/2026

S

S S S

SS

F

ICRA GENERAL NOTES

1. REFER TO 01 35 26 SAFETY REQUIREMENTS FOR ADDITIONAL

INFORMATION.

2. CONSTRUCT ICRA BARRIER PRIOR TO ANY DEMOLITION

WORK.

3. WHERE CLASS IV ICRA IS CALLED OUT ON THE DEMO PLANS,

EXISTING MECHANICAL ROOMS CAN BE PLANNED FOR

CLASS III.

4. ALL EXTERIOR WORK TO BE CLASS II ICRA.

5. THE INTENT OF INFECTION CONTROL ISOLATION IS TO

CONTAIN DUST AND PARTICULATE MATTER FROM THE

CONSTRUCTION AREA. PERIMETER TO BE SEALED

COMPLETELY WITH SHEET PLASTIC WHEN NO TEMPORARY

PARTITION IS CALLED OUT.

6. MAINTAIN PRESSURE MONITORS DRUING CONSTRUCTION

OPERATIONS.

7. CONTROL BARRIERS TO BE INSTALLED AND REMOVED ONLY

DURING AFTER HOURS (5:30 PM PST - 6:00 AM PST)

8. LIFE SAFETY EGRESS IS TO BE MAINTAINED AT ALL TIMES.

9. EXACT TEMPORARY WALL PARTITION LAYOUT TO BE

PROVIDED BY CONTRACTOR. DIMENSIONS AND EXACT

LAYOUT TO BE REVIEWED AT THE CONSTRUCTION SITE WITH

COR APPROVAL.

DEMO/ICRA LEGEND

TEMPORARY WALL (REFER TO WALL TYPES)

AREA OF SAWCUT FLOOR SLAB DEMOLITION

(REFER TO STRUCTURAL)

AREA NOT IN PROJECT SCOPE

NOTE: SEE SHEET AD001 FOR DEMOLITION GENERAL NOTES.

A D

B

2 3

1 1

EXPOSED

STRUCTURE

ABOVE

B1B10

EMS OFFICE

B1B11

CUSTOMER SUPPORT

B1B11A

IRM OFFICE

B1B08

MECHANICAL

B1B09

CHASE

B1B06A

ELECTRICAL UPS

B1B16

LAUNDRY SUITE

B1B16D

OFFICE

B1B16C

STORAGE

B1B-5

CORRIDOR

B1B16G2

SOILED LAUNDRY

B1B15

CLOTHING ROOM

LOST & FOUND

B1B14

IRM CUSTOMER

SUPPORT

B1B14A

SERVER ROOM

B1B-3

CORRIDOR

B1A01

SUITE

B1B-4

CORRIDOR

A

B architecture +engineering

SEVEN

GENERATIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID SET

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

570-20-308REPLACE AND EXPAND CHILLED

WATER INFRASTRUCTURE,

BUILDING 1 N/A

TCMH07/01/2026

FRESNO VA HOSPITAL

2615 E. CLINTON AVE, FRESNO, CA 93703

SEVEN GENERATIONS ARCHITECTURE + ENGINEERING

600 E. MICHIGAN AVE., SUITE B

KALAMAZOO, MI 49007

269-927-0144

DAVENERGY SOLUTIONS

2207 GARNET AVE, SUITE 1

SAN DIEGO, CA 22108

612-770-8552

A/E:

A u to d e s k D o c s /2

V A

F re s n o C h ill e d

W a te r

In fr a s tr u c tu re /2

V

A F re s n o

C h ill e d

W a te r

In fr a s tr u c tu re

A R

C H

-R

.r v t

/2

/2

:5

:5

P

M

SCALE: As indicated

AD102A

BASEMENT DEMO PLAN - AREA A

DEMOLITION KEY NOTES

NO. DESCRIPTION

1 REMOVE EXISTING ACOUSTICAL CEILING TILE AND GRID SYSTEM INCLUDING ASSOCIATED HANGERS, METAL TEE GRID, AND EDGE ANGLES AS REQUIRED FOR DEMOLITION AND INSTALLATION OF

CONDENSATE/CHILLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]

2 REMOVE EXISTING GYPSUM BOARD OR PLASTER CEILING OVER METAL LATH ATTACHED TO SUSPENDED COLD ROLLED CHANNELS AS REQUIRED AND TO THE EXTENT FOR DEMOLITION AND INSTALLATION OF CONDENSATE/CHILLLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]. PATCH

& REPAIR ADJACENT SURFACES TO REMAIN AS NECESSARY.

3 REMOVE EXISTING ADHERED ACOUSTICAL CEILING ATTACHED TO SUSPENDED GYPSUM OR CEMENT PLASTER SUSPENDED CEILING AS REQUIRED AND TO THE EXTENT FOR DEMOLITION AND INSTALLATION OF CONDENSATE/CHILLED WATER SYSTEM. . EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]. PATCH

& REPAIR ADJACENT SURFACES TO REMAIN AS NECESSARY.

12 SAW-CUT AND REMOVE FLOOR DECK AND SLAB. REFER TO STRUCTURAL DRAWINGS FOR STRUCTURAL

SUPPORT MODIFICATIONS REQUIRED AND EXACT SAW-CUT DIMENSIONS AND PLACEMENT.

NORTH

SCALE: 1/8" = 1'-0"

BASEMENT FLOOR DEMOLITION

PLAN - UNIT A

NOTE: THIS AREA TO BE CLASS IV ICRA

Revisions: Date:

BID SET 05/04/2026

BULLETIN 1 07/01/2026

ASI 01 07/24/2026

S

S

S

F

ICRA GENERAL NOTES

1. REFER TO 01 35 26 SAFETY REQUIREMENTS FOR ADDITIONAL

INFORMATION.

2. CONSTRUCT ICRA BARRIER PRIOR TO ANY DEMOLITION

WORK.

3. WHERE CLASS IV ICRA IS CALLED OUT ON THE DEMO PLANS,

EXISTING MECHANICAL ROOMS CAN BE PLANNED FOR

CLASS III.

4. ALL EXTERIOR WORK TO BE CLASS II ICRA.

5. THE INTENT OF INFECTION CONTROL ISOLATION IS TO

CONTAIN DUST AND PARTICULATE MATTER FROM THE

CONSTRUCTION AREA. PERIMETER TO BE SEALED

COMPLETELY WITH SHEET PLASTIC WHEN NO TEMPORARY

PARTITION IS CALLED OUT.

6. MAINTAIN PRESSURE MONITORS DRUING CONSTRUCTION

OPERATIONS.

7. CONTROL BARRIERS TO BE INSTALLED AND REMOVED ONLY

DURING AFTER HOURS (5:30 PM PST - 6:00 AM PST)

8. LIFE SAFETY EGRESS IS TO BE MAINTAINED AT ALL TIMES.

9. EXACT TEMPORARY WALL PARTITION LAYOUT TO BE

PROVIDED BY CONTRACTOR. DIMENSIONS AND EXACT

LAYOUT TO BE REVIEWED AT THE CONSTRUCTION SITE WITH

COR APPROVAL.

DEMO/ICRA LEGEND

TEMPORARY WALL (REFER TO WALL TYPES)

AREA OF SAWCUT FLOOR SLAB DEMOLITION

(REFER TO STRUCTURAL)

AREA NOT IN PROJECT SCOPE

NOTE: SEE SHEET AD001 FOR DEMOLITION GENERAL NOTES.

A D

A

A D

A

EXPOSED STRUCTURE ABOVE

EXPOSED

STRUCTURE

ABOVE

EXPOSED

STRUCTURE

ABOVE

EXPOSED

STRUCTURE

ABOVE

EXPOSED

STRUCTURE

ABOVE

2 1

EXPOSED

STRUCTURE

ABOVE

B1A13

TELECOMMUNICATION

OFFICE

B1A12

TELEPHONE

OPERATORS

REFRIG.

REFRIG.

MEAL

PRE-PREP

COLD BOX 7

B1A-4

CORRIDOR

BOX 5

COLD

CHEFS

COLD BOX 1

B1A10

EAT PREP.

B1A08

NUTRITION & FOOD

KITCHEN

PREPARATION

AREA

KITHCEN

DISHWASH

AREA

KITCHEN

B1A04

CHEMICAL

STORAGE

NO.3

DUMBWAITER

STORES

DRY

B1A01A

OFFICE

B1A01.1

OFFICE

1A85

HEALTH

INFORMATION

MANAGEMENT

B1A01

SUITE

B1A01.4

VESTIBULE

B1A-1

CORRIDOR

B1A02

LAUNDRY CHUTE

P-1

PASSENGER

ELEVATOR

P-2

PASSENGER

ELEVATOR

P-3

ELEVATOR LOBBY

B1A-2

CORRIDOR

B1A-3

CORRIDOR

B1B-2

CORRIDOR

B1B10

EMS OFFICE

B1B11

CUSTOMER SUPPORT

B1B11A

IRM OFFICE

B1B07

BIOMEDICAL

ENGINEERING

B1B08

MECHANICAL

NO.4

DUMBWAITER

B1B02

CANTEEN STORAGE

B1A03

MECHANICAL

B1B09

CHASE

B1B06A

ELECTRICAL UPS

B1B06

ELECTRICAL VAULT

B1B05

MECHANICAL

CLOSET

B1B-1

CORRIDOR

A

B architecture +engineering

SEVEN

GENERATIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID SET

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

570-20-308REPLACE AND EXPAND CHILLED

WATER INFRASTRUCTURE,

BUILDING 1 N/A

TCMH07/01/2026

FRESNO VA HOSPITAL

2615 E. CLINTON AVE, FRESNO, CA 93703

SEVEN GENERATIONS ARCHITECTURE + ENGINEERING

600 E. MICHIGAN AVE., SUITE B

KALAMAZOO, MI 49007

269-927-0144

DAVENERGY SOLUTIONS

2207 GARNET AVE, SUITE 1

SAN DIEGO, CA 22108

612-770-8552

A/E:

A u to d e s k D o c s /2

V A

F re s n o C h ill e d

W a te r

In fr a s tr u c tu re /2

V

A F re s n o

C h ill e d

W a te r

In fr a s tr u c tu re

A R

C H

-R

.r v t

/2

/2

:5

:5

P

M

SCALE: As indicated

AD102B

BASEMENT DEMO PLAN - AREA B

DEMOLITION KEY NOTES

NO. DESCRIPTION

1 REMOVE EXISTING ACOUSTICAL CEILING TILE AND GRID SYSTEM INCLUDING ASSOCIATED HANGERS, METAL TEE GRID, AND EDGE ANGLES AS REQUIRED FOR DEMOLITION AND INSTALLATION OF

CONDENSATE/CHILLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]

2 REMOVE EXISTING GYPSUM BOARD OR PLASTER CEILING OVER METAL LATH ATTACHED TO SUSPENDED COLD ROLLED CHANNELS AS REQUIRED AND TO THE EXTENT FOR DEMOLITION AND INSTALLATION OF CONDENSATE/CHILLLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]. PATCH

& REPAIR ADJACENT SURFACES TO REMAIN AS NECESSARY.

12 SAW-CUT AND REMOVE FLOOR DECK AND SLAB. REFER TO STRUCTURAL DRAWINGS FOR STRUCTURAL

SUPPORT MODIFICATIONS REQUIRED AND EXACT SAW-CUT DIMENSIONS AND PLACEMENT.

NORTH

SCALE: 1/8" = 1'-0"

BASEMENT FLOOR DEMOLITION

PLAN - UNIT B

NOTE: THIS AREA TO BE CLASS IV ICRA

Revisions: Date:

BID SET 05/04/2026

BULLETIN 1 07/01/2026

ASI 01 07/24/2026

1. REFER TO 01 35 26 SAFETY REQUIREMENTS FOR ADDITIONAL

INFORMATION.

2. CONSTRUCT ICRA BARRIER PRIOR TO ANY DEMOLITION

WORK.

3. WHERE CLASS IV ICRA IS CALLED OUT ON THE DEMO PLANS,

EXISTING MECHANICAL ROOMS CAN BE PLANNED FOR

CLASS III.

4. ALL EXTERIOR WORK TO BE CLASS II ICRA.

5. THE INTENT OF INFECTION CONTROL ISOLATION IS TO

CONTAIN DUST AND PARTICULATE MATTER FROM THE

CONSTRUCTION AREA. PERIMETER TO BE SEALED

COMPLETELY WITH SHEET PLASTIC WHEN NO TEMPORARY

PARTITION IS CALLED OUT.

6. MAINTAIN PRESSURE MONITORS DRUING CONSTRUCTION

OPERATIONS.

7. CONTROL BARRIERS TO BE INSTALLED AND REMOVED ONLY

DURING AFTER HOURS (5:30 PM PST - 6:00 AM PST)

8. LIFE SAFETY EGRESS IS TO BE MAINTAINED AT ALL TIMES.

9. EXACT TEMPORARY WALL PARTITION LAYOUT TO BE

PROVIDED BY CONTRACTOR. DIMENSIONS AND EXACT

LAYOUT TO BE REVIEWED AT THE CONSTRUCTION SITE WITH

COR APPROVAL.

DEMO/ICRA LEGEND

TEMPORARY WALL (REFER TO WALL TYPES)

AREA OF SAWCUT FLOOR SLAB DEMOLITION

(REFER TO STRUCTURAL)

AREA NOT IN PROJECT SCOPE

NOTE: SEE SHEET AD001 FOR DEMOLITION GENERAL NOTES.

A D

B

1B11

PHARMACY

CHECK-IN AREA

1B-4

CORRIDOR

1A04

ELIGIBILITY

3B10K.2

STORAGE

1B-5

CORRIDOR

1B15

VCS RETAIL STORE

1B16

VCS STOCK RM

1B20

CAFETERIA

1B20D

CAFETERIA FOOD

COURT

1B20E

CAFETERIA DINING

1B20B

STORAGE

A

B architecture +engineering

SEVEN

GENERATIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID SET

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

570-20-308REPLACE AND EXPAND CHILLED

WATER INFRASTRUCTURE,

BUILDING 1 N/A

TCMH07/01/2026

FRESNO VA HOSPITAL

2615 E. CLINTON AVE, FRESNO, CA 93703

SEVEN GENERATIONS ARCHITECTURE + ENGINEERING

600 E. MICHIGAN AVE., SUITE B

KALAMAZOO, MI 49007

269-927-0144

DAVENERGY SOLUTIONS

2207 GARNET AVE, SUITE 1

SAN DIEGO, CA 22108

612-770-8552

A/E:

A u to d e s k D o c s /2

V A

F re s n o C h ill e d

W a te r

In fr a s tr u c tu re /2

V

A F re s n o

C h ill e d

W a te r

In fr a s tr u c tu re

A R

C H

-R

.r v t

/2

/2

:5

:5

P

M

SCALE: As indicated

AD103A

FIRST FLOOR DEMO PLAN - AREA

A

DEMOLITION KEY NOTES

NO. DESCRIPTION

1 REMOVE EXISTING ACOUSTICAL CEILING TILE AND GRID SYSTEM INCLUDING ASSOCIATED HANGERS, METAL TEE GRID, AND EDGE ANGLES AS REQUIRED FOR DEMOLITION AND INSTALLATION OF

CONDENSATE/CHILLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]

12 SAW-CUT AND REMOVE FLOOR DECK AND SLAB. REFER TO STRUCTURAL DRAWINGS FOR STRUCTURAL

SUPPORT MODIFICATIONS REQUIRED AND EXACT SAW-CUT DIMENSIONS AND PLACEMENT.

NORTH

SCALE: 1/8" = 1'-0"

FIRST FLOOR DEMOLITION

PLAN - UNIT A

NOTE: THIS AREA TO BE CLASS IV ICRA

Revisions: Date:

BID SET 05/04/2026

BULLETIN 1 07/01/2026

ASI 01 07/24/2026

ICRA GENERAL NOTES

1. REFER TO 01 35 26 SAFETY REQUIREMENTS FOR ADDITIONAL

INFORMATION.

2. CONSTRUCT ICRA BARRIER PRIOR TO ANY DEMOLITION

WORK.

3. WHERE CLASS IV ICRA IS CALLED OUT ON THE DEMO PLANS,

EXISTING MECHANICAL ROOMS CAN BE PLANNED FOR

CLASS III.

4. ALL EXTERIOR WORK TO BE CLASS II ICRA.

5. THE INTENT OF INFECTION CONTROL ISOLATION IS TO

CONTAIN DUST AND PARTICULATE MATTER FROM THE

CONSTRUCTION AREA. PERIMETER TO BE SEALED

COMPLETELY WITH SHEET PLASTIC WHEN NO TEMPORARY

PARTITION IS CALLED OUT.

6. MAINTAIN PRESSURE MONITORS DRUING CONSTRUCTION

OPERATIONS.

7. CONTROL BARRIERS TO BE INSTALLED AND REMOVED ONLY

DURING AFTER HOURS (5:30 PM PST - 6:00 AM PST)

8. LIFE SAFETY EGRESS IS TO BE MAINTAINED AT ALL TIMES.

9. EXACT TEMPORARY WALL PARTITION LAYOUT TO BE

PROVIDED BY CONTRACTOR. DIMENSIONS AND EXACT

LAYOUT TO BE REVIEWED AT THE CONSTRUCTION SITE WITH

COR APPROVAL.

DEMO/ICRA LEGEND

TEMPORARY WALL (REFER TO WALL TYPES)

AREA OF SAWCUT FLOOR SLAB DEMOLITION

(REFER TO STRUCTURAL)

AREA NOT IN PROJECT SCOPE

NOTE: SEE SHEET AD001 FOR DEMOLITION GENERAL NOTES.

A D

A

A D

A

1 1

1 1

2 2

1B06

INPATIENT

PHARMACY SUITE

1B06A

PHARMACY SUPPLY

& PROCUREMENT

1B03

STAIR NO. 2

1B06I

INPATIENT

PHARMACY

1B08

PHARMACY REFILL

CONSULTATION

1B-3

CORRIDOR

1B02

PHARMACY SVC

1B-2

CORRIDOR

1A01

ELEVATOR LOBBY

1B11

PHARMACY

CHECK-IN AREA

1B-4

CORRIDOR

1A08

HEALTHY VET

1A16A

BAS

1A-2

CORRIDOR

1A01A

CHECK IN

1A02

ELIGIBILITY

1A04

ELIGIBILITY

1A09A

DAV

1A09

SVC OFFICES

1A06

TOILET

1A11

TOILET

1A12

STORAGE

1A09D

AMVETS

1A15

EMPLOYEE HEALTH

E116A

PRIMARY CARE

1A15B

TOILET

1A15A.1

TOILET

1A-3

CORRIDOR

1A18

WAITING ROOM

1A18J

TOILET

1A18A

POLICE ADMIN.

OFFICE

1A18F

PATIENT ADVOCATE

1A18B

POLICE OFFICE

3B10K.2

STORAGE

1A07

HOUSEKEEPING

A

B architecture +engineering

SEVEN

GENERATIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID SET

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

570-20-308REPLACE AND EXPAND CHILLED

WATER INFRASTRUCTURE,

BUILDING 1 N/A

TCMH07/01/2026

FRESNO VA HOSPITAL

2615 E. CLINTON AVE, FRESNO, CA 93703

SEVEN GENERATIONS ARCHITECTURE + ENGINEERING

600 E. MICHIGAN AVE., SUITE B

KALAMAZOO, MI 49007

269-927-0144

DAVENERGY SOLUTIONS

2207 GARNET AVE, SUITE 1

SAN DIEGO, CA 22108

612-770-8552

A/E:

A u to d e s k D o c s /2

V A

F re s n o C h ill e d

W a te r

In fr a s tr u c tu re /2

V

A F re s n o

C h ill e d

W a te r

In fr a s tr u c tu re

A R

C H

-R

.r v t

/2

/2

:5

:0

P

M

SCALE: As indicated

AD103B

FIRST FLOOR DEMO PLAN - AREA

B

DEMOLITION KEY NOTES

NO. DESCRIPTION

1 REMOVE EXISTING ACOUSTICAL CEILING TILE AND GRID SYSTEM INCLUDING ASSOCIATED HANGERS, METAL TEE GRID, AND EDGE ANGLES AS REQUIRED FOR DEMOLITION AND INSTALLATION OF

CONDENSATE/CHILLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]

2 REMOVE EXISTING GYPSUM BOARD OR PLASTER CEILING OVER METAL LATH ATTACHED TO SUSPENDED COLD ROLLED CHANNELS AS REQUIRED AND TO THE EXTENT FOR DEMOLITION AND INSTALLATION OF CONDENSATE/CHILLLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]. PATCH

& REPAIR ADJACENT SURFACES TO REMAIN AS NECESSARY.

3 REMOVE EXISTING ADHERED ACOUSTICAL CEILING ATTACHED TO SUSPENDED GYPSUM OR CEMENT PLASTER SUSPENDED CEILING AS REQUIRED AND TO THE EXTENT FOR DEMOLITION AND INSTALLATION OF CONDENSATE/CHILLED WATER SYSTEM. . EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]. PATCH

& REPAIR ADJACENT SURFACES TO REMAIN AS NECESSARY.

12 SAW-CUT AND REMOVE FLOOR DECK AND SLAB. REFER TO STRUCTURAL DRAWINGS FOR STRUCTURAL

SUPPORT MODIFICATIONS REQUIRED AND EXACT SAW-CUT DIMENSIONS AND PLACEMENT.

NORTH

SCALE: 1/8" = 1'-0"

FIRST FLOOR DEMOLITION PLAN

- UNIT B

NOTE: THIS AREA TO BE CLASS IV ICRA

Revisions: Date:

BID SET 05/04/2026

BULLETIN 1 07/01/2026

ASI 01 07/24/2026

1. REFER TO 01 35 26 SAFETY REQUIREMENTS FOR ADDITIONAL

INFORMATION.

2. CONSTRUCT ICRA BARRIER PRIOR TO ANY DEMOLITION

WORK.

3. WHERE CLASS IV ICRA IS CALLED OUT ON THE DEMO PLANS,

EXISTING MECHANICAL ROOMS CAN BE PLANNED FOR

CLASS III.

4. ALL EXTERIOR WORK TO BE CLASS II ICRA.

5. THE INTENT OF INFECTION CONTROL ISOLATION IS TO

CONTAIN DUST AND PARTICULATE MATTER FROM THE

CONSTRUCTION AREA. PERIMETER TO BE SEALED

COMPLETELY WITH SHEET PLASTIC WHEN NO TEMPORARY

PARTITION IS CALLED OUT.

6. MAINTAIN PRESSURE MONITORS DRUING CONSTRUCTION

OPERATIONS.

7. CONTROL BARRIERS TO BE INSTALLED AND REMOVED ONLY

DURING AFTER HOURS (5:30 PM PST - 6:00 AM PST)

8. LIFE SAFETY EGRESS IS TO BE MAINTAINED AT ALL TIMES.

9. EXACT TEMPORARY WALL PARTITION LAYOUT TO BE

PROVIDED BY CONTRACTOR. DIMENSIONS AND EXACT

LAYOUT TO BE REVIEWED AT THE CONSTRUCTION SITE WITH

COR APPROVAL.

DEMO/ICRA LEGEND

TEMPORARY WALL (REFER TO WALL TYPES)

AREA OF SAWCUT FLOOR SLAB DEMOLITION

(REFER TO STRUCTURAL)

AREA NOT IN PROJECT SCOPE

NOTE: SEE SHEET AD001 FOR DEMOLITION GENERAL NOTES.

1 1 1

1 1

A D

B

2B13

ANATOMIC

PATHOLOGY

2B24B

MICROBIOLOGY

LAB

2B24E

AUTOCLAVE

2B24C

TOILET

2B24

CLINICAL

LABORATORY

2B23

SPECIMEN

COLLECTION

2B18

PATHOLOGY/LAB

MEDICINE

2B-2

CORRIDOR

2B19A

CONFERENCE

2B21

ANCILLARY TESTING

COORD.

2B-2

CORRIDOR

A

B architecture +engineering

SEVEN

GENERATIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID SET

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

570-20-308REPLACE AND EXPAND CHILLED

WATER INFRASTRUCTURE,

BUILDING 1 N/A

TCMH07/01/2026

FRESNO VA HOSPITAL

2615 E. CLINTON AVE, FRESNO, CA 93703

SEVEN GENERATIONS ARCHITECTURE + ENGINEERING

600 E. MICHIGAN AVE., SUITE B

KALAMAZOO, MI 49007

269-927-0144

DAVENERGY SOLUTIONS

2207 GARNET AVE, SUITE 1

SAN DIEGO, CA 22108

612-770-8552

A/E:

A u to d e s k D o c s /2

V A

F re s n o C h ill e d

W a te r

In fr a s tr u c tu re /2

V

A F re s n o

C h ill e d

W a te r

In fr a s tr u c tu re

A R

C H

-R

.r v t

/2

/2

:5

:0

P

M

SCALE: As indicated

AD104A

SECOND FLOOR DEMO PLAN -

AREA A

DEMOLITION KEY NOTES

NO. DESCRIPTION

1 REMOVE EXISTING ACOUSTICAL CEILING TILE AND GRID SYSTEM INCLUDING ASSOCIATED HANGERS, METAL TEE GRID, AND EDGE ANGLES AS REQUIRED FOR DEMOLITION AND INSTALLATION OF

CONDENSATE/CHILLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]

2 REMOVE EXISTING GYPSUM BOARD OR PLASTER CEILING OVER METAL LATH ATTACHED TO SUSPENDED COLD ROLLED CHANNELS AS REQUIRED AND TO THE EXTENT FOR DEMOLITION AND INSTALLATION OF CONDENSATE/CHILLLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]. PATCH

& REPAIR ADJACENT SURFACES TO REMAIN AS NECESSARY.

4 REMOVE A PORTION OF EXISTING CASEWORK AND COUNTERTOP AS REQUIRED FOR NEW

CONSTRUCTION. TURN OVER TO OWNER UNLESS DIRECTED OTHERWISE. PATCH AND REPAIR EXPOSED

SURFACES TO REMAIN AS REQUIRED TO RECEIVE NEW CONSTRUCTION AND FINISHES.

12 SAW-CUT AND REMOVE FLOOR DECK AND SLAB. REFER TO STRUCTURAL DRAWINGS FOR STRUCTURAL

SUPPORT MODIFICATIONS REQUIRED AND EXACT SAW-CUT DIMENSIONS AND PLACEMENT.

NORTH

SCALE: 1/8" = 1'-0"

SECOND FLOOR DEMOLITION

PLAN - UNIT A

NOTE: THIS AREA TO BE CLASS IV ICRA

Revisions: Date:

BID SET 05/04/2026

BULLETIN 1 07/01/2026

ASI 01 07/24/2026

ICRA GENERAL NOTES

1. REFER TO 01 35 26 SAFETY REQUIREMENTS FOR ADDITIONAL

INFORMATION.

2. CONSTRUCT ICRA BARRIER PRIOR TO ANY DEMOLITION

WORK.

3. WHERE CLASS IV ICRA IS CALLED OUT ON THE DEMO PLANS,

EXISTING MECHANICAL ROOMS CAN BE PLANNED FOR

CLASS III.

4. ALL EXTERIOR WORK TO BE CLASS II ICRA.

5. THE INTENT OF INFECTION CONTROL ISOLATION IS TO

CONTAIN DUST AND PARTICULATE MATTER FROM THE

CONSTRUCTION AREA. PERIMETER TO BE SEALED

COMPLETELY WITH SHEET PLASTIC WHEN NO TEMPORARY

PARTITION IS CALLED OUT.

6. MAINTAIN PRESSURE MONITORS DRUING CONSTRUCTION

OPERATIONS.

7. CONTROL BARRIERS TO BE INSTALLED AND REMOVED ONLY

DURING AFTER HOURS (5:30 PM PST - 6:00 AM PST)

8. LIFE SAFETY EGRESS IS TO BE MAINTAINED AT ALL TIMES.

9. EXACT TEMPORARY WALL PARTITION LAYOUT TO BE

PROVIDED BY CONTRACTOR. DIMENSIONS AND EXACT

LAYOUT TO BE REVIEWED AT THE CONSTRUCTION SITE WITH

COR APPROVAL.

DEMO/ICRA LEGEND

TEMPORARY WALL (REFER TO WALL TYPES)

AREA OF SAWCUT FLOOR SLAB DEMOLITION

(REFER TO STRUCTURAL)

AREA NOT IN PROJECT SCOPE

NOTE: SEE SHEET AD001 FOR DEMOLITION GENERAL NOTES.

1 1 1 1

1 1 1

A D

A

A D

A

1 1

1 1

2B10A

RADIOLOGY ROOM

2B10C

TOILET

2B10

CONTROL RM

2B-1

CORRIDOR

2B11

STORAGE/DUMBWAITER

2B12

CHANGING RM

2B03

STORAGE/DUMBWAITER

2B-1

CORRIDOR

2B13A

STORAGE

2B13

ANATOMIC

PATHOLOGY

2A11

IMAGING ADPAC

2B29

IMAGING X-RAY

WAITING ROOM

2A07B

MRI CONTROL

ROOM/WORK AREA

2A06

TOILET

2A08

TOILET

2A09A

CLEAN SUPPLY

2A09

ULTRASOUND SUITE

2A09B

ULTRASOUND 2

2A13

SPECIAL

PROOCEDURES

PRE/POST

OPERATIVE

3A-6

GURNEY STORAGE

2A13B

SPECIAL

PROCEDURES O.R.

2A16B

CHIEF IMAGING

2A-1

CORRIDOR

2A16A

ADMN. ASSIST.

2A16

IMAGING SUITE

2A20

VSO OFFICE

2A23

ULTRASOUND ROOM

2A16E

OFFICE

2A16D

OFFICE

2A25A

ULTRASOUND ROOM

2A25

ULTRASOUND

OFFICE

2A27J

IMAGINE OFFICE

2A27A

COPY RM

2A27

CORRIDOR

2A27H

IMAGING ADMIN

2A27K

TOILET

A

B architecture +engineering

SEVEN

GENERATIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID SET

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

570-20-308REPLACE AND EXPAND CHILLED

WATER INFRASTRUCTURE,

BUILDING 1 N/A

TCMH07/01/2026

FRESNO VA HOSPITAL

2615 E. CLINTON AVE, FRESNO, CA 93703

SEVEN GENERATIONS ARCHITECTURE + ENGINEERING

600 E. MICHIGAN AVE., SUITE B

KALAMAZOO, MI 49007

269-927-0144

DAVENERGY SOLUTIONS

2207 GARNET AVE, SUITE 1

SAN DIEGO, CA 22108

612-770-8552

A/E:

A u to d e s k D o c s /2

V A

F re s n o C h ill e d

W a te r

In fr a s tr u c tu re /2

V

A F re s n o

C h ill e d

W a te r

In fr a s tr u c tu re

A R

C H

-R

.r v t

/2

/2

:5

:0

P

M

SCALE: As indicated

AD104B

SECOND FLOOR DEMO PLAN -

AREA B

DEMOLITION KEY NOTES

NO. DESCRIPTION

1 REMOVE EXISTING ACOUSTICAL CEILING TILE AND GRID SYSTEM INCLUDING ASSOCIATED HANGERS, METAL TEE GRID, AND EDGE ANGLES AS REQUIRED FOR DEMOLITION AND INSTALLATION OF

CONDENSATE/CHILLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]

2 REMOVE EXISTING GYPSUM BOARD OR PLASTER CEILING OVER METAL LATH ATTACHED TO SUSPENDED COLD ROLLED CHANNELS AS REQUIRED AND TO THE EXTENT FOR DEMOLITION AND INSTALLATION OF CONDENSATE/CHILLLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]. PATCH

& REPAIR ADJACENT SURFACES TO REMAIN AS NECESSARY.

3 REMOVE EXISTING ADHERED ACOUSTICAL CEILING ATTACHED TO SUSPENDED GYPSUM OR CEMENT PLASTER SUSPENDED CEILING AS REQUIRED AND TO THE EXTENT FOR DEMOLITION AND INSTALLATION OF CONDENSATE/CHILLED WATER SYSTEM. . EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]. PATCH

& REPAIR ADJACENT SURFACES TO REMAIN AS NECESSARY.

4 REMOVE A PORTION OF EXISTING CASEWORK AND COUNTERTOP AS REQUIRED FOR NEW

CONSTRUCTION. TURN OVER TO OWNER UNLESS DIRECTED OTHERWISE. PATCH AND REPAIR EXPOSED

SURFACES TO REMAIN AS REQUIRED TO RECEIVE NEW CONSTRUCTION AND FINISHES.

12 SAW-CUT AND REMOVE FLOOR DECK AND SLAB. REFER TO STRUCTURAL DRAWINGS FOR STRUCTURAL

SUPPORT MODIFICATIONS REQUIRED AND EXACT SAW-CUT DIMENSIONS AND PLACEMENT.

NORTH

SCALE: 1/8" = 1'-0"

SECOND FLOOR DEMOLITION

PLAN - UNIT B

NOTE: THIS AREA TO BE CLASS IV ICRA

Revisions: Date:

BID SET 05/04/2026

BULLETIN 1 07/01/2026

ASI 01 07/24/2026

1. REFER TO 01 35 26 SAFETY REQUIREMENTS FOR ADDITIONAL

INFORMATION.

2. CONSTRUCT ICRA BARRIER PRIOR TO ANY DEMOLITION

WORK.

3. WHERE CLASS IV ICRA IS CALLED OUT ON THE DEMO PLANS,

EXISTING MECHANICAL ROOMS CAN BE PLANNED FOR

CLASS III.

4. ALL EXTERIOR WORK TO BE CLASS II ICRA.

5. THE INTENT OF INFECTION CONTROL ISOLATION IS TO

CONTAIN DUST AND PARTICULATE MATTER FROM THE

CONSTRUCTION AREA. PERIMETER TO BE SEALED

COMPLETELY WITH SHEET PLASTIC WHEN NO TEMPORARY

PARTITION IS CALLED OUT.

6. MAINTAIN PRESSURE MONITORS DRUING CONSTRUCTION

OPERATIONS.

7. CONTROL BARRIERS TO BE INSTALLED AND REMOVED ONLY

DURING AFTER HOURS (5:30 PM PST - 6:00 AM PST)

8. LIFE SAFETY EGRESS IS TO BE MAINTAINED AT ALL TIMES.

9. EXACT TEMPORARY WALL PARTITION LAYOUT TO BE

PROVIDED BY CONTRACTOR. DIMENSIONS AND EXACT

LAYOUT TO BE REVIEWED AT THE CONSTRUCTION SITE WITH

COR APPROVAL.

DEMO/ICRA LEGEND

TEMPORARY WALL (REFER TO WALL TYPES)

AREA OF SAWCUT FLOOR SLAB DEMOLITION

(REFER TO STRUCTURAL)

AREA NOT IN PROJECT SCOPE

NOTE: SEE SHEET AD001 FOR DEMOLITION GENERAL NOTES.

A D

B

2 2

3B08

OFFICE

3B08B

SHOWER

3B08E

SHOWER

3B09B

RESTROOM

3B10C

TOILET

3B09A

WOMENS'

RESTROOM

3B-4B

SCRUB AREA

3B10J

EQUIP STORAGE

3B-4

CORRIDOR

3B09D

HOUSEKPG

3B10A

O.R. #1

3B10J.1

ELEC.

3B-3A

CORRIDOR

3B09A

WOMENS'

RESTROOM

3B-3

CORRIDOR

3B09D.1

COMM

3B10K.1

AUTOCLAVE

3B10L

SUBSTERILE

A

B architecture +engineering

SEVEN

GENERATIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID SET

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

570-20-308REPLACE AND EXPAND CHILLED

WATER INFRASTRUCTURE,

BUILDING 1 N/A

TCMH07/01/2026

FRESNO VA HOSPITAL

2615 E. CLINTON AVE, FRESNO, CA 93703

SEVEN GENERATIONS ARCHITECTURE + ENGINEERING

600 E. MICHIGAN AVE., SUITE B

KALAMAZOO, MI 49007

269-927-0144

DAVENERGY SOLUTIONS

2207 GARNET AVE, SUITE 1

SAN DIEGO, CA 22108

612-770-8552

A/E:

A u to d e s k D o c s /2

V A

F re s n o C h ill e d

W a te r

In fr a s tr u c tu re /2

V

A F re s n o

C h ill e d

W a te r

In fr a s tr u c tu re

A R

C H

-R

.r v t

/2

/2

:5

:0

P

M

SCALE: As indicated

AD105A

THIRD FLOOR DEMO PLAN - AREA

A

DEMOLITION KEY NOTES

NO. DESCRIPTION

1 REMOVE EXISTING ACOUSTICAL CEILING TILE AND GRID SYSTEM INCLUDING ASSOCIATED HANGERS, METAL TEE GRID, AND EDGE ANGLES AS REQUIRED FOR DEMOLITION AND INSTALLATION OF

CONDENSATE/CHILLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]

2 REMOVE EXISTING GYPSUM BOARD OR PLASTER CEILING OVER METAL LATH ATTACHED TO SUSPENDED COLD ROLLED CHANNELS AS REQUIRED AND TO THE EXTENT FOR DEMOLITION AND INSTALLATION OF CONDENSATE/CHILLLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]. PATCH

& REPAIR ADJACENT SURFACES TO REMAIN AS NECESSARY.

5 REMOVE EXISTING LOCKERS AND BENCH. TURN OVER TO OWNER UNLESS DIRECTED OTHERWISE. PATCH AND REPAIR EXPOSED SURFACES TO REMAIN AS REQUIRED TO RECEIVE NEW CONSTRUCTION AND

FINISHES.

12 SAW-CUT AND REMOVE FLOOR DECK AND SLAB. REFER TO STRUCTURAL DRAWINGS FOR STRUCTURAL

SUPPORT MODIFICATIONS REQUIRED AND EXACT SAW-CUT DIMENSIONS AND PLACEMENT.

NORTH

SCALE: 1/8" = 1'-0"

THIRD FLOOR DEMOLITION

PLAN - UNIT A

NOTE: THIS AREA TO BE CLASS IV ICRA

Revisions: Date:

BID SET 05/04/2026

BULLETIN 1 07/01/2026

ASI 01 07/24/2026

ICRA GENERAL NOTES

1. REFER TO 01 35 26 SAFETY REQUIREMENTS FOR ADDITIONAL

INFORMATION.

2. CONSTRUCT ICRA BARRIER PRIOR TO ANY DEMOLITION

WORK.

3. WHERE CLASS IV ICRA IS CALLED OUT ON THE DEMO PLANS,

EXISTING MECHANICAL ROOMS CAN BE PLANNED FOR

CLASS III.

4. ALL EXTERIOR WORK TO BE CLASS II ICRA.

5. THE INTENT OF INFECTION CONTROL ISOLATION IS TO

CONTAIN DUST AND PARTICULATE MATTER FROM THE

CONSTRUCTION AREA. PERIMETER TO BE SEALED

COMPLETELY WITH SHEET PLASTIC WHEN NO TEMPORARY

PARTITION IS CALLED OUT.

6. MAINTAIN PRESSURE MONITORS DRUING CONSTRUCTION

OPERATIONS.

7. CONTROL BARRIERS TO BE INSTALLED AND REMOVED ONLY

DURING AFTER HOURS (5:30 PM PST - 6:00 AM PST)

8. LIFE SAFETY EGRESS IS TO BE MAINTAINED AT ALL TIMES.

9. EXACT TEMPORARY WALL PARTITION LAYOUT TO BE

PROVIDED BY CONTRACTOR. DIMENSIONS AND EXACT

LAYOUT TO BE REVIEWED AT THE CONSTRUCTION SITE WITH

COR APPROVAL.

DEMO/ICRA LEGEND

TEMPORARY WALL (REFER TO WALL TYPES)

AREA OF SAWCUT FLOOR SLAB DEMOLITION

(REFER TO STRUCTURAL)

AREA NOT IN PROJECT SCOPE

NOTE: SEE SHEET AD001 FOR DEMOLITION GENERAL NOTES.

A D

A

A D

A

5 1

2 2

2 1 1 1

3B06

MECHANICAL

3B-1

CORRIDOR

3B08

OFFICE

3B06B

SURGERY STORAGE

3B08A

STORAGE

3B07

STORAGE

3B07

STORAGE

NO.1

DUMBWAITER

3B-2

CORRIDOR

3B08B

SHOWER

3B08E

SHOWER

3B09B

RESTROOM

3B10C

TOILET

3B09A

WOMENS'

RESTROOM

3A02A

PURCHASING

3A-1

CORRIDOR

3A04A

PROCEDURE 2

3A-2

CORRIDOR

3A03

TOILET

3A02B

CHIEF SPS

3A02C

CHIEF INV MGMT

3A02D.1

OFFICE

3A02F

SPD PREP RM

3A02F.1

STORAGE

3A02G

SPD DECON

3A15

SPD DECON

3A-3

CORRIDOR

3A04

GI LAB SUITE

3A10

IMAGING RM 1

3A10B

HOTLAB

3A10A

CONTROL RM

3A20

RADIATION SAFTEY

OFFICE

3A20A

STORAGE

3A14

TOILET3A-4

CORRDIOR

3A15B

TOILET

3A15A

HOUSEKPG

3B-1

CORRIDOR

A

B architecture +engineering

SEVEN

GENERATIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID SET

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

570-20-308REPLACE AND EXPAND CHILLED

WATER INFRASTRUCTURE,

BUILDING 1 N/A

TCMH07/01/2026

FRESNO VA HOSPITAL

2615 E. CLINTON AVE, FRESNO, CA 93703

SEVEN GENERATIONS ARCHITECTURE + ENGINEERING

600 E. MICHIGAN AVE., SUITE B

KALAMAZOO, MI 49007

269-927-0144

DAVENERGY SOLUTIONS

2207 GARNET AVE, SUITE 1

SAN DIEGO, CA 22108

612-770-8552

A/E:

A u to d e s k D o c s /2

V A

F re s n o C h ill e d

W a te r

In fr a s tr u c tu re /2

V

A F re s n o

C h ill e d

W a te r

In fr a s tr u c tu re

A R

C H

-R

.r v t

/2

/2

:5

:0

P

M

SCALE: As indicated

AD105B

THIRD FLOOR DEMO PLAN - AREA

B

DEMOLITION KEY NOTES

NO. DESCRIPTION

1 REMOVE EXISTING ACOUSTICAL CEILING TILE AND GRID SYSTEM INCLUDING ASSOCIATED HANGERS, METAL TEE GRID, AND EDGE ANGLES AS REQUIRED FOR DEMOLITION AND INSTALLATION OF

CONDENSATE/CHILLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]

2 REMOVE EXISTING GYPSUM BOARD OR PLASTER CEILING OVER METAL LATH ATTACHED TO SUSPENDED COLD ROLLED CHANNELS AS REQUIRED AND TO THE EXTENT FOR DEMOLITION AND INSTALLATION OF CONDENSATE/CHILLLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]. PATCH

& REPAIR ADJACENT SURFACES TO REMAIN AS NECESSARY.

5 REMOVE EXISTING LOCKERS AND BENCH. TURN OVER TO OWNER UNLESS DIRECTED OTHERWISE. PATCH AND REPAIR EXPOSED SURFACES TO REMAIN AS REQUIRED TO RECEIVE NEW CONSTRUCTION AND

FINISHES.

12 SAW-CUT AND REMOVE FLOOR DECK AND SLAB. REFER TO STRUCTURAL DRAWINGS FOR STRUCTURAL

SUPPORT MODIFICATIONS REQUIRED AND EXACT SAW-CUT DIMENSIONS AND PLACEMENT.

NORTH

SCALE: 1/8" = 1'-0"

THIRD FLOOR DEMOLITION

PLAN - UNIT B

NOTE: THIS AREA TO BE CLASS IV ICRA

Revisions: Date:

BID SET 05/04/2026

BULLETIN 1 07/01/2026

ASI 01 07/24/2026

F

ICRA GENERAL NOTES

1. REFER TO 01 35 26 SAFETY REQUIREMENTS FOR ADDITIONAL

INFORMATION.

2. CONSTRUCT ICRA BARRIER PRIOR TO ANY DEMOLITION

WORK.

3. WHERE CLASS IV ICRA IS CALLED OUT ON THE DEMO PLANS,

EXISTING MECHANICAL ROOMS CAN BE PLANNED FOR

CLASS III.

4. ALL EXTERIOR WORK TO BE CLASS II ICRA.

5. THE INTENT OF INFECTION CONTROL ISOLATION IS TO

CONTAIN DUST AND PARTICULATE MATTER FROM THE

CONSTRUCTION AREA. PERIMETER TO BE SEALED

COMPLETELY WITH SHEET PLASTIC WHEN NO TEMPORARY

PARTITION IS CALLED OUT.

6. MAINTAIN PRESSURE MONITORS DRUING CONSTRUCTION

OPERATIONS.

7. CONTROL BARRIERS TO BE INSTALLED AND REMOVED ONLY

DURING AFTER HOURS (5:30 PM PST - 6:00 AM PST)

8. LIFE SAFETY EGRESS IS TO BE MAINTAINED AT ALL TIMES.

9. EXACT TEMPORARY WALL PARTITION LAYOUT TO BE

PROVIDED BY CONTRACTOR. DIMENSIONS AND EXACT

LAYOUT TO BE REVIEWED AT THE CONSTRUCTION SITE WITH

COR APPROVAL.

DEMO/ICRA LEGEND

TEMPORARY WALL (REFER TO WALL TYPES)

AREA OF SAWCUT FLOOR SLAB DEMOLITION

(REFER TO STRUCTURAL)

AREA NOT IN PROJECT SCOPE

NOTE: SEE SHEET AD001 FOR DEMOLITION GENERAL NOTES.

1 1

1 1

678 9

4B-4

WAITING AREA

4B-3

CORRIDOR

4B19

EXAM ROOM

4B46D

CONFERENCE 4B46

WOMENS HEALTH

WAITING

4B-4

WAITING AREA

4B46E

EXAM ROOM

4B-6A

CORRIDOR

4B46H

EXAM ROOM

4B46O

OFFICE

4B-6

CORRIDOR

4B46N

OFFICE

4B46K

OFFICE

4B36

EXAM ROOM

4B-5

CORRIDOR

4B-5C

CORRIDOR

4B38

OFFICE

4B46B

MTG/BREAK ROOM

4B39

CLEAN SUPPLY4B37

OFFICE

4B46B.1

TOILET

4B42

COMM. ROOM

4B32

EXAM ROOM

4B33

TOILET

4B-5B

CORRIDOR

4B20

EXAM ROOM

4B26

EXAM ROOM

4B25

EXAM ROOM

4B23

EXAM ROOM

4B22

EXAM ROOM

4B-5A

CORRIDOR

4B21

STORAGE ROOM

4B24

CORRIDOR

A

B architecture +engineering

SEVEN

GENERATIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID SET

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

570-20-308REPLACE AND EXPAND CHILLED

WATER INFRASTRUCTURE,

BUILDING 1 N/A

TCMH07/01/2026

FRESNO VA HOSPITAL

2615 E. CLINTON AVE, FRESNO, CA 93703

SEVEN GENERATIONS ARCHITECTURE + ENGINEERING

600 E. MICHIGAN AVE., SUITE B

KALAMAZOO, MI 49007

269-927-0144

DAVENERGY SOLUTIONS

2207 GARNET AVE, SUITE 1

SAN DIEGO, CA 22108

612-770-8552

A/E:

A u to d e s k D o c s /2

V A

F re s n o C h ill e d

W a te r

In fr a s tr u c tu re /2

V

A F re s n o

C h ill e d

W a te r

In fr a s tr u c tu re

A R

C H

-R

.r v t

/2

/2

:5

:0

P

M

SCALE: As indicated

AD106A

FOURTH FLOOR DEMO PLAN -

AREA A

DEMOLITION KEY NOTES

NO. DESCRIPTION

1 REMOVE EXISTING ACOUSTICAL CEILING TILE AND GRID SYSTEM INCLUDING ASSOCIATED HANGERS, METAL TEE GRID, AND EDGE ANGLES AS REQUIRED FOR DEMOLITION AND INSTALLATION OF

CONDENSATE/CHILLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]

2 REMOVE EXISTING GYPSUM BOARD OR PLASTER CEILING OVER METAL LATH ATTACHED TO SUSPENDED COLD ROLLED CHANNELS AS REQUIRED AND TO THE EXTENT FOR DEMOLITION AND INSTALLATION OF CONDENSATE/CHILLLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]. PATCH

& REPAIR ADJACENT SURFACES TO REMAIN AS NECESSARY.

6 REMOVE ALL EXISTING WALL-MOUNTED EQUIPMENT. PATCH AND REPAIR WITH FINISH PAINT ALL WALL

SURFACES. TURN BALANCE OVER TO OWNER UNLESS DIRECTED OTHERWISE.

7 REMOVE EXISTING WALL FINISHES, WALL BASE, AND ALL OTHER ITEMS ATTACHED TO THE WALLS. TURN OVER TO OWNER, UNLESS DIRECTED OTHERWISE. PATCH & REPAIR EXPOSED SURFACES TO REMAIN AS

REQUIRED FOR NEW CONSTRUCTION AND/OR NEW FINISHES.

8 REMOVE EXISTING FLOORING AND FLOOR FINISHES INCLUDING ALL ADHESIVES, SETTING MATERIALS DOWN TO EXISTING SUBSTRATE. GRIND CONCRETE FLOORS AS REQUIRED TO PROVIDE A SMOOTH AND

UNIFORM SURFACE FOR NEW FINISHES.

9 REMOVE EXISTING CASEWORK AND COUNTERTOPS, AND PLUMBING EQUIPMENT. PATCH AND REPAIR

WALL SURFACES TO REMAIN.

12 SAW-CUT AND REMOVE FLOOR DECK AND SLAB. REFER TO STRUCTURAL DRAWINGS FOR STRUCTURAL

SUPPORT MODIFICATIONS REQUIRED AND EXACT SAW-CUT DIMENSIONS AND PLACEMENT.

NORTH

SCALE: 1/8" = 1'-0"

FOURTH FLOOR DEMOLITION

PLAN - UNIT A

NOTE: THIS AREA TO BE CLASS IV ICRA

Revisions: Date:

BID SET 05/04/2026

BULLETIN 1 07/01/2026

ASI 01 07/24/2026

F

ICRA GENERAL NOTES

1. REFER TO 01 35 26 SAFETY REQUIREMENTS FOR ADDITIONAL

INFORMATION.

2. CONSTRUCT ICRA BARRIER PRIOR TO ANY DEMOLITION

WORK.

3. WHERE CLASS IV ICRA IS CALLED OUT ON THE DEMO PLANS,

EXISTING MECHANICAL ROOMS CAN BE PLANNED FOR

CLASS III.

4. ALL EXTERIOR WORK TO BE CLASS II ICRA.

5. THE INTENT OF INFECTION CONTROL ISOLATION IS TO

CONTAIN DUST AND PARTICULATE MATTER FROM THE

CONSTRUCTION AREA. PERIMETER TO BE SEALED

COMPLETELY WITH SHEET PLASTIC WHEN NO TEMPORARY

PARTITION IS CALLED OUT.

6. MAINTAIN PRESSURE MONITORS DRUING CONSTRUCTION

OPERATIONS.

7. CONTROL BARRIERS TO BE INSTALLED AND REMOVED ONLY

DURING AFTER HOURS (5:30 PM PST - 6:00 AM PST)

8. LIFE SAFETY EGRESS IS TO BE MAINTAINED AT ALL TIMES.

9. EXACT TEMPORARY WALL PARTITION LAYOUT TO BE

PROVIDED BY CONTRACTOR. DIMENSIONS AND EXACT

LAYOUT TO BE REVIEWED AT THE CONSTRUCTION SITE WITH

COR APPROVAL.

DEMO/ICRA LEGEND

TEMPORARY WALL (REFER TO WALL TYPES)

AREA OF SAWCUT FLOOR SLAB DEMOLITION

(REFER TO STRUCTURAL)

AREA NOT IN PROJECT SCOPE

NOTE: SEE SHEET AD001 FOR DEMOLITION GENERAL NOTES.

A D

A

A D

A

678 9

1 1

2 2

1 1

EXPOSED

STRUCTURE

ABOVE

4B07

CONFERENCE

4B08

MECHANICAL

4B14

OFFICE

4B-4

WAITING AREA

4B-3

CORRIDOR

4B13

OFFICE

4B-1

CORRIDOR

4B02

OFFICE WORK AREA

4B09

OFFICE

4B01

STAFF LOUNGE/

BREAK RM

4B01A

STORAGE

4B01B

TOILET

4B-2

CORRIDOR

4B19

EXAM ROOM

4A-1

CORRIDOR

4A-2

CORRIDOR

4A04

GI OFFICE

4A-4

CORRIDOR

4A-5D

CORRIDOR

4A27

EXAM RM

4A-1

CORRIDOR

4A-1

CORRIDOR

4A-3

CORRIDOR

4A-3

CORRIDOR

4A02F

OFFICE

4A02G

OFFICE

4A02H

OFFICE

4A14

TOILET

4A13

EXAM RM

4A-5A

CORRIDOR

4A10

EXAM ROOM

4A09

EXAM ROOM

4A20

EXAM ROOM

4A-5

CORRIDOR

4A-5B

CORRIDOR

4A-5

CORRIDOR

4A25

EXAM RM

4A31

COMM RM

4A33

EXAM RM

4A-5E

CORRIDOR

4A37

EXAM RM

4A36

OFFICE

4A38

EXAM RM

4A-5

CORRIDOR

4A45

CLEAN SUPPLY

4A43

EXAM RM

4A-6

CORRIDOR

4A-5F

CORRIDOR

4A56

EXAM ROOM

4A55

CLEAN SUPPLY

4A-5G

CORRIDOR

4A49

EXAM ROOM

4B-5

CORRIDOR

4B22

EXAM ROOM

4B-5A

CORRIDOR

4B21

STORAGE ROOM

4B24

CORRIDOR

A

B architecture +engineering

SEVEN

GENERATIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID SET

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

570-20-308REPLACE AND EXPAND CHILLED

WATER INFRASTRUCTURE,

BUILDING 1 N/A

TCMH07/01/2026

FRESNO VA HOSPITAL

2615 E. CLINTON AVE, FRESNO, CA 93703

SEVEN GENERATIONS ARCHITECTURE + ENGINEERING

600 E. MICHIGAN AVE., SUITE B

KALAMAZOO, MI 49007

269-927-0144

DAVENERGY SOLUTIONS

2207 GARNET AVE, SUITE 1

SAN DIEGO, CA 22108

612-770-8552

A/E:

A u to d e s k D o c s /2

V A

F re s n o C h ill e d

W a te r

In fr a s tr u c tu re /2

V

A F re s n o

C h ill e d

W a te r

In fr a s tr u c tu re

A R

C H

-R

.r v t

/2

/2

:5

:1

P

M

SCALE: As indicated

AD106B

FOURTH FLOOR DEMO PLAN -

AREA B

DEMOLITION KEY NOTES

NO. DESCRIPTION

1 REMOVE EXISTING ACOUSTICAL CEILING TILE AND GRID SYSTEM INCLUDING ASSOCIATED HANGERS, METAL TEE GRID, AND EDGE ANGLES AS REQUIRED FOR DEMOLITION AND INSTALLATION OF

CONDENSATE/CHILLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]

2 REMOVE EXISTING GYPSUM BOARD OR PLASTER CEILING OVER METAL LATH ATTACHED TO SUSPENDED COLD ROLLED CHANNELS AS REQUIRED AND TO THE EXTENT FOR DEMOLITION AND INSTALLATION OF CONDENSATE/CHILLLED WATER SYSTEM. EXISTING CEILING MOUNTED LIGHT FIXTURES, SPEAKERS, CAMERAS, FIRE ALARMS, MECHANICAL DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS, ETC. TO BE TEMPORARILY SUPPORTED FOR REINSTALLATION IN NEW CEILING FINISH; REFER TO REFLECTED CEILING PLANS FOR EXISTING AND REINSTALLED LOCATIONS. [NOTE:

ITEMS SHALL NOT BE TEMPORARILY OR PERMANENTLY SUSPENDED FROM FIRE SUPPRESSION LINES]. PATCH

& REPAIR ADJACENT SURFACES TO REMAIN AS NECESSARY.

6 REMOVE ALL EXISTING WALL-MOUNTED EQUIPMENT. PATCH AND REPAIR WITH FINISH PAINT ALL WALL

SURFACES. TURN BALANCE OVER TO OWNER UNLESS DIRECTED OTHERWISE.

7 REMOVE EXISTING WALL FINISHES, WALL BASE, AND ALL OTHER ITEMS ATTACHED TO THE WALLS. TURN OVER TO OWNER, UNLESS DIRECTED OTHERWISE. PATCH & REPAIR EXPOSED SURFACES TO REMAIN AS

REQUIRED FOR NEW CONSTRUCTION AND/OR NEW FINISHES.

8 REMOVE EXISTING FLOORING AND FLOOR FINISHES INCLUDING ALL ADHESIVES, SETTING MATERIALS DOWN TO EXISTING SUBSTRATE. GRIND CONCRETE FLOORS AS REQUIRED TO PROVIDE A SMOOTH AND

UNIFORM SURFACE FOR NEW FINISHES.

9 REMOVE EXISTING CASEWORK AND COUNTERTOPS, AND PLUMBING EQUIPMENT. PATCH AND REPAIR

WALL SURFACES TO REMAIN.

12 SAW-CUT AND REMOVE FLOOR DECK AND SLAB. REFER TO STRUCTURAL DRAWINGS FOR STRUCTURAL

SUPPORT MODIFICATIONS REQUIRED AND EXACT SAW-CUT DIMENSIONS AND PLACEMENT.

NORTH

SCALE: 1/8" = 1'-0"

FOURTH FLOOR DEMOLITION

PLAN - UNIT B

NOTE: THIS AREA TO BE CLASS IV ICRA

Revisions: Date:

BID SET 05/04/2026

BULLETIN 1 07/01/2026

ASI 01 07/24/2026

ICRA GENERAL NOTES

1. REFER TO 01 35 26 SAFETY REQUIREMENTS FOR ADDITIONAL

INFORMATION.

2. CONSTRUCT ICRA BARRIER PRIOR TO ANY DEMOLITION

WORK.

3. WHERE CLASS IV ICRA IS CALLED OUT ON THE DEMO PLANS,

EXISTING MECHANICAL ROOMS CAN BE PLANNED FOR

CLASS III.

4. ALL EXTERIOR WORK TO BE CLASS II ICRA.

5. THE INTENT OF INFECTION CONTROL ISOLATION IS TO

CONTAIN DUST AND PARTICULATE MATTER FROM THE

CONSTRUCTION AREA. PERIMETER TO BE SEALED

COMPLETELY WITH SHEET PLASTIC WHEN NO TEMPORARY

PARTITION IS CALLED OUT.

6. MAINTAIN PRESSURE MONITORS DRUING CONSTRUCTION

OPERATIONS.

7. CONTROL BARRIERS TO BE INSTALLED AND REMOVED ONLY

DURING AFTER HOURS (5:30 PM PST - 6:00 AM PST)

8. LIFE SAFETY EGRESS IS TO BE MAINTAINED AT ALL TIMES.

9. EXACT TEMPORARY WALL PARTITION LAYOUT TO BE

PROVIDED BY CONTRACTOR. DIMENSIONS AND EXACT

LAYOUT TO BE REVIEWED AT THE CONSTRUCTION SITE WITH

COR APPROVAL.

DEMO/ICRA LEGEND

TEMPORARY…