36C24619B0039-007.pdf

PDF Posted

Attached to
Construct New Clinical Lab Expansion (VA-18-00152139) Federal contract opportunity
Solicitation number
36C24619B0039
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6

About this file

This document provides details for a federal construction contract opportunity with the Department of Veterans Affairs. The solicitation seeks a Service Disabled Veteran Owned Small Business to provide construction services for a new clinical lab expansion project located at the H.H. McGuire VA Medical Center in Richmond, Virginia. The project scope includes partial renovation and an 18,050 square foot addition. Construction must be completed within 680 calendar days of receiving the notice to proceed. The estimated cost is between $5-10 million. The NAICS code is 236220 and the small business size standard is $36.5 million. Drawings and specifications will be provided on August 15, 2019. A pre-proposal conference will also be held on this date. Questions must be emailed to the listed contracting officer by the specified due date. This opportunity is 100% set aside for SDVOSBs.

36C24619B0039 S02 ELECTRICAL_Bid Documents.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Construct New Clinical Lab Expansion (VA-18-00152139), newest first.
File Type Posted
36C24619B0039-0003000.docx DOCX document
36C24619B0039-0003002.pdf PDF
36C24619B0039-0003003.pdf PDF
36C24619B0039-0003001.pdf PDF
36C24619B0039-0003001.pdf PDF
36C24619B0039-0003003.pdf PDF
36C24619B0039-0003002.pdf PDF
36C24619B0039-0003000.docx DOCX document
36C24619B0039-0002000.docx DOCX document
36C24619B0039-0002000.docx DOCX document
36C24619B0039-0001000.docx DOCX document
36C24619B0039-0001000.docx DOCX document
36C24619B0039-009.pdf PDF
36C24619B0039-008.pdf PDF
36C24619B0039-003.pdf PDF
36C24619B0039-010.pdf PDF
36C24619B0039-005.pdf PDF
36C24619B0039-002.docx DOCX document
36C24619B0039-006.pdf PDF
36C24619B0039-012.pdf PDF
36C24619B0039-013.pdf PDF
36C24619B0039-004.pdf PDF
36C24619B0039-001.docx DOCX document
36C24619B0039-011.pdf PDF
36C24619B0039-009.pdf PDF
36C24619B0039-005.pdf PDF
36C24619B0039-008.pdf PDF
36C24619B0039-006.pdf PDF
36C24619B0039-007.pdf PDF
36C24619B0039-002.docx DOCX document
36C24619B0039-013.pdf PDF
36C24619B0039-012.pdf PDF
36C24619B0039-010.pdf PDF
36C24619B0039-011.pdf PDF
36C24619B0039-001.docx DOCX document
36C24619B0039-004.pdf PDF
36C24619B0039-003.pdf PDF
36C24619B0039-000.docx DOCX document
36C24619B0039-000.docx DOCX document
Show all 39

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. COMPLY WITH ALL CURRENT APPLICABLE CODES AND

STANDARDS.

2. PROVIDE SEALANT AROUND ALL ELECTRICAL OUTLETS, PLUMBING

FIXTURES, PIPING, AND EQUIPMENT ABUTTING OR PENETRATING A

WALL OR PARTITION INCLUDING FIRESTOPPING AT FIRE RATED

ASSEMBLES.

3. CONDUIT SHALL BE CONTINUOUS AND COMPLETE BETWEEN

PANELS, JUNCTION, OUTLET, PULL AND FIXTURE BOXES. IT SHALL

BE KEPT CLEAN AND UNOBSTRUCTED INSIDE WITH ENDS FREE OF

BURRS AND OTHER PROJECTIONS WHICH WOULD DAMAGE OR

IMPEDE PULLING OF WIRE. ALL CONDUIT SHALL BE INSTALLED

PARALLEL AND PERPENDICULAR TO THE BUILDING LINES. ALL

CONDUIT SHALL BE ROUTED CONCEALED IN FINISHED AREAS

EXCEPT WHERE OTHERWISE NOTED.

4. UNLESS OTHERWISE NOTED, ALL WIRES AND CABLES SHALL BE

CONTINUOUS WITHOUT SPLICES OR TAPS IN CONDUIT RUNS. ALL

WIRING SHALL BE IN CONDUIT OR AS NOTED. ALL SPLICES SHALL

BE MADE AT OUTLET BOXES, PULL BOXES OR JUNCTION BOXES. AT

ALL JOINTS, CONDUCTORS SHALL BE SPLICED OR JOINED AS TO

BE MECHANICALLY AND ELECTRICALLY SECURE.

5. IDENTIFICATION OF NEUTRAL, GROUNDING OF CIRCUITS, NUMBER

OF WIRES IN CONDUIT SHALL COMPLY IN ALL RESPECTS WITH THE

REQUIREMENTS OF THE NEC.

6. WIRE SHALL NOT BE INSTALLED IN CONDUIT UNTIL ALL WORK

WHICH COULD CAUSE INJURY TO THE CONDUCTORS IS COMPLETE.

7. ALL MATERIAL SHALL CONFORM TO NEMA, ANSI AND U.S.

STANDARDS, WHICHEVER APPLIES AND SHALL BEAR THE

INSPECTION LABEL OF UNDERWRITER LABORATORIES, INC.

8. ALL BOXES AND ENCLOSURES SHALL BE SET PLUMB, SQUARE AND

SECURELY FASTENED. BOXES IN FINISHED WALLS SHALL BE FLUSH

WITH FINISH SURFACE. ALL PULL AND JUNCTION BOXES SHALL BE

SIZED PER NEC ARTICLE 314.

9. PROVIDE GROUNDING AND BONDING OF ALL METAL RACEWAYS AS

REQUIRED BY NEC.

10.PROVIDE NEW TYPEWRITTEN DIRECTORIES FOR ALL PANELS

INSTALLED UNDER THIS CONTRACT.

11. ALL ELECTRICAL WORK SHALL BE IN STRICT COMPLIANCE WITH

THE CURRENT EDITION OF THE NEC AS ADOPTED BY THE

AUTHORITY HAVING JURISDICTION INCLUDING ANY AMENDMENTS,

ORDINANCES, AND INTERPRETATIONS. ELECTRICAL WORK SHALL

ALSO COMPLY WITH ANY APPLICABLE FEDERAL AND STATE

REGULATIONS.

12.COORDINATE INSTALLATION OF CONDUIT WITH OTHER TRADES

AND EQUIPMENT SUPPLIERS AS REQUIRED PRIOR TO ROUGH-IN.

13.PROVIDE AND MAINTAIN ELECTRICAL SAFETY AND WORKING

CLEARANCES IN FRONT OF AND AROUND ALL ELECTRICAL PANELS

AND DISTRIBUTION EQUIPMENT IN ACCORDANCE WITH NEC.

14.ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR CUTTING

AND CORE DRILLING ALL PENETRATIONS THROUGH FLOORS,

WALLS, ETC.

15.IT IS NOT INTENDED THAT THE PLANS INDICATE ALL CONDUIT

ROUTES, PULL BOXES, ETC. ELECTRICAL CONTRACTOR SHALL BE

RESPONSIBLE FOR DETERMINING ACTUAL CONDUIT ROUTING,

QUANTITY, AND LOCATION OF PULL BOXES WITHIN ACCESSIBLE

LOCATIONS. PROVIDE SCREW-COVER PULL BOXES IN CONDUIT

RUNS AS REQUIRED TO LIMIT NUMBER OF BENDS TO NO MORE

THAN THREE (3) OR 270 DEGREES TOTAL. SIZE PULL BOXES IN

ACCORDANCE WITH NEC. DOCUMENT ON RECORD DRAWINGS THE

SIZE AND LOCATION OF PULL BOXES USED IN FEEDER CONDUIT

RUNS.

16.REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION ABOUT

QUALITY AND GENERAL INSTALLATION REQUIREMENTS OF

ELECTRICAL CONSTRUCTION MATERIALS, ITEMS, AND DEVICES.

17.CONDUIT RUNS ARE SHOWN FOR REFERENCE AND BIDDING

PURPOSES ONLY. CONTRACTOR SHALL VERIFY EXISTING FIELD

CONDITIONS AND DETERMINE SHORTEST AND LEAST DISRUPTIVE

ROUTE FOR CONDUIT RUNS. COORDINATE WITH OTHER TRADES

AND CONFIRM ROUTE SELECTION WITH OWNER PRIOR TO BID. ANY

DEVIATIONS FROM DRAWINGS SHALL BE SHOWN IN DETAIL ON

AS-BUILT DRAWINGS BY CONTRACTOR.

18.FOR QUALITY ASSURANCE, ALL ELECTRICAL EQUIPMENT SHALL BE

UL LISTED AND APPROVED. ALSO, PERFORM WORK IN

ACCORDANCE WITH THE NATIONAL ELECTRICAL CONTRACTOR

ASSOCIATION (NECA) "STANDARD OF INSTALLATION."

19.ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. SIZE AND LOCATION

OF EQUIPMENT AND WIRING ARE SHOWN TO SCALE WHERE

POSSIBLE, BUT MAY BE DISTORTED FOR CLARITY ON THE

DRAWINGS. FINAL LOCATIONS OF OUTLETS AND EQUIPMENT

SHALL BE AS SHOWN IN ENLARGED DETAILS OR AS APPROVED BY

THE COR.

20.THE PLANS DO NOT INDICATE ALL THE NECESSARY BENDS,

OFFSETS, PULL BOXES AND OBSTRUCTIONS. IT SHALL BE THE

RESPONSIBILITY OF THE CONTRACTOR TO INSTALL HIS WORK TO

CONFORM TO THE STRUCTURE, MAINTAIN HEADROOM AND KEEP

OPENINGS AND PASSAGEWAYS CLEAR.

21.GROUNDING OF THE ELECTRICAL SYSTEM SHALL BE BY MEANS OF

A GREEN INSULATED GROUNDING CONDUCTOR INSTALLED WITH

FEEDER CONDUCTORS IN ALL CONDUITS WHETHER OR NOT

INDICATED ON DRAWINGS. GROUNDING CONDUCTORS SHALL BE

PROVIDE GROUNDING CONDUCTOR IN ALL TELEPHONE AND CATV

SERVICE CONDUITS.

22.PROVIDE ALL CUTTING AND PATCHING REQUIRED FOR THE

PROPER INSTALLATION OF THE NEW ELECTRICAL WORK. ALL

PATCHING SHALL BE OF THE SAME MATERIALS, WORKMANSHIP,

AND FINISH AND SHALL ACCURATELY MATCH ALL ADJACENT

WORK.

23.CLEAN UP RESULTANT DEBRIS FROM THIS WORK AND REMOVE

FROM THE SITE. DISCONNECT AND REMOVE ALL TEMPORARY

POWER INCLUDING BUT, NOT LIMITED TO PANELS, FIXTURES,

BOXES AND WIRING.

24.TEST FOR GROUNDS AND SHORTS, TO ENSURE PROPER

OPERATION OF ELECTRICAL EQUIPMENT. REPAIR OR REPLACE

FAULTY EQUIPMENT AT NO ADDITIONAL COST TO THE VA.

25.CONTRACTOR TO NOTE THAT WHEN A SPECIFIC DIRECTION IS

SPECIFIED SUCH AS "EAST", THAT DIRECTION IS "PLAN EAST" AND

NOT "TRUE EAST".

26.LETTERS SUCH AS "WP", "GFCI" ADJACENT TO ANY SYMBOL

INDICATE SPECIAL CONSTRUCTION IS REQUIRED. SEE

ABBREVIATIONS FOR DEFINITIONS.

27.SIZES OF WIRE AND CABLE ARE BASED ON COPPER CONDUCTORS.

ALUMINUM CONDUCTORS ARE NOT ACCEPTABLE.

28.ELEVATIONS FOR ELECTRICAL EQUIPMENT ARE SHOWN TO

CENTER OF DEVICE OR ENCLOSURE UNLESS NOTED OTHERWISE.

29.RECEPTACLES AND TELE/DATA JACKS SHALL BE LOCATED 18" AFF

UNLESS NOTED OTHERWISE. LIGHT SWITCHES SHALL BE LOCATED

48" AFF UNLESS NOTED OTHERWISE.

30.REFER TO "UTILITIES" DRAWINGS FOR EXACT PLACEMENT OF

EQUIPMENT AND LOCATIONS OF ELECTRICAL EQUIPMENT NOT

OTHERWISE SHOWN ON ELECTRICAL DRAWINGS. (CIVIL

DRAWINGS).

31.ALL PANELBOARD LOCKS SHALL BE KEYED TO MATCH EXISTING

SITE KEYING. COORDINATE WITH COR AND VAMC'S SFIC

DEPARTMENT FOR EXACT REQUIREMENTS.

32.LABEL ALL ELECTRICAL EQUIPMENT WITH THEIR SOURCE OF

ELECTRICAL SUPPLY, EXCEPT BRANCH-CIRCUIT DEVICES, WHICH

SHALL BE LABELED WITH THEIR CIRCUIT DESIGNATION - INCLUDING

PANEL NAME AND CIRCUIT BREAKER NUMBERS.

33.COORDINATE WITH COR AND ARRANGE FOR ELECTRICIAN

SUPERVISOR OVERSIGHT IN ADVANCE OF WORKING ON ESSENTIAL

ELECTRICAL SYSTEM (EES) EQUIPMENT OR SWITCHGEAR. SUCH

OVERSIGHT IS MANDATORY FOR WORKING ON THESE

CATEGORIES OF EQUIPMENT.

34.PROJECT INCLUDES REQUIREMENTS FOR 30-DAY LOAD STUDIES

PRIOR TO CONNECTING LOAD. CONTRACTOR SHALL DELAY

BUILDING CONNECTIONS TO LAB ELECTRICAL ROOM UNTIL AFTER

STUDY CONFIRMS ADEQUATE CAPACITY FOR NEW LOAD.

35.FOR ABBREVIATIONS AND SYMBOLS, SEE SHEETS EP002 AND

EP603.

36.REFERENCE SHEET PL602 FOR PNEUMATIC TUBE SYSTEM DETAILS.

37.INCLUDE WITHIN BID COST TO PROVIDE 3 ADDITIONAL 20-AMP

CIRCUITS, AN ADDITIONAL 30-AMP CIRCUIT, AND AN ADDITIONAL

50-AMP CIRCUIT, INCLUDING ALL MOBILIZATION, CONNECTIONS,

RECEPTACLES, AND AS OTHERWISE REQUIRED TO MOVE OR

PROVIDE NEW CONNECTIONS TO EQUIPMENT NOT SHOWN ON

PLANS. ALSO INCLUDE DEMOLITION WHERE RELOCATION IS

REQUIRED. SUCH CIRCUITS SHALL BE EITHER THREE-PHASE, OR

SINGLE PHASE, AND DIRECTION FOR THESE CIRCUITS WILL OCCUR

AFTER FURNITURE INSTALLATION HAS BEGUN. PATCH AND

REFINISH SURFACES ASSOCIATED WITH DEMOLITION.

38.(PART) ANNOTATION INDICATES MULTIPLE CONNECTIONS TO THE

SAME HOMERUN. CONNECT TO IDENTIFIED CIRCUIT BEFORE

ENTERING PANELBOARD.

GENERAL NOTES

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

VA FORM 08 - 6231

A

F i l e

P a t h

FULLY

SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE:

ARCHITECT/ENGINEER OF RECORD

SEAL

CONSULTANT

321 4 5 6 7 8 9 10

NEW CLINICAL LAB FOR

SURGICAL EXPANSION

RICHMOND, VIRGINIA

652-319

PROJECT DIRECTOR

AUGUST 2018

REVISIONS: DATE:

Group, Inc.

11031 SOUTH PIKES PEAK DRIVE #202

PARKER, COLORADO 80138

PH: 303.841.3922

WWW.AES-GRP.COM

BID DOCUMENTS

DWG. OF 162

NAME: TINA DEBELLA, PE

PHONE: 804.675.5495

EMAIL: Tina.DeBella@va.gov

ELECTRICAL

GENERAL NOTES

EP001

MMMGGR

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

VA FORM 08 - 6231

A

F i l e

P a t h

FULLY

SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE:

ARCHITECT/ENGINEER OF RECORD

SEAL

CONSULTANT

321 4 5 6 7 8 9 10

NEW CLINICAL LAB FOR

SURGICAL EXPANSION

RICHMOND, VIRGINIA

652-319

PROJECT DIRECTOR

AUGUST 2018

REVISIONS: DATE:

Group, Inc.

11031 SOUTH PIKES PEAK DRIVE #202

PARKER, COLORADO 80138

PH: 303.841.3922

WWW.AES-GRP.COM

BID DOCUMENTS

DWG. OF 162

NAME: TINA DEBELLA, PE

PHONE: 804.675.5495

EMAIL: Tina.DeBella@va.gov

P V A D

U

V A

R i c h m o n d

L a b D r a w i n g s E l e c t r i c a l V A D

U

R I C H

M O

N D

L A B

E P X

G e n e r a l d w g

P M

A R C H f u l l b l e e d

E x

I n c h e s

INDICATES QUANTITY OF DUCTS (4" MIN. IF NOT IDENTIFIED,

ASSEMBLY - TYPE AND NUMBER DESIGNATION AS INDICATED:

SEC, - SECONDARY RACK MOUNTED EQUIPMENT

STREET LIGHTING, DIRECT BURIAL DUCT LINE

EXISTING PAD MOUNTED TRANSFORMER

UNDERGROUND DUCT LINE, CONCRETE ENCASED NUMERAL

VOLTAGE (POTENTIAL) TRANSFORMER (VT/PT),

NON-DRAWOUT-QUANTITY AND

VOLTAGE RATING AS INDICATED

POWER FACTOR METER

KILOWATT HOUR METER

CURRENT TRANSFORMER (CT)-SECOND

NUMERAL OF TRANSFORMATION RATIO

IDENTIFIES NOMINAL CURRENT OF METERING

/ACCESSORY CIRCUIT, NUMERAL IN PARENTHESIS

INDICATES QUANTITY OF CT'S

AMMETER WITH PHASE SELECTOR SWITCH

VOLTMETER WITH PHASE SELECTOR SWITCH

400/5

(3)

VS

AS

(3)

7200-120 (3)

(3)

AMMETER

VOLTMETER

GROUNDING SYSTEM - ELECTRODE AND CONDUCTOR

(BARE COPPER) - SIZE AS INDICATED

CONDUIT STUB-OUT

PHOTOELECTRIC CONTROL RELAYPC

#4

SECONDARY UNDERGROUND FEEDER, DIRECT BURIAL DUCT LINE

FOR COMM. TYP, 5" FOR ELEC. TYP.) LETTER "P" INDICATES

ELECTRICAL POWER LINE, "C" A COMMUNICATIONS TYPE LINE.

ELECTRICAL EQUIPMENT IN PAD MOUNTED CABINET OR EQUIP.

ST-4, - SWITCH STATION NUMBER 4

ST-4

SL

UF

4P

TRANSFORMER-WIRING CONNECTIONS AS INDICATED

FUSE - POWER AND CONTROL

APPLICATIONS RESPECTIVELY, SIZE AS INDICATED

9KV

DRAW-OUT DEVICE

100E

CABLE TERMINATION

8E

SWITCH ASSEMBLY

ELECTRICAL CONNECTION

DASHED LINES UNDERGROUND (UNLESS OTHERWISE NOTED)

CONTACTOR

(2#12+#12 GRD)1/2"C

QUANTITY OF GROUND WIRES

POWER DISTRIBUTION PANEL WITH MAIN

CIRCUIT BREAKER

CONDUIT SIZE

CONDUIT RUN - SCHEMATIC DIAGRAM

QUANTITY OF PHASE AND NEUTRAL WIRES

KW KILOWATT

VT VOLTAGE TRANSFORMER

WEATHERPROOF

XMFR

WPF

W/ W/O

WP

W

TRANSFORMER

WATER PROOF

WITHOUT

WITH

WEST

POLYVINYL CHLORIDE

NORMALLY OPEN, NUMBER

NATIONAL ELECTRICAL CODE

MAIN SWITCHBOARD

POWER FACTOR

PRIMARY SWITCH STATION

NOT IN CONTRACT

OUTSIDE DIAMETER

SPECIFICATIONS

SWITCH STATION

KILOWATT HOURS

KILOVOLT AMPERES REACTIVE

ST

V

VA

UG

URD

TYP

TEL

SWGR

SYM

UNDERGROUND

VOLT AMPERE

VOLT

TYPICAL

SWITCHGEAR

SYMMETRICAL

TELEPHONE

SEC

SPEC

REQD

S

RECP

REF

PSS

PVC

REQUIRED

SECONDARY

SOUTH

RECEPTACLE

REFERENCE

NEC

O.C.

PF

PFCS

PH

PNL

NO

OD

NEUT

NIC

ON CENTER

PHASE

PANELBOARD

NEUTRAL

MH

MSB

N

MIN

LTG

MAX

KVAR

KWH

MANHOLE

MINIMUM

NORTH

LIGHTING

MAXIMUM

CURRENT TRANSFORMER

CONTRACTING OFFICER'S REPRESENTATIVE

CONTROL POWER TRANSFORMER

ELECTRICAL OR ELECTRIC

GROUND FAULT CIRCUIT INTERRUPTER

GANG OPERATED

GALVANIZED RIGID STEEL CONDUIT

KILOVOLT AMPERES

KILO CIRCULAR MIL

EXIST EXISTING

GND OR GRD GROUND

K

KV

KVA

KCMIL

J-BOX

GRC

GOVT

G.O.

KEY

KILOVOLTS

GOVERNMENT

JUNCTION BOX

FIN

FUT

GFCI

FLEX

FDN

FIG

EXP

EXT

FINISH

FLEXIBLE

FUTURE

EXPOSED

EXTERIOR

FOUNDATION

FIGURE

ENCL

EQUIP

EXC

ENT

ELEC

E

DISC

DWG

ENCLOSURE

ENTRANCE

EQUIPMENT

EXCAVATE

DISCONNECT

DRAWING

EAST

CPT

CU

DET

DIM

CT

CONT

COR

CONC

CL

COPPER

DIMENSION

DETAIL

CENTER LINE

CONCENTRIC

CONTINUOUS

CIRCUIT BREAKER

AMMETER SWITCH

(NOT ALL ABBREVIATIONS REQUIRED FOR THIS PROJECT)

AMPS INTERRUPTING CAPACITY (SYM RMS)

AMERICAN NATIONAL STANDARDS INSTITUTE

AMERICAN WIRE GAGE

AUX

C

CKT

CB

BLDG

AS

AWG

ANSI

AIC

AUXILIARY

CIRCUIT

CONDUIT

BUILDING

AL

ALT

ALUMINUM

ALTERNATE

POLE NUMBER

ELECTRICAL POWER DISTRIBUTION POLE

LIGHTING CONTROL CABINET

WP

GFI

20A

CONDUIT TURNING TOWARD VIEWER

CONDUIT TURNING AWAY FROM VIEWER

600A200A

STREET LIGHTING FIXTURE, FIXTURE TYPE AS NOTED

FUT - INDICATES FUTURE LIGHTING FIXTURE LOCATION

A

(NO. OF CONNECTIONS AS SHOWN)

SECTIONALIZING CABINET

FAULT DETECTOR, MANUAL RESET

WATT/VAR METER

TIME OVERCURRENT

CAPACITIVE TRIP

ELECTRICAL SWITCH OPERATOR

F

W/V

C.T.

EO

FUT

"NG-1" - POWER SOURCE (PANEL AND CIRCUIT NO.)

NG-1

GUY WIRE

FOUR POINT JUNCTION

IN ELECTRICAL MANHOLE

SYSTEMSYS

STREET LIGHTING FIXTURE, FIXTURE TYPE AS NOTEDA

1,3 - INDICATES CIRCUIT NUMBER

1,3

PF

KWH

V

A

UNDERGROUND RESIDENTIAL

DISTRIBUTION

POWER FACTOR CORRECTION

STATION

DISCONNECT SWITCH, SIZE AND TYPE AS INDICATED

COMBINATION STARTER W/ EXTERNALLY OPERATED

MOTOR STARTER, TYPE AND SIZE AS INDICATED

VARIABLE FREQUENCY DRIVE

IN SCHEDULE.

DISCONNECT.

IN SCHEDULE.

VFD

MOTOR - EQUIPMENT SCHEDULE IDENTIFICATION

MOLDED CASE CB OF A GIVEN FRAME SIZE

MOLDED CASE CIRCUIT BREAKER, FIXED TRIP.

THREE POLE UNLESS DESIGNATED '1P' OR '2P'

NORMALLY CLOSED MOMENTARY PUSHBUTTON

AS SHOWN.

MEFX

NORMALLY CLOSED CONTACT

NORMALLY OPEN CONTACT

ELECTRIC METER

NORMALLY OPEN MOMENTARY PUSHBUTTON

SA

WITH ADJUSTABLE TRIP SETTINGS350 AT

400 AF

30A 2P

CONCRETE PAD MOUNTED TRANSFORMER INSTALLATION ANSI

(C84.1) VOLTAGE CONFIGURATION AS INDICATED.

(#6 MIN. CONDUCTOR IF NOT SHOWN)

GROUND CONNECTION - TO STANDARD ROD

TYPE ELECTRODE TO NEAREST STRUCTURAL STEEL

GROUND FAULT RELAYG

JUNCTION BOX, 4" SQUARE UNLESS NOTED OTHERWISEJ

FLOOR DUPLEX RECEPTACLE OUTLET

AA

MANUAL STARTER WITH THERMAL OVERLOADS

SOS

SD

STO

S3

S

DIMMER SWITCH

SWITCH WITH OCCUPANCY SENSOR

SINGLE POLE SWITCH

THREE WAY SWITCH

A A

A A

AFF48"

A

A

OCCUPANCY SENSOR FOR LIGHTING CONTROLOS

A

SP SWITCH WITH PILOT LIGHT

FLOOR FOUR-PLEX RECEPTACLE OUTLET

CEILING MOUNTED DUPLEX RECEPTACLE OUTLET

C

A A

RECESSED INCANDESCENT, FLUORESCENT OR H.I.D.

LUMINAIRE,UPPER CASE LETTER IDENTIFIES FIXTURE

TYPE.

CAN LIGHTS. UPPER CASE LETTER IDENTIFIES FIXTURE TYPE.

DARKENED AREA INDICATES EMERGENCY FIXTURE

WALL MOUNTED COMPACT FLUORECENT, OR H.I.D.

LUMINAIRE, UPPER CASE LETTER IDENTIFIES FIXTURE

TYPE.

SURFACE MOUNTED OR SUSPENDED INDUSTRIAL, HIGH

BAY OR STRIP FLUORESCENT FIXTURE NO LENS. UPPER

CASE LETTER IDENTIFIES THE FIXTURE TYPE.

DARKENED AREA INDICATES EMERGENCY FIXTURE.

SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE W/

LENS. UPPER CASE LETTER DESIGNATES THE FIXTURE

TYPE. DARKENED AREA INDICATES EMERGENCY

FIXTURE POWERED BY A BATTERY INVERTER.

WALL(SURFACE) MOUNTED FLUORESCENT LIGHT

FIXTURE W/ LENS. UPPER CASE LETTER DESIGNATES

THE FIXTURE TYPE. DARKENED AREA INDICATES

EMERGENCY FIXTURE.

2'X4' SURFACE MOUNTED FLUORESCENT FIXTURE.

UPPER CASE LETTER DESIGNATES THE FIXTURE TYPE.

DARKENED AREA INDICATES EMERGENCY FIXTURE.

WALL MTD. EXIT SIGN, ARROW IDENTIFIES DIRECTION

OF EGRESS SINGLE FACE.

WALL MTD. EXIT SIGN, ARROWS IDENTIFY DIRECTION OF

EGRESS DOUBLE FACES

CEILING MTD. EXIT SIGN, ARROW IDENTIFIES DIRECTION

OF EGRESS SINGLE FACE

CEILING MTD. EXIT SIGN, ARROW IDENTIFIES DIRECTION

OF EGRESS DOUBLE FACES

2P, 3W GROUNDING TYPE RECEPTACLE - 125V, CONVENTIONAL DUPLEX,

NEMA 5-20R. RECEPTACLE COVERPLATE SHALL BE PROVIDED WITH

LABEL STATING "COMPUTER".

BRANCH CIRCUIT AND FEEDER WIRING. ARROWS AND

LETTER/NUMERALS IDENTIFY ABV. GRADE HOME-RUN CIRCUITS. ALL

CONDUIT SHALL CONTAIN A GREEN INSULATED GROUND WIRE SIZED IN

ACCORDANCE WITH 2005 NEC TABLE 250.122, UNLESS OTHERWISE

NOTED. ONE TICK MEANS 1 POLE CKT. TWO TICKS MEANS 2 POLE CKT,

THREE TICKS MEANS 3 POLE CKT.

SPECIAL RECEPTACLE, PROVIDE RECEPTACLE CONFIGURATION NOTED

LIGHTING AND APPLIANCE TYPE PANELBOARD. - SURFACE MOUNTED

DUPLEX RECEPTACLE - 2P,3W GROUNDING TYPE RECEPTACLE, 125V,

NUMERAL ADJACENT IDENTIFIES CURRENT RATING IN AMPS (NO

DESIGNATION INDICATES 15A MIN.) GFI INDICATES DEVICE WITH

INTEGRAL GROUND FAULT PROTECTION, WP INDICATES

WEATHERPROOF

CATV OUTLET, 18"AFF, UNLESS NOTED OTHERWISE. "2"

DENOTES DUPLEX JACK.

KEYED NOTES

SEPARABLE CONNECTOR IN PRIMARY DISTRIBUTION LINE

(ELBOW TERMINATOR AND BUSHING COMBINATION)-LOAD

BREAK (200A) AND NON-LOADBREAK (600A) STYLES

RESPECTIVELY

SURGE ARRESTER - VOLTAGE RATING AND

CLASS AS NOTED

AUTOMATIC TRANSFER SWITCHATS

GENERATORGEN

MCC MOTOR CONTROL CENTER

SWBD SWITCHBOARD

3# 2/0,15KV + #2/0,600V N

UNDERGROUND ELECTRICAL FEEDER -

QUANTITY, SIZE, AND VOLTAGE RATING OF PHASE

AND NEUTRAL CONDUCTORS AS INDICATED

PHOTOSENSOR FOR DAYLIGHTING CONTROLPS

LIGHTNING PROTECTION CABLE - CLASS II ALUMINUM SIZE PER NFPA 780

MINIMUM.

AIR TERMINAL - BARE ALUMINUM 5/8" DIAMETER X 12" LONG, MOUNTING

HARDWARE AS REQUIRED FOR EACH SPECIFIC TYPE OF LOCATION.

GROUND TERMINAL - COPPER CLAD STEEL GROUND ROD, 3/4" DIAMETER X 10'

LONG.

THROUGH WALL PENETRATION - 1" PVC FROM HIGHER ROOF TO LOWER ROOF,

INSTALLED BY ELECTRICAL CONTRACTOR. SEAL INSIDE OF CONDUIT AND

OUTSIDE OF CONDUIT TO BE WEATHER TIGHT.

THROUGH ROOF PENETRATION - 1" PVC INSTALLED BY ELECTRICAL

CONTRACTOR DOWN TO GROUND. FLASHING DONE BY ROOFING CONTRACTOR.

SEAL INSIDE OF CONDUIT AND OUTSIDE OF CONDUIT TO BE WEATHER TIGHT.

PROVIDE SEALING, FLASHING, AND COUNTER FLASHING AS REQUIRED TO

MAINTAIN WARRANTY OF ROOF WITH WEATHER-TIGHT SEAL.

WIRING GRAPHICS PRIMARY DISTRIBUTION ELECTRICAL POWER LEGEND WIRING GRAPHIC - SECONDARY DISTRIBUTION EXTERIOR ELECTRICAL LEGEND

INTERIOR ELECTRICAL LEGEND

GENERAL

LIGHTNING PROTECTION LEGEND

ELECTRICAL ABBREVIATIONS

A-AMP AMPERE

AC ABOVE-COUNTER

MOMENTARY PUSHBUTTON / DEADFRONT GFCI PROTECTOR

VACANCY SENSOR FOR DAYLIGHTING CONTROLVA

AF AMPERE FRAME

AMPERE TRIPAT

A

A A

2'X4' RECESSED MOUNTED FLUORESCENT FIXTURE.

UPPER CASE LETTER DESIGNATES THE FIXTURE TYPE.

DARKENED AREA INDICATES EMERGENCY FIXTURE.

DETAIL NUMBER

SHEET NUMBER

ELECTRICAL STRIP MOLD ((OUTLETS ON (2'-6") CENTERS OR AS DESIGNATED

ON DRAWINGS)), MTD ABOVE COUNTER TOP OR AS INDICATED.

c WALL MOUNTED COVER PLATE

ENCLOSED CIRCUIT BREAKERECB

U.O.N UNLESS OTHERWISE NOTED

EES ESSENTIAL ELECTRICAL SYSTEM

A

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

VA FORM 08 - 6231

A

F i l e

P a t h

FULLY

SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE:

ARCHITECT/ENGINEER OF RECORD

SEAL

CONSULTANT

321 4 5 6 7 8 9 10

NEW CLINICAL LAB FOR

SURGICAL EXPANSION

RICHMOND, VIRGINIA

652-319

PROJECT DIRECTOR

AUGUST 2018

REVISIONS: DATE:

Group, Inc.

11031 SOUTH PIKES PEAK DRIVE #202

PARKER, COLORADO 80138

PH: 303.841.3922

WWW.AES-GRP.COM

BID DOCUMENTS

DWG. OF 162

NAME: TINA DEBELLA, PE

PHONE: 804.675.5495

EMAIL: Tina.DeBella@va.gov

ELECTRICAL GRAPHICS, SYMBOLS

AND ABBREVIATIONS

EP002

MMMGGR

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

VA FORM 08 - 6231

A

F i l e

P a t h

FULLY

SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE:

ARCHITECT/ENGINEER OF RECORD

SEAL

CONSULTANT

321 4 5 6 7 8 9 10

NEW CLINICAL LAB FOR

SURGICAL EXPANSION

RICHMOND, VIRGINIA

652-319

PROJECT DIRECTOR

AUGUST 2018

REVISIONS: DATE:

Group, Inc.

11031 SOUTH PIKES PEAK DRIVE #202

PARKER, COLORADO 80138

PH: 303.841.3922

WWW.AES-GRP.COM

BID DOCUMENTS

DWG. OF 162

NAME: TINA DEBELLA, PE

PHONE: 804.675.5495

EMAIL: Tina.DeBella@va.gov

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

VA FORM 08 - 6231

A

F i l e

P a t h

FULLY

SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE:

ARCHITECT/ENGINEER OF RECORD

SEAL

CONSULTANT

321 4 5 6 7 8 9 10

NEW CLINICAL LAB FOR

SURGICAL EXPANSION

RICHMOND, VIRGINIA

652-319

PROJECT DIRECTOR

AUGUST 2018

REVISIONS: DATE:

Group, Inc.

11031 SOUTH PIKES PEAK DRIVE #202

PARKER, COLORADO 80138

PH: 303.841.3922

WWW.AES-GRP.COM

BID DOCUMENTS

DWG. OF 162

NAME: TINA DEBELLA, PE

PHONE: 804.675.5495

EMAIL: Tina.DeBella@va.gov

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

VA FORM 08 - 6231

A

F i l e

P a t h

FULLY

SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE:

ARCHITECT/ENGINEER OF RECORD

SEAL

CONSULTANT

321 4 5 6 7 8 9 10

NEW CLINICAL LAB FOR

SURGICAL EXPANSION

RICHMOND, VIRGINIA

652-319

PROJECT DIRECTOR

AUGUST 2018

REVISIONS: DATE:

Group, Inc.

11031 SOUTH PIKES PEAK DRIVE #202

PARKER, COLORADO 80138

PH: 303.841.3922

WWW.AES-GRP.COM

BID DOCUMENTS

DWG. OF 162

NAME: TINA DEBELLA, PE

PHONE: 804.675.5495

EMAIL: Tina.DeBella@va.gov

P V A D

U

V A

R i c h m o n d

L a b D r a w i n g s E l e c t r i c a l V A D

U

R I C H

M O

B

E P X

G e n e r a l d w g

P M

A R l l b l e e d

E x

I n c h e s

GENERAL NOTES

1. EQUIPMENT SHOWN WITH BOLD LINEWEIGHTS INDICATES EQUIPMENT TO BE

FURNISHED AND INSTALLED BY THE CONTRACTOR.

KEY NOTES

1. BASE BID: PROVIDE INTEGRAL DAY TANK WITH 72 HOUR FUEL CAPACITY

RUNNING AT FULL LOAD.

DEDUCTIVE BID ALTERNATE 1: OMIT GENERATOR SET AND ASSOCIATED

RECEPTACLE.

2. BASE BID:ROUTE BELOW-GRADE TO BUILDING, SEAL PENETRATION AT WALL,

BOTH INTERIOR AND EXTERIOR TO CONDUIT. ROUTE CONCEALED WITHIN

BUILDING. REFERENCE ONE-LINE FOR ADDITIONAL REQUIREMENTS. PROVIDE

ADDITIONAL, SIMILAR, BELOW-GRADE CONNECTION FOR RECEPTACLE. PROVIDE

NEW CIRCUIT AND CONNECT RECEPTACLE TO NEAREST NON-EES PANELBOARD

WITH CAPACITY.

DEDUCTIVE BID ALTERNATE #1: DISREGARD KEY NOTE #2, THIS SHEET.

T

T

T

T

T

T

T

T

T

T T

T T

T

T

T

W

W

W

W W

W

W

W

W

W

W

W W

W W

W W

W W

W W W W

W

W

W

W

SD

SD

SD

SD

SD

SD

S

D

S

D

S

D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S

D

S

D

S

D

S

D

S

D

S

D

S

D

S

D

S

D

S

D

S

D

S

D

S

D

S

D

S

D

S

D

S

D

SS

SS

SS

SS

SS

SS

SS

SS

SSSS

SS

S

S

S

S

S

S

E

E

E

S

D

S

D

SD

SD

S D

E

E

E

E

E

E

E

E E

E

E

E

E

E

E E

E

E

E E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

BOLD BOUNDARY INDICATES

NEW LAB AREA (3RD FLOOR)

1DIESEL

GENERATOR

WP

GFCI

ATS & LOADBANK

DISCONNECTS2

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

VA FORM 08 - 6231

A

F i l e

P a t h

FULLY

SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE:

ARCHITECT/ENGINEER OF RECORD

SEAL

CONSULTANT

321 4 5 6 7 8 9 10

NEW CLINICAL LAB FOR

SURGICAL EXPANSION

RICHMOND, VIRGINIA

652-319

PROJECT DIRECTOR

AUGUST 2018

REVISIONS: DATE:

Group, Inc.

11031 SOUTH PIKES PEAK DRIVE #202

PARKER, COLORADO 80138

PH: 303.841.3922

WWW.AES-GRP.COM

BID DOCUMENTS

DWG. OF 162

NAME: TINA DEBELLA, PE

PHONE: 804.675.5495

EMAIL: Tina.DeBella@va.gov

ELECTRICAL

SITE PLAN (PARTIAL)

ES101

WBRGGR

SCALE:

ES101

ELECTRICAL SITE PLAN (PARTIAL)

1/16" = 1'-0"

KEYPLAN PLAN

NORTH

N

TN

16'0 8' 32'

SCALE:1/16"=1'-0"

P V A D

U

V A

R i c h m o n d

L a b D r a w i n g s E l e c t r i c a l V A D

U

R I C H

M O

B

E S

S i t e

P l a n d w g

P M

A R l l b l e e d

E x

I n c h e s

FURNISHED AND INSTALLED BY THE CONTRACTOR.

2. LIGHT FIXTURES ARE MOUNTED AT 9'-0" A.F.F. UNLESS OTHERWISE NOTED.

3. SEE LUMINARIES SCHEDULE ON SHEET EL501.

4. PROVIDE ENTIRETY UNDER BASE BID. PROVIDE REDUCED SCOPE PER REGIONS

SHOWN ON GX002 COMMENSURATE WITH AWARDED DEDUCTIVE BID

ALTERNATES. REFERENCE SHEET EL131.2 FOR REDUCED SCOPE WITHIN EACH

REGION, APPLICABLE TO FOOTPRINT AREAS SHOWN ON GX002 ONLY.

5. PROVIDE POWER PACKS AND RELAYS AS REQUIRED FOR LIGHTING CONTROL,

AND AS REQUIRED TO SWITCH RECEPTACLES FOR OCCUPANCY CONTROL, IN

ACCORDANCE WITH ASHRAE 90.1.

KEY NOTES

1. SWITCH IN ROOM SHOWN FOR SIMPLICITY. TWO SEPARATE SWITCHES WILL BE

INSTALLED IN THE ROOM AND LOCATION SHOWN, ONE FOR THE NORMAL LIGHT

FIXTURE, AND ONE FOR THE EMERGENCY LIGHT FIXTURE CONFIGURED AS

SHOWN IN THE DETAIL ON SHEET EL501. FIELD-VERIFY CIRCUIT LOADING WILL

NOT EXCEED 14A, AND PROVIDE REPORT TO COR ACCORDINGLY.

2. NOT USED.

3. FIND EXISTING STAIRWELL LIGHTING CIRCUIT AND ADD NEW STAIRWELL LIGHT

FIXTURES TO THIS CIRCUIT. PROVIDE CONDUIT AND CONDUCTOR AS REQUIRED

TO ADD THESE FIXTURES TO THIS CIRCUIT. MOUNT 8'-0" AFF.

4. DIMMING CONTROL FOR THIS LUMINAIRE SHALL ALLOW LUMINAIRE TO DIM TO

DARK(OFF).

5. LIGHTING AND CONTROLS INCLUDED FROM REFRIGERATOR MANUFACTURER.

INSTALL PER MANUFACTURER INSTRUCTIONS.

F

F

F

A

A

FF

H

H

A

A

A

H

H

H

A

A

A

A

F

A AA

A

A

A A

A

NPQRSTUVW

X

Wn

A

A A

A A AA A A A A

A

A A A A A

A

A

A

A

A

A

A

A A

A

A

A

A

A

A

A

A

A

A

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS OS

OS OS

OS OS

OS

OS

OS

OS

CORRIDOR

3F101

CORRIDOR

3F109

BIOMED

3F102

ANCILLARY TESTING

3F104

DRUG TESTING

3F106

IMMUNOLOGY

3F108

IT CLOSET

3F105

ELEC CLOS

3F103

ACCESSIONING

3F107a

FEE BASIS

3F107b

HEMATOLOGY

3F107e

CHEMISTRY

3F107f

R E

F R

I G

E R

A T

E D

S T

O R

A G

E

F

BLOOD BANK

3F107c

CYTOLOGY

3F107h

HISTOLOGY

3F107g

OPEN OFFICE

3F107j

ARCHIVE

3F128

CLEAN SUPPLY

3F134

BSL-3 LAB

3F132

MEN'S TOILET

3F110

WOMEN'S TOILET

3F112

STAFF TOILET

3F113

BREAK ROOM

3F114

DIRECTOR'S OFFICE

3F118b

CMT OFFICE

3F118c

OFFICE VESTIBULE

3F106a

OFFICE #1

3F106b

OFFICE #2 OFFICE #3

3F106d

OFFICE #4

3F106e

OFFICE #5

3F106f

ADMINISTRATION

3F118a

OFFICE #6

3F119

ADPAC

3F117

DRUG TESTING TOILET

3F106a

JANITOR

3F111

MICROBIOLOGY

3F107d

EQUIPMENT RM

3F133

ANTE ROOM

3F131

GAS TANK ROOM

3F130

FLAMMABLE STORAGE

3F129

D a

D b

D d

D c f f f f ff f f f

D g

D h k Df

Dk OCC

D

OCC OCC

OCC

OCC

OCC

OCC

OCC

OCC DDOCC D D

k k k mn m n n n

D

OCC

OCC

OCC

OCC

OCC

OCC

D

D

D D

D D

D D

D

OCC

VAC

D D

OSOS

OSOS

3F106c k f f f a

OS OS

c b h h h j j r d

OS

d e s

OS

s

OS

D q

OS

OS

OS

q q q

PANEL 3F-NH1

CIRCUIT #9

PANEL 3F-NH1

CIRCUIT #13

PANEL 3F-NH1

CIRCUIT #1

PANEL 3F-ESP1

CIRCUIT #3

PANEL 3F-NH1

CIRCUIT #5

PANEL 3F-ESP1

CIRCUIT #1

1 1

1 1

D s

D j

D r

G

G j

G e r

G j

G j

G q

G q

G q

G h

G h

G h

G G q

G G j

G G j

G

G h

G h

G q

G q

G q

G j

G j

G j

G j

G h

G h

G q

G G q

G

G b

G b G b G b

G a

G a

G a

G a

G a

G a

G b G b

G r

G G r

G s

G s

G s G s

G G s

G s

G s

G r

G r

G r

G r

G r

G G r

G G r

G

G d

G d

G d

G d

G d G G d

G

G e

G

G e

G e

G e

G e

G e

G e

G g

G g

G g

G g

G g

G g

G g

G

G

G

G G

G

G c

G c

G

G G c

G c

G

G G

G

G

OS

g

A

A

A A

A

A

G

G

GG

A

A n m

A mA

A

A

S

S

PANEL 3F-NH1

CIRCUIT #3

A n t

H

H

G

G

G

G

GG

H

H

H

H

OS

OS

A

G

G

G

G

G G

G G

G

H

G

G

G

G

G

G

G

G

G

G

G

G

A A

A t t t

OS

c

PANEL 3F-NH1

CIRCUIT #7

PANEL 3F-ESP1

CIRCUIT #7

PANEL 3F-ESP1

CIRCUIT #5

PANEL 3F-ESP1

CIRCUIT #9

Q

Q

D e

D t

PANEL 3F-NH1

CIRCUIT #11

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

VA FORM 08 - 6231

A

F i l e

P a t h

FULLY

SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE:

ARCHITECT/ENGINEER OF RECORD

SEAL

CONSULTANT

321 4 5 6 7 8 9 10

NEW CLINICAL LAB FOR

SURGICAL EXPANSION

RICHMOND, VIRGINIA

652-319

PROJECT DIRECTOR

AUGUST 2018

REVISIONS: DATE:

Group, Inc.

11031 SOUTH PIKES PEAK DRIVE #202

PARKER, COLORADO 80138

PH: 303.841.3922

WWW.AES-GRP.COM

BID DOCUMENTS

DWG. OF 162

KEYPLAN

LAB EXPANSION

PLAN

NORTH

NAME: TINA DEBELLA, PE

PHONE: 804.675.5495

EMAIL: Tina.DeBella@va.gov

TN

N

3RD FLOOR

LIGHTING PLAN AND SCHEDULE

EL131

MMMGGR

SCALE:

EL131

3RD FLOOR LIGHTING PLAN

1/8" = 1'-0"

8'0 4' 16'

SCALE:1/8"=1'-0"

P V A D

U

V A

R i c h m o n d

L a b D r a w i n g s E l e c t r i c a l V A D

U

R I C H

M O

B

E L

L i g h t i n g

P l a n d w g

P M

A R l l b l e e d

E x

I n c h e s

FURNISHED AND INSTALLED BY THE CONTRACTOR.

2. LIGHT FIXTURES ARE MOUNTED AT 9'-0" A.F.F. UNLESS OTHERWISE NOTED.

3. SEE LUMINARIES SCHEDULE ON SHEET EL501.

4. REFERENCE GX002 FOR ZONES ASSOCIATED WITH EACH DEDUCTIVE BID

ALTERNATE. THIS SHEET SHOWS EFFECT OF DEDUCTIVE ALTERNATES 4, 5, AND

6 COMBINED. APPLY TO ACTUAL AWARDED SCOPE WITHIN ZONES DEFINED AT

GX002, ON A ZONE-BY-ZONE BASIS. PROVIDE LIGHTING INFRASTRUCTURE PER

EL131 FOR REMAINING REGIONS.

5. PROVIDE POWER PACKS AND RELAYS AS REQUIRED FOR LIGHTING CONTROL,

AND AS REQUIRED TO SWITCH RECEPTACLES FOR OCCUPANCY CONTROL, IN

ACCORDANCE WITH ASHRAE 90.1.

KEY NOTES

1. SWITCH IN ROOM SHOWN FOR SIMPLICITY. TWO SEPARATE SWITCHES WILL BE

INSTALLED IN THE ROOM AND LOCATION SHOWN, ONE FOR THE NORMAL LIGHT

FIXTURE, AND ONE FOR THE EMERGENCY LIGHT FIXTURE CONFIGURED AS

SHOWN IN THE DETAIL ON SHEET EL501.

2. NOT USED.

3. FIND EXISTING STAIRWELL LIGHTING CIRCUIT AND ADD NEW STAIRWELL LIGHT

FIXTURES TO THIS CIRCUIT. PROVIDE CONDUIT AND CONDUCTOR AS REQUIRED

TO ADD THESE FIXTURES TO THIS CIRCUIT. MOUNT 8'-0" AFF. FIELD-VERIFY

CIRCUIT LOADING WILL NOT EXCEED 14A, AND PROVIDE REPORT TO COR

ACCORDINGLY.

4. DIMMING CONTROL FOR THIS LUMINAIRE SHALL ALLOW LUMINAIRE TO DIM TO

DARK (OFF).

5. LIGHTING AND CONTROLS INCLUDED FROM REFRIGERATOR MANUFACTURER.

PROVIDE POWER PER MANUFACTURER INSTRUCTIONS.

Q Q Q QQ Q Q Q

P

F

PF

P F

P

F

PF

CORRIDOR

C3F-1

81 SF

IT CLOSET

3F-104

105 SF

ELEC CLOS

3F-102

387 SF

ACCESSIONING

3F-106a

467 SF

FEE BASIS

3F-106b

1908 SF

MICROBIOLOGY

3F-106d

1019 SF

HEMATOLOGY

3F-106e

1534 SF

CHEMISTRY

3F-106f

231 SF

REFRIGERATEDSTORAGE

3F-126

544 SF

BLOOD BANK

3F-106c

496 SF

CYTOLOGY

3F-106h

1179 SF

OPEN OFFICE

3F-106j

273 SF

ARCHIVE

3F-124

372 SF

CLEAN SUPPLY

3F-131

147 SF

BSL-3 LAB

3F-129

70 SF

STAFF TOILET

3F-108

121 SF

EQUIPMENT ROOM

3F-130

77 SF

FLAMMABLE STORAGE

3F-125

125 SF

ANTE ROOM

3F-128

1583 SF

HISTOLOGY

3F-106g

93 SF

GAS TANK ROOM

3F-127

164 SF

STAIR

3F-S2

NPQRSTUVW

X

Wn

A

A

A

A A

F

A A A

A

A

A

A

A

A A

A

A

A

A

A

A

A

A

A

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

D a

D b

D d

D c

D e f f f f ff f f f

D g

D h

D f

D k

OCC

k k k

D

OCC

OCC

OCC

OCC

OCC

D

DOCC

OS

k f f f a

OS OS

c b h h h j j r d

OS

d e s

OS

s

OS

D q

OS

OS

OS

q q q D s

D j

D r

G

G j

G e r

G j

G j

G q

G q

G q

G h

G h

G h

G G q

G G j

G G j

G

G h

G h

G q

G q

G q

G j

G j

G j

G j

G h

G h

G q

G G q

G

G b

G b G b G b

G a

G a

G a

G a

G a

G a

G b G b

G r

G G r

G s

G s

G s G s

G G s

G s

G s

G r

G r

G r

G r

G r

G G r

G G r

G

G d

G d

G d

G d

G d G G d

G

G e

G

G e

G e

G e

G e

G e

G e

G g

G g

G g

G g

G g

G g

G g

G

G

G

G G

G

G c

G c

G

G G c

G c

G

G G

G

G

OS

g

A

G

G

GG

D t t

H

H

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

A A

A t t t

OS

c

Q

Q

Q QQ Q Q

S

S

PANEL 3F-NH1

CIRCUIT #13

PANEL 3F-NH1

CIRCUIT #1

PANEL 3F-ESP1

CIRCUIT #3

PANEL 3F-NH1

CIRCUIT #5

PANEL 3F-NH1

CIRCUIT #3PANEL 3F-NH1

CIRCUIT #7

PANEL 3F-ESP1

CIRCUIT #7

PANEL 3F-ESP1

CIRCUIT #5

PANEL

3F-ESP1

CIRCUIT #9

PANEL 3F-ESP1

CIRCUIT #1

PANEL 3F-ESP1

CIRCUIT #1

DEDUCTIVE ALTERNATE # 6

NORTH INTERIOR BATHROOMS 3F109, 3F110, 3F111, 3F108 AND CORRIDOR C3F-2

DEDUCTIVE ALTERNATE # 5

NORTH INTERIOR ROOMS C3F3, 3F114, 3F115, 3F116, 3F117, 3F118, 3F120, 3F121, 3F122, 3F119 AND 3F123

DEDUCTIVE ALTERNATE # 4

NORTH INTERIOR ROOMS 3F101, 3F103, 3F105, 3F105a, 3F107, 3F112 AND 3F113

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

VA FORM 08 - 6231

A

F i l e

P a t h

FULLY

SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE:

ARCHITECT/ENGINEER OF RECORD

SEAL

CONSULTANT

321 4 5 6 7 8 9 10

NEW CLINICAL LAB FOR

SURGICAL EXPANSION

RICHMOND, VIRGINIA

652-319

PROJECT DIRECTOR

AUGUST 2018

REVISIONS: DATE:

Group, Inc.

11031 SOUTH PIKES PEAK DRIVE #202

PARKER, COLORADO 80138

PH: 303.841.3922

WWW.AES-GRP.COM

BID DOCUMENTS

DWG. OF 162

KEYPLAN

LAB EXPANSION

PLAN

NORTH

NAME: TINA DEBELLA, PE

PHONE: 804.675.5495

EMAIL: Tina.DeBella@va.gov

TN

N

3RD FLOOR LIGHTING PLAN

DEDUCTIVE BID ALTERNATE 4, 5 & 6

EL131.2

MMMGGR

SCALE:

EL131.2

BID ALTERNATE 4, 5 & 6

3RD FLOOR LIGHTING PLAN

1/8" = 1'-0"

8'0 4' 16'

SCALE:1/8"=1'-0"

P V A D

U

V A

R i c h m o n d

L a b D r a w i n g s E l e c t r i c a l V A D

U

R I C H

M O

B

E L

L i g h t i n g

P l a n d w g

P M

A R l l b l e e d

E x

I n c h e s

FURNISHED AND INSTALLED BY THE CONTRACTOR.

2. ALL VACANCY SENSORS SHALL BE SET TO THE MAXIMUM DELAY OFF.

3. ALL LIGHTS WILL BE SWITCHED WITH THE VACANCY SENSOR, DURING

EMERGENCY OPERATIONS, THE EMERGENCY FIXTURES WILL REMAIN ON.

REFER TO THE EMERGENCY BYPASS DETAIL ON SHEET EL501 FOR A POSSIBLE

CONFIGURATION.

4. SEE LUMINARIES SCHEDULE ON SHEET EL501.

KEY NOTES

1. FIND EXISTING STAIRWELL LIGHTING CIRCUIT AND ADD NEW STAIRWELL LIGHT

FIXTURES TO THIS CIRCUIT. PROVIDE CONDUIT AND CONDUCTOR AS REQUIRED

TO ADD THESE FIXTURES TO THIS CIRCUIT. MOUNT 8'-0" AFF. FIELD-VERIFY

CIRCUIT LOADING WILL NOT EXCEED 14A, AND PROVIDE REPORT TO COR,

ACCORDINGLY. ("S"-TYPE LUMINAIRES.)

2. PROVIDE A UL-LISTED CONTROL PANEL, INCLUDING FABRICATION, BY A UL 508

PANEL SHOP. CABINET SHALL INCLUDE RAIL-MOUNTED TIMER SUITABLE FOR

8-HOUR ON WITH AUTOMATIC OFF. LIGHTING CONTROL ACCESSORIES SHALL

INCLUDE TWO (2) STATUS LIGHTS (GREEN AT ON, RED AT AUTO-OFF) ON OUTER

COVER AND A HAND-OFF-AUTO SWITCH. PROVIDE ADDITIONAL COMPONENTS AS

REQUIRED FOR COMPLETE FUNCTIONALITY. PROVIDE FUNCTIONALITY FOR

MOMENTARY WALL SWITCHES AND PROVIDE TWO (2) CONTROLLED

CONTACTORS FOR 20 AMP 277V LIGHTING CIRCUITS.

3. PROVIDE 24VDC OR 120VAC MOMENTARY WALL SWITCH, AT CONTRACTOR'S

OPTION, TO MATCH THE TIMING CONTACTOR LIGHTING CONTROL PANEL.

NPQRSTUVW

QQQ

QQQ

QQQ

Q Q Q QQ

Q Q

QQQ QQQ Q

QQQQ Q Q QQ

INTERSTITIAL

3F-INT

S

S

PANEL 3F-ESP1

CIRCUITS #11

PANEL 3F-ESP1

CIRCUITS #11

PANEL 3F-NH1

CIRCUITS #15

PANEL 3F-NH1

CIRCUITS #15

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

VA FORM 08 - 6231

A

F i l e

P a t h

FULLY

SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE:

ARCHITECT/ENGINEER OF RECORD

SEAL

CONSULTANT

321 4 5 6 7 8 9 10

NEW CLINICAL LAB FOR

SURGICAL EXPANSION

RICHMOND, VIRGINIA

652-319

PROJECT DIRECTOR

AUGUST 2018

REVISIONS: DATE:

Group, Inc.

11031 SOUTH PIKES PEAK DRIVE #202

PARKER, COLORADO 80138

PH: 303.841.3922

WWW.AES-GRP.COM

BID DOCUMENTS

DWG. OF 162

KEYPLAN

LAB EXPANSION

PLAN

NORTH

NAME: TINA DEBELLA, PE

PHONE: 804.675.5495

EMAIL: Tina.DeBella@va.gov

TN

N

3RD FLOOR

INTERSTITIAL LIGHTING PLAN

EL132

MMMGGR

SCALE:

EL132

3RD FLOOR INTERSTITIAL LIGHTING PLAN

1/8" = 1'-0"

8'0 4' 16'

SCALE:1/8"=1'-0"

P V A D

U

V A

R i c h m o n d

L a b D r a w i n g s E l e c t r i c a l V A D

U

R I C H

M O

B

E L

L i g h t i n g

P l a n d w g

P M

A R l l b l e e d

E x

I n c h e s

1. ANY LIGHT FIXTURE SUBSTITUTION REQUESTS WILL REQUIRE THE SUBMITTAL

OF PHOTOMETRIC VALUES OF AFFECTED SPACES FOR VERIFICATION OF

PROPER LIGHTING LEVELS TO ENSURE THE DESIGN INTENT IS MAINTAINED.

2. PROVIDE UL 924-LISTED EQUIPMENT WHERE TRANSFERRING POWER FROM

NORMAL TO EMERGENCY DURING A POWER LOSS.

LUMINAIRE SCHEDULE

TYPE LAMPS DESCRIPTION VOLTAGE

WATTS

MANUFACTURER CATALOG NO.

A LED 2'x4' LED 120-277V 48.1W

PHILIPS 2DLG49L835-4-D-UNV-DIM

D LED 6" LED DOWNLIGHT 120-277V

20.5W

PATHWAY 6VLED150035K/64LEDMDSCLPF

F LED RESTROOM; WALL MOUNT VANITY LIGHT 120-277V

40W

WILLIAMS WMAUD-2-L15/835D

G LED RECESSED CLEAN ROOM 2'x4' LED 120-277V 109.8W

FAIL-SAFE CLM-24-4INS-A12125-LD3-3STD-35-UNV-ED1C

OR APPROVED EQUAL

H LED 1'x4' LED 120-277V 21W

PHILIPS 1DLG27L835-4-D-UNV-DIM

Q LED LINEAR LED STRIP WITH WIDE OPTICAL

DISTRIBUTION

120-277V

47.1W

METALUX 4SNLED-LD5-56SL-LC-UNV-L835-CD1-U

R LED INDUSTRIAL, COLD STORAGE, 4' LED LIGHTING

STRIP

120-277V

81W

METALUX 4VT2-LD4-8-FR50-UNV-L835

OR APPROVED EQUAL

S LED 50" LINEAR SURFACE-MOUNT WALL SCONCE

WITH TAMPER-RESISTANT POLYCARBONATE

REFRACTOR.

120-277V

68.3W

FAIL-SAFE FPS-4-LD4-2-STD-35K-OPL-UNV-EDD-1

EXIT LED GREEN EDGE-LIT LED ILLUMINATED EXIT SIGN 120/277V

3W

PHILIPS 44RLU1G

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

VA FORM 08 - 6231

A

F i l e

P a t h

FULLY

SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE:

ARCHITECT/ENGINEER OF RECORD

SEAL

CONSULTANT

321 4 5 6 7 8 9 10

NEW CLINICAL LAB FOR

SURGICAL EXPANSION

RICHMOND, VIRGINIA

652-319

PROJECT DIRECTOR

AUGUST 2018

REVISIONS: DATE:

Group, Inc.

11031 SOUTH PIKES PEAK DRIVE #202

PARKER, COLORADO 80138

PH: 303.841.3922

WWW.AES-GRP.COM

BID DOCUMENTS

DWG. OF 162

NAME: TINA DEBELLA, PE

PHONE: 804.675.5495

EMAIL: Tina.DeBella@va.gov

LIGHTING SCHEDULE AND DETAILS

EL501

MMMGGR

SCALE:

EL501

LIGHTING SCHEDULE

NTS

SCALE:

EL501

EMERGENCY BYPASS DIAGRAM

NTS

P V A D

U

V A

R i c h m o n d

L a b D r a w i n g s E l e c t r i c a l V A D

U

R I C H

M O

B

E L

L i g h t i n g

S c h e d u l e d w g

P M

A R l l b l e e d

E x

I n c h e s

FURNISHED AND INSTALLED BY THE CONTRACTOR.

2. ELECTRICAL GEAR SHOWN FOR LOCATION PURPOSE. REFER TO ONE-LINE

DIAGRAM ON SHEET EP601 FOR EQUIPMENT INTERCONNECTION

REQUIREMENTS.

3. HATCHED AREA SHOWS RELATIVE LOCATION OF NEW LAB AND NEW

ELECTRICAL ROOM ON 3RD FLOOR TO PROVIDE LATERAL DISTANCE

INFORMATION FOR ELECTRICAL RUNS. UTILIZE ELECTRICAL ROOMS FOR

VERTICAL ROUTING AND INTERSTITIAL SPACES FOR LATERAL ROUTING OF

ELECTRICAL CONDUITS WHERE POSSIBLE.

EP101

VAULT-3

NEW LAB ABOVE SEE

GENERAL NOTE 3

NEW

ELECT

RM

ECLDOF

X F

M R

P N

L P

N L

P N

L P

N L

P N

L P

N L

P N

L P

N L

P N

L

A T

S A

T S

A T

S X

F M

R X

F M

R D

IS

C

D

IS

C

SWGR

ECPDOF

ECBCF

TSF

ATS-SF

LIFE

SAFETY #1

EELOF

TEF

EEPDOF

ECBEF

TCF

ATS-CF

CRITICAL

#1

ESLDOF

ESPDOF

ECBSF

EELDOF

SIDE PNL

EEPOF

ATS-EF

EQUIP #1

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

VA FORM 08 - 6231

A

F i l e

P a t h

FULLY

SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE:

ARCHITECT/ENGINEER OF RECORD

SEAL

CONSULTANT

321 4 5 6 7 8 9 10

NEW CLINICAL LAB FOR

SURGICAL EXPANSION

RICHMOND, VIRGINIA

652-319

PROJECT DIRECTOR

AUGUST 2018

REVISIONS: DATE:

Group, Inc.

11031 SOUTH PIKES PEAK DRIVE #202

PARKER, COLORADO 80138

PH: 303.841.3922

WWW.AES-GRP.COM

BID DOCUMENTS

DWG. OF 162

NAME: TINA DEBELLA, PE

PHONE: 804.675.5495

EMAIL: Tina.DeBella@va.gov

BASEMENT

POWER PLAN

EP101

WBRGGR

SCALE:

EP101

BASEMENT POWER PLAN

1/8" = 1'-0"

SCALE:

EP101

TRANSFORMER VAULT-3

ENLARGED POWER PLAN

1/4" = 1'-0"

KEYPLAN

LAB EXPANSION

PLAN

NORTH

N

TN

8'0 4' 16'

SCALE:1/8"=1'-0"

4'0 2' 8'

SCALE:1/4"=1'-0"

P V A D

U

V A

R i c h m o n d

L a b D r a w i n g s E l e c t r i c a l V A D

U

R I C H

M O

B

E P

P o w e r

P l a n d w g

P M

A R l l b l e e d

E x

I n c h e s

FURNISHED AND INSTALLED BY THE CONTRACTOR.

2. ELECTRICAL GEAR SHOWN FOR LOCATION PURPOSE. REFER TO ONE-LINE

DIAGRAM ON SHEET EP401 FOR EQUIPMENT INTERCONNECTION

REQUIREMENTS.

3. HATCHED AREA SHOWS RELATIVE LOCATION OF NEW LAB AND NEW

ELECTRICAL ROOM ON 3RD FLOOR TO PROVIDE LATERAL DISTANCE

INFORMATION FOR ELECTRICAL RUNS. UTILIZE ELECTRICAL ROOMS FOR

VERTICAL ROUTING AND INTERSTITIAL SPACES FOR LATERAL ROUTING OF

ELECTRICAL CONDUITS WHERE POSSIBLE.

ELEC RM

1D-154

NEW LAB ABOVE SEE

GENERAL NOTE 3

EEH1A

NEW

ELECT

RM

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

VA FORM 08 - 6231

A

F i l e

P a t h

FULLY

SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE:

ARCHITECT/ENGINEER OF RECORD

SEAL

CONSULTANT

321 4 5 6 7 8 9 10

NEW CLINICAL LAB FOR

SURGICAL EXPANSION

RICHMOND, VIRGINIA

652-319

PROJECT DIRECTOR

AUGUST 2018

REVISIONS: DATE:

Group, Inc.

11031 SOUTH PIKES PEAK DRIVE #202

PARKER, COLORADO 80138

PH: 303.841.3922

WWW.AES-GRP.COM

BID DOCUMENTS

DWG. OF 162

NAME: TINA DEBELLA, PE

PHONE: 804.675.5495

EMAIL: Tina.DeBella@va.gov

1ST FLOOR

POWER PLAN

EP111

WBRGGR

SCALE:

EP111

1ST FLOOR POWER PLAN

1/8" = 1'-0"

KEYPLAN

LAB EXPANSION

PLAN

NORTH

TN

N

8'0 4' 16'

SCALE:1/8"=1'-0"

P V A D

U

V A

R i c h m o n d

L a b D r a w i n g s E l e c t r i c a l V A D

U

R I C H

M O

B

E P

P o w e r

P l a n d w g

P M

A R l l b l e e d

E x

I n c h e s

KEY NOTES

1. FURNISH AND INSTALL GROUND BAR. CONNECT TO ALL AVAILABLE GROUNDING

POINTS PER NEC REQUIREMENTS. ADD GROUND RODS AS NECESSARY.

2. FURNISH AND INSTALL L6-30R TYPE RECEPTACLE.

3. RELOCATE SIEMENS APTIO AUTOMATION ELECTRICAL GEAR LOCATED IN

ELECTRICAL ROOM 3A-148 TO THIS EQUIPMENT ROOM. ELECTRICAL GEAR

INCLUDES FLOOR MOUNTED UPS, 60kVA;208V-400/231V SPECIAL EQUIPMENT

TRANSFORMER & ASSOCIATED PANELBOARD. RE-FEED TO MAINTAIN EXISTING

POWER SOURCE WHICH IS PANEL LD3AA#1,3,5 LOCATED WITHIN ORIGIN ROOM.

USE (4#4+1#8G)1-1/4"C. PROVIDE A 60-AMP, 3-POLE ENCLOSED CIRCUIT BREAKER

IN-LINE, ADJACENT TO TRANSFORMER, BETWEEN TRANSFORMER AND UPS.

PROVIDE A 40-AMP, 3-POLE ENCLOSED CIRCUIT BREAKER IN-LINE, ADJACENT TO

TRANSFORMER, BETWEEN TRANSFORMER AND APTIO DISCONNECT. REFERENCE

ONE-LINE AND SHEET EP131 FOR ADDITIONAL REQUIREMENTS. PROVIDE RACKING

AND ADJUST LOCATIONS AS REQUIRED TO PROVIDE NEC 110.26 WORKING

CLEARANCE.

4. RELOCATE SIEMENS APTIO AUTOMATION SYSTEM AIR COMPRESSOR FROM ROOM

3A-147 TO EQUIPMENT ROOM. RE-FEED TO MAINTAIN EXISTING POWER SOURCE

WHICH IS PANEL EEL3AC#12,14,16 LOCATED IN ELEC ROOM 3A-148. USE

(4#8+1#10G)1"C. PROVIDE LOCAL LOCKABLE DISCONNECT.

5. PROVIDE CONNECTION FOR AUTOFLUSH AND AUTOSINK POWER. COORDINATE

POWER CONNECTION METHOD WITH EQUIPMENT CONFIGURATION.

6. PROVIDE CONNECTION FOR ROBOT COMMUNICATION SYSTEM POWER.

EQUIPMENT BY VENDOR. PROVIDE 120V, 1Ø POWER SOURCE, CAPPED OFF.

7. PROVIDE GFCI-TYPE RECEPTACLE AT ELEVATION 4 INCHES ABOVE TOP OF SINK

BOWL.

8. PROVIDE DEADFRONT-STYLE GFCI PROTECTION AS REQUIRED TO PROTECT

RECEPTACLES CONNECTED TO THIS CIRCUIT.

9. NOT USED

10. LOCATE DISCONNECT SWITCH ABOVE THE GROUND BAR LOCATION. MOUNT

GROUND BAR SO IT DOES NOT AFFECT EQUIPMENT CLEARANCE AT DISCONNECT.

11. PROVIDE RECEPTACLES FOR ACCESS CONTROL PANELS IN EXISTING MICU

BIOMED ROOM. COORDINATE WITH TELECOM SHEET TN132.

12. PROVIDE SWITCH AND CIRCUIT AS REQUIRED TO TOGGLE TOILET AND SINK

FIXTURES BETWEEN OPERABLE AND NON-OPERABLE STATES.

13. BASE BID:BOLD DASHED BOUNDARY INDICATES EQUIPMENT TO BE INSTALLED,

EXCEPT FOR PORTIONS IDENTIFIED AS PART OF A DEDUCTIVE BID ALTERNATE.

VERIFY IF THIS EQUIPMENT IS TO BE INSTALLED PRIOR TO COMMENCEMENT OF

WORK. ELECTRICAL INFRASTRUCTURE IN THIS BOUNDARY IS INCLUDED UNDER

THE BASE BID.

14. DEDUCTIVE BID ALTERNATE 4: ELECTRICAL INFRASTRUCTURE ON THIS SHEET IN

THIS BOUNDARY IS EXCLUDED UNDER DEDUCTIVE BID ALTERNATE 4. REFERENCE

EP131.2 FOR ADDITIONAL REQUIREMENTS.

15. DEDUCTIVE BID ALTERNATE 5: ELECTRICAL INFRASTRUCTURE ON THIS SHEET IN

THIS BOUNDARY IS EXCLUDED UNDER DEDUCTIVE BID ALTERNATE 5. REFERENCE

EP131.2 FOR ADDITIONAL REQUIREMENTS.

16. DEDUCTIVE BID ALTERNATE 6: ELECTRICAL INFRASTRUCTURE ON THIS SHEET IN

THIS BOUNDARY IS EXCLUDED UNDER DEDUCTIVE BID ALTERNATE 6. REFERENCE

EP131.2 FOR ADDITIONAL REQUIREMENTS.

17. PROVIDE DOORBELL SYSTEM PUSH BUTTON +48" AFF. SEE 5/EP132 FOR

ADDITIONAL REQUIREMENTS.

18. PROVIDE POWER CONNECTION, RACEWAYS, AND ENCLOSURES FOR PACS

SYSTEM AT THIS LOCATION. SEE 3/TN502 AND 7/TN502 FOR ADDITIONAL

REQUIREMENTS. PROVIDE PACS SYSTEM MATCHING HOSPITAL STANDARD.

19. BASE BID:SAME AS KEY NOTE#18, EXCEPT NO POWER CONDUCTORS OR PACS

COMPONENTS.

DEDUCTIVE BID ALTERNATE #2: OMIT PACS SYSTEM FROM DOOR IDENTIFIED IN

ENTIRETY.

20. PROVIDE SPLIT-YOKE DUPLEX RECEPTACLE(S), WITH TOP HALF

OCCUPANCY-SWITCHED PER ASHRAE 90.1.

1.

2.

3.

4.

5.

6.

7.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

GFCI, AC

AC

GFCI, AC

GFCI

GFCI

GFCI

GFCI

GFCI, AC

GFCI, AC

GFCI

GFCI, AC

GFCI

XFMR

PANEL

UPS

AIR COMP.

J6

J J

5J 5 GFCI, AC

PANEL 3F-NL1

CIRCUIT #53

PANEL 3F-NL1

CIRCUIT #51

PANEL 3F-NL1

CIRCUIT #55

7 7

PANEL 3F-NL1

CIRCUIT #59

PANEL 3F-NL1

CIRCUIT #61

PACS

PANEL 3F-NL1

CIRCUIT #69

J

J

PANEL 3F-NL1

CIRCUIT #79,81

PANEL 3F-NL1

CIRCUIT #57

PANEL 3F-NL1

CIRCUIT #49

PANEL 3F-NL1

CIRCUIT #71

PANEL 3F-NL1

CIRCUIT #41

PANEL 3F-NL1

CIRCUIT #19

PANEL 3F-NL1

CIRCUIT #18

PANEL 3F-NL1

CIRCUIT #12

PANEL 3F-NL1

CIRCUIT #83

PANEL 3F-NL1

CIRCUIT #21

PANEL 3F-NL2

CIRCUIT #30

JPANEL 3F-ESP1

CIRCUIT #2

J

PANEL 3F-ESP1

CIRCUIT #4

PANEL 3F-EEL2

CIRCUIT #83

J J

PANEL 3F-NL1

CIRCUIT #43

PANEL 3F-NL1

CIRCUIT #23

PANEL 3F-NL1

CIRCUIT #47

PANEL 3F-NL1

CIRCUIT #14

PANEL 3F-NL1

CIRCUIT #10

PANEL 3F-NL1

CIRCUIT #45

CORRIDOR

C3F-1

CORRIDOR

C3F-2

BIOMED

3F-101

ANCILLARY TESTING

3F-103

DRUG TESTING

3F-105

IMMUNOLOGY

3F-107

IT CLOSET

ACCESSIONING

3F-106a

FEE BASIS

3F-106b

MICROBIOLOGY

3F-106d

HEMATOLOGY

3F-106e

CHEMISTRY

3F-106f

REFRIGERATEDSTORAGE

3F-126

BLOOD BANK

3F-106c

CYTOLOGY

3F-106h

OPEN OFFICE

3F-106j

ARCHIVE

3F-124

CLEAN SUPPLY

3F-131

BSL-3 LAB

3F-129

MEN'S TOILET

3F-109

WOMEN'S TOILET

3F-111

STAFF TOILET

3F-108

DRUG TESTING TOILET

3F-105a

JANITOR

3F-110

EQUIPMENT ROOM

3F-130

FLAMMABLE STORAGE

3F-125

ANTE ROOM

3F-128

BREAK ROOM

3F-112

CORRIDOR

C3F-3

OFFICE #1

3F-114

OFFICE #2

3F-115

OFFICE #3

3F-116

OFFICE #4

3F-117

OFFICE #5

3F-118

ADMINISTRATION

3F-120

DIRECTOR'S OFFICE

3F-121

CMT OFFICE

3F-122

OFFICE #6

3F-123

ADPAC/RESIDENTS

3F-119

HISTOLOGY

3F-106g

GAS TANK ROOM

3F-127

STAIR

3F-S2

CONF ROOM

3F-113

DEDUCTIVE BID

ALTERNATE 5

DEDUCTIVE BID

ALTERNATE 4

DEDUCTIVE BID

ALTERNATE 6

13 16 13 14

P

F

PF

R E

F

R E

F

P F

P F

P

F

PF

J 17

M

PANEL 3F-EEL2

CIRCUIT #27

PANEL 3F-EEL2

CIRCUIT #29

ECB ECB

18 18

18 18

19 19

19 19

19 1919

13 16

13 16

13 14

PANEL 3F-NL1

CIRCUIT #63

PANEL 3F-NL2

CIRCUIT #6 (PART)

GENERAL NOTES

1. EQUIPMENT SHOWN WITH BOLD LINEWEIGHTS INDICATES EQUIPMENT TO BE

FURNISHED AND INSTALLED BY THE CONTRACTOR.

2. ELECTRICAL GEAR SHOWN FOR LOCATION PURPOSE. REFER TO ONE-LINE

DIAGRAM ON SHEET EP401 FOR EQUIPMENT INTERCONNECTION REQUIREMENTS.

3. MAINTAIN NEC REQUIRED CLEARANCES DURING INSTALLATION OF NEW

ELECTRICAL GEAR. PROVIDE STRUT RACKING AS REQUIRED FOR COMPLIANCE.

4. ANY FLOOR MOUNTED ELECTRICAL GEAR SHALL BE INSTALLED ON AN

EQUIPMENT PAD, 4" MINIMUM THICKNESS.

5. EQUIPMENT FOR BOTH THE BASE BID AND DEDUCTIVE BID ALTERNATES ARE

SHOWN ON THE PLANS.

6. ALL WIRE RUNS SHOWN ON DRAWINGS ARE RUN THROUGH THE SPACE ABOVE

THE CEILING GRID ON THIS FLOOR. LOCATE PRE-FURNITURE INFRASTRUCTURE

AS REQUIRED TO FEED FURNITURE SHOWN ON TN131 AFTER FURNITURE IS

INSTALLED.

7. MOUNT CEILING - MOUNTED AND POWER-POLE JUNCTION BOXES CONCEALED,

WITHIN THE ABOVE - CEILING SPACE.

3F-EEL2

3F-TN1

3F-NH1

3F-EEP1

3F-TEE13F-TEE2

3F-EEL1

3F-ESP1

3F-NL1

3F-NL2

DS-EEP1

3F-NL1-ECB

+48"

AFF

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED DRAWN

DRAWING TITLE

VA FORM 08 - 6231

A

F i l e

P a t h

FULLY

SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE:

ARCHITECT/ENGINEER OF RECORD

SEAL

CONSULTANT

321 4 5 6 7 8 9 10

NEW CLINICAL LAB FOR

SURGICAL EXPANSION

RICHMOND, VIRGINIA

652-319

PROJECT DIRECTOR

AUGUST 2018

REVISIONS: DATE:

Group, Inc.

11031 SOUTH PIKES PEAK DRIVE #202

PARKER, COLORADO 80138

PH: 303.841.3922

WWW.AES-GRP.COM

BID DOCUMENTS

DWG. OF 162

NAME: TINA DEBELLA, PE

PHONE: 804.675.5495

EMAIL: Tina.DeBella@va.gov

3RD FLOOR POWER PLAN

POST FURNITURE CONSTRUCTION

EP131

WBRGGR

SCALE:

EP131

POST FURNITURE CONSTRUCTION

3RD FLOOR POWER PLAN

1/8" = 1'-0"

SCALE:

EP131

ENLARGED PLAN

ELEC CLOS 3F103

1/2" = 1'-0"

KEYPLAN

LAB EXPANSION

PLAN

NORTH

N

TN

8'0 4' 16'

SCALE:1/8"=1'-0"

2' 4'0 1'

SCALE:1/2"=1'-0"

EP132

EP132

EP133

EP133

EP132

EP132

EP132

EP132

EP132

EP131

P V A D

U

V A

R i c h m o n d

L a b D r a w i n g s E l e c t r i c a l V A D

U

R I C H

M O

B

E P

P o w e r

P l a n d w g

P M

A R l l b l e e d

E x

I n c h e s

# KEY NOTES

1. FURNISH AND INSTALL GROUND BAR. CONNECT TO ALL AVAILABLE GROUNDING

POINTS PER NEC REQUIREMENTS. ADD GROUND RODS AS NECESSARY.

2. FURNISH AND INSTALL L6-30R TYPE RECEPTACLE.

3. RELOCATE SIEMENS APTIO AUTOMATION ELECTRICAL GEAR LOCATED IN

ELECTRICAL ROOM 3A-148 TO THIS EQUIPMENT ROOM. ELECTRICAL GEAR

INCLUDES FLOOR MOUNTED UPS, 60kVA;208V-400/231V SPECIAL EQUIPMENT

TRANSFORMER & ASSOCIATED PANELBOARD. RE-FEED TO MAINTAIN EXISTING

POWER SOURCE WHICH IS PANEL LD3AA#1,3,5 LOCATED WITHIN ORIGIN ROOM.

USE (4#4+1#8G)1-1/4"C. PROVIDE A 60-AMP, 3-POLE ENCLOSED CIRCUIT BREAKER

IN-LINE, ADJACENT TO TRANSFORMER, BETWEEN TRANSFORMER AND UPS.

PROVIDE A 40-AMP, 3-POLE ENCLOSED CIRCUIT BREAKER IN-LINE, ADJACENT TO

TRANSFORMER, BETWEEN TRANSFORMER AND APTIO DISCONNECT. REFERENCE

ONE-LINE AND SHEET EP131 FOR ADDITIONAL REQUIREMENTS. PROVIDE RACKING

AND ADJUST LOCATIONS AS REQUIRED TO PROVIDE NEC 110.26 WORKING

CLEARANCE.

4. RELOCATE SIEMENS APTIO AUTOMATION SYSTEM AIR COMPRESSOR FROM ROOM

3A-147 TO EQUIPMENT ROOM. RE-FEED TO MAINTAIN EXISTING POWER SOURCE

WHICH IS PANEL EEL3AC#12,14,16 LOCATED IN ELEC ROOM 3A-148. USE

(4#8+1#10G)1"C. PROVIDE LOCAL LOCKABLE DISCONNECT.

5. PROVIDE CONNECTION FOR AUTOFLUSH AND AUTOSINK POWER. COORDINATE

POWER CONNECTION METHOD WITH EQUIPMENT CONFIGURATION.

6. PROVIDE CONNECTION FOR ROBOT COMMUNICATION SYSTEM POWER.

EQUIPMENT BY VENDOR. PROVIDE 120V, 1Ø POWER SOURCE, CAPPED OFF.

7. PROVIDE GFCI-TYPE RECEPTACLE AT ELEVATION 4 INCHES ABOVE TOP OF SINK

BOWL.

8. PROVIDE DEADFRONT-STYLE GFCI PROTECTION AS REQUIRED TO PROTECT

RECEPTACLES CONNECTED TO THIS CIRCUIT.

9. NOT USED

10. LOCATE DISCONNECT SWITCH ABOVE THE GROUND BAR LOCATION. MOUNT

GROUND BAR SO IT DOES NOT AFFECT EQUIPMENT CLEARANCE AT DISCONNECT.

11. PROVIDE RECEPTACLES FOR ACCESS CONTROL PANELS IN EXISTING MICU

BIOMED ROOM. COORDINATE WITH TELECOM SHEET TN132.

12. PROVIDE SWITCH AND CIRCUIT AS REQUIRED TO TOGGLE TOILET AND SINK

FIXTURES BETWEEN OPERABLE AND NON-OPERABLE STATES.

13. BASE BID:BOLD DASHED BOUNDARY INDICATES EQUIPMENT TO BE INSTALLED,

EXCEPT FOR PORTIONS IDENTIFIED AS PART OF A DEDUCTIVE BID ALTERNATE.

VERIFY IF THIS EQUIPMENT IS TO BE INSTALLED PRIOR TO COMMENCEMENT OF

WORK. ELECTRICAL INFRASTRUCTURE IN THIS BOUNDARY IS INCLUDED UNDER

THE BASE BID.

14. DEDUCTIVE BID ALTERNATE 4: ELECTRICAL INFRASTRUCTURE ON THIS SHEET IN

THIS BOUNDARY IS EXCLUDED UNDER DEDUCTIVE BID ALTERNATE 4. REFERENCE

EP131.2 FOR ADDITIONAL REQUIREMENTS.

15. DEDUCTIVE BID ALTERNATE 5: ELECTRICAL INFRASTRUCTURE ON THIS SHEET IN

THIS BOUNDARY IS EXCLUDED UNDER DEDUCTIVE BID ALTERNATE 5. REFERENCE

EP131.2 FOR ADDITIONAL REQUIREMENTS.

16. DEDUCTIVE BID ALTERNATE 6: ELECTRICAL INFRASTRUCTURE ON THIS SHEET IN

THIS BOUNDARY IS EXCLUDED UNDER DEDUCTIVE BID ALTERNATE 6. REFERENCE

EP131.2 FOR ADDITIONAL REQUIREMENTS.

17. PROVIDE DOORBELL SYSTEM PUSH BUTTON +48" AFF. SEE 5/EP132 FOR

ADDITIONAL REQUIREMENTS.

18. PROVIDE POWER CONNECTION, RACEWAYS, AND ENCLOSURES FOR PACS

SYSTEM AT THIS LOCATION. SEE 3/TN502 AND 7/TN502 FOR ADDITIONAL

REQUIREMENTS. PROVIDE PACS SYSTEM MATCHING HOSPITAL STANDARD.

19. BASE BID:SAME AS KEY NOTE#18, EXCEPT NO POWER CONDUCTORS OR PACS

COMPONENTS.

DEDUCTIVE BID ALTERNATE #2: OMIT PACS SYSTEM FROM DOOR IDENTIFIED IN

ENTIRETY.

20. PROVIDE SPLIT-YOKE DUPLEX RECEPTACLE(S), WITH TOP HALF

OCCUPANCY-SWITCHED PER ASHRAE 90.1.

GFCI, AC

AC

GFCI, AC

GFCI

GFCI

GFCI

GFCI

GFCI, AC

GFCI, AC

GFCI

GFCI, AC

GFCI

XFMR

PANEL

UPS

AIR COMP.

J6

J J

5J 5 GFCI, AC

PANEL 3F-NL1

CIRCUIT #53

PANEL 3F-NL1

CIRCUIT #51

PANEL 3F-NL1

CIRCUIT #55

7 7

PANEL 3F-NL1

CIRCUIT #59

PANEL 3F-NL1

CIRCUIT #61

PACS

PANEL 3F-NL1

CIRCUIT #69

J

J

PANEL 3F-NL1

CIRCUIT #79,81

PANEL 3F-NL1

CIRCUIT #57

PANEL 3F-NL1

CIRCUIT #49

PANEL 3F-NL1

CIRCUIT #71

PANEL 3F-NL1

CIRCUIT #41

PANEL 3F-NL1

CIRCUIT #19

PANEL 3F-NL1

CIRCUIT #18

PANEL 3F-NL1

CIRCUIT #12

PANEL 3F-NL1

CIRCUIT #83

PANEL 3F-NL1

CIRCUIT #21

PANEL 3F-NL2

CIRCUIT #30

JPANEL 3F-ESP1

CIRCUIT #2

J

PANEL 3F-ESP1

CIRCUIT #4

PANEL 3F-EEL2

CIRCUIT #83

J J

PANEL 3F-NL1

CIRCUIT #43

PANEL 3F-NL1

CIRCUIT #23

PANEL 3F-NL1

CIRCUIT #47

PANEL 3F-NL1

CIRCUIT #14

PANEL 3F-NL1

CIRCUIT #10

PANEL 3F-NL1

CIRCUIT #45

CORRIDOR

C3F-1

CORRIDOR

C3F-2

BIOMED

3F-101

ANCILLARY TESTING

3F-103

DRUG TESTING

3F-105

IMMUNOLOGY

3F-107

IT CLOSET

ACCESSIONING

3F-106a

FEE BASIS

3F-106b

MICROBIOLOGY

3F-106d

HEMATOLOGY

3F-106e

CHEMISTRY

3F-106f

REFRIGERATEDSTORAGE

3F-126

BLOOD BANK

3F-106c

CYTOLOGY

3F-106h

OPEN OFFICE

3F-106j

ARCHIVE

3F-124

CLEAN SUPPLY

3F-131

BSL-3 LAB

3F-129

MEN'S TOILET

3F-109

WOMEN'S TOILET

3F-111

STAFF TOILET

3F-108

DRUG TESTING TOILET

3F-105a

JANITOR

3F-110

EQUIPMENT ROOM

3F-130

FLAMMABLE STORAGE

3F-125

ANTE ROOM

3F-128

BREAK ROOM

3F-112

CORRIDOR

C3F-3

OFFICE #1

3F-114

OFFICE #2

3F-115

OFFICE #3

3F-116

OFFICE #4

3F-117

OFFICE #5

3F-118

ADMINISTRATION

3F-120

DIRECTOR'S OFFICE

3F-121

CMT OFFICE

3F-122

OFFICE #6

3F-123

ADPAC/RESIDENTS

3F-119

HISTOLOGY

3F-106g

GAS TANK ROOM

3F-127

STAIR

3F-S2

CONF ROOM

3F-113

DEDUCTIVE BID

ALTERNATE 5

DEDUCTIVE BID

ALTERNATE 4

DEDUCTIVE BID

ALTERNATE 6

13 16 13 14

P

F

PF

R E

F

R E

F

P F

P F

P

F

PF

J 17

M

PANEL 3F-EEL2

CIRCUIT #27

PANEL 3F-EEL2

CIRCUIT #29

ECB ECB

18 18

18 18

19 19

19 19

19 1919

13 16

13 16

13 14

PANEL 3F-NL1

CIRCUIT #63

PANEL 3F-NL2

CIRCUIT #6 (PART)

3F-EEL2

3F-TN1

3F-NH1

3F-EEP1

3F-TEE13F-TEE2

3F-EEL1

3F-ESP1

3F-NL1

3F-NL2

DS-EEP1

3F-NL1-ECB

+48"

AFF

GENERAL NOTES

1. EQUIPMENT SHOWN WITH BOLD LINEWEIGHTS INDICATES EQUIPMENT TO BE

FURNISHED AND INSTALLED BY THE CONTRACTOR.

2. ELECTRICAL GEAR SHOWN FOR LOCATION PURPOSE. REFER TO ONE-LINE

DIAGRAM ON SHEET EP401 FOR EQUIPMENT INTERCONNECTION REQUIREMENTS.

3. MAINTAIN NEC REQUIRED CLEARANCES DURING INSTALLATION OF NEW

ELECTRICAL GEAR. PROVIDE STRUT RACKING AS REQUIRED FOR COMPLIANCE.

4. ANY FLOOR MOUNTED ELECTRICAL GEAR SHALL BE INSTALLED ON AN

EQUIPMENT PAD, 4" MINIMUM THICKNESS.

5. EQUIPMENT FOR BOTH THE BASE BID AND DEDUCTIVE BID ALTERNATES ARE

SHOWN ON THE PLANS.

6. ALL WIRE RUNS SHOWN ON DRAWINGS ARE RUN THROUGH THE SPACE ABOVE

THE CEILING GRID ON THIS FLOOR.