This solicitation seeks construction services for a new clinical lab expansion project located at a VA medical center. The project involves a partial renovation and 18,050 square foot addition. Services include all labor, materials, equipment, transportation and supervision. Drawings and specifications will be provided on August 15, 2019. A pre-proposal conference will be held on an unspecified date. Questions must be emailed to the Contracting Officer by the stated deadline. The NAICS code is 236220 and the estimated cost is between $5-10 million. The performance period is 680 calendar days. This opportunity is 100% set aside for SDVOSBs. Offers will only be accepted from qualified SDVOSB concerns.
36C24619B0039 S02 ELECTRICAL_Bid Documents.pdf
View the file
Other files for this federal contract opportunity
Show all 39
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. COMPLY WITH ALL CURRENT APPLICABLE CODES AND
STANDARDS.
2. PROVIDE SEALANT AROUND ALL ELECTRICAL OUTLETS, PLUMBING
FIXTURES, PIPING, AND EQUIPMENT ABUTTING OR PENETRATING A
WALL OR PARTITION INCLUDING FIRESTOPPING AT FIRE RATED
ASSEMBLES.
3. CONDUIT SHALL BE CONTINUOUS AND COMPLETE BETWEEN
PANELS, JUNCTION, OUTLET, PULL AND FIXTURE BOXES. IT SHALL
BE KEPT CLEAN AND UNOBSTRUCTED INSIDE WITH ENDS FREE OF
BURRS AND OTHER PROJECTIONS WHICH WOULD DAMAGE OR
IMPEDE PULLING OF WIRE. ALL CONDUIT SHALL BE INSTALLED
PARALLEL AND PERPENDICULAR TO THE BUILDING LINES. ALL
CONDUIT SHALL BE ROUTED CONCEALED IN FINISHED AREAS
EXCEPT WHERE OTHERWISE NOTED.
4. UNLESS OTHERWISE NOTED, ALL WIRES AND CABLES SHALL BE
CONTINUOUS WITHOUT SPLICES OR TAPS IN CONDUIT RUNS. ALL
WIRING SHALL BE IN CONDUIT OR AS NOTED. ALL SPLICES SHALL
BE MADE AT OUTLET BOXES, PULL BOXES OR JUNCTION BOXES. AT
ALL JOINTS, CONDUCTORS SHALL BE SPLICED OR JOINED AS TO
BE MECHANICALLY AND ELECTRICALLY SECURE.
5. IDENTIFICATION OF NEUTRAL, GROUNDING OF CIRCUITS, NUMBER
OF WIRES IN CONDUIT SHALL COMPLY IN ALL RESPECTS WITH THE
REQUIREMENTS OF THE NEC.
6. WIRE SHALL NOT BE INSTALLED IN CONDUIT UNTIL ALL WORK
WHICH COULD CAUSE INJURY TO THE CONDUCTORS IS COMPLETE.
7. ALL MATERIAL SHALL CONFORM TO NEMA, ANSI AND U.S.
STANDARDS, WHICHEVER APPLIES AND SHALL BEAR THE
INSPECTION LABEL OF UNDERWRITER LABORATORIES, INC.
8. ALL BOXES AND ENCLOSURES SHALL BE SET PLUMB, SQUARE AND
SECURELY FASTENED. BOXES IN FINISHED WALLS SHALL BE FLUSH
WITH FINISH SURFACE. ALL PULL AND JUNCTION BOXES SHALL BE
SIZED PER NEC ARTICLE 314.
9. PROVIDE GROUNDING AND BONDING OF ALL METAL RACEWAYS AS
REQUIRED BY NEC.
10.PROVIDE NEW TYPEWRITTEN DIRECTORIES FOR ALL PANELS
INSTALLED UNDER THIS CONTRACT.
11. ALL ELECTRICAL WORK SHALL BE IN STRICT COMPLIANCE WITH
THE CURRENT EDITION OF THE NEC AS ADOPTED BY THE
AUTHORITY HAVING JURISDICTION INCLUDING ANY AMENDMENTS,
ORDINANCES, AND INTERPRETATIONS. ELECTRICAL WORK SHALL
ALSO COMPLY WITH ANY APPLICABLE FEDERAL AND STATE
REGULATIONS.
12.COORDINATE INSTALLATION OF CONDUIT WITH OTHER TRADES
AND EQUIPMENT SUPPLIERS AS REQUIRED PRIOR TO ROUGH-IN.
13.PROVIDE AND MAINTAIN ELECTRICAL SAFETY AND WORKING
CLEARANCES IN FRONT OF AND AROUND ALL ELECTRICAL PANELS
AND DISTRIBUTION EQUIPMENT IN ACCORDANCE WITH NEC.
14.ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR CUTTING
AND CORE DRILLING ALL PENETRATIONS THROUGH FLOORS,
WALLS, ETC.
15.IT IS NOT INTENDED THAT THE PLANS INDICATE ALL CONDUIT
ROUTES, PULL BOXES, ETC. ELECTRICAL CONTRACTOR SHALL BE
RESPONSIBLE FOR DETERMINING ACTUAL CONDUIT ROUTING,
QUANTITY, AND LOCATION OF PULL BOXES WITHIN ACCESSIBLE
LOCATIONS. PROVIDE SCREW-COVER PULL BOXES IN CONDUIT
RUNS AS REQUIRED TO LIMIT NUMBER OF BENDS TO NO MORE
THAN THREE (3) OR 270 DEGREES TOTAL. SIZE PULL BOXES IN
ACCORDANCE WITH NEC. DOCUMENT ON RECORD DRAWINGS THE
SIZE AND LOCATION OF PULL BOXES USED IN FEEDER CONDUIT
RUNS.
16.REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION ABOUT
QUALITY AND GENERAL INSTALLATION REQUIREMENTS OF
ELECTRICAL CONSTRUCTION MATERIALS, ITEMS, AND DEVICES.
17.CONDUIT RUNS ARE SHOWN FOR REFERENCE AND BIDDING
PURPOSES ONLY. CONTRACTOR SHALL VERIFY EXISTING FIELD
CONDITIONS AND DETERMINE SHORTEST AND LEAST DISRUPTIVE
ROUTE FOR CONDUIT RUNS. COORDINATE WITH OTHER TRADES
AND CONFIRM ROUTE SELECTION WITH OWNER PRIOR TO BID. ANY
DEVIATIONS FROM DRAWINGS SHALL BE SHOWN IN DETAIL ON
AS-BUILT DRAWINGS BY CONTRACTOR.
18.FOR QUALITY ASSURANCE, ALL ELECTRICAL EQUIPMENT SHALL BE
UL LISTED AND APPROVED. ALSO, PERFORM WORK IN
ACCORDANCE WITH THE NATIONAL ELECTRICAL CONTRACTOR
ASSOCIATION (NECA) "STANDARD OF INSTALLATION."
19.ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. SIZE AND LOCATION
OF EQUIPMENT AND WIRING ARE SHOWN TO SCALE WHERE
POSSIBLE, BUT MAY BE DISTORTED FOR CLARITY ON THE
DRAWINGS. FINAL LOCATIONS OF OUTLETS AND EQUIPMENT
SHALL BE AS SHOWN IN ENLARGED DETAILS OR AS APPROVED BY
THE COR.
20.THE PLANS DO NOT INDICATE ALL THE NECESSARY BENDS,
OFFSETS, PULL BOXES AND OBSTRUCTIONS. IT SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR TO INSTALL HIS WORK TO
CONFORM TO THE STRUCTURE, MAINTAIN HEADROOM AND KEEP
OPENINGS AND PASSAGEWAYS CLEAR.
21.GROUNDING OF THE ELECTRICAL SYSTEM SHALL BE BY MEANS OF
A GREEN INSULATED GROUNDING CONDUCTOR INSTALLED WITH
FEEDER CONDUCTORS IN ALL CONDUITS WHETHER OR NOT
INDICATED ON DRAWINGS. GROUNDING CONDUCTORS SHALL BE
PROVIDE GROUNDING CONDUCTOR IN ALL TELEPHONE AND CATV
SERVICE CONDUITS.
22.PROVIDE ALL CUTTING AND PATCHING REQUIRED FOR THE
PROPER INSTALLATION OF THE NEW ELECTRICAL WORK. ALL
PATCHING SHALL BE OF THE SAME MATERIALS, WORKMANSHIP,
AND FINISH AND SHALL ACCURATELY MATCH ALL ADJACENT
WORK.
23.CLEAN UP RESULTANT DEBRIS FROM THIS WORK AND REMOVE
FROM THE SITE. DISCONNECT AND REMOVE ALL TEMPORARY
POWER INCLUDING BUT, NOT LIMITED TO PANELS, FIXTURES,
BOXES AND WIRING.
24.TEST FOR GROUNDS AND SHORTS, TO ENSURE PROPER
OPERATION OF ELECTRICAL EQUIPMENT. REPAIR OR REPLACE
FAULTY EQUIPMENT AT NO ADDITIONAL COST TO THE VA.
25.CONTRACTOR TO NOTE THAT WHEN A SPECIFIC DIRECTION IS
SPECIFIED SUCH AS "EAST", THAT DIRECTION IS "PLAN EAST" AND
NOT "TRUE EAST".
26.LETTERS SUCH AS "WP", "GFCI" ADJACENT TO ANY SYMBOL
INDICATE SPECIAL CONSTRUCTION IS REQUIRED. SEE
ABBREVIATIONS FOR DEFINITIONS.
27.SIZES OF WIRE AND CABLE ARE BASED ON COPPER CONDUCTORS.
ALUMINUM CONDUCTORS ARE NOT ACCEPTABLE.
28.ELEVATIONS FOR ELECTRICAL EQUIPMENT ARE SHOWN TO
CENTER OF DEVICE OR ENCLOSURE UNLESS NOTED OTHERWISE.
29.RECEPTACLES AND TELE/DATA JACKS SHALL BE LOCATED 18" AFF
UNLESS NOTED OTHERWISE. LIGHT SWITCHES SHALL BE LOCATED
48" AFF UNLESS NOTED OTHERWISE.
30.REFER TO "UTILITIES" DRAWINGS FOR EXACT PLACEMENT OF
EQUIPMENT AND LOCATIONS OF ELECTRICAL EQUIPMENT NOT
OTHERWISE SHOWN ON ELECTRICAL DRAWINGS. (CIVIL
DRAWINGS).
31.ALL PANELBOARD LOCKS SHALL BE KEYED TO MATCH EXISTING
SITE KEYING. COORDINATE WITH COR AND VAMC'S SFIC
DEPARTMENT FOR EXACT REQUIREMENTS.
32.LABEL ALL ELECTRICAL EQUIPMENT WITH THEIR SOURCE OF
ELECTRICAL SUPPLY, EXCEPT BRANCH-CIRCUIT DEVICES, WHICH
SHALL BE LABELED WITH THEIR CIRCUIT DESIGNATION - INCLUDING
PANEL NAME AND CIRCUIT BREAKER NUMBERS.
33.COORDINATE WITH COR AND ARRANGE FOR ELECTRICIAN
SUPERVISOR OVERSIGHT IN ADVANCE OF WORKING ON ESSENTIAL
ELECTRICAL SYSTEM (EES) EQUIPMENT OR SWITCHGEAR. SUCH
OVERSIGHT IS MANDATORY FOR WORKING ON THESE
CATEGORIES OF EQUIPMENT.
34.PROJECT INCLUDES REQUIREMENTS FOR 30-DAY LOAD STUDIES
PRIOR TO CONNECTING LOAD. CONTRACTOR SHALL DELAY
BUILDING CONNECTIONS TO LAB ELECTRICAL ROOM UNTIL AFTER
STUDY CONFIRMS ADEQUATE CAPACITY FOR NEW LOAD.
35.FOR ABBREVIATIONS AND SYMBOLS, SEE SHEETS EP002 AND
EP603.
36.REFERENCE SHEET PL602 FOR PNEUMATIC TUBE SYSTEM DETAILS.
37.INCLUDE WITHIN BID COST TO PROVIDE 3 ADDITIONAL 20-AMP
CIRCUITS, AN ADDITIONAL 30-AMP CIRCUIT, AND AN ADDITIONAL
50-AMP CIRCUIT, INCLUDING ALL MOBILIZATION, CONNECTIONS,
RECEPTACLES, AND AS OTHERWISE REQUIRED TO MOVE OR
PROVIDE NEW CONNECTIONS TO EQUIPMENT NOT SHOWN ON
PLANS. ALSO INCLUDE DEMOLITION WHERE RELOCATION IS
REQUIRED. SUCH CIRCUITS SHALL BE EITHER THREE-PHASE, OR
SINGLE PHASE, AND DIRECTION FOR THESE CIRCUITS WILL OCCUR
AFTER FURNITURE INSTALLATION HAS BEGUN. PATCH AND
REFINISH SURFACES ASSOCIATED WITH DEMOLITION.
38.(PART) ANNOTATION INDICATES MULTIPLE CONNECTIONS TO THE
SAME HOMERUN. CONNECT TO IDENTIFIED CIRCUIT BEFORE
ENTERING PANELBOARD.
GENERAL NOTES
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
F i l e
P a t h
FULLY
SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:
ARCHITECT/ENGINEER OF RECORD
SEAL
CONSULTANT
321 4 5 6 7 8 9 10
NEW CLINICAL LAB FOR
SURGICAL EXPANSION
RICHMOND, VIRGINIA
652-319
PROJECT DIRECTOR
AUGUST 2018
REVISIONS: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF 162
NAME: TINA DEBELLA, PE
PHONE: 804.675.5495
EMAIL: Tina.DeBella@va.gov
ELECTRICAL
GENERAL NOTES
EP001
MMMGGR
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
F i l e
P a t h
FULLY
SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:
ARCHITECT/ENGINEER OF RECORD
SEAL
CONSULTANT
321 4 5 6 7 8 9 10
NEW CLINICAL LAB FOR
SURGICAL EXPANSION
RICHMOND, VIRGINIA
652-319
PROJECT DIRECTOR
AUGUST 2018
REVISIONS: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF 162
NAME: TINA DEBELLA, PE
PHONE: 804.675.5495
EMAIL: Tina.DeBella@va.gov
P V A D
U
V A
R i c h m o n d
L a b D r a w i n g s E l e c t r i c a l V A D
U
R I C H
M O
N D
L A B
E P X
G e n e r a l d w g
P M
A R C H f u l l b l e e d
E x
I n c h e s
INDICATES QUANTITY OF DUCTS (4" MIN. IF NOT IDENTIFIED,
ASSEMBLY - TYPE AND NUMBER DESIGNATION AS INDICATED:
SEC, - SECONDARY RACK MOUNTED EQUIPMENT
STREET LIGHTING, DIRECT BURIAL DUCT LINE
EXISTING PAD MOUNTED TRANSFORMER
UNDERGROUND DUCT LINE, CONCRETE ENCASED NUMERAL
VOLTAGE (POTENTIAL) TRANSFORMER (VT/PT),
NON-DRAWOUT-QUANTITY AND
VOLTAGE RATING AS INDICATED
POWER FACTOR METER
KILOWATT HOUR METER
CURRENT TRANSFORMER (CT)-SECOND
NUMERAL OF TRANSFORMATION RATIO
IDENTIFIES NOMINAL CURRENT OF METERING
/ACCESSORY CIRCUIT, NUMERAL IN PARENTHESIS
INDICATES QUANTITY OF CT'S
AMMETER WITH PHASE SELECTOR SWITCH
VOLTMETER WITH PHASE SELECTOR SWITCH
400/5
(3)
VS
AS
(3)
7200-120 (3)
(3)
AMMETER
VOLTMETER
GROUNDING SYSTEM - ELECTRODE AND CONDUCTOR
(BARE COPPER) - SIZE AS INDICATED
CONDUIT STUB-OUT
PHOTOELECTRIC CONTROL RELAYPC
#4
SECONDARY UNDERGROUND FEEDER, DIRECT BURIAL DUCT LINE
FOR COMM. TYP, 5" FOR ELEC. TYP.) LETTER "P" INDICATES
ELECTRICAL POWER LINE, "C" A COMMUNICATIONS TYPE LINE.
ELECTRICAL EQUIPMENT IN PAD MOUNTED CABINET OR EQUIP.
ST-4, - SWITCH STATION NUMBER 4
ST-4
SL
UF
4P
TRANSFORMER-WIRING CONNECTIONS AS INDICATED
FUSE - POWER AND CONTROL
APPLICATIONS RESPECTIVELY, SIZE AS INDICATED
9KV
DRAW-OUT DEVICE
100E
CABLE TERMINATION
8E
SWITCH ASSEMBLY
ELECTRICAL CONNECTION
DASHED LINES UNDERGROUND (UNLESS OTHERWISE NOTED)
CONTACTOR
(2#12+#12 GRD)1/2"C
QUANTITY OF GROUND WIRES
POWER DISTRIBUTION PANEL WITH MAIN
CIRCUIT BREAKER
CONDUIT SIZE
CONDUIT RUN - SCHEMATIC DIAGRAM
QUANTITY OF PHASE AND NEUTRAL WIRES
KW KILOWATT
VT VOLTAGE TRANSFORMER
WEATHERPROOF
XMFR
WPF
W/ W/O
WP
W
TRANSFORMER
WATER PROOF
WITHOUT
WITH
WEST
POLYVINYL CHLORIDE
NORMALLY OPEN, NUMBER
NATIONAL ELECTRICAL CODE
MAIN SWITCHBOARD
POWER FACTOR
PRIMARY SWITCH STATION
NOT IN CONTRACT
OUTSIDE DIAMETER
SPECIFICATIONS
SWITCH STATION
KILOWATT HOURS
KILOVOLT AMPERES REACTIVE
ST
V
VA
UG
URD
TYP
TEL
SWGR
SYM
UNDERGROUND
VOLT AMPERE
VOLT
TYPICAL
SWITCHGEAR
SYMMETRICAL
TELEPHONE
SEC
SPEC
REQD
S
RECP
REF
PSS
PVC
REQUIRED
SECONDARY
SOUTH
RECEPTACLE
REFERENCE
NEC
O.C.
PF
PFCS
PH
PNL
NO
OD
NEUT
NIC
ON CENTER
PHASE
PANELBOARD
NEUTRAL
MH
MSB
N
MIN
LTG
MAX
KVAR
KWH
MANHOLE
MINIMUM
NORTH
LIGHTING
MAXIMUM
CURRENT TRANSFORMER
CONTRACTING OFFICER'S REPRESENTATIVE
CONTROL POWER TRANSFORMER
ELECTRICAL OR ELECTRIC
GROUND FAULT CIRCUIT INTERRUPTER
GANG OPERATED
GALVANIZED RIGID STEEL CONDUIT
KILOVOLT AMPERES
KILO CIRCULAR MIL
EXIST EXISTING
GND OR GRD GROUND
K
KV
KVA
KCMIL
J-BOX
GRC
GOVT
G.O.
KEY
KILOVOLTS
GOVERNMENT
JUNCTION BOX
FIN
FUT
GFCI
FLEX
FDN
FIG
EXP
EXT
FINISH
FLEXIBLE
FUTURE
EXPOSED
EXTERIOR
FOUNDATION
FIGURE
ENCL
EQUIP
EXC
ENT
ELEC
E
DISC
DWG
ENCLOSURE
ENTRANCE
EQUIPMENT
EXCAVATE
DISCONNECT
DRAWING
EAST
CPT
CU
DET
DIM
CT
CONT
COR
CONC
CL
COPPER
DIMENSION
DETAIL
CENTER LINE
CONCENTRIC
CONTINUOUS
CIRCUIT BREAKER
AMMETER SWITCH
(NOT ALL ABBREVIATIONS REQUIRED FOR THIS PROJECT)
AMPS INTERRUPTING CAPACITY (SYM RMS)
AMERICAN NATIONAL STANDARDS INSTITUTE
AMERICAN WIRE GAGE
AUX
C
CKT
CB
BLDG
AS
AWG
ANSI
AIC
AUXILIARY
CIRCUIT
CONDUIT
BUILDING
AL
ALT
ALUMINUM
ALTERNATE
POLE NUMBER
ELECTRICAL POWER DISTRIBUTION POLE
LIGHTING CONTROL CABINET
WP
GFI
20A
CONDUIT TURNING TOWARD VIEWER
CONDUIT TURNING AWAY FROM VIEWER
600A200A
STREET LIGHTING FIXTURE, FIXTURE TYPE AS NOTED
FUT - INDICATES FUTURE LIGHTING FIXTURE LOCATION
A
(NO. OF CONNECTIONS AS SHOWN)
SECTIONALIZING CABINET
FAULT DETECTOR, MANUAL RESET
WATT/VAR METER
TIME OVERCURRENT
CAPACITIVE TRIP
ELECTRICAL SWITCH OPERATOR
F
W/V
C.T.
EO
FUT
"NG-1" - POWER SOURCE (PANEL AND CIRCUIT NO.)
NG-1
GUY WIRE
FOUR POINT JUNCTION
IN ELECTRICAL MANHOLE
SYSTEMSYS
STREET LIGHTING FIXTURE, FIXTURE TYPE AS NOTEDA
1,3 - INDICATES CIRCUIT NUMBER
1,3
PF
KWH
V
A
UNDERGROUND RESIDENTIAL
DISTRIBUTION
POWER FACTOR CORRECTION
STATION
DISCONNECT SWITCH, SIZE AND TYPE AS INDICATED
COMBINATION STARTER W/ EXTERNALLY OPERATED
MOTOR STARTER, TYPE AND SIZE AS INDICATED
VARIABLE FREQUENCY DRIVE
IN SCHEDULE.
DISCONNECT.
IN SCHEDULE.
VFD
MOTOR - EQUIPMENT SCHEDULE IDENTIFICATION
MOLDED CASE CB OF A GIVEN FRAME SIZE
MOLDED CASE CIRCUIT BREAKER, FIXED TRIP.
THREE POLE UNLESS DESIGNATED '1P' OR '2P'
NORMALLY CLOSED MOMENTARY PUSHBUTTON
AS SHOWN.
MEFX
NORMALLY CLOSED CONTACT
NORMALLY OPEN CONTACT
ELECTRIC METER
NORMALLY OPEN MOMENTARY PUSHBUTTON
SA
WITH ADJUSTABLE TRIP SETTINGS350 AT
400 AF
30A 2P
CONCRETE PAD MOUNTED TRANSFORMER INSTALLATION ANSI
(C84.1) VOLTAGE CONFIGURATION AS INDICATED.
(#6 MIN. CONDUCTOR IF NOT SHOWN)
GROUND CONNECTION - TO STANDARD ROD
TYPE ELECTRODE TO NEAREST STRUCTURAL STEEL
GROUND FAULT RELAYG
JUNCTION BOX, 4" SQUARE UNLESS NOTED OTHERWISEJ
FLOOR DUPLEX RECEPTACLE OUTLET
AA
MANUAL STARTER WITH THERMAL OVERLOADS
SOS
SD
STO
S3
S
DIMMER SWITCH
SWITCH WITH OCCUPANCY SENSOR
SINGLE POLE SWITCH
THREE WAY SWITCH
A A
A A
AFF48"
A
A
OCCUPANCY SENSOR FOR LIGHTING CONTROLOS
A
SP SWITCH WITH PILOT LIGHT
FLOOR FOUR-PLEX RECEPTACLE OUTLET
CEILING MOUNTED DUPLEX RECEPTACLE OUTLET
C
A A
RECESSED INCANDESCENT, FLUORESCENT OR H.I.D.
LUMINAIRE,UPPER CASE LETTER IDENTIFIES FIXTURE
TYPE.
CAN LIGHTS. UPPER CASE LETTER IDENTIFIES FIXTURE TYPE.
DARKENED AREA INDICATES EMERGENCY FIXTURE
WALL MOUNTED COMPACT FLUORECENT, OR H.I.D.
LUMINAIRE, UPPER CASE LETTER IDENTIFIES FIXTURE
TYPE.
SURFACE MOUNTED OR SUSPENDED INDUSTRIAL, HIGH
BAY OR STRIP FLUORESCENT FIXTURE NO LENS. UPPER
CASE LETTER IDENTIFIES THE FIXTURE TYPE.
DARKENED AREA INDICATES EMERGENCY FIXTURE.
SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE W/
LENS. UPPER CASE LETTER DESIGNATES THE FIXTURE
TYPE. DARKENED AREA INDICATES EMERGENCY
FIXTURE POWERED BY A BATTERY INVERTER.
WALL(SURFACE) MOUNTED FLUORESCENT LIGHT
FIXTURE W/ LENS. UPPER CASE LETTER DESIGNATES
THE FIXTURE TYPE. DARKENED AREA INDICATES
EMERGENCY FIXTURE.
2'X4' SURFACE MOUNTED FLUORESCENT FIXTURE.
UPPER CASE LETTER DESIGNATES THE FIXTURE TYPE.
DARKENED AREA INDICATES EMERGENCY FIXTURE.
WALL MTD. EXIT SIGN, ARROW IDENTIFIES DIRECTION
OF EGRESS SINGLE FACE.
WALL MTD. EXIT SIGN, ARROWS IDENTIFY DIRECTION OF
EGRESS DOUBLE FACES
CEILING MTD. EXIT SIGN, ARROW IDENTIFIES DIRECTION
OF EGRESS SINGLE FACE
CEILING MTD. EXIT SIGN, ARROW IDENTIFIES DIRECTION
OF EGRESS DOUBLE FACES
2P, 3W GROUNDING TYPE RECEPTACLE - 125V, CONVENTIONAL DUPLEX,
NEMA 5-20R. RECEPTACLE COVERPLATE SHALL BE PROVIDED WITH
LABEL STATING "COMPUTER".
BRANCH CIRCUIT AND FEEDER WIRING. ARROWS AND
LETTER/NUMERALS IDENTIFY ABV. GRADE HOME-RUN CIRCUITS. ALL
CONDUIT SHALL CONTAIN A GREEN INSULATED GROUND WIRE SIZED IN
ACCORDANCE WITH 2005 NEC TABLE 250.122, UNLESS OTHERWISE
NOTED. ONE TICK MEANS 1 POLE CKT. TWO TICKS MEANS 2 POLE CKT,
THREE TICKS MEANS 3 POLE CKT.
SPECIAL RECEPTACLE, PROVIDE RECEPTACLE CONFIGURATION NOTED
LIGHTING AND APPLIANCE TYPE PANELBOARD. - SURFACE MOUNTED
DUPLEX RECEPTACLE - 2P,3W GROUNDING TYPE RECEPTACLE, 125V,
NUMERAL ADJACENT IDENTIFIES CURRENT RATING IN AMPS (NO
DESIGNATION INDICATES 15A MIN.) GFI INDICATES DEVICE WITH
INTEGRAL GROUND FAULT PROTECTION, WP INDICATES
WEATHERPROOF
CATV OUTLET, 18"AFF, UNLESS NOTED OTHERWISE. "2"
DENOTES DUPLEX JACK.
KEYED NOTES
SEPARABLE CONNECTOR IN PRIMARY DISTRIBUTION LINE
(ELBOW TERMINATOR AND BUSHING COMBINATION)-LOAD
BREAK (200A) AND NON-LOADBREAK (600A) STYLES
RESPECTIVELY
SURGE ARRESTER - VOLTAGE RATING AND
CLASS AS NOTED
AUTOMATIC TRANSFER SWITCHATS
GENERATORGEN
MCC MOTOR CONTROL CENTER
SWBD SWITCHBOARD
3# 2/0,15KV + #2/0,600V N
UNDERGROUND ELECTRICAL FEEDER -
QUANTITY, SIZE, AND VOLTAGE RATING OF PHASE
AND NEUTRAL CONDUCTORS AS INDICATED
PHOTOSENSOR FOR DAYLIGHTING CONTROLPS
LIGHTNING PROTECTION CABLE - CLASS II ALUMINUM SIZE PER NFPA 780
MINIMUM.
AIR TERMINAL - BARE ALUMINUM 5/8" DIAMETER X 12" LONG, MOUNTING
HARDWARE AS REQUIRED FOR EACH SPECIFIC TYPE OF LOCATION.
GROUND TERMINAL - COPPER CLAD STEEL GROUND ROD, 3/4" DIAMETER X 10'
LONG.
THROUGH WALL PENETRATION - 1" PVC FROM HIGHER ROOF TO LOWER ROOF,
INSTALLED BY ELECTRICAL CONTRACTOR. SEAL INSIDE OF CONDUIT AND
OUTSIDE OF CONDUIT TO BE WEATHER TIGHT.
THROUGH ROOF PENETRATION - 1" PVC INSTALLED BY ELECTRICAL
CONTRACTOR DOWN TO GROUND. FLASHING DONE BY ROOFING CONTRACTOR.
SEAL INSIDE OF CONDUIT AND OUTSIDE OF CONDUIT TO BE WEATHER TIGHT.
PROVIDE SEALING, FLASHING, AND COUNTER FLASHING AS REQUIRED TO
MAINTAIN WARRANTY OF ROOF WITH WEATHER-TIGHT SEAL.
WIRING GRAPHICS PRIMARY DISTRIBUTION ELECTRICAL POWER LEGEND WIRING GRAPHIC - SECONDARY DISTRIBUTION EXTERIOR ELECTRICAL LEGEND
INTERIOR ELECTRICAL LEGEND
GENERAL
LIGHTNING PROTECTION LEGEND
ELECTRICAL ABBREVIATIONS
A-AMP AMPERE
AC ABOVE-COUNTER
MOMENTARY PUSHBUTTON / DEADFRONT GFCI PROTECTOR
VACANCY SENSOR FOR DAYLIGHTING CONTROLVA
AF AMPERE FRAME
AMPERE TRIPAT
A
A A
2'X4' RECESSED MOUNTED FLUORESCENT FIXTURE.
UPPER CASE LETTER DESIGNATES THE FIXTURE TYPE.
DARKENED AREA INDICATES EMERGENCY FIXTURE.
DETAIL NUMBER
SHEET NUMBER
ELECTRICAL STRIP MOLD ((OUTLETS ON (2'-6") CENTERS OR AS DESIGNATED
ON DRAWINGS)), MTD ABOVE COUNTER TOP OR AS INDICATED.
c WALL MOUNTED COVER PLATE
ENCLOSED CIRCUIT BREAKERECB
U.O.N UNLESS OTHERWISE NOTED
EES ESSENTIAL ELECTRICAL SYSTEM
A
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
F i l e
P a t h
FULLY
SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:
ARCHITECT/ENGINEER OF RECORD
SEAL
CONSULTANT
321 4 5 6 7 8 9 10
NEW CLINICAL LAB FOR
SURGICAL EXPANSION
RICHMOND, VIRGINIA
652-319
PROJECT DIRECTOR
AUGUST 2018
REVISIONS: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF 162
NAME: TINA DEBELLA, PE
PHONE: 804.675.5495
EMAIL: Tina.DeBella@va.gov
ELECTRICAL GRAPHICS, SYMBOLS
AND ABBREVIATIONS
EP002
MMMGGR
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
F i l e
P a t h
FULLY
SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:
ARCHITECT/ENGINEER OF RECORD
SEAL
CONSULTANT
321 4 5 6 7 8 9 10
NEW CLINICAL LAB FOR
SURGICAL EXPANSION
RICHMOND, VIRGINIA
652-319
PROJECT DIRECTOR
AUGUST 2018
REVISIONS: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF 162
NAME: TINA DEBELLA, PE
PHONE: 804.675.5495
EMAIL: Tina.DeBella@va.gov
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
F i l e
P a t h
FULLY
SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:
ARCHITECT/ENGINEER OF RECORD
SEAL
CONSULTANT
321 4 5 6 7 8 9 10
NEW CLINICAL LAB FOR
SURGICAL EXPANSION
RICHMOND, VIRGINIA
652-319
PROJECT DIRECTOR
AUGUST 2018
REVISIONS: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF 162
NAME: TINA DEBELLA, PE
PHONE: 804.675.5495
EMAIL: Tina.DeBella@va.gov
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
F i l e
P a t h
FULLY
SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:
ARCHITECT/ENGINEER OF RECORD
SEAL
CONSULTANT
321 4 5 6 7 8 9 10
NEW CLINICAL LAB FOR
SURGICAL EXPANSION
RICHMOND, VIRGINIA
652-319
PROJECT DIRECTOR
AUGUST 2018
REVISIONS: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF 162
NAME: TINA DEBELLA, PE
PHONE: 804.675.5495
EMAIL: Tina.DeBella@va.gov
P V A D
U
V A
R i c h m o n d
L a b D r a w i n g s E l e c t r i c a l V A D
U
R I C H
M O
B
E P X
G e n e r a l d w g
P M
A R l l b l e e d
E x
I n c h e s
GENERAL NOTES
1. EQUIPMENT SHOWN WITH BOLD LINEWEIGHTS INDICATES EQUIPMENT TO BE
FURNISHED AND INSTALLED BY THE CONTRACTOR.
KEY NOTES
1. BASE BID: PROVIDE INTEGRAL DAY TANK WITH 72 HOUR FUEL CAPACITY
RUNNING AT FULL LOAD.
DEDUCTIVE BID ALTERNATE 1: OMIT GENERATOR SET AND ASSOCIATED
RECEPTACLE.
2. BASE BID:ROUTE BELOW-GRADE TO BUILDING, SEAL PENETRATION AT WALL,
BOTH INTERIOR AND EXTERIOR TO CONDUIT. ROUTE CONCEALED WITHIN
BUILDING. REFERENCE ONE-LINE FOR ADDITIONAL REQUIREMENTS. PROVIDE
ADDITIONAL, SIMILAR, BELOW-GRADE CONNECTION FOR RECEPTACLE. PROVIDE
NEW CIRCUIT AND CONNECT RECEPTACLE TO NEAREST NON-EES PANELBOARD
WITH CAPACITY.
DEDUCTIVE BID ALTERNATE #1: DISREGARD KEY NOTE #2, THIS SHEET.
T
T
T
T
T
T
T
T
T
T T
T T
T
T
T
W
W
W
W W
W
W
W
W
W
W
W W
W W
W W
W W
W W W W
W
W
W
W
SD
SD
SD
SD
SD
SD
S
D
S
D
S
D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
SS
SS
SS
SS
SS
SS
SS
SS
SSSS
SS
S
S
S
S
S
S
E
E
E
S
D
S
D
SD
SD
S D
E
E
E
E
E
E
E
E E
E
E
E
E
E
E E
E
E
E E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
BOLD BOUNDARY INDICATES
NEW LAB AREA (3RD FLOOR)
1DIESEL
GENERATOR
WP
GFCI
ATS & LOADBANK
DISCONNECTS2
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
F i l e
P a t h
FULLY
SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:
ARCHITECT/ENGINEER OF RECORD
SEAL
CONSULTANT
321 4 5 6 7 8 9 10
NEW CLINICAL LAB FOR
SURGICAL EXPANSION
RICHMOND, VIRGINIA
652-319
PROJECT DIRECTOR
AUGUST 2018
REVISIONS: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF 162
NAME: TINA DEBELLA, PE
PHONE: 804.675.5495
EMAIL: Tina.DeBella@va.gov
ELECTRICAL
SITE PLAN (PARTIAL)
ES101
WBRGGR
SCALE:
ES101
ELECTRICAL SITE PLAN (PARTIAL)
1/16" = 1'-0"
KEYPLAN PLAN
NORTH
N
TN
16'0 8' 32'
SCALE:1/16"=1'-0"
P V A D
U
V A
R i c h m o n d
L a b D r a w i n g s E l e c t r i c a l V A D
U
R I C H
M O
B
E S
S i t e
P l a n d w g
P M
A R l l b l e e d
E x
I n c h e s
FURNISHED AND INSTALLED BY THE CONTRACTOR.
2. LIGHT FIXTURES ARE MOUNTED AT 9'-0" A.F.F. UNLESS OTHERWISE NOTED.
3. SEE LUMINARIES SCHEDULE ON SHEET EL501.
4. PROVIDE ENTIRETY UNDER BASE BID. PROVIDE REDUCED SCOPE PER REGIONS
SHOWN ON GX002 COMMENSURATE WITH AWARDED DEDUCTIVE BID
ALTERNATES. REFERENCE SHEET EL131.2 FOR REDUCED SCOPE WITHIN EACH
REGION, APPLICABLE TO FOOTPRINT AREAS SHOWN ON GX002 ONLY.
5. PROVIDE POWER PACKS AND RELAYS AS REQUIRED FOR LIGHTING CONTROL,
AND AS REQUIRED TO SWITCH RECEPTACLES FOR OCCUPANCY CONTROL, IN
ACCORDANCE WITH ASHRAE 90.1.
KEY NOTES
1. SWITCH IN ROOM SHOWN FOR SIMPLICITY. TWO SEPARATE SWITCHES WILL BE
INSTALLED IN THE ROOM AND LOCATION SHOWN, ONE FOR THE NORMAL LIGHT
FIXTURE, AND ONE FOR THE EMERGENCY LIGHT FIXTURE CONFIGURED AS
SHOWN IN THE DETAIL ON SHEET EL501. FIELD-VERIFY CIRCUIT LOADING WILL
NOT EXCEED 14A, AND PROVIDE REPORT TO COR ACCORDINGLY.
2. NOT USED.
3. FIND EXISTING STAIRWELL LIGHTING CIRCUIT AND ADD NEW STAIRWELL LIGHT
FIXTURES TO THIS CIRCUIT. PROVIDE CONDUIT AND CONDUCTOR AS REQUIRED
TO ADD THESE FIXTURES TO THIS CIRCUIT. MOUNT 8'-0" AFF.
4. DIMMING CONTROL FOR THIS LUMINAIRE SHALL ALLOW LUMINAIRE TO DIM TO
DARK(OFF).
5. LIGHTING AND CONTROLS INCLUDED FROM REFRIGERATOR MANUFACTURER.
INSTALL PER MANUFACTURER INSTRUCTIONS.
F
F
F
A
A
FF
H
H
A
A
A
H
H
H
A
A
A
A
F
A AA
A
A
A A
A
NPQRSTUVW
X
Wn
A
A A
A A AA A A A A
A
A A A A A
A
A
A
A
A
A
A
A A
A
A
A
A
A
A
A
A
A
A
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS OS
OS OS
OS OS
OS
OS
OS
OS
CORRIDOR
3F101
CORRIDOR
3F109
BIOMED
3F102
ANCILLARY TESTING
3F104
DRUG TESTING
3F106
IMMUNOLOGY
3F108
IT CLOSET
3F105
ELEC CLOS
3F103
ACCESSIONING
3F107a
FEE BASIS
3F107b
HEMATOLOGY
3F107e
CHEMISTRY
3F107f
R E
F R
I G
E R
A T
E D
S T
O R
A G
E
F
BLOOD BANK
3F107c
CYTOLOGY
3F107h
HISTOLOGY
3F107g
OPEN OFFICE
3F107j
ARCHIVE
3F128
CLEAN SUPPLY
3F134
BSL-3 LAB
3F132
MEN'S TOILET
3F110
WOMEN'S TOILET
3F112
STAFF TOILET
3F113
BREAK ROOM
3F114
DIRECTOR'S OFFICE
3F118b
CMT OFFICE
3F118c
OFFICE VESTIBULE
3F106a
OFFICE #1
3F106b
OFFICE #2 OFFICE #3
3F106d
OFFICE #4
3F106e
OFFICE #5
3F106f
ADMINISTRATION
3F118a
OFFICE #6
3F119
ADPAC
3F117
DRUG TESTING TOILET
3F106a
JANITOR
3F111
MICROBIOLOGY
3F107d
EQUIPMENT RM
3F133
ANTE ROOM
3F131
GAS TANK ROOM
3F130
FLAMMABLE STORAGE
3F129
D a
D b
D d
D c f f f f ff f f f
D g
D h k Df
Dk OCC
D
OCC OCC
OCC
OCC
OCC
OCC
OCC
OCC DDOCC D D
k k k mn m n n n
D
OCC
OCC
OCC
OCC
OCC
OCC
D
D
D D
D D
D D
D
OCC
VAC
D D
OSOS
OSOS
3F106c k f f f a
OS OS
c b h h h j j r d
OS
d e s
OS
s
OS
D q
OS
OS
OS
q q q
PANEL 3F-NH1
CIRCUIT #9
PANEL 3F-NH1
CIRCUIT #13
PANEL 3F-NH1
CIRCUIT #1
PANEL 3F-ESP1
CIRCUIT #3
PANEL 3F-NH1
CIRCUIT #5
PANEL 3F-ESP1
CIRCUIT #1
1 1
1 1
D s
D j
D r
G
G j
G e r
G j
G j
G q
G q
G q
G h
G h
G h
G G q
G G j
G G j
G
G h
G h
G q
G q
G q
G j
G j
G j
G j
G h
G h
G q
G G q
G
G b
G b G b G b
G a
G a
G a
G a
G a
G a
G b G b
G r
G G r
G s
G s
G s G s
G G s
G s
G s
G r
G r
G r
G r
G r
G G r
G G r
G
G d
G d
G d
G d
G d G G d
G
G e
G
G e
G e
G e
G e
G e
G e
G g
G g
G g
G g
G g
G g
G g
G
G
G
G G
G
G c
G c
G
G G c
G c
G
G G
G
G
OS
g
A
A
A A
A
A
G
G
GG
A
A n m
A mA
A
A
S
S
PANEL 3F-NH1
CIRCUIT #3
A n t
H
H
G
G
G
G
GG
H
H
H
H
OS
OS
A
G
G
G
G
G G
G G
G
H
G
G
G
G
G
G
G
G
G
G
G
G
A A
A t t t
OS
c
PANEL 3F-NH1
CIRCUIT #7
PANEL 3F-ESP1
CIRCUIT #7
PANEL 3F-ESP1
CIRCUIT #5
PANEL 3F-ESP1
CIRCUIT #9
Q
Q
D e
D t
PANEL 3F-NH1
CIRCUIT #11
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
F i l e
P a t h
FULLY
SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:
ARCHITECT/ENGINEER OF RECORD
SEAL
CONSULTANT
321 4 5 6 7 8 9 10
NEW CLINICAL LAB FOR
SURGICAL EXPANSION
RICHMOND, VIRGINIA
652-319
PROJECT DIRECTOR
AUGUST 2018
REVISIONS: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF 162
KEYPLAN
LAB EXPANSION
PLAN
NORTH
NAME: TINA DEBELLA, PE
PHONE: 804.675.5495
EMAIL: Tina.DeBella@va.gov
TN
N
3RD FLOOR
LIGHTING PLAN AND SCHEDULE
EL131
MMMGGR
SCALE:
EL131
3RD FLOOR LIGHTING PLAN
1/8" = 1'-0"
8'0 4' 16'
SCALE:1/8"=1'-0"
P V A D
U
V A
R i c h m o n d
L a b D r a w i n g s E l e c t r i c a l V A D
U
R I C H
M O
B
E L
L i g h t i n g
P l a n d w g
P M
A R l l b l e e d
E x
I n c h e s
FURNISHED AND INSTALLED BY THE CONTRACTOR.
2. LIGHT FIXTURES ARE MOUNTED AT 9'-0" A.F.F. UNLESS OTHERWISE NOTED.
3. SEE LUMINARIES SCHEDULE ON SHEET EL501.
4. REFERENCE GX002 FOR ZONES ASSOCIATED WITH EACH DEDUCTIVE BID
ALTERNATE. THIS SHEET SHOWS EFFECT OF DEDUCTIVE ALTERNATES 4, 5, AND
6 COMBINED. APPLY TO ACTUAL AWARDED SCOPE WITHIN ZONES DEFINED AT
GX002, ON A ZONE-BY-ZONE BASIS. PROVIDE LIGHTING INFRASTRUCTURE PER
EL131 FOR REMAINING REGIONS.
5. PROVIDE POWER PACKS AND RELAYS AS REQUIRED FOR LIGHTING CONTROL,
AND AS REQUIRED TO SWITCH RECEPTACLES FOR OCCUPANCY CONTROL, IN
ACCORDANCE WITH ASHRAE 90.1.
KEY NOTES
1. SWITCH IN ROOM SHOWN FOR SIMPLICITY. TWO SEPARATE SWITCHES WILL BE
INSTALLED IN THE ROOM AND LOCATION SHOWN, ONE FOR THE NORMAL LIGHT
FIXTURE, AND ONE FOR THE EMERGENCY LIGHT FIXTURE CONFIGURED AS
SHOWN IN THE DETAIL ON SHEET EL501.
2. NOT USED.
3. FIND EXISTING STAIRWELL LIGHTING CIRCUIT AND ADD NEW STAIRWELL LIGHT
FIXTURES TO THIS CIRCUIT. PROVIDE CONDUIT AND CONDUCTOR AS REQUIRED
TO ADD THESE FIXTURES TO THIS CIRCUIT. MOUNT 8'-0" AFF. FIELD-VERIFY
CIRCUIT LOADING WILL NOT EXCEED 14A, AND PROVIDE REPORT TO COR
ACCORDINGLY.
4. DIMMING CONTROL FOR THIS LUMINAIRE SHALL ALLOW LUMINAIRE TO DIM TO
DARK (OFF).
5. LIGHTING AND CONTROLS INCLUDED FROM REFRIGERATOR MANUFACTURER.
PROVIDE POWER PER MANUFACTURER INSTRUCTIONS.
Q Q Q QQ Q Q Q
P
F
PF
P F
P
F
PF
CORRIDOR
C3F-1
81 SF
IT CLOSET
3F-104
105 SF
ELEC CLOS
3F-102
387 SF
ACCESSIONING
3F-106a
467 SF
FEE BASIS
3F-106b
1908 SF
MICROBIOLOGY
3F-106d
1019 SF
HEMATOLOGY
3F-106e
1534 SF
CHEMISTRY
3F-106f
231 SF
REFRIGERATEDSTORAGE
3F-126
544 SF
BLOOD BANK
3F-106c
496 SF
CYTOLOGY
3F-106h
1179 SF
OPEN OFFICE
3F-106j
273 SF
ARCHIVE
3F-124
372 SF
CLEAN SUPPLY
3F-131
147 SF
BSL-3 LAB
3F-129
70 SF
STAFF TOILET
3F-108
121 SF
EQUIPMENT ROOM
3F-130
77 SF
FLAMMABLE STORAGE
3F-125
125 SF
ANTE ROOM
3F-128
1583 SF
HISTOLOGY
3F-106g
93 SF
GAS TANK ROOM
3F-127
164 SF
STAIR
3F-S2
NPQRSTUVW
X
Wn
A
A
A
A A
F
A A A
A
A
A
A
A
A A
A
A
A
A
A
A
A
A
A
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
D a
D b
D d
D c
D e f f f f ff f f f
D g
D h
D f
D k
OCC
k k k
D
OCC
OCC
OCC
OCC
OCC
D
DOCC
OS
k f f f a
OS OS
c b h h h j j r d
OS
d e s
OS
s
OS
D q
OS
OS
OS
q q q D s
D j
D r
G
G j
G e r
G j
G j
G q
G q
G q
G h
G h
G h
G G q
G G j
G G j
G
G h
G h
G q
G q
G q
G j
G j
G j
G j
G h
G h
G q
G G q
G
G b
G b G b G b
G a
G a
G a
G a
G a
G a
G b G b
G r
G G r
G s
G s
G s G s
G G s
G s
G s
G r
G r
G r
G r
G r
G G r
G G r
G
G d
G d
G d
G d
G d G G d
G
G e
G
G e
G e
G e
G e
G e
G e
G g
G g
G g
G g
G g
G g
G g
G
G
G
G G
G
G c
G c
G
G G c
G c
G
G G
G
G
OS
g
A
G
G
GG
D t t
H
H
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
A A
A t t t
OS
c
Q
Q
Q QQ Q Q
S
S
PANEL 3F-NH1
CIRCUIT #13
PANEL 3F-NH1
CIRCUIT #1
PANEL 3F-ESP1
CIRCUIT #3
PANEL 3F-NH1
CIRCUIT #5
PANEL 3F-NH1
CIRCUIT #3PANEL 3F-NH1
CIRCUIT #7
PANEL 3F-ESP1
CIRCUIT #7
PANEL 3F-ESP1
CIRCUIT #5
PANEL
3F-ESP1
CIRCUIT #9
PANEL 3F-ESP1
CIRCUIT #1
PANEL 3F-ESP1
CIRCUIT #1
DEDUCTIVE ALTERNATE # 6
NORTH INTERIOR BATHROOMS 3F109, 3F110, 3F111, 3F108 AND CORRIDOR C3F-2
DEDUCTIVE ALTERNATE # 5
NORTH INTERIOR ROOMS C3F3, 3F114, 3F115, 3F116, 3F117, 3F118, 3F120, 3F121, 3F122, 3F119 AND 3F123
DEDUCTIVE ALTERNATE # 4
NORTH INTERIOR ROOMS 3F101, 3F103, 3F105, 3F105a, 3F107, 3F112 AND 3F113
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
F i l e
P a t h
FULLY
SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:
ARCHITECT/ENGINEER OF RECORD
SEAL
CONSULTANT
321 4 5 6 7 8 9 10
NEW CLINICAL LAB FOR
SURGICAL EXPANSION
RICHMOND, VIRGINIA
652-319
PROJECT DIRECTOR
AUGUST 2018
REVISIONS: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF 162
KEYPLAN
LAB EXPANSION
PLAN
NORTH
NAME: TINA DEBELLA, PE
PHONE: 804.675.5495
EMAIL: Tina.DeBella@va.gov
TN
N
3RD FLOOR LIGHTING PLAN
DEDUCTIVE BID ALTERNATE 4, 5 & 6
EL131.2
MMMGGR
SCALE:
EL131.2
BID ALTERNATE 4, 5 & 6
3RD FLOOR LIGHTING PLAN
1/8" = 1'-0"
8'0 4' 16'
SCALE:1/8"=1'-0"
P V A D
U
V A
R i c h m o n d
L a b D r a w i n g s E l e c t r i c a l V A D
U
R I C H
M O
B
E L
L i g h t i n g
P l a n d w g
P M
A R l l b l e e d
E x
I n c h e s
FURNISHED AND INSTALLED BY THE CONTRACTOR.
2. ALL VACANCY SENSORS SHALL BE SET TO THE MAXIMUM DELAY OFF.
3. ALL LIGHTS WILL BE SWITCHED WITH THE VACANCY SENSOR, DURING
EMERGENCY OPERATIONS, THE EMERGENCY FIXTURES WILL REMAIN ON.
REFER TO THE EMERGENCY BYPASS DETAIL ON SHEET EL501 FOR A POSSIBLE
CONFIGURATION.
4. SEE LUMINARIES SCHEDULE ON SHEET EL501.
KEY NOTES
1. FIND EXISTING STAIRWELL LIGHTING CIRCUIT AND ADD NEW STAIRWELL LIGHT
FIXTURES TO THIS CIRCUIT. PROVIDE CONDUIT AND CONDUCTOR AS REQUIRED
TO ADD THESE FIXTURES TO THIS CIRCUIT. MOUNT 8'-0" AFF. FIELD-VERIFY
CIRCUIT LOADING WILL NOT EXCEED 14A, AND PROVIDE REPORT TO COR,
ACCORDINGLY. ("S"-TYPE LUMINAIRES.)
2. PROVIDE A UL-LISTED CONTROL PANEL, INCLUDING FABRICATION, BY A UL 508
PANEL SHOP. CABINET SHALL INCLUDE RAIL-MOUNTED TIMER SUITABLE FOR
8-HOUR ON WITH AUTOMATIC OFF. LIGHTING CONTROL ACCESSORIES SHALL
INCLUDE TWO (2) STATUS LIGHTS (GREEN AT ON, RED AT AUTO-OFF) ON OUTER
COVER AND A HAND-OFF-AUTO SWITCH. PROVIDE ADDITIONAL COMPONENTS AS
REQUIRED FOR COMPLETE FUNCTIONALITY. PROVIDE FUNCTIONALITY FOR
MOMENTARY WALL SWITCHES AND PROVIDE TWO (2) CONTROLLED
CONTACTORS FOR 20 AMP 277V LIGHTING CIRCUITS.
3. PROVIDE 24VDC OR 120VAC MOMENTARY WALL SWITCH, AT CONTRACTOR'S
OPTION, TO MATCH THE TIMING CONTACTOR LIGHTING CONTROL PANEL.
NPQRSTUVW
QQQ
QQQ
QQQ
Q Q Q QQ
Q Q
QQQ QQQ Q
QQQQ Q Q QQ
INTERSTITIAL
3F-INT
S
S
PANEL 3F-ESP1
CIRCUITS #11
PANEL 3F-ESP1
CIRCUITS #11
PANEL 3F-NH1
CIRCUITS #15
PANEL 3F-NH1
CIRCUITS #15
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
F i l e
P a t h
FULLY
SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:
ARCHITECT/ENGINEER OF RECORD
SEAL
CONSULTANT
321 4 5 6 7 8 9 10
NEW CLINICAL LAB FOR
SURGICAL EXPANSION
RICHMOND, VIRGINIA
652-319
PROJECT DIRECTOR
AUGUST 2018
REVISIONS: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF 162
KEYPLAN
LAB EXPANSION
PLAN
NORTH
NAME: TINA DEBELLA, PE
PHONE: 804.675.5495
EMAIL: Tina.DeBella@va.gov
TN
N
3RD FLOOR
INTERSTITIAL LIGHTING PLAN
EL132
MMMGGR
SCALE:
EL132
3RD FLOOR INTERSTITIAL LIGHTING PLAN
1/8" = 1'-0"
8'0 4' 16'
SCALE:1/8"=1'-0"
P V A D
U
V A
R i c h m o n d
L a b D r a w i n g s E l e c t r i c a l V A D
U
R I C H
M O
B
E L
L i g h t i n g
P l a n d w g
P M
A R l l b l e e d
E x
I n c h e s
1. ANY LIGHT FIXTURE SUBSTITUTION REQUESTS WILL REQUIRE THE SUBMITTAL
OF PHOTOMETRIC VALUES OF AFFECTED SPACES FOR VERIFICATION OF
PROPER LIGHTING LEVELS TO ENSURE THE DESIGN INTENT IS MAINTAINED.
2. PROVIDE UL 924-LISTED EQUIPMENT WHERE TRANSFERRING POWER FROM
NORMAL TO EMERGENCY DURING A POWER LOSS.
LUMINAIRE SCHEDULE
TYPE LAMPS DESCRIPTION VOLTAGE
WATTS
MANUFACTURER CATALOG NO.
A LED 2'x4' LED 120-277V 48.1W
PHILIPS 2DLG49L835-4-D-UNV-DIM
D LED 6" LED DOWNLIGHT 120-277V
20.5W
PATHWAY 6VLED150035K/64LEDMDSCLPF
F LED RESTROOM; WALL MOUNT VANITY LIGHT 120-277V
40W
WILLIAMS WMAUD-2-L15/835D
G LED RECESSED CLEAN ROOM 2'x4' LED 120-277V 109.8W
FAIL-SAFE CLM-24-4INS-A12125-LD3-3STD-35-UNV-ED1C
OR APPROVED EQUAL
H LED 1'x4' LED 120-277V 21W
PHILIPS 1DLG27L835-4-D-UNV-DIM
Q LED LINEAR LED STRIP WITH WIDE OPTICAL
DISTRIBUTION
120-277V
47.1W
METALUX 4SNLED-LD5-56SL-LC-UNV-L835-CD1-U
R LED INDUSTRIAL, COLD STORAGE, 4' LED LIGHTING
STRIP
120-277V
81W
METALUX 4VT2-LD4-8-FR50-UNV-L835
OR APPROVED EQUAL
S LED 50" LINEAR SURFACE-MOUNT WALL SCONCE
WITH TAMPER-RESISTANT POLYCARBONATE
REFRACTOR.
120-277V
68.3W
FAIL-SAFE FPS-4-LD4-2-STD-35K-OPL-UNV-EDD-1
EXIT LED GREEN EDGE-LIT LED ILLUMINATED EXIT SIGN 120/277V
3W
PHILIPS 44RLU1G
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
F i l e
P a t h
FULLY
SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:
ARCHITECT/ENGINEER OF RECORD
SEAL
CONSULTANT
321 4 5 6 7 8 9 10
NEW CLINICAL LAB FOR
SURGICAL EXPANSION
RICHMOND, VIRGINIA
652-319
PROJECT DIRECTOR
AUGUST 2018
REVISIONS: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF 162
NAME: TINA DEBELLA, PE
PHONE: 804.675.5495
EMAIL: Tina.DeBella@va.gov
LIGHTING SCHEDULE AND DETAILS
EL501
MMMGGR
SCALE:
EL501
LIGHTING SCHEDULE
NTS
SCALE:
EL501
EMERGENCY BYPASS DIAGRAM
NTS
P V A D
U
V A
R i c h m o n d
L a b D r a w i n g s E l e c t r i c a l V A D
U
R I C H
M O
B
E L
L i g h t i n g
S c h e d u l e d w g
P M
A R l l b l e e d
E x
I n c h e s
FURNISHED AND INSTALLED BY THE CONTRACTOR.
2. ELECTRICAL GEAR SHOWN FOR LOCATION PURPOSE. REFER TO ONE-LINE
DIAGRAM ON SHEET EP601 FOR EQUIPMENT INTERCONNECTION
REQUIREMENTS.
3. HATCHED AREA SHOWS RELATIVE LOCATION OF NEW LAB AND NEW
ELECTRICAL ROOM ON 3RD FLOOR TO PROVIDE LATERAL DISTANCE
INFORMATION FOR ELECTRICAL RUNS. UTILIZE ELECTRICAL ROOMS FOR
VERTICAL ROUTING AND INTERSTITIAL SPACES FOR LATERAL ROUTING OF
ELECTRICAL CONDUITS WHERE POSSIBLE.
EP101
VAULT-3
NEW LAB ABOVE SEE
GENERAL NOTE 3
NEW
ELECT
RM
ECLDOF
X F
M R
P N
L P
N L
P N
L P
N L
P N
L P
N L
P N
L P
N L
P N
L
A T
S A
T S
A T
S X
F M
R X
F M
R D
IS
C
D
IS
C
SWGR
ECPDOF
ECBCF
TSF
ATS-SF
LIFE
SAFETY #1
EELOF
TEF
EEPDOF
ECBEF
TCF
ATS-CF
CRITICAL
#1
ESLDOF
ESPDOF
ECBSF
EELDOF
SIDE PNL
EEPOF
ATS-EF
EQUIP #1
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
F i l e
P a t h
FULLY
SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:
ARCHITECT/ENGINEER OF RECORD
SEAL
CONSULTANT
321 4 5 6 7 8 9 10
NEW CLINICAL LAB FOR
SURGICAL EXPANSION
RICHMOND, VIRGINIA
652-319
PROJECT DIRECTOR
AUGUST 2018
REVISIONS: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF 162
NAME: TINA DEBELLA, PE
PHONE: 804.675.5495
EMAIL: Tina.DeBella@va.gov
BASEMENT
POWER PLAN
EP101
WBRGGR
SCALE:
EP101
BASEMENT POWER PLAN
1/8" = 1'-0"
SCALE:
EP101
TRANSFORMER VAULT-3
ENLARGED POWER PLAN
1/4" = 1'-0"
KEYPLAN
LAB EXPANSION
PLAN
NORTH
N
TN
8'0 4' 16'
SCALE:1/8"=1'-0"
4'0 2' 8'
SCALE:1/4"=1'-0"
P V A D
U
V A
R i c h m o n d
L a b D r a w i n g s E l e c t r i c a l V A D
U
R I C H
M O
B
E P
P o w e r
P l a n d w g
P M
A R l l b l e e d
E x
I n c h e s
FURNISHED AND INSTALLED BY THE CONTRACTOR.
2. ELECTRICAL GEAR SHOWN FOR LOCATION PURPOSE. REFER TO ONE-LINE
DIAGRAM ON SHEET EP401 FOR EQUIPMENT INTERCONNECTION
REQUIREMENTS.
3. HATCHED AREA SHOWS RELATIVE LOCATION OF NEW LAB AND NEW
ELECTRICAL ROOM ON 3RD FLOOR TO PROVIDE LATERAL DISTANCE
INFORMATION FOR ELECTRICAL RUNS. UTILIZE ELECTRICAL ROOMS FOR
VERTICAL ROUTING AND INTERSTITIAL SPACES FOR LATERAL ROUTING OF
ELECTRICAL CONDUITS WHERE POSSIBLE.
ELEC RM
1D-154
NEW LAB ABOVE SEE
GENERAL NOTE 3
EEH1A
NEW
ELECT
RM
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
F i l e
P a t h
FULLY
SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:
ARCHITECT/ENGINEER OF RECORD
SEAL
CONSULTANT
321 4 5 6 7 8 9 10
NEW CLINICAL LAB FOR
SURGICAL EXPANSION
RICHMOND, VIRGINIA
652-319
PROJECT DIRECTOR
AUGUST 2018
REVISIONS: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF 162
NAME: TINA DEBELLA, PE
PHONE: 804.675.5495
EMAIL: Tina.DeBella@va.gov
1ST FLOOR
POWER PLAN
EP111
WBRGGR
SCALE:
EP111
1ST FLOOR POWER PLAN
1/8" = 1'-0"
KEYPLAN
LAB EXPANSION
PLAN
NORTH
TN
N
8'0 4' 16'
SCALE:1/8"=1'-0"
P V A D
U
V A
R i c h m o n d
L a b D r a w i n g s E l e c t r i c a l V A D
U
R I C H
M O
B
E P
P o w e r
P l a n d w g
P M
A R l l b l e e d
E x
I n c h e s
KEY NOTES
1. FURNISH AND INSTALL GROUND BAR. CONNECT TO ALL AVAILABLE GROUNDING
POINTS PER NEC REQUIREMENTS. ADD GROUND RODS AS NECESSARY.
2. FURNISH AND INSTALL L6-30R TYPE RECEPTACLE.
3. RELOCATE SIEMENS APTIO AUTOMATION ELECTRICAL GEAR LOCATED IN
ELECTRICAL ROOM 3A-148 TO THIS EQUIPMENT ROOM. ELECTRICAL GEAR
INCLUDES FLOOR MOUNTED UPS, 60kVA;208V-400/231V SPECIAL EQUIPMENT
TRANSFORMER & ASSOCIATED PANELBOARD. RE-FEED TO MAINTAIN EXISTING
POWER SOURCE WHICH IS PANEL LD3AA#1,3,5 LOCATED WITHIN ORIGIN ROOM.
USE (4#4+1#8G)1-1/4"C. PROVIDE A 60-AMP, 3-POLE ENCLOSED CIRCUIT BREAKER
IN-LINE, ADJACENT TO TRANSFORMER, BETWEEN TRANSFORMER AND UPS.
PROVIDE A 40-AMP, 3-POLE ENCLOSED CIRCUIT BREAKER IN-LINE, ADJACENT TO
TRANSFORMER, BETWEEN TRANSFORMER AND APTIO DISCONNECT. REFERENCE
ONE-LINE AND SHEET EP131 FOR ADDITIONAL REQUIREMENTS. PROVIDE RACKING
AND ADJUST LOCATIONS AS REQUIRED TO PROVIDE NEC 110.26 WORKING
CLEARANCE.
4. RELOCATE SIEMENS APTIO AUTOMATION SYSTEM AIR COMPRESSOR FROM ROOM
3A-147 TO EQUIPMENT ROOM. RE-FEED TO MAINTAIN EXISTING POWER SOURCE
WHICH IS PANEL EEL3AC#12,14,16 LOCATED IN ELEC ROOM 3A-148. USE
(4#8+1#10G)1"C. PROVIDE LOCAL LOCKABLE DISCONNECT.
5. PROVIDE CONNECTION FOR AUTOFLUSH AND AUTOSINK POWER. COORDINATE
POWER CONNECTION METHOD WITH EQUIPMENT CONFIGURATION.
6. PROVIDE CONNECTION FOR ROBOT COMMUNICATION SYSTEM POWER.
EQUIPMENT BY VENDOR. PROVIDE 120V, 1Ø POWER SOURCE, CAPPED OFF.
7. PROVIDE GFCI-TYPE RECEPTACLE AT ELEVATION 4 INCHES ABOVE TOP OF SINK
BOWL.
8. PROVIDE DEADFRONT-STYLE GFCI PROTECTION AS REQUIRED TO PROTECT
RECEPTACLES CONNECTED TO THIS CIRCUIT.
9. NOT USED
10. LOCATE DISCONNECT SWITCH ABOVE THE GROUND BAR LOCATION. MOUNT
GROUND BAR SO IT DOES NOT AFFECT EQUIPMENT CLEARANCE AT DISCONNECT.
11. PROVIDE RECEPTACLES FOR ACCESS CONTROL PANELS IN EXISTING MICU
BIOMED ROOM. COORDINATE WITH TELECOM SHEET TN132.
12. PROVIDE SWITCH AND CIRCUIT AS REQUIRED TO TOGGLE TOILET AND SINK
FIXTURES BETWEEN OPERABLE AND NON-OPERABLE STATES.
13. BASE BID:BOLD DASHED BOUNDARY INDICATES EQUIPMENT TO BE INSTALLED,
EXCEPT FOR PORTIONS IDENTIFIED AS PART OF A DEDUCTIVE BID ALTERNATE.
VERIFY IF THIS EQUIPMENT IS TO BE INSTALLED PRIOR TO COMMENCEMENT OF
WORK. ELECTRICAL INFRASTRUCTURE IN THIS BOUNDARY IS INCLUDED UNDER
THE BASE BID.
14. DEDUCTIVE BID ALTERNATE 4: ELECTRICAL INFRASTRUCTURE ON THIS SHEET IN
THIS BOUNDARY IS EXCLUDED UNDER DEDUCTIVE BID ALTERNATE 4. REFERENCE
EP131.2 FOR ADDITIONAL REQUIREMENTS.
15. DEDUCTIVE BID ALTERNATE 5: ELECTRICAL INFRASTRUCTURE ON THIS SHEET IN
THIS BOUNDARY IS EXCLUDED UNDER DEDUCTIVE BID ALTERNATE 5. REFERENCE
EP131.2 FOR ADDITIONAL REQUIREMENTS.
16. DEDUCTIVE BID ALTERNATE 6: ELECTRICAL INFRASTRUCTURE ON THIS SHEET IN
THIS BOUNDARY IS EXCLUDED UNDER DEDUCTIVE BID ALTERNATE 6. REFERENCE
EP131.2 FOR ADDITIONAL REQUIREMENTS.
17. PROVIDE DOORBELL SYSTEM PUSH BUTTON +48" AFF. SEE 5/EP132 FOR
ADDITIONAL REQUIREMENTS.
18. PROVIDE POWER CONNECTION, RACEWAYS, AND ENCLOSURES FOR PACS
SYSTEM AT THIS LOCATION. SEE 3/TN502 AND 7/TN502 FOR ADDITIONAL
REQUIREMENTS. PROVIDE PACS SYSTEM MATCHING HOSPITAL STANDARD.
19. BASE BID:SAME AS KEY NOTE#18, EXCEPT NO POWER CONDUCTORS OR PACS
COMPONENTS.
DEDUCTIVE BID ALTERNATE #2: OMIT PACS SYSTEM FROM DOOR IDENTIFIED IN
ENTIRETY.
20. PROVIDE SPLIT-YOKE DUPLEX RECEPTACLE(S), WITH TOP HALF
OCCUPANCY-SWITCHED PER ASHRAE 90.1.
1.
2.
3.
4.
5.
6.
7.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
GFCI, AC
AC
GFCI, AC
GFCI
GFCI
GFCI
GFCI
GFCI, AC
GFCI, AC
GFCI
GFCI, AC
GFCI
XFMR
PANEL
UPS
AIR COMP.
J6
J J
5J 5 GFCI, AC
PANEL 3F-NL1
CIRCUIT #53
PANEL 3F-NL1
CIRCUIT #51
PANEL 3F-NL1
CIRCUIT #55
7 7
PANEL 3F-NL1
CIRCUIT #59
PANEL 3F-NL1
CIRCUIT #61
PACS
PANEL 3F-NL1
CIRCUIT #69
J
J
PANEL 3F-NL1
CIRCUIT #79,81
PANEL 3F-NL1
CIRCUIT #57
PANEL 3F-NL1
CIRCUIT #49
PANEL 3F-NL1
CIRCUIT #71
PANEL 3F-NL1
CIRCUIT #41
PANEL 3F-NL1
CIRCUIT #19
PANEL 3F-NL1
CIRCUIT #18
PANEL 3F-NL1
CIRCUIT #12
PANEL 3F-NL1
CIRCUIT #83
PANEL 3F-NL1
CIRCUIT #21
PANEL 3F-NL2
CIRCUIT #30
JPANEL 3F-ESP1
CIRCUIT #2
J
PANEL 3F-ESP1
CIRCUIT #4
PANEL 3F-EEL2
CIRCUIT #83
J J
PANEL 3F-NL1
CIRCUIT #43
PANEL 3F-NL1
CIRCUIT #23
PANEL 3F-NL1
CIRCUIT #47
PANEL 3F-NL1
CIRCUIT #14
PANEL 3F-NL1
CIRCUIT #10
PANEL 3F-NL1
CIRCUIT #45
CORRIDOR
C3F-1
CORRIDOR
C3F-2
BIOMED
3F-101
ANCILLARY TESTING
3F-103
DRUG TESTING
3F-105
IMMUNOLOGY
3F-107
IT CLOSET
ACCESSIONING
3F-106a
FEE BASIS
3F-106b
MICROBIOLOGY
3F-106d
HEMATOLOGY
3F-106e
CHEMISTRY
3F-106f
REFRIGERATEDSTORAGE
3F-126
BLOOD BANK
3F-106c
CYTOLOGY
3F-106h
OPEN OFFICE
3F-106j
ARCHIVE
3F-124
CLEAN SUPPLY
3F-131
BSL-3 LAB
3F-129
MEN'S TOILET
3F-109
WOMEN'S TOILET
3F-111
STAFF TOILET
3F-108
DRUG TESTING TOILET
3F-105a
JANITOR
3F-110
EQUIPMENT ROOM
3F-130
FLAMMABLE STORAGE
3F-125
ANTE ROOM
3F-128
BREAK ROOM
3F-112
CORRIDOR
C3F-3
OFFICE #1
3F-114
OFFICE #2
3F-115
OFFICE #3
3F-116
OFFICE #4
3F-117
OFFICE #5
3F-118
ADMINISTRATION
3F-120
DIRECTOR'S OFFICE
3F-121
CMT OFFICE
3F-122
OFFICE #6
3F-123
ADPAC/RESIDENTS
3F-119
HISTOLOGY
3F-106g
GAS TANK ROOM
3F-127
STAIR
3F-S2
CONF ROOM
3F-113
DEDUCTIVE BID
ALTERNATE 5
DEDUCTIVE BID
ALTERNATE 4
DEDUCTIVE BID
ALTERNATE 6
13 16 13 14
P
F
PF
R E
F
R E
F
P F
P F
P
F
PF
J 17
M
PANEL 3F-EEL2
CIRCUIT #27
PANEL 3F-EEL2
CIRCUIT #29
ECB ECB
18 18
18 18
19 19
19 19
19 1919
13 16
13 16
13 14
PANEL 3F-NL1
CIRCUIT #63
PANEL 3F-NL2
CIRCUIT #6 (PART)
GENERAL NOTES
1. EQUIPMENT SHOWN WITH BOLD LINEWEIGHTS INDICATES EQUIPMENT TO BE
FURNISHED AND INSTALLED BY THE CONTRACTOR.
2. ELECTRICAL GEAR SHOWN FOR LOCATION PURPOSE. REFER TO ONE-LINE
DIAGRAM ON SHEET EP401 FOR EQUIPMENT INTERCONNECTION REQUIREMENTS.
3. MAINTAIN NEC REQUIRED CLEARANCES DURING INSTALLATION OF NEW
ELECTRICAL GEAR. PROVIDE STRUT RACKING AS REQUIRED FOR COMPLIANCE.
4. ANY FLOOR MOUNTED ELECTRICAL GEAR SHALL BE INSTALLED ON AN
EQUIPMENT PAD, 4" MINIMUM THICKNESS.
5. EQUIPMENT FOR BOTH THE BASE BID AND DEDUCTIVE BID ALTERNATES ARE
SHOWN ON THE PLANS.
6. ALL WIRE RUNS SHOWN ON DRAWINGS ARE RUN THROUGH THE SPACE ABOVE
THE CEILING GRID ON THIS FLOOR. LOCATE PRE-FURNITURE INFRASTRUCTURE
AS REQUIRED TO FEED FURNITURE SHOWN ON TN131 AFTER FURNITURE IS
INSTALLED.
7. MOUNT CEILING - MOUNTED AND POWER-POLE JUNCTION BOXES CONCEALED,
WITHIN THE ABOVE - CEILING SPACE.
3F-EEL2
3F-TN1
3F-NH1
3F-EEP1
3F-TEE13F-TEE2
3F-EEL1
3F-ESP1
3F-NL1
3F-NL2
DS-EEP1
3F-NL1-ECB
+48"
AFF
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
VA FORM 08 - 6231
A
F i l e
P a t h
FULLY
SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE:
ARCHITECT/ENGINEER OF RECORD
SEAL
CONSULTANT
321 4 5 6 7 8 9 10
NEW CLINICAL LAB FOR
SURGICAL EXPANSION
RICHMOND, VIRGINIA
652-319
PROJECT DIRECTOR
AUGUST 2018
REVISIONS: DATE:
Group, Inc.
11031 SOUTH PIKES PEAK DRIVE #202
PARKER, COLORADO 80138
PH: 303.841.3922
WWW.AES-GRP.COM
BID DOCUMENTS
DWG. OF 162
NAME: TINA DEBELLA, PE
PHONE: 804.675.5495
EMAIL: Tina.DeBella@va.gov
3RD FLOOR POWER PLAN
POST FURNITURE CONSTRUCTION
EP131
WBRGGR
SCALE:
EP131
POST FURNITURE CONSTRUCTION
3RD FLOOR POWER PLAN
1/8" = 1'-0"
SCALE:
EP131
ENLARGED PLAN
ELEC CLOS 3F103
1/2" = 1'-0"
KEYPLAN
LAB EXPANSION
PLAN
NORTH
N
TN
8'0 4' 16'
SCALE:1/8"=1'-0"
2' 4'0 1'
SCALE:1/2"=1'-0"
EP132
EP132
EP133
EP133
EP132
EP132
EP132
EP132
EP132
EP131
P V A D
U
V A
R i c h m o n d
L a b D r a w i n g s E l e c t r i c a l V A D
U
R I C H
M O
B
E P
P o w e r
P l a n d w g
P M
A R l l b l e e d
E x
I n c h e s
# KEY NOTES
1. FURNISH AND INSTALL GROUND BAR. CONNECT TO ALL AVAILABLE GROUNDING
POINTS PER NEC REQUIREMENTS. ADD GROUND RODS AS NECESSARY.
2. FURNISH AND INSTALL L6-30R TYPE RECEPTACLE.
3. RELOCATE SIEMENS APTIO AUTOMATION ELECTRICAL GEAR LOCATED IN
ELECTRICAL ROOM 3A-148 TO THIS EQUIPMENT ROOM. ELECTRICAL GEAR
INCLUDES FLOOR MOUNTED UPS, 60kVA;208V-400/231V SPECIAL EQUIPMENT
TRANSFORMER & ASSOCIATED PANELBOARD. RE-FEED TO MAINTAIN EXISTING
POWER SOURCE WHICH IS PANEL LD3AA#1,3,5 LOCATED WITHIN ORIGIN ROOM.
USE (4#4+1#8G)1-1/4"C. PROVIDE A 60-AMP, 3-POLE ENCLOSED CIRCUIT BREAKER
IN-LINE, ADJACENT TO TRANSFORMER, BETWEEN TRANSFORMER AND UPS.
PROVIDE A 40-AMP, 3-POLE ENCLOSED CIRCUIT BREAKER IN-LINE, ADJACENT TO
TRANSFORMER, BETWEEN TRANSFORMER AND APTIO DISCONNECT. REFERENCE
ONE-LINE AND SHEET EP131 FOR ADDITIONAL REQUIREMENTS. PROVIDE RACKING
AND ADJUST LOCATIONS AS REQUIRED TO PROVIDE NEC 110.26 WORKING
CLEARANCE.
4. RELOCATE SIEMENS APTIO AUTOMATION SYSTEM AIR COMPRESSOR FROM ROOM
3A-147 TO EQUIPMENT ROOM. RE-FEED TO MAINTAIN EXISTING POWER SOURCE
WHICH IS PANEL EEL3AC#12,14,16 LOCATED IN ELEC ROOM 3A-148. USE
(4#8+1#10G)1"C. PROVIDE LOCAL LOCKABLE DISCONNECT.
5. PROVIDE CONNECTION FOR AUTOFLUSH AND AUTOSINK POWER. COORDINATE
POWER CONNECTION METHOD WITH EQUIPMENT CONFIGURATION.
6. PROVIDE CONNECTION FOR ROBOT COMMUNICATION SYSTEM POWER.
EQUIPMENT BY VENDOR. PROVIDE 120V, 1Ø POWER SOURCE, CAPPED OFF.
7. PROVIDE GFCI-TYPE RECEPTACLE AT ELEVATION 4 INCHES ABOVE TOP OF SINK
BOWL.
8. PROVIDE DEADFRONT-STYLE GFCI PROTECTION AS REQUIRED TO PROTECT
RECEPTACLES CONNECTED TO THIS CIRCUIT.
9. NOT USED
10. LOCATE DISCONNECT SWITCH ABOVE THE GROUND BAR LOCATION. MOUNT
GROUND BAR SO IT DOES NOT AFFECT EQUIPMENT CLEARANCE AT DISCONNECT.
11. PROVIDE RECEPTACLES FOR ACCESS CONTROL PANELS IN EXISTING MICU
BIOMED ROOM. COORDINATE WITH TELECOM SHEET TN132.
12. PROVIDE SWITCH AND CIRCUIT AS REQUIRED TO TOGGLE TOILET AND SINK
FIXTURES BETWEEN OPERABLE AND NON-OPERABLE STATES.
13. BASE BID:BOLD DASHED BOUNDARY INDICATES EQUIPMENT TO BE INSTALLED,
EXCEPT FOR PORTIONS IDENTIFIED AS PART OF A DEDUCTIVE BID ALTERNATE.
VERIFY IF THIS EQUIPMENT IS TO BE INSTALLED PRIOR TO COMMENCEMENT OF
WORK. ELECTRICAL INFRASTRUCTURE IN THIS BOUNDARY IS INCLUDED UNDER
THE BASE BID.
14. DEDUCTIVE BID ALTERNATE 4: ELECTRICAL INFRASTRUCTURE ON THIS SHEET IN
THIS BOUNDARY IS EXCLUDED UNDER DEDUCTIVE BID ALTERNATE 4. REFERENCE
EP131.2 FOR ADDITIONAL REQUIREMENTS.
15. DEDUCTIVE BID ALTERNATE 5: ELECTRICAL INFRASTRUCTURE ON THIS SHEET IN
THIS BOUNDARY IS EXCLUDED UNDER DEDUCTIVE BID ALTERNATE 5. REFERENCE
EP131.2 FOR ADDITIONAL REQUIREMENTS.
16. DEDUCTIVE BID ALTERNATE 6: ELECTRICAL INFRASTRUCTURE ON THIS SHEET IN
THIS BOUNDARY IS EXCLUDED UNDER DEDUCTIVE BID ALTERNATE 6. REFERENCE
EP131.2 FOR ADDITIONAL REQUIREMENTS.
17. PROVIDE DOORBELL SYSTEM PUSH BUTTON +48" AFF. SEE 5/EP132 FOR
ADDITIONAL REQUIREMENTS.
18. PROVIDE POWER CONNECTION, RACEWAYS, AND ENCLOSURES FOR PACS
SYSTEM AT THIS LOCATION. SEE 3/TN502 AND 7/TN502 FOR ADDITIONAL
REQUIREMENTS. PROVIDE PACS SYSTEM MATCHING HOSPITAL STANDARD.
19. BASE BID:SAME AS KEY NOTE#18, EXCEPT NO POWER CONDUCTORS OR PACS
COMPONENTS.
DEDUCTIVE BID ALTERNATE #2: OMIT PACS SYSTEM FROM DOOR IDENTIFIED IN
ENTIRETY.
20. PROVIDE SPLIT-YOKE DUPLEX RECEPTACLE(S), WITH TOP HALF
OCCUPANCY-SWITCHED PER ASHRAE 90.1.
GFCI, AC
AC
GFCI, AC
GFCI
GFCI
GFCI
GFCI
GFCI, AC
GFCI, AC
GFCI
GFCI, AC
GFCI
XFMR
PANEL
UPS
AIR COMP.
J6
J J
5J 5 GFCI, AC
PANEL 3F-NL1
CIRCUIT #53
PANEL 3F-NL1
CIRCUIT #51
PANEL 3F-NL1
CIRCUIT #55
7 7
PANEL 3F-NL1
CIRCUIT #59
PANEL 3F-NL1
CIRCUIT #61
PACS
PANEL 3F-NL1
CIRCUIT #69
J
J
PANEL 3F-NL1
CIRCUIT #79,81
PANEL 3F-NL1
CIRCUIT #57
PANEL 3F-NL1
CIRCUIT #49
PANEL 3F-NL1
CIRCUIT #71
PANEL 3F-NL1
CIRCUIT #41
PANEL 3F-NL1
CIRCUIT #19
PANEL 3F-NL1
CIRCUIT #18
PANEL 3F-NL1
CIRCUIT #12
PANEL 3F-NL1
CIRCUIT #83
PANEL 3F-NL1
CIRCUIT #21
PANEL 3F-NL2
CIRCUIT #30
JPANEL 3F-ESP1
CIRCUIT #2
J
PANEL 3F-ESP1
CIRCUIT #4
PANEL 3F-EEL2
CIRCUIT #83
J J
PANEL 3F-NL1
CIRCUIT #43
PANEL 3F-NL1
CIRCUIT #23
PANEL 3F-NL1
CIRCUIT #47
PANEL 3F-NL1
CIRCUIT #14
PANEL 3F-NL1
CIRCUIT #10
PANEL 3F-NL1
CIRCUIT #45
CORRIDOR
C3F-1
CORRIDOR
C3F-2
BIOMED
3F-101
ANCILLARY TESTING
3F-103
DRUG TESTING
3F-105
IMMUNOLOGY
3F-107
IT CLOSET
ACCESSIONING
3F-106a
FEE BASIS
3F-106b
MICROBIOLOGY
3F-106d
HEMATOLOGY
3F-106e
CHEMISTRY
3F-106f
REFRIGERATEDSTORAGE
3F-126
BLOOD BANK
3F-106c
CYTOLOGY
3F-106h
OPEN OFFICE
3F-106j
ARCHIVE
3F-124
CLEAN SUPPLY
3F-131
BSL-3 LAB
3F-129
MEN'S TOILET
3F-109
WOMEN'S TOILET
3F-111
STAFF TOILET
3F-108
DRUG TESTING TOILET
3F-105a
JANITOR
3F-110
EQUIPMENT ROOM
3F-130
FLAMMABLE STORAGE
3F-125
ANTE ROOM
3F-128
BREAK ROOM
3F-112
CORRIDOR
C3F-3
OFFICE #1
3F-114
OFFICE #2
3F-115
OFFICE #3
3F-116
OFFICE #4
3F-117
OFFICE #5
3F-118
ADMINISTRATION
3F-120
DIRECTOR'S OFFICE
3F-121
CMT OFFICE
3F-122
OFFICE #6
3F-123
ADPAC/RESIDENTS
3F-119
HISTOLOGY
3F-106g
GAS TANK ROOM
3F-127
STAIR
3F-S2
CONF ROOM
3F-113
DEDUCTIVE BID
ALTERNATE 5
DEDUCTIVE BID
ALTERNATE 4
DEDUCTIVE BID
ALTERNATE 6
13 16 13 14
P
F
PF
R E
F
R E
F
P F
P F
P
F
PF
J 17
M
PANEL 3F-EEL2
CIRCUIT #27
PANEL 3F-EEL2
CIRCUIT #29
ECB ECB
18 18
18 18
19 19
19 19
19 1919
13 16
13 16
13 14
PANEL 3F-NL1
CIRCUIT #63
PANEL 3F-NL2
CIRCUIT #6 (PART)
3F-EEL2
3F-TN1
3F-NH1
3F-EEP1
3F-TEE13F-TEE2
3F-EEL1
3F-ESP1
3F-NL1
3F-NL2
DS-EEP1
3F-NL1-ECB
+48"
AFF
GENERAL NOTES
1. EQUIPMENT SHOWN WITH BOLD LINEWEIGHTS INDICATES EQUIPMENT TO BE
FURNISHED AND INSTALLED BY THE CONTRACTOR.
2. ELECTRICAL GEAR SHOWN FOR LOCATION PURPOSE. REFER TO ONE-LINE
DIAGRAM ON SHEET EP401 FOR EQUIPMENT INTERCONNECTION REQUIREMENTS.
3. MAINTAIN NEC REQUIRED CLEARANCES DURING INSTALLATION OF NEW
ELECTRICAL GEAR. PROVIDE STRUT RACKING AS REQUIRED FOR COMPLIANCE.
4. ANY FLOOR MOUNTED ELECTRICAL GEAR SHALL BE INSTALLED ON AN
EQUIPMENT PAD, 4" MINIMUM THICKNESS.
5. EQUIPMENT FOR BOTH THE BASE BID AND DEDUCTIVE BID ALTERNATES ARE
SHOWN ON THE PLANS.
6. ALL WIRE RUNS SHOWN ON DRAWINGS ARE RUN THROUGH THE SPACE ABOVE
THE CEILING GRID ON THIS FLOOR.