SPKLR2-2026 Blank.xlsx

XLSX spreadsheet 15 KB Posted

Attached to
Fire Suppression Sprinklers at Coatesville VAMC
Solicitation number
36C24426Q0415
Issued by

About this file

This file is a pricing template (SPKLR2-2026 Blank.xlsx) associated with a solicitation for fire suppression sprinkler system inspection and maintenance services at the Coatesville VA Medical Center. The template is blank and does not contain completed pricing information, specific line items, quantities, or cost data. It is designed to be populated by offerors responding to Solicitation Number 36C24426Q0415 issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4.

The underlying solicitation requires a contractor to perform a five-year obstruction inspection, testing, and maintenance of the facility's sprinkler systems in compliance with NFPA 25 standards. Required services include internal pipe assessments, valve inspections, fire department connection (FDC) hydrostatic testing, hydrant flow testing, sprinkler gauge replacements, and annual fire pump inspections in Building 1. All work must be completed within 30 calendar days of award, conducted Monday through Friday between 8:00 a.m. and 4:30 p.m., with no weekend or Federal holiday work permitted. The contractor must coordinate system shutdowns with the VA Point of Contact, comply with VA safety protocols, and ensure qualified technicians perform all work while wearing visible company identification badges.

View the file

Other files

File Type Posted
36C24426Q0415 0005.docx DOCX document
36C24426Q0415 0004.docx DOCX document
Site Visit Information 07-9-2026.docx DOCX document
RFI Q and As.docx DOCX document
SPKLR38-2026 Blank.xlsx XLSX spreadsheet
SPKLR57-2026 Blank.xlsx XLSX spreadsheet
36C24426Q0415 0003.docx DOCX document
SPKLR139-2026.xlsx XLSX spreadsheet
SPKLR1-2026 Blank.xlsx XLSX spreadsheet
SPKLR39-2026 Blank.xlsx XLSX spreadsheet
SPKLR7-2026 Blank.xlsx XLSX spreadsheet
SPKLR59-2026.xlsx XLSX spreadsheet
SPKLR8-2026 Blank.xlsx XLSX spreadsheet
SPKLR9-2026 Blank.xlsx XLSX spreadsheet
SPKLR4-2026 Blank.xlsx XLSX spreadsheet
SPKLR138-2026 Blank.xlsx XLSX spreadsheet
SPKLR3-2026 Blank.xlsx XLSX spreadsheet
SPKLR6-2026.xlsx XLSX spreadsheet
SPKLR69-2026.xlsx XLSX spreadsheet
SPKLR138E-2026 Blank.xlsx XLSX spreadsheet
36C24426Q0415 0002.docx DOCX document
36C24426Q0415 0001.docx DOCX document
SCA 2015-5791 Rev 31.pdf PDF
36C24426Q0415.docx DOCX document
852.219-75 MUST SIGN AND RETURN WITH PROPOSAL.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Building 2

SPRINKLER SYSTEM INSPECTION AND TEST
Building 2
Year 20261ST2ND
Date
Inspector
Main Drain
Static Pressure
Residual Pressure
Chamber Refill Time
Flow Test Results
FloorTest Location6"Zone6"Zone
BASEMENT 2002-0151CENTER STAIR
FIRST 2002-0162CENTER STAIR
SECOND 2002-0168CENTER STAIR
ATTIC 2002-0171CENTER STAIR
Tamper Valve Test Results
DEVICELOCATION
OS & Y 2002-0148SVC. RM.
P.I.V. 2002-0157N.E. OF BLDG.
MAIN RISER 2002-0149CENTER STAIR
BSMT. ZONE 2002-0150CENTER STAIR
EAST STANDPIPE 2002-0156EAST STAIR
WEST STNDPIPE 2002-0154WEST STAIR
1ST FL. ZONE 2002-0163CENTER STAIR
2ND FL. ZONE 2002-0169CENTER STAIR
ATTIC ZONE 2002-0170CENTER STAIR
SPRINKLER BOXSVC. RM.
FDCBY WEST ENTRANCE
TESTED SEMI-ANNUALLY IAW
NFPA 25: STANDARD FOR THE INSPECTION, TESTING AND MAINTENANCE
OF WATER BASED FIRE PROTECTION SYSTEMS, 2023 EDITION
ACCEPTABLE TESTING RESULTS
P = PASSED INSPECTION / TEST
F = FAILED INSPECTION / TEST
D= DISCONNECTED
C= CONTRACTOR TEST
TIMED RESULTS NOTED IN MINUTES AND SECONDS ( EXAMPLE 1M 30S )