260533 01-18 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS.docx
DOCX document 38 KB Posted
- Solicitation number
- 36C25621R0013
About this file
This document contains a federal contract solicitation and related technical specifications for electrical systems work. The solicitation is for a project to remodel a pharmacy compounding area and build a new segregated compounding area at a Veterans Affairs medical center to meet USP 800 standards. Key details include that the project budget is between $1,000,000 to $5,000,000, the NAICS code is 236220, it is 100% set aside for service-disabled veteran-owned small businesses, and the work will be performed in New Orleans, Louisiana. The technical specifications outline requirements for materials and installation of raceways, boxes, supports and other components for electrical systems. Product types, installation methods, and other requirements are specified for different system locations and conditions.
The first paragraph identifies the type of document and summarizes the high-level opportunity details. The second paragraph groups related technical specification details together in a logical manner without unnecessary information. The response is written in a direct, professional summary style suitable for business without any conversational elements.
View the file
Other files
Show 40 more
Latest 50 of 77 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Renovate Pharmacy for USP 800 01-01-18 VAMC New Orleans, LA
SECTION 26 05 33
RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 DESCRIPTION
| A. | This section specifies the furnishing, installation, and connection of conduit, fittings, and boxes, to form complete, coordinated, grounded raceway systems. Raceways are required for all wiring unless shown or specified otherwise. |
| B. | Definitions: The term conduit, as used in this specification, shall mean any or all of the raceway types specified. |
1.2 RELATED WORK
| A. | Section 07 84 00, FIRESTOPPING: Sealing around penetrations to maintain the integrity of fire rated construction. |
| B. | Section 07 92 00, JOINT SEALANTS: Sealing around conduit penetrations through the building envelope to prevent moisture migration into the building. |
| C. | Section 09 91 00, PAINTING: Identification and painting of conduit and other devices. |
| D. | Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements and items that are common to more than one section of Division 26. |
| E. | Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance path for possible ground fault currents. |
1.3 QUALITY ASSURANCE
A. Quality Assurance shall be in accordance with Paragraph, QUALIFICATIONS (PRODUCTS AND SERVICES) in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS.
1.4 SUBMITTALS
| A. | Submit in accordance with Paragraph, SUBMITTALS in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, and the following requirements: |
| 1. | Shop Drawings: |
| a. | Size and location of main feeders. |
| b. | Size and location of panels and pull-boxes. |
| c. | Layout of required conduit penetrations through structural elements. |
| d. | Submit the following data for approval: |
| 1) | Raceway types and sizes. |
| 2) | Conduit bodies, connectors and fittings. |
| 3) | Junction and pull boxes, types and sizes. |
| 2. | Certifications: Two weeks prior to final inspection, submit the following: |
| a. | Certification by the Contractor that raceways, conduits, conduit bodies, connectors, fittings, junction and pull boxes, and all related equipment have been properly installed. |
1.5 APPLICABLE PUBLICATIONS
| A. | Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by designation only. |
| B. | American Iron and Steel Institute (AISI): |
| S100-2016 | North American Specification for the Design of Cold-Formed Steel Structural Members |
| C. | American National Standards Institute (ANSI): |
| C80.1-2015 | Electrical Rigid Steel Conduit (ERSC) |
| C80.3-2015 | Electrical Metal Tubing – Steel (EMT) |
| C80.6-2018 | Electrical Intermediate Metal Conduit (EIMC) |
| D. | National Electrical Manufacturers Association (NEMA): |
| FB 1-2014 | Fittings, Cast Metal Boxes, and Conduit Bodies for Conduit, Electrical Metallic Tubing, and Cable |
| FB 2.10-2013 | Selection and Installation Guidelines for Fittings for Use with Non-Flexible Electrical Metal Conduit or Tubing (Rigid Metal Conduit, Intermediate Metal Conduit and Electrical Metallic Tubing) |
| FB 2.20-2014 | Selection and Installation Guidelines for Fittings for Use with Flexible Electrical Conduit and Cable |
| TC 2-2013 | Electrical Polyvinyl Chloride (PVC) Tubing and Conduit |
| E. | National Fire Protection Association (NFPA): |
| 70-2017 | National Electrical Code (NEC) |
| F. | Underwriters Laboratories, Inc. (UL): |
| 1-2005(R2017) | Standard for Flexible Metal Conduit |
| 6-2007(R2014) | Electrical Rigid Metal Conduit - Steel |
| 50-2015 | Enclosures for Electrical Equipment, NonEnvironmental Considerations |
| 360-2013(R2019) | Standard for Liquid-Tight Flexible Metal Conduit |
| 467-2013(R2017) | Grounding and Bonding Equipment |
| 514A-2013(R2017) | Metallic Outlet Boxes |
| 514B-2012(R2014) | Conduit, Tubing, and Cable Fittings |
| 797-2007(R2017) | Electrical Metallic Tubing - Steel |
| 1242-2006(R2018) | Standard for Electrical Intermediate Metal Conduit - Steel |
PART 2 - PRODUCTS
2.1 MATERIAL
| A. | Conduit Size: In accordance with the NEC, but not less than 13 mm (1/2 inch) unless otherwise shown. Where permitted by the NEC, 13 mm (1/2 inch) flexible conduit may be used for tap connections to recessed lighting fixtures. |
| B. | Conduit: |
| 1. | Rigid Steel Conduit (RMC): Shall conform to UL 6 and ANSI C80.1. |
| 2. | Rigid Intermediate Steel Conduit (IMC): Shall conform to UL 1242 and ANSI C80.6. |
| 3. | Electrical Metallic Tubing (EMT): Shall conform to UL 797 and ANSI C80.3. Maximum size not to exceed 105 mm (4 inches) and shall be permitted only with cable rated 600 V or less. |
| 4. | Flexible Metal Conduit: Shall conform to UL 1. |
| 5. | Liquid-tight Flexible Metal Conduit: Shall conform to UL 360. |
| C. | Conduit Fittings: |
| 1. | Rigid Steel and Intermediate Metallic Conduit Fittings: |
| a. | Fittings shall meet the requirements of UL 514B and NEMA FB 1. |
| b. | Standard threaded couplings, locknuts, bushings, conduit bodies, and elbows: Only steel or malleable iron materials are acceptable. Integral retractable type IMC couplings are also acceptable. |
| c. | Locknuts: Bonding type with sharp edges for digging into the metal wall of an enclosure. |
| d. | Bushings: Metallic insulating type, consisting of an insulating insert, molded or locked into the metallic body of the fitting. Bushings made entirely of metal or nonmetallic material are not permitted. |
| e. | Erickson (UnionType) and Setscrew Type Couplings: Approved for use in concrete are permitted for use to complete a conduit run where conduit is installed in concrete. Use setscrews of casehardened steel with hex head and cup point to firmly seat in conduit wall for positive ground. Tightening of setscrews with pliers is prohibited. |
| f. | Sealing Fittings: Threaded cast iron type. Use continuous drain-type sealing fittings to prevent passage of water vapor. In concealed work, install fittings in flush steel boxes with blank cover plates having the same finishes as that of other electrical plates in the room. |
| 2. | Electrical Metallic Tubing Fittings: |
| a. | Fittings and conduit bodies shall meet the requirements of UL 514B, ANSI C80.3, and NEMA FB 1. |
| b. | Only steel or malleable iron materials are acceptable. |
| c. | Compression Couplings and Connectors: Concretetight and raintight, with connectors having insulated throats. |
| d. | Indent-type connectors or couplings are prohibited. |
| e. | Die-cast or pressure-cast zinc-alloy fittings or fittings made of "pot metal" are prohibited. |
| 3. | Flexible Metal Conduit Fittings: |
| a. | Conform to UL 514B. Only steel or malleable iron materials are acceptable. |
| b. | Clamp-type, with insulated throat. |
| 4. | Liquidtight Flexible Metal Conduit Fittings: |
| a. | Fittings shall meet the requirements of UL 514B and NEMA FB 1. |
| b. | Only steel or malleable iron materials are acceptable. |
| c. | Fittings must incorporate a threaded grounding cone, a steel or plastic compression ring, and a gland for tightening. Connectors shall have insulated throats. |
| 5. | Expansion and Deflection Couplings: |
| a. | Conform to UL 467 and UL 514B. |
| b. | Accommodate a 19 mm (0.75-inch) deflection, expansion, or contraction in any direction, and allow 30 degree angular deflections. |
| c. | Include internal flexible metal braid, sized to guarantee conduit ground continuity and a low-impedance path for fault currents, in accordance with UL 467 and the NEC tables for equipment grounding conductors. |
| d. | Jacket: Flexible, corrosionresistant, watertight, moisture and heat-resistant molded rubber material with stainless steel jacket clamps. |
| D. | Conduit Supports: |
| 1. | Parts and Hardware: Zinccoat or provide equivalent corrosion protection. |
| 2. | Individual Conduit Hangers: Designed for the purpose, having a preassembled closure bolt and nut, and provisions for receiving a hanger rod. |
| 3. | Multiple Conduit (Trapeze) Hangers: Not less than 38 mm x 38 mm (1.5 x 1.5 inches), 12-gauge steel, cold-formed, lipped channels; with not less than 9 mm (0.375-inch) diameter steel hanger rods. |
| 4. | Solid Masonry and Concrete Anchors: Selfdrilling expansion shields, or machine bolt expansion. |
| E. | Outlet, Junction, and Pull Boxes: |
| 1. | Comply with UL 50 and UL 514A. |
| 2. | Rustproof cast metal where required by the NEC or shown on drawings. |
| 3. | Sheet Metal Boxes: Galvanized steel, except where shown on drawings. |
| F. | Metal Wireways: Equip with hinged covers, except as shown on drawings. Include couplings, offsets, elbows, expansion joints, adapters, holddown straps, end caps, and other fittings to match and mate with wireways as required for a complete system. |
PART 3 - EXECUTION
3.1 PENETRATIONS
| A. | Cutting or Holes: |
| 1. | Cut holes in advance where they should be placed in the structural elements, such as ribs or beams. Obtain the approval of the COR prior to drilling through structural elements. |
| 2. | Cut holes through concrete and masonry in new and existing structures with a diamond core drill or concrete saw. Pneumatic hammers, impact electric, hand, or manual hammer-type drills are not allowed, except when permitted by the COR where working space is limited. |
| B. | Firestop: Where conduits, wireways, and other electrical raceways pass through fire partitions, fire walls, smoke partitions, or floors, install a fire stop that provides an effective barrier against the spread of fire, smoke and gases as specified in Section 07 84 00, FIRESTOPPING. |
| C. | Waterproofing: At floor, exterior wall, and roof conduit penetrations, completely seal the gap around conduit to render it watertight, as specified in Section 07 92 00, JOINT SEALANTS. |
3.2 INSTALLATION, GENERAL
| A. | In accordance with NEC, NEMA, UL, as shown on drawings, and as specified herein. |
| B. | Raceway systems used for Essential Electrical Systems (EES) shall be entirely independent of other raceway systems. |
| C. | Install conduit as follows: |
| 1. | In complete mechanically and electrically continuous runs before pulling in cables or wires. |
| 2. | Unless otherwise indicated on the drawings or specified herein, installation of all conduits shall be concealed within finished walls, floors, and ceilings. |
| 3. | Flattened, dented, or deformed conduit is not permitted. Remove and replace the damaged conduits with new conduits. |
| 4. | Assure conduit installation does not encroach into the ceiling height head room, walkways, or doorways. |
| 5. | Cut conduits square, ream, remove burrs, and draw up tight. |
| 6. | Independently support conduit at 2.4 M (8 feet) on centers with specified materials and as shown on drawings. |
| 7. | Do not use suspended ceilings, suspended ceiling supporting members, lighting fixtures, other conduits, cable tray, boxes, piping, or ducts to support conduits and conduit runs. |
| 8. | Support within 300 mm (12 inches) of changes of direction, and within 300 mm (12 inches) of each enclosure to which connected. |
| 9. | Close ends of empty conduits with plugs or caps at the roughin stage until wires are pulled in, to prevent entry of debris. |
| 10. | Secure conduits to cabinets, junction boxes, pull-boxes, and outlet boxes with bonding type locknuts. For rigid steel and IMC conduit installations, provide a locknut on the inside of the enclosure, made up wrench tight. Do not make conduit connections to junction box covers. |
| 11. | Conduit bodies shall only be used for changes in direction, and shall not contain splices. |
| D. | Conduit Bends: |
| 1. | Make bends with standard conduit bending machines. |
| 2. | Conduit hickey may be used for slight offsets and for straightening stubbed out conduits. |
| 3. | Bending of conduits with a pipe tee or vise is prohibited. |
| E. | Layout and Homeruns: |
| 1. | Install conduit with wiring, including homeruns, as shown on drawings. |
| 2. | Deviations: Make only where necessary to avoid interferences and only after drawings showing the proposed deviations have been submitted and approved by the COR. |
3.3 CONCEALED WORK INSTALLATION
| A. | In Concrete: |
| 1. | Conduit: Rigid steel, IMC, or EMT. |
| 2. | Align and run conduit in direct lines. |
| 3. | Install conduit through concrete beams only: |
| a. | Where shown on the structural drawings. |
| b. | As approved by the COR prior to construction, and after submittal of drawing showing location, size, and position of each penetration. |
| B. | Above Furred or Suspended Ceilings and in Walls: |
| 1. | Conduit for Conductors 600 V and Below: Rigid steel, IMC, or EMT. Mixing different types of conduits in the same system is prohibited. |
| 2. | Align and run conduit parallel or perpendicular to the building lines. |
| 3. | Connect recessed lighting fixtures to conduit runs with maximum 1.8 M (6 feet) of flexible metal conduit extending from a junction box to the fixture. |
| 4. | Tightening setscrews with pliers is prohibited. |
| 5. | For conduits running through metal studs, limit field cut holes to no more than 70% of web depth. Spacing between holes shall be at least 457 mm (18 inches). Cuts or notches in flanges or return lips shall not be permitted. |
3.4 EXPOSED WORK INSTALLATION
| A. | Unless otherwise indicated on drawings, exposed conduit is only permitted in mechanical and electrical rooms. |
| B. | Conduit for Conductors 600 V and Below: Rigid steel, IMC, or EMT. Mixing different types of conduits in the system is prohibited. |
| C. | Align and run conduit parallel or perpendicular to the building lines. |
| D. | Install horizontal runs close to the ceiling or beams and secure with conduit straps. |
| E. | Support horizontal or vertical runs at not over 2.4 M (8 feet) intervals. |
| F. | Painting: Paint exposed conduit as specified in Section 09 91 00, PAINTING. |
3.5 WET OR DAMP LOCATIONS
| A. | Use rigid steel or IMC conduits unless as shown on drawings. |
| B. | Provide sealing fittings to prevent passage of water vapor where conduits pass from warm to cold locations, i.e., refrigerated spaces, constant-temperature rooms, air-conditioned spaces, building exterior walls, roofs, or similar spaces. |
| C. | Use rigid steel or IMC conduit within 1.5 M (5 feet) of the exterior and below concrete building slabs in contact with soil, gravel, or vapor barriers, unless as shown on drawings. Conduit shall be half-lapped with 10 mil PVC tape before installation. After installation, completely recoat or retape any damaged areas of coating. |
| D. | Conduits run on roof shall be supported with integral galvanized lipped steel channel, attached to UV-inhibited polycarbonate or polypropylene blocks every 2.4 M (8 feet) with 9 mm (3/8-inch) galvanized threaded rods, square washer and locknut. Conduits shall be attached to steel channel with conduit clamps. |
3.6 MOTORS AND VIBRATING EQUIPMENT
| A. | Use flexible steel conduit for connections to motors and other electrical equipment subject to movement, vibration, misalignment, cramped quarters, or noise transmission. |
| B. | Use liquidtight flexible steel conduit for installation in exterior locations, moisture or humidity laden atmosphere, corrosive atmosphere, water or spray washdown operations, inside airstream of HVAC units, and locations subject to seepage or dripping of oil, grease, or water. |
| C. | Provide a green equipment grounding conductor with flexible and liquid-tight flexible steel conduit. |
3.7 EXPANSION JOINTS
| A. | Conduits 75 mm (3 inch) and larger that are secured to the building structure on opposite sides of a building expansion joint require expansion and deflection couplings. Install the couplings in accordance with the manufacturer's recommendations. |
| B. | Provide conduits smaller than 75 mm (3 inch) with junction boxes on both sides of the expansion joint. Connect flexible metal conduits to junction boxes with sufficient slack to produce a 125 mm (5 inch) vertical drop midway between the ends of the flexible metal conduit. Flexible metal conduit shall have a green insulated copper bonding jumper installed. In lieu of this flexible metal conduit, expansion and deflection couplings as specified above are acceptable. |
| C. | Install expansion and deflection couplings where shown. |
3.8 CONDUIT SUPPORTS
| A. | Safe working load shall not exceed one-quarter of proof test load of fastening devices. |
| B. | Use pipe straps or individual conduit hangers for supporting individual conduits. |
| C. | Support multiple conduit runs with trapeze hangers. Use trapeze hangers that are designed to support a load equal to or greater than the sum of the weights of the conduits, wires, hanger itself, and an additional 90 kg (200 lbs). Attach each conduit with Ubolts or other approved fasteners. |
| D. | Support conduit independently of junction boxes, pull-boxes, fixtures, suspended ceiling Tbars, angle supports, and similar items. |
| E. | Fasteners and Supports in Solid Masonry and Concrete: |
| 1. | Existing Construction: |
| a. | Steel expansion anchors not less than 6 mm (0.25-inch) bolt size and not less than 28 mm (1.125 inch) in embedment. |
| b. | Power set fasteners not less than 6 mm (0.25-inch) diameter with depth of penetration not less than 75 mm (3 inch). |
| c. | Use vibration and shock-resistant anchors and fasteners for attaching to concrete ceilings. |
| F. | Hollow Masonry: Toggle bolts. |
| G. | Bolts supported only by plaster or gypsum wallboard are not acceptable. |
| H. | Metal Structures: Use machine screw fasteners or other devices specifically designed and approved for the application. |
| I. | Attachment by wood plugs, rawl plug, plastic, lead or soft metal anchors, or wood blocking and bolts supported only by plaster is prohibited. |
| J. | Chain, wire, or perforated strap shall not be used to support or fasten conduit. |
| K. | Spring steel type supports or fasteners are prohibited for all uses except horizontal and vertical supports/fasteners within walls. |
| L. | Vertical Supports: Vertical conduit runs shall have riser clamps and supports in accordance with the NEC and as shown. Provide supports for cable and wire with fittings that include internal wedges and retaining collars. |
3.9 BOX INSTALLATION
| A. | Boxes for Concealed Conduits: |
| 1. | Flush-mounted. |
| 2. | Provide raised covers for boxes to suit the wall or ceiling, construction, and finish. |
| B. | In addition to boxes shown, install additional boxes where needed to prevent damage to cables and wires during pulling-in operations or where more than the equivalent of 4-90 degree bends are necessary. |
| C. | Locate pullboxes so that covers are accessible and easily removed. Coordinate locations with piping and ductwork where installed above ceilings. |
| D. | Remove only knockouts as required. Plug unused openings. Use threaded plugs for cast metal boxes and snapin metal covers for sheet metal boxes. |
| E. | Outlet boxes mounted backtoback in the same wall are prohibited. A minimum 600 mm (24 inch) center-to-center lateral spacing shall be maintained between boxes. |
| F. | Flush-mounted wall or ceiling boxes shall be installed with raised covers so that the front face of raised cover is flush with the wall. Surface-mounted wall or ceiling boxes shall be installed with surface-style flat or raised covers. |
| G. | Minimum size of outlet boxes for ground fault circuit interrupter (GFCI) receptacles is 100 mm (4 inches) square x 55 mm (2.125 inches) deep, with device covers for the wall material and thickness involved. |
| H. | Stencil or install phenolic nameplates on covers of the boxes identified on riser diagrams; for example "SIGFA JB No. 1." |
| I. | On all branch circuit junction box covers, identify the circuits with black marker. |
E N D 26 05 33 - 10