072113 Thermal Insulation.docx

DOCX document 29 KB Posted

Attached to
Z2DA--Proj #: 629-18-127, Remodel Pharmacy for USP 800
Solicitation number
36C25621R0013
Issued by

About this file

This document contains a federal contract solicitation for remodeling pharmacy services to meet USP 800 requirements. The solicitation is for a 100% Service-Disabled Veteran-Owned Small Business set-aside to provide all labor, materials, tools, and equipment to remodel the current pharmacy compounding area and build out a new segregated compounding area at the Southeast Louisiana Veterans Health Care System facility in New Orleans. The project cost is estimated to be between $1,000,000 and $5,000,000. Offerors must be verified as a Service-Disabled Veteran-Owned Small Business in the Vendor Information Pages database. The work is to be performed in New Orleans, Louisiana under NAICS code 236220 with a small business size standard of $39.5 million. The solicitation includes requirements for registration in the System for Award Management database.

View the file

Other files

File Type Posted
36C25621R0013 0002.docx DOCX document
Sign in Sheet - Pharmacy Remodel Project.pdf PDF
36C25621R0013 0001.pdf PDF
054000 Cold-Formed Metal Framing.docx DOCX document
013323 Shop Drawings.docx DOCX document
262921 01-17 ENCLOSED SWITCHES AND CIRCUIT BREAKERS.docx DOCX document
230593 02-15 TESTING ADJUSTING AND BALANCING FOR HVAC.docx DOCX document
000110 TOC.docx DOCX document
EXHIBIT C SUBCONTRACTOR INFORMATION AND CONSENT.docx DOCX document
General Decision LA 20190041 05-31-2019 Orleans Parish LA Building.pdf PDF
224000 09-15 PLUMBING FIXTURES.docx DOCX document
EXHIBIT A PERFORMANCE RELEVANCY SURVEY (1).docx DOCX document
260526 01-17 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS.docx DOCX document
017419 Construction Waste Management.doc DOC document
102600 Wall and Door Protection.docx DOCX document
220711 09-19 PLUMBING INSULATION.docx DOCX document
234000 2-12 HVAC AIR CLEANING DEVICES.doc DOC document
230541 02-15 NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT.docx DOCX document
230711 02-15 HVAC AND BOILER PLANT INSULATION.docx DOCX document
233100 3-13 HVAC DUCTS AND CASINGS .docx DOCX document
Architectural Final.pdf PDF
087113 ADO.docx DOCX document
088000 Glazing.docx DOCX document
230800 11-16 COMMISSIONING OF HVAC SYSTEMS.docx DOCX document
260519 01-17 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES.docx DOCX document
092900 Gypsum Board.docx DOCX document
221300 09-15 FACILITY SANITARY AND VENT PIPING.docx DOCX document
230511 8-17 COMMON WORK RESULTS FOR HVAC.docx DOCX document
000115 List of Drawings.docx DOCX document
092216 Non-Structural Metal Framing.docx DOCX document
Fire Protection Final.pdf PDF
099100 Painting.docx DOCX document
232500 02-15 HVAC WATER TREATMENT.docx DOCX document
Exhibit B Past and Present Performance Questionnaire.docx DOCX document
233700 02-15 AIR OUTLETS AND INLETS.docx DOCX document
087100 Door Hardware.docx DOCX document
081113 HM Doors and Frames.docx DOCX document
051200 Structural Steel.docx DOCX document
079200 Joint Sealants.docx DOCX document
262726 01-18 WIRING DEVICES.docx DOCX document
36C25621R0013_2.docx DOCX document
010000 General Requirements.docx DOCX document
075423 Thermoplastic Polyolefin Roofing.docx DOCX document
220523 09-15 GENERAL-DUTY VALVES FOR PLUMBING PIPING.docx DOCX document
260511 01-16 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS .docx DOCX document
096723-30 Resinous Decorative Mortar Flooring.docx DOCX document
078400 Firestopping.docx DOCX document
230923 9-11 DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC.doc DOC document
230512 08-17 GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT.docx DOCX document
211313 06-15 WET-PIPE SPRINKLER SYSTEMS.docx DOCX document
Show 40 more

Latest 50 of 77 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Renovate Pharmacy for USP 800 10-01-17 VAMC New Orleans, LA

SECTION 07 21 13

THERMAL INSULATION

GENERAL

SUMMARY

Section Includes:

Acoustical insulation.

Batt and blanket insulation at interior framed partitions and ceilings.

RELATED REQUIREMENTS

Safing Insulation: Section 07 84 00, FIRESTOPPING.

APPLICABLE PUBLICATIONS

Comply with references to extent specified in this section.

ASTM International (ASTM):

C55215 - Cellular Glass Thermal Insulation.

C55313 - Mineral Fiber Blanket Thermal Insulation for Commercial and Industrial Applications.

C66512 - MineralFiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing.

C95415 - Steel Drill Screws for the Application of Gypsum Panel Products or Metal Plaster Base to Steel Studs From 0.033 (0.84 mm) inch to 0.112 inch (2.84 mm) in thickness.

C100214 - Steel SelfPiercing Tapping Screws for Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs.

E8415a - Surface Burning Characteristics of Building Materials.

F166715 - Driven Fasteners: Nails, Spikes, and Staples.

SUBMITTALS

Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

Manufacturer's Literature and Data:

Description of each product.

Adhesive indicating manufacturer recommendation for each application.

DELIVERY

Deliver products in manufacturer's original sealed packaging.

Mark packaging, legibly. Indicate manufacturer's name or brand, type, production run number, and manufacture date.

Before installation, return or dispose of products within distorted, damaged, or opened packaging.

STORAGE AND HANDLING

Store products indoors in dry, weathertight facility.

Protect products from damage during handling and construction operations.

WARRANTY

Construction Warranty: FAR clause 52.246-21, "Warranty of Construction."

PRODUCTS

INSULATION - GENERAL

Insulation Thickness:

Provide thickness required by Rvalue shown on drawings.

Provide thickness indicated when Rvalue is not shown on drawings.

Insulation Types:

Provide one insulation type for each application.

Sustainable Construction Requirements:

Insulation Recycled Content:

Rock wool material: 75 percent recovered material.

ACOUSTICAL INSULATION

Semi Rigid, Batts and Blankets:

Widths and lengths to fit tight against framing.

Mineral Fiber boards: ASTM C553, Type II, flexible, or Type III, semi rigid unfaced.

Density: nominal 4.5 pound.

Mineral Fiber Batt or Blankets: ASTM C665 unfaced.

Maximum Surface Burning Characteristics: ASTM E84.

Flame Spread Rating: 25.

Smoke Developed Rating: 450.

ACCESSORIES

Fasteners:

Staples or Nails: ASTM F1667, zinccoated, size and type to suit application.

Screws: ASTM C954 or ASTM C1002, size and length to suit application with washer minimum 50 mm (2 inches) diameter.

Impaling Pins: Steel pins with head minimum 50 mm (2 inches) diameter.

Length: As required to extend beyond insulation and retain cap washer when washer is placed on pin.

Adhesive: Type recommended by manufacturer to suit application.

Tape:

Pressure sensitive adhesive on one face.

EXECUTION

PREPARATION

Examine and verify substrate suitability for product installation.

Protect existing construction and completed work from damage.

Clean substrates. Remove contaminants capable of affecting subsequently installed product's performance.

INSTALLATION - GENERAL

Install products according to manufacturer's instructions and approved submittal drawings.

When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.

Install insulation with vapor barrier facing the heated side, unless indicated otherwise.

Install batt and blanket insulation with joints tight. Fill framing voids completely. Seal penetrations, terminations, facing joints, facing cuts, tears, and unlapped joints with tape.

Fit insulation tight against adjoining construction and penetrations, unless indicated otherwise.

ACOUSTICAL INSULATION

General:

Install insulation without voids.

Pack insulation around door frames and windows, in building expansion joints, door soffits, and other voids.

Pack behind outlets, around pipes, ducts, and services encased in walls.

Hold insulation in place with pressure sensitive tape.

Lap facer flanges together over framing for continuous surface. Seal all penetrations through the insulation and facers.

Do not compress insulation below required thickness except where embedded items prevent required thickness.

Semi Rigid, Batts and Blankets:

When insulation is not full thickness of cavity, adhere insulation to one side of cavity, maintaining continuity of insulation and covering penetrations or embedments.

Wood Framing:

Fasten blanket insulation between wood framing and joists with nails or staples through flanged edges of insulation.

Space fastenings maximum 150 mm (6 inches) on center.

Metal Framing:

Fasten insulation between metal framing with pressure sensitive tape continuous along flanged edges.

At metal framing or ceilings suspension systems, install blanket insulation above suspended ceilings or metal framing at right angles to the main runners or framing.

Tape insulation tightly together so no gaps occur and metal framing members are covered by insulation.

CLEANING

Remove excess adhesive before adhesive sets.

PROTECTION

Protect insulation from construction operations.

Repair damage.

- E N D - 07 21 13 - 1