087113 ADO.docx

DOCX document 29 KB Posted

Attached to
Z2DA--Proj #: 629-18-127, Remodel Pharmacy for USP 800
Solicitation number
36C25621R0013
Issued by

About this file

This file provides specifications for automatic door operators and related controls to be installed as part of a pharmacy renovation project at the Southeast Louisiana Veterans Health Care System facility in New Orleans, Louisiana. The project requires providing all labor, materials and equipment to remodel the current pharmacy compounding area and build out a new segregated compounding area to meet USP 800 standards. The work must be performed by a verified Service-Disabled Veteran-Owned Small Business, and offers will only be accepted from contractors registered in the System for Award Management database. The magnitude of the construction project is estimated between $1 million and $5 million.

View the file

Other files

File Type Posted
36C25621R0013 0002.docx DOCX document
Sign in Sheet - Pharmacy Remodel Project.pdf PDF
36C25621R0013 0001.pdf PDF
054000 Cold-Formed Metal Framing.docx DOCX document
013323 Shop Drawings.docx DOCX document
262921 01-17 ENCLOSED SWITCHES AND CIRCUIT BREAKERS.docx DOCX document
230593 02-15 TESTING ADJUSTING AND BALANCING FOR HVAC.docx DOCX document
000110 TOC.docx DOCX document
EXHIBIT C SUBCONTRACTOR INFORMATION AND CONSENT.docx DOCX document
General Decision LA 20190041 05-31-2019 Orleans Parish LA Building.pdf PDF
224000 09-15 PLUMBING FIXTURES.docx DOCX document
EXHIBIT A PERFORMANCE RELEVANCY SURVEY (1).docx DOCX document
260526 01-17 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS.docx DOCX document
017419 Construction Waste Management.doc DOC document
102600 Wall and Door Protection.docx DOCX document
220711 09-19 PLUMBING INSULATION.docx DOCX document
234000 2-12 HVAC AIR CLEANING DEVICES.doc DOC document
230541 02-15 NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT.docx DOCX document
230711 02-15 HVAC AND BOILER PLANT INSULATION.docx DOCX document
072113 Thermal Insulation.docx DOCX document
233100 3-13 HVAC DUCTS AND CASINGS .docx DOCX document
Architectural Final.pdf PDF
088000 Glazing.docx DOCX document
230800 11-16 COMMISSIONING OF HVAC SYSTEMS.docx DOCX document
260519 01-17 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES.docx DOCX document
092900 Gypsum Board.docx DOCX document
221300 09-15 FACILITY SANITARY AND VENT PIPING.docx DOCX document
230511 8-17 COMMON WORK RESULTS FOR HVAC.docx DOCX document
000115 List of Drawings.docx DOCX document
092216 Non-Structural Metal Framing.docx DOCX document
Fire Protection Final.pdf PDF
099100 Painting.docx DOCX document
232500 02-15 HVAC WATER TREATMENT.docx DOCX document
Exhibit B Past and Present Performance Questionnaire.docx DOCX document
233700 02-15 AIR OUTLETS AND INLETS.docx DOCX document
087100 Door Hardware.docx DOCX document
081113 HM Doors and Frames.docx DOCX document
051200 Structural Steel.docx DOCX document
079200 Joint Sealants.docx DOCX document
262726 01-18 WIRING DEVICES.docx DOCX document
36C25621R0013_2.docx DOCX document
010000 General Requirements.docx DOCX document
075423 Thermoplastic Polyolefin Roofing.docx DOCX document
220523 09-15 GENERAL-DUTY VALVES FOR PLUMBING PIPING.docx DOCX document
260511 01-16 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS .docx DOCX document
096723-30 Resinous Decorative Mortar Flooring.docx DOCX document
078400 Firestopping.docx DOCX document
230923 9-11 DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC.doc DOC document
230512 08-17 GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT.docx DOCX document
211313 06-15 WET-PIPE SPRINKLER SYSTEMS.docx DOCX document
Show 40 more

Latest 50 of 77 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Renovate Pharmacy for USP 800 VAMC New Orleans, LA 02-01-16

SECTION 08 71 13

AUTOMATIC DOOR OPERATORS

GENERAL

SUMMARY

Section Includes:

Automatic operators for swinging doors.

RELATED REQUIREMENTS

Door Hardware: Section 08 71 00, DOOR HARDWARE.

Electric General Wiring, Connections and Equipment Requirements: Division 26, ELECTRICAL.

APPLICABLE PUBLICATIONS

Comply with references to extent specified in this section.

ASTM International (ASTM):

B20914 - Aluminum and AluminumAlloy Sheet and Plate.

A1008/A1008M15 - Steel, Sheet, ColdRolled, Carbon, Structural, HighStrength LowAlloy, HighStrength LowAlloy with Improved Formability, Solution Hardened, and Baked Hardenable.

Builders Hardware Manufacturers Association (BHMA):

BHMA A156.1011 - Power Operated Pedestrian Doors.

National Fire Protection Association (NFPA):

10115 - Life Safety Code.

Underwriters Laboratories (UL):

32513 - Standard for Doors, Drapery, Gate, Louver, and Window Operators and Systems.

SUBMITTALS

Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

Submittal Drawings:

Show size, configuration, and fabrication and installation details.

Manufacturer's Literature and Data:

Description of each product.

Installation instructions.

Warranty.

Sustainable Construction Submittals:

Recycled Content: Identify postconsumer and preconsumer recycled content percentage by weight.

Test reports: Certify each product complies with specifications.

Qualifications: Substantiate qualifications comply with specifications.

Manufacturer with project experience list.

Installer with project experience list.

Operation and Maintenance Data:

Care instructions for each exposed finish product.

Startup, maintenance, troubleshooting, emergency, and shutdown instructions for each operational product.

QUALITY ASSURANCE

Manufacturer’s Qualifications:

Regularly manufactures specified products.

Manufactured specified products with satisfactory service on five similar installations for minimum five years.

Provide contact names and addresses for completed projects when requested by Contracting Officer's Representative.

Installer’s Qualifications: Experienced installer, approved by the manufacturer.

WARRANTY

Construction Warranty: FAR clause 52.24621, "Warranty of Construction."

Manufacturer's Warranty: Warrant automatic door operators against material and manufacturing defects.

Warranty Period: Two years.

PRODUCTS

SYSTEM PERFORMANCE

Comply with requirements of BHMA A156.10. Unless otherwise indicated on Drawings, provide operators that move doors from fully closed to fully opened position in five seconds maximum time interval, when speed adjustment is at maximum setting.

Equipment: Conforming to UL 325. Provide key operated power disconnect wall switch for each door installation.

Electrical Wiring, Connections and Equipment: Motors, starters, controls, associated devices, and interconnecting wiring required for installation. Equipment and wiring as specified in Division 26, ELECTRICAL.

PRODUCTS - GENERAL

Provide door operators from one manufacturer.

Provide one type of operator throughout project.

Sustainable Construction Requirements:

Steel Recycled Content: 30 percent total recycled content, minimum.

Aluminum Recycled Content: 80 percent total recycled content, minimum.

SWING DOOR OPERATORS

General:

Type: Institutional type.

Size: As recommended by manufacturer for door weight and sizes.

Function:

Provide operators, enclosed in housing, permitting opening of door by energizing motor and stopped by electrically reducing Voltage and stalling motor against mechanical stop.

Door to close by means of spring energy, and closing force controlled by gear system and motor being used as dynamic brake without power, or controlled by hydraulic closer in electrohydraulic operators.

Opening and Closing Speeds: Field adjustable.

Operators with checking mechanism providing cushioning action at last part of door travel, in both opening and closing cycle.

Operators capable of recycling doors instantaneously to full open position from any point in closing cycle when control switch is activated.

When automatic power is interrupted or shutoff, permit doors to easily open manually without damage to automatic operator system.

Connect hardware with drive arm attached to door with pin linkage rotating in a selflubricating bearing. Prevent doors from pivoting on shaft of operator.

Operator Housing:

ASTM B209, Type 6063T5 aluminum alloy, 112 mm (41/2 inches) wide by 140 mm (5.5 inches) high by 3.2 mm (0.125 inch) thick, aluminum extrusions with enclosed end caps for application to 100 mm (4 inches) and larger frame systems.

Power Operator:

Completely assembled and sealed unit including gear drive transmission, mechanical spring and bearings, located in aluminum case and filled with special lubricant for extreme temperature conditions. Rubber mounted units with provisions for easy maintenance and replacement, without removing door from pivots or frame.

Motors:

Provide with interlock to prevent operation when doors are electrically locked from opening.

Electrical Control:

Selfcontained electrical control unit, including necessary transformers, relays, rectifiers, and other electronic components for proper operation and switching of power operator.

Connecting Harnesses: Interlocking plugs.

Accessories:

Metal mounting supports, brackets and other accessories necessary for installation of operators at head of door frames.

Microprocessor Controls:

Multifunction microprocessor control providing adjustable hold open time (130 seconds) with fully adjustable opening speed, LED indications for sensor input signals and operator status and power assist close options. Control capable of receiving activation signals from any device with normally open dry contact output.

Hold doors held open by low Voltage applied to the continuous duty motor.

Controls:

Adjustable safety circuit that monitors door operation and stops opening direction of door if obstruction is sensed.

Recycle feature that reopens door if obstruction is sensed at any point during closing cycle.

Standard three position key switch with functions for ON, OFF, and HOLD OPEN, mounted on operator enclosure, door frame, or wall, as indicated on drawings.

POWER UNITS

Selfcontained, electric operated and independent of door operator.

Capacity and size of power circuits according to automatic door operator manufacturer's specifications and Division 26 - ELECTRICAL.

DOOR CONTROLS

Control Devices: BHMA A156.10; control opening and closing functions.

Open doors when control device is actuated; hold doors in open positions; then, close doors after a adjustable time period, unless safety device or reactivated control interrupts operation.

Motion Detector:

Mounting: Surface or concealed.

Detection Area: 1500 mm (60 inches) deep and 1500 mm (60 inches) across, plus or minus 150 mm (6 inches).

Response Time: 25 milliseconds, maximum.

Control Power: 24 Volt DC.

Design units to be unaffected by cleaning material, solvents, dust, dirt and outdoor weather conditions.

SAFETY DEVICES

Swing Doors: Install presence sensor on pull side of door to detect any person standing in door swing path and prevent door from opening.

Time delay Switches: Adjustable between 3 to 60 seconds and control closing cycle of doors.

Install decal signs with "In" or "Do Not Enter" on both faces of each door where shown.

EXECUTION

PREPARATION

Examine and verify substrate suitability for product installation.

Verify door opening is correctly sized and within acceptable tolerances.

Protect existing construction and completed work from damage.

INSTALLATION

Install products according to manufacturer's instructions and approved submittal drawings.

When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.

Coordinate door installation with other related work.

Install manual controls and power disconnect switches recessed or semiflush mounted in partitions.

Secure operator components to adjacent construction with suitable fastenings.

Conceal conduits, piping, and electric equipment, in finish work.

Install power units in locations shown.

Where units are mounted on walls, provide metal supports or shelves for units.

Ensure equipment, including time delay switches, are accessible for maintenance and adjustment.

Ensure operators are adjusted and function properly for type of expected traffic.

Synchronize each leaf of pair doors to open and close simultaneously. Permit each door leaf to be opened manually, independent of other door leaf.

Install controls at positions shown and ensuring convenience for expected traffic.

Push Plate Wall Switches Mounting Height: 1000 mm (40 inches) maximum, unless otherwise approved by Contracting Officer's Representative.

DEMONSTRATION AND TRAINING

Instruct VA personnel in proper automatic door operator operation and maintenance.

Trainer: Manufacturer approved instructor.

Training Time: 2 hours minimum.

Coordinate instruction to VA personnel with VA Contracting Officer's Representative.

- E N D - 08 71 13 - 1