26-020-ITB_Conc_A_Ramp_Level_Office_Upgrades_-_Dwgs_04.22.26.pdf
PDF 23 MB Posted
- Attached to
- Concourse A Ramp Level Office Upgrades
- Solicitation number
- 26-020-ITB
- Issued by
- Bell County, Kentucky
About this file
Summary
This is a working drawing set prepared by GRW Engineers for the Kenton County Airport Board's Concourse A Ramp Level Office Upgrades project at Cincinnati/Northern Kentucky International Airport. The drawings document a comprehensive renovation of approximately 20,000 square feet on the ramp level of Concourse A, including the enclosure and upgrade of an existing temporary Emergency Operations Center (EOC) into a permanent facility, expansion of a gathering area into a larger conference or SAMS room, enhancements to the occupied Housekeeping Department office suite and restroom facilities, and finish upgrades in several vacant offices. The project requires a mandatory pre-bid meeting and site visit on Wednesday, April 1, 2026 at 10:00 am at CVG Airport's Main Terminal Ticketing area. Written questions are due by 11:59 pm on Friday, April 17, 2026, with responses posted by 11:59 pm on Tuesday, April 21, 2026. Sealed bids must be received electronically no later than 2:00 pm Eastern Time on Thursday, April 30, 2026, with contract award anticipated for May 26, 2026. The contract duration is 212 calendar days, with liquidated damages of $500.00 per day for delays and work commencement required within 10 days of receiving the Notice to Proceed.
The estimated project cost is approximately $951,000.00, with construction and installation costs estimated at $790,000.00 plus contingency, design, force labor, and miscellaneous costs. This is a federally-funded project under the Airport Improvement Program subject to Buy American Act compliance requiring U.S.-produced steel and manufactured goods unless an FAA waiver applies. Bidders must provide a proposal bond equal to five percent of the total bid amount and, upon award, furnish performance and payment bonds each in the amount of 100 percent of the contract price. All project personnel require airport identification badges at $44.00 per badge, and a $500.00 key deposit is required. Mobilization is capped at ten percent of the total project cost. General contractors must demonstrate specific qualifications including airport Security Identification Display Area (SIDA) experience within the past five years with active airfield operations, eligibility for airport badging, compliance with FAA, TSA, and airport security requirements, and successful implementation of daily safety briefings and quality control programs on similar projects. The project requires a phased construction approach to maintain operational continuity throughout the renovation period.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TITLE SHEET, DRAWING INDEX
AND NOTES
G001
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-G001.DWG 4/10/2026 8:07 AM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
A101
SCALE: 1/64"=1'-0" 0 64' 128'32'
CVG CONCOURSE A LEVEL 1 - RAMP - PLAN2
CONTRACTOR
PARKING
DUMPSTER, LAYDOWN AREA,
AND MATERIAL DELIVERY
A104
A104
SCALE: 1/64"=1'-0" 0 64' 128'32'
CVG CONCOURSE A LEVEL 2 - RAMP - PLAN1
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-G002.DWG 3/23/2026 3:27 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A FIRST LEVEL PLAN -
EXISTING
G002
8'SCALE: 1/16"=1'-0" 0 16' 32'1 CONCOURSE A 1ST LEVEL - LIFE SAFETY PLAN - PROPOSED
PLAN
NORTH
TRAVEL DISTANCE = 88'
TRAVEL PATH: RM C153 TO EXIT
TRAVEL DISTANCE = 91'
TRAVEL PATH: RM C116 TO EXIT
TRAVEL DISTANCE = 112'
TRAVEL PATH: RM C153 TO EXIT
TRAVEL DISTANCE = 141'
TRAVEL PATH: RM C117 TO EXIT
TRAVEL DISTANCE = 130'
TRAVEL PATH: RM C117 TO EXIT
TRAVEL DISTANCE = 215'
TRAVEL PATH: RM C116 TO EXIT
TRAVEL DISTANCE = 98'
TRAVEL PATH: RM C117 TO EXIT
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-LS-101.DWG 3/13/2026 5:36 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A FIRST LEVEL PLAN -
LIFE SAFETY PLAN
LS101
SHEET LEGEND:
GENERAL NOTES:
EXISTING 2-HOUR
WALL
COMMON PATH
EXIT TRAVEL PATH
EXIT SIGNAGE
FE - BRACKET MOUNTED
FIRE EXTINGUISHER
2A:B:C 10LB
KENTUCKY BUILDING CODE 2018 / LIFE SAFETY
Existing Concourse A is two levels, structural steel framing with spray fireproofing, fully sprinkled the lower level (in the area of the proposed renovation) was originally constructed as shell space drawings dated 1986 Delta Airlines. The space was fit up / renovated drawings dated 1993 Delta Airlines.
Site There is no site work in this project scope.
Structural No structural work in project scope.
Existing: Floor is a concrete slab on grade
Walls nonloadbearing CMU and metal framed / gypsum board.
Architectural / Interiors Selective floor / wall demolition, doors, metal stud wall / soffit framing, sound batt insulation, casework / millwork, floor / wall / ceiling finishes, furnishings.
Mechanical Fire suppression, plumbing, HVAC rework existing.
Electrical Reuse rework add to existing power distribution, fire alarm security, data / communications. Replace lighting.
CODES CURRENTLY ADOPTED BY KENTUCKY
2018 Kentucky Building Code (Based on the 2015 International Building Code)
Third Edition 8/2022
2018 Kentucky Residential Code (Based on the 2015 International Residential Code)
2015 International Mechanical Code
2015 International Fire Code (New construction projects, only when specifically referenced by the body of KBC)
2012 International Energy Conservation Code (for use with commercial buildings only)
2009 International Energy Conservation Code (for use with residential buildings only- see definition in IECC)
2009 ICC/ANSI A117.1 Accessible and Usable Buildings and Facilities
Kentucky State Plumbing Law, Regulations & Code (815 KAR Chapter 20)
State Boiler Regulation (KRS 236, 815 KAR 15)
2013 NFPA 13 - Installation of Sprinkler Systems
2013 NFPA 13D - Installation of Sprinkler Systems in One-and Two-Family Dwellings and Manufactured Homes
2013 NFPA 13R - Installation of Sprinkler Systems in Residential Occupancies Up to and Including Four Stories in Height
2013 NFPA 14 - Installation of Standpipe and Hose Systems
2012 NFPA 54 - National Fuel Gas Code
2023 NFPA 70 - National Electrical Code
2013 NFPA 72 - National Fire Alarm and Signaling Code
2012 NFPA 101 - Life Safety Code (Health Care Facilities)
2015 International Existing Building Code
The above is for reference only and is only representative of the many codes and standards currently used in Kentucky. For specific applications not listed above, refer to Chapter 35 of the KBC and IBC.
Existing Building:
2A construction structural steel with spray fire protection, fully sprinkled, 2 stories.
See following summary based on current code.
Chapter 3 Use and Occupancy Classification (Use and Occupancy remain the same for the reconfigured / renovated are)
First level existing renovation area
304.1 Business Group B, Office
311 Storage Group S-2
Second level existing no work
303.3 Assembly Group A-2 Restaurants / Bars
303.4 Assembly Group A-3, Waiting areas in Transportation terminals
309.1 Mercantile Group M, Retail Stores
Chapter 4 Special Detailed Requirements Based on Use and Occupancy None
Chapter 5 General Height and Area Requirements Table 504.3 Allowable Height in feet above grade plane Type II-A construction with fire suppression A, B, M, S allowable height 85' Table 504.4 Allowable number of stories above grade plane Type II-A construction with fire suppression
Group A-2 and A-3, 4 stories above grade plane Group B and S-2, 6 stories above grade plane Group M, 5 stories above grade plane
Actual existing height 35'-5” / 2 stories at renovation area.
506.2 Allowable Area, SM
Type II-A construction with fire suppression
Use Group A-2, 46,500 SF per floor Use Group A-3, 46,500 SF per floor Use Group B, 112,500 SF per floor
Actual Area (renovation) Concourse A First Level 30,592 SF (Fire Area)
506 Building Area Modification not calculated Table 509 Incidental Uses
Existing automatic sprinkler system in mechanical rooms.
Chapter 6 Types of Construction Existing
Table 601 Fire resistance rating requirements for building elements (hours) for Construction Type II-A Primary structural frame 1 hr.
Exterior bearing walls 1 hr.
Interior bearing walls 1 hr.
Nonbearing walls 0 hr.
Floor construction and associated secondary members 1 hr.
Roof construction and associated members 1 hr.
Table 602 Fire resistance rating requirements for exterior walls is 0 hours for buildings 30' or greater form other buildings. Existing buildings are further apart than 30'
Chapter 7 Fire and Smoke Protection Features 713 Shaft Enclosures, 2-hour fire resistance rating when connecting four stories shall include basement.
The existing drawings indicate:
2 hour rated elevator shaft and stair enclosures constructed of 8”
CMU.
2 hour rated separation wall running from south exterior wall to north exterior wall at the east edge of the renovation area constructed of 8”
CMU.
Chapter 8 Interior Finishes
Table 803.11 Interior wall and ceiling finishes A-3 occupancy / sprinklered
Interior exit stairways / passageways Class B.
Corridors and exit access Class B.
Rooms and enclosed spaces Class C.
Chapter 9 Fire Protection Systems
903.2.1 Group A requires fire suppression.
Building is currently fully suppressed. The fire suppression system will be revised in the renovation area.
Chapter 10 Means of Egress General
Detail reconfigure / renovation Area originally mailroom, later open office, new function Room C117 SAMS (classroom set up) Area originally Delta lounge, later open office, new function Room C116 EOC (classroom set up)
SCALE: 1/8"=1'-0" 0 8' 16'4'1 CONCOURSE A 1ST LEVEL - EXISTING
NORTH
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A101.DWG 4/9/2026 4:34 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A FIRST LEVEL PLAN -
EXISTING
A101
SCALE: 1/8"=1'-0" 0 8' 16'4'1 CONCOURSE A 1ST LEVEL - DEMO
3 3 3
3 3 3 3 3
3 3
3 3
33 33
3 3
4 4
4 4
44444
9'-4"
1'-1"
6'-1"
3'-1 1/2"
3'-0"
4 4
PLAN
NORTH
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A102.DWG 4/8/2026 4:26 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A FIRST LEVEL PLAN -
DEMOLITION
A102
SHEET KEYNOTES:GENERAL NOTES:
1 1
SCALE: 1/8"=1'-0" 0 8' 16'4'1 CONCOURSE A 1ST LEVEL - PROPOSED
28'-6 3/4"
10'-3 1/4"
A-401
1 1 1 1
2 2 2
4'-5 1/2"
3'-0 3/4"
6' -8
/4
'-7
/2
1'
-1
1/ 2"1
8'-11 1/4"
6' -0
10'-4"
4' -7
/2
3'-0"8"
'-5
A-401
PLAN
NORTH
4'-6"
A-501
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A103.DWG 4/9/2026 4:36 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A FIRST LEVEL PLAN -
PROPOSED
A103
SHEET KEYNOTES: WALL TYPE1
GENERAL NOTES: 1
SCALE: 1/4"=1'-0" 0 4' 8'2'1 CONCOURSE A 2ND LEVEL - EXISTING / PROPOSED
PLAN
NORTH
SCALE: 1/4"=1'-0" 0 4' 8'2'2 CONCOURSE A 2ND LEVEL - EXISTING / PROPOSED
PLAN
NORTH
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A104.DWG 3/23/2026 4:13 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A SECOND LEVEL PLAN -
EXISTING / PROPOSED
A104
SHEET KEYNOTES:GENERAL NOTES:
SCALE: 1/8"=1'-0" 0 8' 16'4'1 CONCOURSE A 1ST LEVEL - REFLECTED CEILING PLAN - EXISTING
NORTH
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A105.DWG 3/13/2026 5:38 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A FIRST LEVEL PLAN -
REFLECTED CEILING PLAN - EXISTING
A105
PLAN AND CEILING GRID LEGEND GENERAL NOTES:
SCALE: 1/8"=1'-0" 0 8' 16'4'1 CONCOURSE A 1ST LEVEL - REFLECTED CEILING PLAN - DEMO
1 1
1 1
1 1
1 11
1 1
1 1 1 1 1
1 1
2 2
1 1
22111
3 3
PLAN
NORTH
1 1
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A106.DWG 3/13/2026 5:38 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A FIRST LEVEL PLAN -
REFLECTED CEILING PLAN - DEMO
A106
SCALE: 1/8"=1'-0" 0 8' 16'4'1 CONCOURSE A 1ST LEVEL - REFLECTED CEILING PLAN - PROPOSED
1 1
1 1
1 1
1 11
1 1
1 1 1 1 1
1 1
1 1
1 1
1 1
PLAN
NORTH
1 1 1
1 1
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A107.DWG 3/13/2026 5:40 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A FIRST LEVEL PLAN -
REFLECTED CEILING PLAN - PROPOSED
A107
SHEET KEYNOTES:
2'-3 7/8" 23'-8" 2'-3 7/8"
28'-3 5/8"
98" TV 98" TV 98" TV 55" TV55" TV
SCALE: 3/8"=1'-0" 0 4' 6'2'1 E.O.C C118
3' -8
/4
4'
-2
/2
3/
4"
3' -1
3/
4" 4'
-0
3/
4"
1'-1" 7'-2" 7'-2" 7'-2" 1'-1"
ALREADY
MOUNTED
TO WALL
ALREADY
MOUNTED
TO WALL
ALREADY
MOUNTED
TO WALL
5'-8" 64'-6 3/4"
70'-2 3/4"
98" TV 98" TV 98" TV
SCALE: 3/8"=1'-0" 0 4' 6'2'2 LARGE CONFERENCE ROOM C117
8' -4
/2
98" TV
7'-3 7/8" 7'-2" 8'-11 3/4" 7'-2" 8'-11 3/4" 7'-2" 8'-11 3/4" 7'-2" 7'-3 7/8"
3' -1
3/
4" 4'
-0
3/
4"
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A401.DWG 3/23/2026 11:45 AM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A FIRST LEVEL PLAN -
ELEVATIONS
A401
SCALE: 1/4"=1'-0" 0 4' 8'2'1 ENLARGED RESTROOM - DEMO
A-402
A-402
A-402
SCALE: 1/2"=1'-0" 0 2' 4'1'2 MEN'S RESTROOM DEMO - C151
6 6
SCALE: 1/2"=1'-0" 0 2' 4'1'3 WOMEN'S RESTROOM DEMO - C155
SCALE: 1/2"=1'-0" 0 2' 4'1'4 WOMEN'S RESTROOM DEMO - C155
6 6
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A402.DWG 3/23/2026 3:53 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A FIRST LEVEL PLAN - ADD
ALTERNATE ONE
A402
SCALE: 1/4"=1'-0" 0 4' 8'2'1 ENLARGED RESTROOM - PROPOSED
A-402
A-402
A-402
A-402
A-402
A-402
SCALE: 1/2"=1'-0" 0 2' 4'1'2 MEN'S RESTROOM - C151
3' -0
6"
3'-0"
1' -6
GB-18
GB-42
GB-36
4" 1'
-6
1' -1
0"
TD-1 TD-1 TD-1
1'-6" 5'-0" 3'-0" 3'-0" 2'-10 1/4" 2'-8 1/2" 1'-3 3/4"
1' -5
SCALE: 1/2"=1'-0" 0 2' 4'1'3 MEN'S RESTROOM - C151
MODELNUMBERTRADENAMEPRODUCT MODELNUMBERTRADENAMEPRODUCT MODELNUMBERTRADENAMEPRODUCT MODELNUMBERTRADENAMEPRODUCT
M-1 M-1 M-1 M-1
SD-1 SD-1 SD-1 SD-1
LG-1
1'-3" 2'-6" 2'-6" 2'-6" 6'-1 1/2"
2' -1
0" 3'
-4 " B
.O . G
LA
SS
SCALE: 1/2"=1'-0" 0 2' 4'1'4 WOMEN'S RESTROOM - C155
3' -0
6"
3'-0"
1' -6
GB-18
GB-42
GB-36
TD-1TD-1TD-1TD-1TD-1
1'-4 3/4" 2'-11 5/8" 2'-10 3/8" 2'-10 3/8" 2'-10 3/8" 4'-11 1/4" 1'-6"
SN/TD-1 SN/TD-1 SN/TD-1 SN/TD-1 SN/TD-1
MODELNUMBERTRADENAMEPRODUCT MODELNUMBERTRADENAMEPRODUCT MODELNUMBERTRADENAMEPRODUCT MODELNUMBERTRADENAMEPRODUCT
SCALE: 1/2"=1'-0" 0 2' 4'1'5 WOMEN'S RESTROOM - C155
M-1 M-1 M-1 M-1
SD-1 SD-1 SD-1 SD-1
2' -1
0" 3'
-4 " B
.O . G
LA
SS
1'-7 1/2"
LG-1
2'-3" 2'-3" 2'-3" 1'-7 1/2"
SCALE: 1/2"=1'-0" 0 2' 4'1'6 WOMEN'S RESTROOM - C155
1' -6
1' -1
0"
1'-5 1/4"2'-11 3/4"2'-11 1/4"2'-10 3/4"1'-6"
TD-1TD-1TD-1TD-1
SN/TD-1SN/TD-1SN/TD-1SN/TD-1
MODELNUMBERTRADENAMEPRODUCT MODELNUMBERTRADENAMEPRODUCT MODELNUMBERTRADENAMEPRODUCT
SCALE: 1/2"=1'-0" 0 2' 4'1'7 WOMEN'S RESTROOM - C155
2' -1
0" 3'
-4 " B
.O . G
LA
SS
LG-1
1'-7 1/2"2'-3"2'-3"1'-7 1/2"
M-1 M-1 M-1
SD-1 SD-1 SD-1
MARK COMMENTS
M-1
LG-1 UNDERLAVATORY GUARD
ACCESSORY SCHEDULE
DESCRIPTION MANUFACTURER MFR DESIGNATION
TD-1 TOILET TISSUE (ROLL) DISPENSER BOBRICK B-357
SD-1 SOAP DISPENSER ESD-360-CP
GB-18 GRAB BAR B-6806.99X18
GB-36 B-6806.99X36
GB-42 B-6806.99X42
MIRROR B-165 2448
GRAB BAR
GRAB BAR
PLASTIC
SLOAN
BOBRICK
BOBRICK
BOBRICK
BOBRICK
NOT TO SCALE
ACCESSORY SCHEDULE
SN/TD-1 SANITARY NAPKIN / TAMPON DISPOSAL B-357BOBRICK
CH-1 COAT HOOK B-9542BOBRICK
1/
2" 1'
-8
/4
3/
4"
1/2" X 5" SOLID SURFACE TRIM
SUPPORT BRACKET. PROVIDE
(2) LAYERS OF 3/4" MEDIUM
DENSITY FIBERBOARD W/
PLASTIC LAMINATE FINISH AT
ALL EXPOSED SURFACES.
WALL PLATE. PROVIDE 3/4"
X 3 1/2" MEDIUM DENSITY
FIBERBOARD W/ PLASTIC
LAMINATE FINISH AT ALL
EXPOSED SURFACES
1/2" X 3 1/2" SOLID SURFACE
BACKSPLASH. PROVIDE
BACKSPLASH WHERE
COUNTERTOP ABUTS
ADJACENT TO WALL.
3 1/2" X 2'-0" SOLID SURFACE
COUNTERTOP
SCALE: 1 1/2"=1'-0" 0 1' 1 1/2'1/2'8 CASEWORK DETAIL
3/4" 2" 1'-7" 1 3/4"
2'-0"
2' -1
0"
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A403.DWG 4/21/2026 2:05 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A FIRST LEVEL PLAN - ADD
ALTERNATE ONE
A403
SHEET KEYNOTES:
SCALE: 1/4"=1'-0" 0 4' 8'2'1 CONCOURSE A 1ST LEVEL - C115 EXISTING
NORTH
SCALE: 1/4"=1'-0" 0 4' 8'2'2 CONCOURSE A 1ST LEVEL - C115 PROPOSED
24'-0"
'-0
PLAN
NORTH
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A404.DWG 3/13/2026 5:46 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A FIRST LEVEL PLAN - ADD
ALTERNATE TWO
A404
WALL TYPE1
SCALE: 1/4"=1'-0" 0 4' 8'2'1
CONCOURSE A 1ST LEVEL
ENLARGED REFLECTED CEILING PLAN C115 EXISTING
PLAN
NORTH
SCALE: 1/4"=1'-0" 0 4' 8'2'2
CONCOURSE A 1ST LEVEL
ENLARGED REFLECTED CEILING PLAN C115 PROPOSED
PLAN
NORTH
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A405.DWG 3/13/2026 5:46 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A FIRST LEVEL PLAN - ADD
ALTERNATE TWO
A405
SCALE: 1/4"=1'-0" 0 4' 8'2'4
CONCOURSE A 1ST LEVEL
ENLARGED PLAN C144 DEMO
3'-4"2'-10"
PLAN
NORTH
SCALE: 1/4"=1'-0" 0 4' 8'2'5
CONCOURSE A 1ST LEVEL
ENLARGED PLAN C144 PROPOSED
PLAN
NORTH
SCALE: 1 1/2"=1'-0" 0 1' 1 1/2'1/2'2 EXTERIOR DOOR DETAIL - JAMB C
3 5/8" BRICK VENEER
1 1/4" CAVITY
1 1/2" EXTRUDED POLYSTYRENE
8" C.M.U
2"
HOLLOW METAL FRAMES
3/8" CONTINUOUS SEALANT EACH
SIDE OF DOOR FRAME
1'-2"
8"23
4"35 8"
1'-2"
SCALE: 1 1/2"=1'-0" 0 1' 1 1/2'1/2'1 EXTERIOR DOOR DETAIL - HEAD C
1'-2"
8"23
4"35 8"
3 5/8" BRICK VENEER
1 1/4" CAVITY
1 1/2" EXTRUDED POLYSTYRENE
8" C.M.U
HOLLOW METAL FRAMES
3/8" CONTINUOUS SEALANT EACH
SIDE OF DOOR FRAME
2"
1'-2"
L5x31/2"x5/16"
6" BRG EA END
HOLLOW METAL FRAMES
SCALE: 1 1/2"=1'-0" 0 1' 1 1/2'1/2'3 EXTERIOR DOOR DETAIL - SILL C
1'-2"
REMOVE C.M.U 4" BELOW AND POUR
NEW 4" SLAB
EXISTING SIDEWALK
HOLLOW METAL DOOR AND FRAME,
SEE DOOR SCHEDULE.
ADA COMPLIANT SADDLE
THRESHOLD - 1/2" HIGH MAX AT
INTERIOR LOCATIONS
DOOR SWEEP
EXISTING 8" SLAB
2" OR 4" FIELD VERIFY TO MATCH
COURSES
PROVIDE COMPRESSIBLE FILLER,
BACKER ROD, AND URETHANE SEALANT
PROVIDE COMPRESSIBLE FILLER,
BACKER ROD, AND URETHANE
SEALANT
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A406.DWG 3/13/2026 5:49 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A FIRST LEVEL PLAN - ADD
ALTERNATE THREE
A406
SCALE: 1/4"=1'-0" 0 4' 8'2'1 CONCOURSE A 2ND LEVEL - EXISTING / DEMO
NORTH
SCALE: 1/4"=1'-0" 0 4' 8'2'2 CONCOURSE A 2ND LEVEL - PROPOSED
PLAN
NORTH
6' -7
/4
6'-7 1/4"5' -6
/4
3'
-7
/4
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A407.DWG 4/9/2026 4:38 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A SECOND LEVEL PLAN -
ADD ALTERNATE FOUR
A407
WALL TYPE1SHEET KEYNOTES:
SCALE: 1/4"=1'-0" 0 4' 8'2'1 CONCOURSE A 2ND LEVEL - DEMO / PROPOSED
NORTH
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A407-1.DWG 4/9/2026 4:39 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A SECOND LEVEL PLAN -
ADD ALTERNATE FOUR
A407 1
CONCOURSE A 2ND LEVEL
REFLECTED CEILING PLAN - EXISTING / DEMO
PLAN
NORTH
SCALE: 1/4"=1'-0" 0 4' 8'2'2
CONCOURSE A 2ND LEVEL
REFLECTED CEILING PLAN - EXISTING / DEMO
PLAN
NORTH
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A408.DWG 3/23/2026 4:11 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A SECOND LEVEL PLAN -
ADD ALTERNATE FOUR
A408
CONCOURSE A 2ND LEVEL
REFLECTED CEILING PLAN - PROPOSED
PLAN
NORTH
SCALE: 1/4"=1'-0" 0 4' 8'2'2
CONCOURSE A 2ND LEVEL
REFLECTED CEILING PLAN - PROPOSED
PLAN
NORTH
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A409.DWG 3/23/2026 4:11 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A SECOND LEVEL PLAN -
ADD ALTERNATE FOUR
A409
PRE-MANUFACTURED
EXTERIOR AWNING
SCALE: 3/4"=1'-0" 0 2' 3'1'1 EXTERIOR AWNING ELEVATION
3 5/8" BRICK VENEER
1 1/4" CAVITY
UPPER STRUT
LOWER STRUT
SADDLE BRACKET
SIDE CHANNEL
GUTTER BRACKET
3/8" THROUGH BOLTS
WALL BRACKETS
GUTTER
1 1/2" EXTRUDED POLYSTYRENE
8" C.M.U
1'-2"
8"23
4"35 8"
4"
SCALE: 1 1/2"=1'-0" 0 1' 1 1/2'1/2'2 EXTERIOR AWNING SECTION
3/8" ANCHOR BOLT
(ALIGN WITH EXISTING
VERTICAL JOINTS, STAGGER
BOLTS TO BE 1" ABOVE AND
BELOW CENTER)
3"
6" 65 8"
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A501.DWG 3/16/2026 9:15 AM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
ARCHITECTURAL
DETAILS
A501
GENERAL NOTES:
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A601.DWG 4/21/2026 2:06 PM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A FIRST LEVEL PLAN -
ROOM FINISH SCHEDULE
A601
ROOM FINISH SCHEDULE
ROOM IDENTIFICATION FLOOR WALLS CEILING ROOM SIGNAGE
COMMENTSROOM
NUMBER ROOM NAME AREA (SF) FLOOR FINISH -
EXISTING
BASE
FINISH
BUILDING ORIENTATION INDICATES PLAN NORTH
CEILING
MATERIAL
CEILING
FINISH
CEILING
HEIGHT
(A.F.F.)
SIGNAGE TYPENORTH SOUTH EAST WEST
MATERIAL FINISH MATERIAL FINISH MATERIAL FINISH MATERIAL FINISH
C100 VESTIBULE 47.65 EXISTING RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP TYP-1 PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C101 RECEIVING 150.38 EXISTING RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 10'-5" TYP-1 PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C102 ELEVATOR EQUIPMENT 54.64 EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING TYP-1 NO WORK, INCLUDED TO INDIACTE ROOM SIGNAGE NEEDED
C103 CORRIDOR 424.99 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C104 VACANT 155.96 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C105 MANAGER OFFICE 210.93 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C106 ENV SERV STORAGE 212.45 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C107 ENV SERV STORAGE 194.97 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C108 CX STORAGE 308.41 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C109 LEAD OFFICE 259.29 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C110 SUPERVISOR OFFICE 259.29 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C111 HOUSEKEEPING CONFERENCE 259.29 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C112 TRAINING ROOM 259.29 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C113 ENV SERV STORAGE 258.88 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C114 CORRIDOR 353.01 CPT RB-1 GYP.BD PT-1 GYP. BD PT-1 GYP. BD PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" CARPET, PAINT & NEW CEILING TILES AND GRID
C115 VACANT 1089.61 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-2 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C116 E.O.C 2,205.00 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-3 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C117 LARGE CONFERENCE ROOM 2,205.77 CPT RB-1 CMU PT-1 GYP. BD PT-1 CMU PT-1 GYP. BD PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-3 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C118 CONFERENCE ROOM STORAGE 347.47 CPT RB-1 CMU PT-1 GYP. BD PT-1 CMU PT-1 GYP. BD PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C119 PSA STORAGE 194.24 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C120 VACANT 105.85 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C121 VACANT 153.02 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C122 VACANT 152.59 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C123 CORRIDOR 502.88 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-7 1/2" CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C124 VACANT 195.72 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C125 EOC / AIRPORT OPS STORAGE 441.84 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C125A VESTIBULE 128.18 CPT RB-1 GYP.BD PT-1 GYP. BD PT-1 GYP. BD PT-1 GYP. BD PT-1 ACP-1 SEE RCP 8'-4 1/2" CARPET, PAINT & CEILING TILES
C126 VACANT 117.58 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C127 VACANT 118.12 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C128 VACANT 236.38 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C130 CORRIDOR 171.4 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C131 VACANT 140.87 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C132 VACANT 140.87 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C133 CORRIDOR 485.05 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C134 VACANT 110.03 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C135 VACANT 109.81 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C136 VACANT 109.81 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C137 VACANT 208.62 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C139 HUDDLE ROOM 107.61 EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING NO WORK, INCLUDED TO INDICATE ROOM NAME CHANGE
C140 CORRIDOR 539.81 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C147 HOUSEKEEPING STORAGE 787.65 CPT RB-1 VARIES PT-1 CMU PT-1 GYP. BD PT-1 GYP. BD PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C149 CORRIDOR 210.38 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C150 MEN'S LOCKER ROOM 231.74 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C151 MEN'S RESTROOM 287.97 EXISTING TILE CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-5 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C152 ELEVATOR EQUIPMENT 52.42 EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING TYP-1 NO WORK, INCLUDED TO INDIACTE ROOM SIGNAGE NEEDED
C153 HOUSEKEEPING BREAKROOM 817.09 EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING TYP-1 NO WORK, INCLUDED TO INDIACTE ROOM SIGNAGE NEEDED
C154 CORRIDOR 199.95 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C155 WOMEN'S RESTROOM 635.13 EXISTING TILE CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-4 CLEAN TILE, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C156 WOMEN'S LOCKER ROOM 229.52 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C157 LOCKER ROOM 175.75 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C158 LOCKER ROOM 176.09 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C161 JANITOR STORGE 196.85 CONC RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP TYP-1 NO WORK, INCLUDED TO INDIACTE ROOM SIGNAGE NEEDED
C162 CORRIDOR 918.58 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP VARIES CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C163 ELECTRICAL 39.13 EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING TYP-1 NO WORK, INCLUDED TO INDIACTE ROOM SIGNAGE NEEDED
C164 ELEVATOR EQUIPMENT 161.81 EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING TYP-1 NO WORK, INCLUDED TO INDIACTE ROOM SIGNAGE NEEDED
C165 VACANT 246.88 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C166 AMBASSADOR STORAGE 283.11 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C167 PSA UNIFORM STORAGE 287.62 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 7'-11 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
D101 VACANT 402.09 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-7 1/2" CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
D102 VACANT 130.88 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-0" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
D166 CORRIDOR 173.28 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
D172 CORRIDOR 95.43 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
D173 VACANT 121.22 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
D174 VACANT 120.83 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
D175 STORAGE 46.02 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-5" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
D176 VACANT 141.31 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
D177 VACANT 141.31 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 ACP-1 SEE RCP 8'-4 1/2" TYP-1 CARPET, PAINT, CEILING TILES, CLEAN GRID & CAULK CMU IF NEEDED
C20 STAIR 202.36 CONC RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 TYP-2 PAINT & CAULK CMU IF NEEDED
C21 STAIR 239.05 CONC RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 TYP-2 PAINT & CAULK CMU IF NEEDED
C23 STAIR 317.62 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 TYP-2 PAINT
C24 STAIR 319.8 CPT RB-1 CMU PT-1 CMU PT-1 CMU PT-1 CMU PT-1 TYP-2 PAINT
FINISH LEGEND
SYMBOL MANUFACTURER COLOR / STYLE FINISH
FLOORING CARPET TILE CPT-1 MILLIKEN CUSTOM, T170R09XMRA-X17003 39.4" x 39.4" - MONOLITHIC
WALLS
PAINT PT-1 SHERWIN WILLIAMS SW7063 NEBULOUS WHITE INTERIOR PAINT EGGSHELL
RUBBER BASE RB-1 JOHNSONITE #20 CHARCOAL 6", COVE BASE
CEILINGS CEILING TILES ACP-1 USG MARS #88985 24" x 48"
SIGNAGE ROOM SIGNAGE
TYP-1 APCO SIGNS ARCADIA SEE SPEC
TYP-2 APCO SIGNS ARCADIA SEE SPEC
TYP-3 APCO SIGNS ARCADIA SEE SPEC
TYP-4 APCO SIGNS DP-TACTILE PROCESS ADA SEE SPEC
TYP-5 APCO SIGNS DP-TACTILE PROCESS ADA SEE SPEC
SCALE: 1 1/2"=1'-0" 0 1' 1 1/2'1/2'1 DETAIL - HEAD A
SCALE: 1 1/2"=1'-0" 0 1' 1 1/2'1/2'2 DETAIL - JAMB A
SCALE: 1 1/2"=1'-0" 0 1' 1 1/2'1/2'3 DETAIL - SILL A
SC
H
ED
H
G T
A
WIDTH
SCHED
SC
H
ED
H G
T.
SCHED.
WIDTH
HOLLOW
METAL
F.F.
2"
2" 2"
SC
H
ED
H G
T.
SCHED.
WIDTH
F.F.
2"
2" 2"
SCALE: 1 1/2"=1'-0" 0 1' 1 1/2'1/2'5 EXTERIOR DOOR DETAIL - JAMB B
3 5/8" BRICK VENEER
1 1/4" CAVITY
1 1/2" EXTRUDED POLYSTYRENE
8" C.M.U
2"
HOLLOW METAL FRAMES
3/8" CONTINUOUS SEALANT EACH
SIDE OF DOOR FRAME
1'-2"
8"23
4"35 8"
1'-2"
SCALE: 1 1/2"=1'-0" 0 1' 1 1/2'1/2'4 EXTERIOR DOOR DETAIL - HEAD B
1'-2"
8"23
4"35 8"
3 5/8" BRICK VENEER
1 1/4" CAVITY
1 1/2" EXTRUDED POLYSTYRENE
8" C.M.U
HOLLOW METAL FRAMES
3/8" CONTINUOUS SEALANT EACH
SIDE OF DOOR FRAME
2"
1'-2"
2" OR 4" FIELD VERIFY TO MATCH
COURSES
HOLLOW METAL FRAME
SCALE: 1 1/2"=1'-0" 0 1' 1 1/2'1/2'6 EXTERIOR DOOR DETAIL - SILL B
1'-2"
EXISTING SIDEWALK
HOLLOW METAL DOOR AND FRAME,
SEE DOOR SCHEDULE.
ADA COMPLIANT SADDLE
THRESHOLD - 1/2" HIGH MAX AT
INTERIOR LOCATIONS
DOOR SWEEP
EXISTING 8" SLAB
PROVIDE COMPRESSIBLE FILLER,
BACKER ROD, AND URETHANE SEALANT
EXISTING CMU LINTEL
CVG CONCOURSE A -
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A602.DWG 3/16/2026 9:15 AM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A FIRST LEVEL PLAN -
DOOR AND FRAME SCHEDULE
A602
DOOR AND FRAME SCHEDULE
DOOR FRAME
FIRE
RATING
LABLE
HARDWARE
WALL TYP. COMMENTSDOOR
MARK FROM ROOM TO ROOM
SIZE DOOR
MATERIAL DOOR TYPE FRAME
MATERIAL
FRAME
TYPE
DETAIL
SET NUMBER
WIDTH HEIGHT THICKNESS HEAD JAMB SILL
D2-IFN1 S.A.M.S - C117 CORRIDOR - C103 3'-0" 7'-0" 1 3/4" HM A HM 1 A A A AC-04 GYP. BD SEE SPECS FOR DOOR AND DOOR HARDWARE
D2-IFN2 S.A.M.S - C117 CORRIDOR - C114 3'-0" 7'-0" 1 3/4" HM A HM 1 A A A 01 GYP. BD SEE SPECS FOR DOOR AND DOOR HARDWARE
D2-IFN3 E.O.C - C116 VACANT - C115 6'-0" 7'-0" 1 3/4" HM A HM 1 A A A AC-05 GYP. BD SEE SPECS FOR DOOR AND DOOR HARDWARE
D2-IFN4 CORRIDOR CONFERENCE ROOM - C115 3'-0" 7'-0" 1 3/4" HM A HM 1 A A A 02 GYP. BD ADD ALTERNATE TWO, SEE SHEET A404
D2-IFN5 CORRIDOR CONFERENCE ROOM - C115 3'-0" 7'-0" 1 3/4" HM A HM 1 A A A 02 GYP. BD ADD ALTERNATE TWO, SEE SHEET A404
D3-IFN1 E.O.C - C116 CORRIDOR - C140 3'-0" 7'-0" 1 3/4" HM A HM 1 A A A AC-05 GYP. BD SEE SPECS FOR DOOR AND DOOR HARDWARE
D3-IFN2 E.O.C - C116 CORRIODOR - C133 3'-0" 7'-0" 1 3/4" HM A HM 1 A A A AC-05 GYP. BD SEE SPECS FOR DOOR AND DOOR HARDWARE
D3-IFN4 S.A.M.S - C117 VESTIBULE - C125A 3'-0" 7'-0" 1 3/4" HM A HM 1 A A A 01 GYP. BD SEE SPECS FOR DOOR AND DOOR HARDWARE
D3-IFN5 S.A.M.S - C117 S.A.M.S STORGAE - C118 3'-0" 7'-0" 1 3/4" HM A HM 2 A A A 04 GYP. BD SEE SPECS FOR DOOR AND DOOR HARDWARE
D3-IFN6 CORRIDOR - C130 CORRIDOR - C123 3'-0" 7'-0" 1 3/4" HM A HM 1 A A A AC-05 GYP. BD SEE SPECS FOR DOOR AND DOOR HARDWARE
D3-IFN7 KCAB OPS DEPT. BREAKROOM EXTERIOR 3'0" 7'-0" 1 3/4" HM A HM 1 C C C AC-07 CMU ADD ALTERNATE THREE, SEE SHEET A406
D2-1300 VACANT - C115 ELEVATOR EQUIPMENT 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-1350 RECEIVING ELEVATOR EQUIPMENT 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-1360 VESTIBULE RECEIVING 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-1370 VESTIBULE STAIR C20 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-1381 VESTIBULE CAGED SMOKING AREA 3'-0" 7'-0" 1 3/4" HM A HM
D2-1390 STAIR C21 EXTERIOR 3'-0" 7'-0" 1 3/4" HM A HM
D2-1400 CORRIDOR - C162 ELECTRICAL 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-1410 STAIR C21 ELEVATOR EQUIPMENT 3'-0" 7'-0" 1 3/4" HM A HM
D2-IF03 CORRIDOR - C103 VACANT 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF04 CORRIDOR - C103 MANAGER OFFICE 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF05 CORRIDOR - C103 ENV SERV STORAGE 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF06 CORRIDOR - C103 ENV SERV STORAGE 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF7A CORRIDOR - C103 CX STORAGE 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF7B CORRIDOR - C103 CX STORAGE 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF08 CORRIDOR - C103 STAIR C20 3'-0" 7'-0" 1 3/4" HM A HM AC-02 CMU PROVIDE NEW DOOR LEAF, REUSE EXISTING HM FRAME
D2-IF09 CORRIDOR - C103 LEAD OFFICE 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF10 CORRIDOR - C103 SUPERVISOR OFFICE 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF11 CORRIDOR - C103 HOUSKEEPING CONFERENCE 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF12 CORRIDOR - C103 TRAINING ROOM 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF13 CORRIDOR - C103 ENV SERV STORAGE 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF14 CORRIDOR - C162 PSA UNIFORM STORAGE 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF15 CORRIDOR - C162 AMBASSADOR STORAGE 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF16 CORRIDOR - C162 VACANT 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF16A VACANT CLOSET 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF16B VACANT CLOSET 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF16C VACANT CLOSET 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF17A CORRIDOR - C154 HOUSEKEEPING BREAKROOM 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF17B CORRIDOR - C154 HOUSEKEEPING BREAKROOM 3'-0" 7'-0" 1 3/4" HM A HM EXISTING TO REMAIN, PAINT TO MATCH NEW
GENERAL NOTES:
LEVEL ONE - RAMP REFRESH
CINCINNATI/NORTHERN KENTUCKY
INTERNATIONAL AIRPORT
KENTON COUNTY AIRPORT BOARD
G:\5035-GRW ON-CALL ARCH-MEP SERVICES\09-CON A RR\WORKING DRAWINGS\AUTOCAD\5035-09-A603.DWG 3/16/2026 9:15 AM NBROOKS
ALL RIGHTS RESERVED:
THIS DOCUMENT IS THE PROPERTY OF GRW ENGINEERS, INC. AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART OR USED FOR CONSTRUCTION
OF OTHER THAN THIS SPECIFIC PROJECT WITHOUT WRITTEN PERMISSION
engineering architecture geospatial www.grwinc.com
CONCOURSE A FIRST LEVEL PLAN -
DOOR AND FRAME SCHEDULE
A603
DOOR AND FRAME SCHEDULE (CONTINUED)
DOOR FRAME
FIRE
RATING
LABLE
HARDWARE
WALL TYP. COMMENTSDOOR
MARK FROM ROOM TO ROOM
SIZE DOOR
MATERIAL DOOR TYPE FRAME
MATERIAL
FRAME
TYPE
DETAIL
SET NUMBER
WIDTH HEIGHT THICKNESS HEAD JAMB SILL
D2-IF18 CORRIDOR - C154 VACANT - C115 3'-0" 7'-0" 1 3/4" HM 1 AC-03 GYP. BD PROVIDE NEW DOOR LEAF, REUSE EXISTING HM FRAME
D2-IF19 CORRIDOR - C154 LOCKER ROOM - C158 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF20 CORRIDOR - C154 LOCKER ROOM - C157 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF27 VACANT - C115 WOMEN'S RESTROOM - C155 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D2-IF28 VACANT - C115 MEN'S RESTROOM - C151 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
F-101 CORRIDOR - C162 STAIR C21 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
F-121B VACANT - D101 EXTERIOR 3'-8" 7'-0" 1 3/4" HM 1 HM 1 B B B AC-08 CMU SEE SPECS FOR DOOR AND DOOR HARDWARE
F-133 CORRIDOR - C162 JANITOR STORAGE - C161 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
F-134A PSA UNIFORM STORAGE ELECTRICAL - C168 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
F-135 CORRIDOR - C149 EXTERIOR 3'-0" 7'-0" 1 3/4" HM 1 HM 1 B B B AC-08 CMU SEE SPECS FOR DOOR AND DOOR HARDWARE
D3-IF32 CORRIDOR - C123 S.A.M.S STORAGE - C118 3'-0" 7'-0" 1 3/4" HM 1 HM 1 A A A 03 GYP. BD SEE SPECS FOR DOOR AND DOOR HARDWARE
D3-IF33 CORRIDOR - C123 PSA STORAGE 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF34 CORRIDOR - C123 VACANT - C120 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF35 CORRIDOR - C123 VACANT - C121 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF36 CORRIDOR - C123 VACANT - C122 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF40B CORRIDOR - C133 EOC / AIRPORT OPS STORAGE - C125 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-1439B E.O.C - C116 VACANT - C124 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF42 CORRIDOR - C123 VACANT - C126 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF43 CORRIDOR - C123 VACANT - C127 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF44 CORRIDOR - C133 VACANT - C128 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF46 CORRIDOR - C130 VACANT - C131 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF47 CORRIDOR - D172 VACANT - D176 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF48 CORRIDOR - D172 STORAGE - D175 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF49 CORRIDOR - D172 VACANT - D174 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF50 VACANT - D101 VACANT - D102 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF52 CORRIDOR - C130 VACANT - C132 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF53 CORRIDOR - D172 VACANT - D177 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF54 CORRIDOR - D172 VACANT - D173 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF56 CORRIDOR - C133 VACANT - C134 3'-0" 7'-0" 1 3/4" HM 1 HM 1 A A A 02 CMU SEE SPECS FOR DOOR AND DOOR HARDWARE
D3-IF57 CORRIDOR - C133 VACANT - C135 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF58 CORRIDOR - C133 VACANT - C136 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF59 CORRIDOR - C133 VACANT - C137 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-IF64C CORRIDOR - C149 HOUSEKEEPING STORAGE 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-64B VACANT - C116 STORAGE - C148 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-1220 CORRIDOR - D166 MECHANICAL 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-1220A CORRIDOR - D166 STORAGE 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
D3-1240 CORRIDOR - D103 CORRIDOR - C133 3'-0" 7'-0" 1 3/4" HM 1 HM 1 A A A AC-05 GYP. BD SEE SPECS FOR DOOR AND DOOR HARDWARE
D3-1250 CORRIDOR - D103 VACANT - D101 3'-0" 7'-0" 1 3/4" HM EXISTING TO REMAIN, PAINT TO MATCH NEW
SECOND LEVEL
D2-2085 CONCOURSE - C100 ENTRY AREA - C107 3'-0" 7'-0" 1 3/4" HM 1 AC-01 GYP. BD PROVIDE NEW DOOR LEAF, REUSE EXISTING HM FRAME
D3-2041 CONCOURSE - C100 ENTRY AREA - D102 3'-0" 7'-0" 1 3/4" HM 1 AC-01 GYP. BD PROVIDE NEW DOOR LEAF, REUSE EXISTING HM FRAME
D3-IFN8 ENTRY AREA - D102 STORAGE - D101 3'-0" 7'-0" 1 3/4" HM 1 HM 1 A A A 05 GYP. BD SEE SPECS FOR DOOR AND DOOR HARDWARE
FIRE PROTECTION GENERAL NOTES:
1. PROVIDE ALL WORK NECESSARY FOR THE COMPLETE FIRE PROTECTION SYSTEM AS INDICATED AND NOTED, INCLUDING ALL CONNECTIONS TO EXISTING WORK, NEW PIPING AND ACCESSORIES AND FINAL FINISH MOUNTING OF SPRINKLERS IN LOCATIONS INDICATED AND TESTING, ALL AS REQUIRED TO MEET ALL PROVISIONS OF NFPA-13 AND THE KY BUILDING CODE. WORK SHALL BE PERFORMED BY A LICENSED SPRINKLER CONTRACTOR AND SHALL BE ACCOMPANIED BY CERTIFICATIONS OF INSPECTION AND APPROVAL BY THE DEPT. OF HOUSING, BUILDINGS AND CONSTRUCTION. ALL SCREWED PIPING SHALL BE MINIMUM SCH 40 STEEL. ALL VICTAULIC TYPE PIPING SHALL BE
MINIMUM SCH 10 STEEL.
2. FIRE PROTECTION COMPONENTS, INCLUDING BUT NOT LIMITED TO PUMPS, VALVES, PIPE & FITTINGS, CONTROL SYSTEMS AND TRIM SHALL BE UL AND/OR FM LISTED FOR FIRE SERVICE, WHERE SUCH LISTING EXISTS.
3. PROVIDE LISTED AIR RELEASE FOR ALL TRAPPED RUNS OF FIRE PROTECTION PIPING.
4. ALL FERROUS FIRE PROTECTION PIPING SHALL BE PAINTED RED WHERE EXPOSED TO VIEW; SHADE TO BE APPROVED
BY ENGINEER.
5. ALL FIRE PROTECTION SHUTOFF VALVES SHALL BE SUPERVISED BY THE ALARM SYSTEM EXCEPT ON JOCKEY PUMP
AND BYPASS.
6. FIRE PROTECTION PIPING CONNECTIONS MAY BE WELDED, FLANGED, SCREWED OR GROOVE-JOINT TYPE PER NFPA-13, 14, 20 AND THE SPECIFICATIONS FOR THIS PROJECT. NO SCREWED PIPING LARGER THAN 2 INCHES. PITCH ALL PIPING
TO DRAIN.
7. SPRINKLERS SHALL BE CENTERED IN 2' x 2' SPACE IN EITHER 2' x 2' OR 2' x 4' GRID LAYOUT.
8. COORDINATE ALL WORK. COORDINATE ALL PIPING AND ACCESSORIES WITH BOTH NEW AND EXISTING MECHANICAL AND ELECTRICAL WORK INCLUDING HVAC, PLUMBING, ELECTRICAL, FIRE ALARM AND COMMUNICATIONS. DO NOT MOUNT SPRINKLERS OR HANG PIPING SUCH AS TO BLOCK ACCESS TO HVAC OR ELECTRICAL EQUIPMENT OR THE
CHANGEOUT OF EQUIPMENT WHEN NECESSARY.
9. PROVIDE SPECIAL SPRINKLERS AS REQUIRED FOR COMPLETE DESIGN. PROVIDE HIGH TEMPERATURE HEADS FOR
AREAS NEAR SPACE HEATING OUTLETS AND EQUIPMENT.
10. HAZARD CLASSIFICATION IS BASED ON INFORMATION KNOWN AT THE TIME OF DESIGN. HAZARD CLASSIFICATION MAY
CHANGE AS BUILDING PROGRESSES.
11. FIRE SYSTEM EXTERIOR APPURTENANCES SHALL BE FINISHED IN EITHER BRASS OR FACTORY FINISH RED (SIAMESE, WATER GONG, TRIM RING, ETC.) PER THE BASE STANDARD FINISH STYLE.
12. A TEST VALVE (INSPECTORS TEST STATION) SHALL BE INSTALLED FOR EACH WET PIPE SYSTEM AND DRY PIPE SYSTEM.
PROVIDE SMOOTH BORE STEEL ORIFICE GIVING A FLOW RATE EQUIVALENT TO ONE SPRINKLER.
13. PROVIDE HEAVY GAUGE GALVANIZED STEEL HOODS AND SHIELDS (OR STAINLESS STEEL) THAT ARE SHOP FABRICATED FOR ELECTRICAL ROOMS AND COMMUNICATION ROOMS TO PROTECT ELECTRICAL…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .