This document is the Fairchild Air Force Base 2025 Base Design Guide Data Sheets, a comprehensive technical reference for architectural, engineering, and construction standards for projects at Fairchild Air Force Base in Washington State. The 121-page document provides detailed specifications and requirements across multiple construction divisions, including concrete, masonry, metals, electrical systems, fire suppression, plumbing, HVAC, communications, landscaping, utilities, and environmental considerations.
The guide covers extensive technical standards such as materials specifications, design requirements, environmental compliance, seismic and wind load considerations, utility installation protocols, landscaping guidelines, and specific color and aesthetic standards for base facilities. Key requirements include using specific manufacturers for equipment, adhering to strict environmental and sustainability practices, implementing force protection standards, following precise color schemes (like "Spanish Moss" for exterior elements), and ensuring compatibility with existing base systems like the Energy Management Control System (EMCS). The document serves as a comprehensive reference to ensure consistency, quality, and compliance in construction and renovation projects at Fairchild Air Force Base.
View the file
Other files for this federal contract opportunity
Show all 32
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Division 03 – Concrete
FAIRCHILD AFB DESIGN GUIDE
DATA SHEETS
TABLE OF CONTENTS
Data Sheets
Description Page
Section 033000 – Cast-in-Place Concrete Data Sheet
Section 042000 – Unit Masonry Data Sheet
Section 050000 – Metals Data Sheet
Section 060000 – General Requirements Data Sheet
Section 080000 – Openings Data Sheet
Section 087100 – Door Hardware Data Sheet
Section 090000 – Finishes Data Sheet
Section 093010 – Ceramic Tile Data Sheet
Section 100000 – Specialties Data Sheet
Section 101400 – Signage Data Sheet
Section 110000 – Equipment Data Sheet
Section 140000 – Conveying Equipment Data Sheet
Section 210000 – Fire Suppression Division 21 – Fire Suppression
Division 14 – Conveying Equipment
Division 11 – Equipment
Division 10 – Specialties
Division 09 – Finishes
Division 08 – Openings
Division 06 – Woods, Plastics, and Composites
Division 05 – Metals
Division 04 – Masonry
FA462025R0001
Attachment 3 - 2025 Base Design Guide Data Sheets
Data Sheet
Section 220000 – Plumbing, General Purpose Data Sheet
Section 230000 – HVAC Equipment Data Sheet
Section 230900 – Instrumentation and Control for HVAC EMCS Data Sheet
Section 235200 – Heating Boilers Data Sheet
Section 260000 – Electrical Data Sheet
Section 262000 – 15 Kv Electrical Distribution Data Sheet
Section 263213 - Engine Generators Data Sheet
Section 264200 – Cathodic Protection Data Sheet
Section 275116 – Mass Notification Systems Data Sheet
Section 275400 – Klaxon and Naoc Alarm System Data Sheet Detail Sheet Detail 1 – Klaxon System at Facility Detail 1 – NAOC System at Facility
Section 284611 – Carbon Monoxide Detection and Alarm Data Sheet
Section 284620 – Fire-Alarm System Data Sheet
Section 312000 – Earth Moving Data Sheet
Section 320000 – Miscellaneous Details Data Sheet Detail Sheet Detail 1 – Sidewalk Intersection Detail 2 – Bollards Detail 3 – Bike Rack Detail 4 – Outdoor Bench
Section 321600 – Curbs and Gutters Detail Sheet Detail 1 – Typical Curb and Gutter
Division 22 – Plumbing
Division 23 – Heating, Ventilating, and Air-Conditioning (HVAC)
Division 26 – Electrical
Division 27 – Communications
Division 28 – Electronic Safety and Security
Division 31 – Earthwork
Division 32 – Exterior Improvements
FA462025R0001
Detail 2 – Typical Curb Cut Detail 3 – Asphalt Curb Backing Detail 4 – Earthen Curb Backing
Section 323100 – Fences and Gates Data Sheet Detail Sheet Detail 1 – Wall Column Detail 2 – Screen Wall Detail 3 – Wall Screen or Enclosure
Section 328400 – Planting Irrigation Data Sheet Detail Sheet Detail 1 – Flush Point Detail 2 – Emitter Detail 3 – Electric Control Valve Detail 4 – Quick Coupler Valve Detail 5 – Auto Drain Valve Detail 6 – Backflow Preventer Detail 7 – Swing Joint
Section 329000 –Planting Data Sheet Contractor Pesticide Documentation Rqmts
Section 329300 – Plants Detail Sheet Detail 1 – Clear View Triangle Detail 2 – Tree Planting Detail 3 – Shrub Planting Detail 4 – Ground Cover Planting Species List
Division 33 – Utilities Section 330000 – Utilities
Data Sheet Atch 1 – Utility Verification Procedures
Division A – Design Specific Requirements Section A.1 – Specification, Drawings and Mapping Requirements
Data Sheet…………………………………………………………….95 Section A.2 – Structural and Civil Requirements
Data Sheet……………………………………………………………104 Section A.3 – Environmental Requirements
Data Sheet……………………………………………………………..182 Section A.4 – ATFP Requirements
Data Sheet……………………………………………………………..199 Section A.5 – Demolition Requirements
Data Sheet……………………………………………………………..204
END OF TABLE OF CONTENTS
FA462025R0001
When developing design/construction documents (UFGS specifications, drawings, submittals, etc.) use the following Design Guide data developed by the 92d Civil Engineer Squadron Engineering Flight.
SECTION 033000 – CAST-IN-PLACE CONCRETE
A. GREEN PROCUREMENT PROGRAM
1. Fairchild Air Force Base has adopted the Green Procurement Program Plan regarding recycling and conserving resources. The Plan requires that some construction materials be composed of a minimum percentage of recycled products. See FAIRCHILD AIR FORCE BASE GUIDE SPECIFICATION Section 016000, Product Requirements, for details.
B. AIR CONTENT
1. Exterior concrete slabs shall have a minimum air content of 6 percent.
C. COMPRESSIVE STRENGTH
1. Exterior concrete slabs shall have a minimum 28-day compressive strength of 4000 psi.
D. CURING COMPOUNDS
1. Except for use on airfield, no liquid curing compounds shall be allowed for Portland Cement Concrete.
E. CONCRETE TEMPERATURE
1. Temperature of fresh concrete shall be maintained between 50°F and 90°F.
Concrete must be protected from freezing during the curing period.
F. HOT WEATHER REQUIREMENTS
1. The Contractor shall prepare a plan which describes the methods and materials which shall be used to protect concrete under hot weather conditions. See ACI 305R, Hot Weather Concreting, for recommended methods and materials. The Contracting Officer Representative will review and approve (or reject) the proposed plan. In addition to the incorporation of this plan, the Contractor shall:
a. Sprinkle forms and underlying material with water immediately before placing the concrete and the concrete shall be placed at the coolest temperature practicable when hot weather concreting procedures are likely to apply.
b. Cease all placement of concrete when the temperature of the fresh concrete exceeds 90 degrees F.
2. Hot weather conditions shall be assumed to prevail when the surface evaporation rate exceeds 0.15 pounds per square foot per hour as determined by using ACI 305R Figure 2.1.5.
G. COLD WEATHER REQUIREMENTS
1. ACI 306R, Cold Weather Concreting, shall be referenced as a specification.
2. The procedures of Section 1.5 of ACI 306R shall be required and submitted to the Contracting Officer representative. The Contracting Officer Representative will review and approve (or reject) the procedures.
3. Concrete damaged by freezing shall be removed and replaced.
FA462025R0001
SECTION 042000 – UNIT MASONRY
1. Fairchild Air Force Base has adopted the Green Procurement Program Plan regarding recycling and conserving resources. The plan requires that some construction materials be composed of a minimum percentage of recycled products. See FAIRCHILD AIR FORCE BASE GUIDE SPECIFICATION Section 016000, Product Requirements, for details.
B. GENERAL
1. Brick and block shall be tested for limited efflorescence.
2. Upon completion UNIT MASONRY walls shall be cleaned and sealed.
3. Brick face and panel systems shall be cleaned at the end of the one year warranty period.
C. COLOR
1. Face Brick and Brick Panel System
a. Brown Varitone Wire Cut as previously manufactured by Interpace Industries Inc.,
b. Imperial Red Mission as previously manufactured by Interpace Industries Inc., or
c. As approved by the Base.
2. Concrete UNIT MASONRY Unit
a. Color requirement:
i. Split faced, normal weight block color to be standard gray color.
ii. Paint to match as approved by the Government.
3. Mockup
Provide 4 ft. by 8 ft. sample panels of UNIT MASONRY construction for evaluation and establishing workmanship expectations. Panel shall be used to evaluate subsequent UNIT MASONRY work for the specific project. Panel shall be removed upon direction of the Government.
FA462025R0001
SECTION 050000 – METALS
1. Fairchild Air Force Base has adopted the Green Procurement Program Plan regarding recycling and conserving resources. The Plan requires that some construction materials be composed of a minimum percentage of recycled products. See FAIRCHILD AIR FORCE BASE GUIDE SPECIFICATION Section 016000, Product Requirements, for details.
B. COLD-FORMED METAL FRAMING
1. Structural metal studs and joists shall be used for all non-residential construction.
2. All exposed metal framing shall be painted to match adjacent finish.
3. See Section 090000, Paragraph C for non-structural wall requirements.
C. STEEL DECK
1. All new steel deck shall be a minimum of 20 gauge.
D. Metal Roofing
1. See FAIRCHILD AIR FORCE BASE GUIDE SPECIFICATION Section 07 – Moisture and thermal protection.
SECTION 060000 – WOOD, PLASTICS, AND COMPOSITES
1. Fairchild Air Force Base has adopted the Green Procurement Program Plan regarding recycling and conserving resources. The Plan requires that some construction materials be composed of a minimum percentage of recycled products. See FAIRCHILD AIR FORCE BASE GUIDE SPECIFICATION Section 016000, Product Requirements, for details.
B. COMPLIANCE
1. Comply with the specified provisions of the Architectural Woodwork Institute AWI P-208, Quality Standards Illustrated as follows:
2. Wood Casework: AWI Section 400, Premium Grade.
3. Plastic Laminate Casework: AWI Section 400, Custom Grade.
4. Wood Paneling: AWI Sections 200 and 500, Premium Grade.
5. Shop Finishing: AWI Section 1500, Premium Grade.
6. Installation: AWI Section 1700, Premium Grade.
SECTION 080000 – OPENINGS
A. DOORS
1. All facilities that serve the public shall have automatic hardware at entry doors along the accessible route of travel.
2. “Balance” doors (with offset pivot hinges) shall be allowed, but only when such doors are 48” in width or wider.
3. Automatic closure of vehicle doors is preferred over manual closure, to ensure that doors are not left open, and for user convenience. Automatic closure shall be accomplished using buried loop detectors and automatic timers, except at restricted area access entry points. Time interval shall be adjustable. Manual operation of vehicle doors shall still be possible in case of emergency or malfunction.
At restricted area access points, provide Automated Entry Control Systems. Coordination and approval must occur with Security Forces prior to procurement of any Automated Entry Control Systems.
4. Hangar doors shall have detectors that disable the heat while the doors are open.
Maximum gaps of a few inches are allowable to account for poor fit between door panels. The heating disable function shall be capable of being overridden by the base EMCS system.
5. Exterior roll-up doors shall have a minimum R-value of R-4.75.
B. WINDOWS
1. Window glass shall be of high quality, performance glazing with dark bronze tint.
2. Window frames shall be anodized aluminum with dark bronze finish, or to match adjacent. Direction will be given by CE.
3. Window systems shall have a maximum U-factor of 0.30.
C. DOOR HARDWARE
1. When developing specifications for this section, use the Fairchild Base Design Guide sectional information developed by the 92d Civil Engineer Squadron Engineering Flight.
D. TRANSLUCENT WALL AND ROOF ASSEMBLIES
1. Exterior face sheet shall be crystal in color.
2. Interior face sheet shall be white in color.
SECTION 087100 – DOOR HARDWARE
A. IN-HOUSE AND CORPS OF ENGINEER PROJECTS
1. Locksets, Latch sets, and Deadbolts
a. The designer shall write the specifications to include the following:
i. “Locksets, latch sets and deadlocks shall be heavy duty weight. To the maximum extent possible, all locksets, latch sets and deadlocks shall be from the same manufacturer, and of matching style, finish, color, etc. All key operated locks shall be compatible with the Best Lock Corporation "BEST" interchangeable cores.”
ii. The keying schedule shall be developed by the designer and be included in either the project specifications or project drawings.
2. Lock cores shall be specified as follows:
a. For Base Contracted Projects:
i. The contractor shall provide seven pin "BEST" "TB" keyway cores (no substitutes) keyed to the Base Best Grandmaster Key controlled system. Final "pinned" cores and keys shall be purchased from "BEST" by the contractor and shipped to the base locksmith so that they are received prior to Substantial Completion. The base will install the final cores and return the construction cores to the manufacturer.
b. For Corps of Engineers (CoE) Contracted Projects:
i. Construction cores shall be provided by the contractor and delivered to the government prior Substantial Completion. The keying schedule shall still be prepared
FA462025R0001
by the designer and included in the either the specifications or drawings, however, it will be annotated with a note that says, “Final cores to be provided by the contractor”.
3. Door hardware. For guidance see FAIRCHILD AIR FORCE BASE GUIDE SPECIFICATION Section 087100 Guidelines, Attachment 1.
SECTION 090000 – FINISHES
A. DESIGN GUIDES
1. All interior and exterior finishes are in various AMC Design Guides and the Fairchild AFB Architectural Compatibility Plan. Copies of these documents can be checked out by hand receipt from the Engineering Flight, 92 CES/CEN.
B. GREEN PROCUREMENT PROGRAM
1. Fairchild Air Force Base has adopted the AF Sustainable Procurement Program regarding procurement of items that use recycled materials and conserve resources. The program requires that some construction materials be composed of a minimum percentage of recycled products.
See FAIRCHILD AIR FORCE BASE GUIDE SPECIFICATION Section 016000, Product Requirements, for details.
C. NON-STRUCTURAL METAL FRAMING
1. Metal studs shall be used for all non-residential construction.
2. All exposed metal framing shall be painted to match adjacent finish.
3. See FAIRCHILD AIR FORCE BASE GUIDE SPECIFICATION Section 05, Section 05000 for load bearing wall requirements.
D. CERAMIC TILE
1. When developing specifications for this section, use the Fairchild Base Design Guide sectional information developed by the 92d Civil Engineer Squadron Engineering Flight.
E. CARPET
1. When developing specifications for this section, use the Fairchild Base Design Guide sectional information developed by the 92d Civil Engineer Squadron Engineering Flight.
2. For projects which are solely for carpet replacement, refer to the current Installation Facilities Standards (IFS) to obtain information on USAF Carpet Program, and the Mandatory Source Selection Contract AFCA (10 August 2018).
F. SUSPENDED CEILINGS
1. Ceiling grid shall be 2’ x 2’ accepting tiles with “tegular” type reveal edges. Drop-out ceilings (foam-grid panels) are not permitted. Ceiling grids shall be seismically braced per the current International building Code.
G. EXTERIOR PAINTING
1. Applies to all base facilities including commercial/industrial buildings, flightline facilities, and administration complexes.
2. Follow AMC Design Guides and the Base Architectural Compatibility Plan.
3. Specific Guidance
a. Exterior colors shall match:
i. Walls: “FAFB Cool Sierra Tan” #CR-133-10 (Sherwin-Williams’ color: “Sierra Tan”
#SW8258).
ii. Doors and Frames: Sherwin-Williams’ color: “Spanish Moss” #SW2070.
iii. Roof Panels: AEP Span – Dura Tech 5000 finish color “Cool Weathered Copper” (SRI 34).
FA462025R0001
iv. Wall Panels: Citadel Architectural Products – Kynar 500 metal finish color: “Bone White”.
v. Paint codes for Sherwin-Williams “Spanish Moss” and “FAFB Cool Sierra Tan” are provided below.
vi.
EXTERIOR ARCHITECTURAL EXTERIOR ARCHITECTURAL
SUPER PAINT LATEX SUPER PAINT LATEX
SATIN IFC 8112NP SATIN IFC 8112NP
2070 SPANISH MOSS 2070 SPANISH MOSS
SHER-COLOR FORMULA SHER-COLOR FORMULA
CCE*COLORANT 0Z 32 64 128
W1-White - 38 - 1 W1-White 4 63 - 1 B1-Black 4 60 1 1 B1-Black 28 47 1 1 R2-Maroon - 24 - - R2-Maroon 2 56 - - Y3-Deep gold 4 4 1 - Y3-Deep gold 20 22 1 -
ONE GALLON
ULTRADEEP
FIVE GALLON
A89T00154 640392379 A89T00154 640392387
EXTERIOR ARCHITECTURAL EXTERIOR ARCHITECTURAL
SUPER PAINT LATEX SUPER PAINT LATEX
SATIN IFC 8112N SATIN IFC 8112NP
CR-133-10 FAFB COOL SIERRA TAN CR-133-10 FAFB COOL SIERRA TAN
CUSTOM MANUAL MATCH CUSTOM MANUAL MATCH
W1-White 2 19 1 1 W1-White 12 34 1 1 B1-Black 4 53 1 - B1-Black 28 11 1 - R2-Maroon - 4 - - R2-Maroon - 20 - - Y3-Deep gold - 9 - 1 Y3-Deep gold - 46 - 1 G2-New Green - 2 - - G2-New Green - 10 - -
ONE GALLON
FIVE GALLON
A89W00153 640392346 A89W00153 640392353
b. Metal roofing shall match AEP Span – Dura Tech 5000 metal finish color “Cool Weathered
Copper”; gutters, fascia and trim shall match “Spanish Moss”.
c. Downspouts shall be “open-face” type with both exterior and interior surfaces (exposed to view) colored to match adjacent facility surface color.
d. Personnel doors, all door trim and window trim shall be “Spanish Moss” or painted to match the body of the facility, as approved by the Contracting Officer. Roll-up doors shall match the
FA462025R0001
building body color if building is painted and shall match “Spanish Moss” if building is mostly brick.
e. Bollards shall be “Spanish Moss” with 4” white reflective (Scotchlite or approved equal) band with its top edge 4” below top of bollard.
f. Exterior paint type (latex, acrylic, etc.) and paint finish (flat, semi-gloss, gloss) shall be determined by the Design Guides and approved by the government.
g. The use of markings, symbols, or signs on buildings is prohibited unless they are part of the approved building paint scheme. No super graphics are authorized on and in facilities.
h. Miscellaneous.
i. Exterior HVAC and electrical equipment, ducts, pipes, and architectural features on or near facilities shall be made "invisible" by painting them to match the adjacent facility surface color. If not near the facility (as determined by the Government), items shall be painted “Spanish Moss”. Landscaping shall also be used when appropriate to reduce visibility of these items.
ii. Exterior handrails for administrative facilities shall be brushed aluminum or dark bronze anodized aluminum and shall not be painted steel. Handrails in industrial areas shall be steel, painted “Spanish Moss.”
iii. All trash dumpsters are to be painted “Spanish Moss.” Utility cabinets, HVAC equipment, trash dumpsters shall be screened in accordance with the Architectural Compatibility Plan.
H. INTERIOR PAINTING
1. Compatibility: Interior design compatibility at Fairchild AFB shall be a cohesive approach to coordination of interior materials, construction details, finish colors and furnishings.
2. Color: Follow AMC Design Guides and the Architectural Compatibility Plan.
a. For interior “cool” white match: Sherwin-Williams “Sleek White” #SW1018
b. For interior “warm” white match: Sherwin-Williams “FAFB Off White” #CR-2546-07
3. Specify Class 5 drywall finish for all walls with semi-gloss paint, Class 4 drywall finish for other paints.
4. Specify special sealer for all gypsum wallboard composed of recycled products.
5. All exposed surfaces, including (but not limited to) ductwork, conduit, grilles, diffusers, piping (sprinkler, water service, drainage, etc.), and equipment (access panels, etc.) shall be painted to match color, texture and finish of adjacent surfaces, unless factory finish is suitable (as determined by Government) or specific exceptions are called out in the specifications. Fire alarm devices are not to be painted. All conduit related to fire protection shall be “red”, and prefinished from the factory. Field painting is prohibited.
6. Painted CMU is not acceptable as an interior finish except inside utility rooms, such as storage, mechanical, electrical, communications, etc.
SECTION 093010 – CERAMIC, QUARRY, AND GLASS TILING
A. PURPOSE
1. Provide technical and functional/aesthetic criteria for the selection, installation, and maintenance of ceramic tile. Ceramic tiles include glazed, unglazed, porcelain, quarry, mosaics and pavers.
These standards do not apply to other hard surface products such as stone, resin, conglomerates, etc.
B. GLOSSARY OF TERMS
FA462025R0001
1. Breaking Strength – In order to determine the strength and durability of ceramic tile, a standard test method (ASTM C648) is used to evaluate the tile. A force is applied to an unsupported portion of the tile specimen until breakage occurs. The ultimate breaking strength is then recorded in pounds. The ANSI standard requires an average breaking strength of 250 lbs. for floor tile.
2. Ceramic Mosaic Tile – Tile formed by either the dust-pressed or plastic method, usually ¼ to 3/8 inch thick, having a facial area of less than six square inches. May be of either porcelain or natural clay composition and they may be either plain or with an abrasive mixture throughout.
3. Coefficient of Friction – This is a term used in physics to describe the amount of force required to cause an object to start moving across a surface. Tiles are tested for coefficient of friction in accordance with ASTM C-1028. A quantitative value can be determined to generally express the relative degree of slip resistance. A higher coefficient indicates increased resistance. Although there is no current ANSI requirement, a minimum coefficient of friction of 0.50 (wet and dry) is the recognized industry standard for a slip-resistant flooring surface. The Occupational Safety and Health Administration (OSHA) also recommends this same standard for walking surfaces. The Americans with Disabilities Act (ADA) recommends a minimum coefficient of friction of 0.60 (wet and dry) for accessible routes and 0.80 for ramps.
4. Durability Classification (Abrasion Resistance) – Glazed ceramic and porcelain tile normally carry a durability class rating. Although there are no official industry standards, most manufacturers give their tile a rating number from I to IV+, according to the results of the Porcelain Enamel Institute (PEI) abrasion test. The Porcelain Enamel Institute rating is not a measurement of quality. It is a scale that clearly indicates the areas of use each manufacturer recommends and has designed their tile to fit.
Rating Traffic Recommended Applications
Class I No Foot Traffic interior residential and commercial wall
Class II Light Traffic interior residential and commercial wall; residential bathroom floor
Class III Light/Moderate residential floor and wall
Class IV Moderate/ Heavy Traffic residential, medium commercial and light institutional floor and wall
Class IV+ Heavy/Extra Heavy Traffic residential, commercial and institutional floor and wall;
subjected to heavy/extra heavy traffic
5. Glazed Tile – Tile with fused impervious facial finish composed of ceramic material, fused to the body of the tile that may be non-vitreous, semi-vitreous, vitreous or impervious.
6. Paver Tile – Glazed or unglazed porcelain or natural clay tile formed by the dust-pressed method having a facial area of six square inches or more.
7. Porcelain Tile – A ceramic mosaic or paver tile that is generally made by the dust-pressed method of composition resulting in a tile that is dense, impervious and fine grained.
8. Quarry Tile – Glazed or unglazed tile, made by the extrusion process from natural clay or shale usually having a facial area of six square inches.
9. Scratch Hardness (MOH’s Hardness) – The relative hardness of glazed tile is an important issue that should be addressed when selecting tile. Scratch resistance of glazes is measured by scratching the surface of the tile with different minerals and assigning a “MOH’s Scale Hardness” number to the glaze, the softest mineral used is talc (a rating of 1) and the hardest is a diamond (a rating of 10 if no scratch). Most glazes used on ceramic tile fall in the five to six range, which is also slightly harder than most steels. Case-hardened steel, such as what is used in drill bits, is
FA462025R0001
approximately six and will scratch most glazes. Quartz, number 7 on the MOH’s scale, will scratch most glazes (sand is a common example of natural quartz).
10. Tile – A ceramic surfacing unit, usually relatively thin in relationship to facial area, made from clay or a mixture of clay and other ceramic materials, called the body of the tile, having either a glazed or unglazed face and fired above red heat in the course of manufacturing to a temperature sufficiently high to produce specific physical properties and characteristics.
11. Unglazed Tile – A hard, dense tile of uniform composition throughout, deriving color and texture from the materials of which the body is made.
12. Water Absorption – ASTM C-373 is the test method for classifying ceramic tile by the percent of its water absorption. Individual tiles are weighed, saturated with water, and then weighed again.
The percent difference between the two conditions is referred to as the water absorption.
Although this test is used to evaluate water absorption of glazed and unglazed product, it can also be a good indicator to predict the stain resistance of the unglazed tiles. Generally, for unglazed tiles, the lower the water absorption, the greater the stain resistance.
a. Impervious - Tiles exhibiting 0.5% or less
b. Vitreous - Tiles exhibiting more than 0.5% but not more than 3.0%
c. Semi-Vitreous - Tiles exhibiting more than 3.0% but not more than 7.0%
d. Non-Vitreous - Tiles exhibiting more than 7.0%
C. LOCATION
1. Tile is appropriate for all areas which may be subject to high foot traffic, wetness, and require the need for increased durability, e.g., dining facilities, kitchens, break rooms, restrooms, entry lobbies, floors and or walls, etc.
D. SELECTION
1. Technical criteria: Select tile based on the performance criteria appropriate for the functional use of the space. There are five properties of ceramic tile to consider: Coefficient of Friction, Durability Classification or PEI, Scratch Hardness, Breaking Strength and Water Absorption.
Select tiles with the following properties:
a. Coefficient of Friction: Floor tile shall have a minimum coefficient of friction of 0.60 (wet and dry) or higher in accordance with ASTM C-1028. Standing water and other contaminants create slippery conditions for any hard surface floor material. Floor applications with exposure to these conditions require extra caution in the tile selection. Use abrasive grains or raised textured tile for greater traction in areas with the possibility of standing water or grease build up.
b. Durability Classification: Floor tile shall be Class IV—Heavy Traffic, durability classification as rated by the manufacturer when tested in accordance with ASTM C-1027 for abrasion resistance as related to foot traffic. Class III can be considered for residential installations.
c. Scratch Hardness: Glazed floor tile shall have a scratch hardness of 6.0 or higher. Do not use glazed tile in areas of high abuse where possible tile breakage may occur. Avoid high gloss or polished tiles for areas with high traffic; use only as accents in floor patterns.
d. Breaking Strength: Tile shall be impact resistant with a minimum breaking strength of 250 lbs in accordance with ASTM C-648.
e. Water absorption: Use only vitreous or impervious tile for most applications in accordance with ASTM C-373.
2. Functional/Aesthetic Criteria: Some products work better in certain functional areas than others.
The pattern, texture, and color or combination of colors will greatly influence the overall appearance of tile. Consider the amount of cleaning and maintenance required when selecting particular tiles and grouts.
FA462025R0001
a. Slip resistance: This is a major factor in the selection of tiles for kitchens and entrance lobbies. There are numerous products that have slip-resisting features for lobbies. Unglazed quarry tile works best for commercial kitchen floor installations. Because of the possibility of water and grease spillage, unglazed tile must be sealed in kitchens.
b. Color: Recommend tile with through-color, that is, color the entire thickness of the tile body.
Avoid solid color tiles unless they are designed into a pattern. Avoid light-colored quarry tile in commercial kitchens. Colors and patterns shall be approved by the Government.
c. Texture: Tiles with a textured surface and an interesting variation of colors will tend to show less surface soiling.
d. Grout: Select medium to dark pigmented grouts. Light grouts tend to change color and trap soil over a period of time. Minimize the visibility of grout by using larger-sized tile.
e. Base: Use a matching tile base in commercial kitchens and other areas subject to excessive water. In other locations, wood or vinyl base may be appropriate. Ensure that there is an aesthetical transition between tile/wood bases and vinyl bases as you progress from one area to another.
E. INSTALLATION
1. Tile: Install tile in accordance with the appropriate ANSI A108/ANSI A118/136-1999 Specifications for the Installation of Ceramic Tile as per manufacturer’s instructions.
a. Provide transition strips wherever the tile meets another floor material to avoid damage to the tile edges and ensure that there are no accessibility issues.
b. Provide trim tile like bull nose at wall edge transitions.
c. Mockup: Provide 4 ft. by 8 ft. sample panels of tile construction (floor and wall) for evaluation and establishing workmanship expectations. Panels shall be used for evaluation of subsequent tile work for the specific project. Panels shall be removed upon direction of the Government.
2. Grout: Ceramic tile grout shall be prepared and installed in accordance with ANSI A108.10.
Follow grout manufacturer’s recommendations as to grouting procedures and precautions.
a. Take special care, especially when grouting with dark pigmented colors, to clean all of the grout from the tile during installation. A grout release is recommended to prevent finely powdered pigments from lodging in the pores of the tile surface. Epoxy grouts are recommended for kitchens, showers and rest rooms.
3. Sealant: Some tiles and grouts do not require sealant, but others require multiple coats of sealant at the time of installation. Do not apply sealant to glazed tile, but unglazed tile must be sealed.
a. Apply sealant to the tile and grout in accordance with manufacturer’s instructions. Perform acceptance tests per manufacturer’s recommendations before accepting the completed installation. Some sealants may also require reapplication several times a year. Application of silicone sealer may be required for maximum protection.
b. Obtain the tile manufacturer’s guidelines for recommended cleaning agents. Ensure that the occupant receives the care information in the form of an Operations & Maintenance Manual.
Include information regarding requirements for reapplication of sealants.
F. CARE AND MAINTENANCE
1. Clean and maintain floor tile according to the manufacturer’s recommendations without being excessive. Obtain specific information on the product used from the tile distributor, contractor or installer. Provide Operations Engineering Service Contracts Element (92 CES/CEOE) with appropriate cleaning and care instructions so this information can be incorporated into base custodial contracts.
FA462025R0001
2. Cleaning: Establish a regular schedule for routine cleaning of tile floors to remove day-to-day dust and other “normal” accumulations (food crumbs, boot and shoe marks, etc.). This includes (but is not limited to) sweeping, dusting, light vacuuming and washing.
a. Identify and remove stains and spillage immediately. Under normal situations, most tile can be easily cleaned using clear water with a manufacturer’s recommended tile cleaner. Always follow up with a rinse of clean water.
b. Do not use undiluted bleach or harsh/abrasive cleaning agents as they can scratch the surface of the tile or degrade the finish surface of either tile or grout. Do not combine ammonia with any bleach as this creates a toxic substance.
c. Tile with coarse or abrasive type surfaces requires more frequent performance of cleaning and/or maintenance. More vigorous agitation with more frequent changes of water is necessary.
3. Maintenance: Maintain the tile on a regular and frequent basis to prevent buildup of soil, grease, residue, soap, detergents, sealers, dampness, liquids, etc., which may reduce the static coefficient of friction, and reduce the aesthetic appearance of the tile.
a. Do not apply waxes or floor polish to ceramic tile floors unless specifically recommended by the manufacturer. Wax cleaner, oil-based detergents and sealants may decrease the slip resistance of ceramic tile. They also have the tendency to attract and trap dirt when not completely removed during the cleaning process.
b. In cases where waxing is recommended, ensure that old wax is stripped according to manufacturer’s recommendations before new wax is applied.
c. Follow manufacturer’s directions when buffing is recommended as a maintenance procedure.
Do not buff excessively, or use coarse buffing pads, as this may cause a permanent burn to the surface of the tiles.
d. Use protective padding to prevent damage when moving any heavy equipment or sharp-edged items over the tile (e.g., moving furniture into a building, bringing in carts of musical instruments for a performance at a club, etc.). This is especially important when tile is used as stair treads.
SECTION 100000 – SPECIALTIES
A. SIGNAGE
1. When developing specifications for this section, use the Fairchild Base Design Guide sectional information developed by the 92d Civil Engineer Squadron Engineering Flight.
B. PAPER TOWEL AND TOILET PAPER DISPENSERS
1. In restrooms, all paper towel and toilet paper dispenser cabinet locks shall be tool operated.
Keyed locks shall not be permitted.
2. Any restroom design shall require locating, furnishing, and installing backing for the specific dispensers needed by the Government's custodial contract, but shall not be installed by the Government’s Custodial Contractor. Dispensers shall meet the paper product and soap specifications outlined below.
FA462025R0001
a. Toilet Tissue Dispensers shall be a high-capacity standard 3-roll type and come complete with a tamper-resistant lock. If a role is used, simply turn the dial to advance to the next role.
Where limited space is an issue, the use of a standard 2-role side-by-side type dispenser is acceptable, where one role is covered, while one is in use. Toilet tissue paper product specifications: 3.25-inch x 4-inch double-ply, 865 sheets per role.
b. Hand Towel Dispensers shall be a high-capacity design and come complete with a tamper-resistant lock. The dispenser shall require the user to only touch the paper product reducing cross-contamination and shall cut the rolled paper product in pre-measured 11-inch lengths.
Dispenser shall hold 1 high-capacity role. Hand towel paper product specifications: 8-inch roll, 800 feet per roll. Multi-fold towels & dispensers are no longer used on the installation.
c. Hand Soap Dispensers shall be a high-capacity cartridge style. Dispenser shall accept a
1-liter replaceable cartridges and come complete with a tamper-resistant lock. The use of refillable liquid containers is no longer supported on the installation.
SECTION 101400 – SIGNAGE
A. OVERVIEW
1. When developing specifications for signage, use UFC 3-120-01, Design: Sign Standards as amended/clarified by this data sheet.
2. Hierarchy:
a. This data sheet. This data sheet incorporates standards set forth in AMC Exterior Sign Standards and AMC Services Signage Policy Supplement.
b. UFC 3-120-01, Design: Sign Standards.
3. Design proposals for all signs (other than the types mentioned in this data sheet) shall be submitted to Base Civil Engineer’s Architectural Compatibility Review Board (ACRB) for approval prior to implementation. Allow a minimum of 30 days in the design process for ACRB review.
B. REFERENCES
1. AMC Exterior Sign Standards
2. AMC Services Signage Policy Supplement
3. ASTM D4956, Standard Specification for Retroreflective Sheeting for Traffic Control, http://www.astm.org/Standards/D4956.htm
4. Fairchild Air Force Base Installation Facilities Standards
5. Manual on Uniform Traffic Control Devices (MUTCD), Federal Highway Administration http://mutcd.fhwa.dot.gov/
6. UFC 3-120-01, Design: Sign Standards http://www.wbdg.org/ccb/DOD/UFC/ufc_3_120_01.pdf
C. TYPOGRAPHY, GRAPHICS, AND SIGN PLACEMENT
1. Graphics
a. For exterior signs, where a shield or emblem is referenced, use the AMC shield for units under AMC. Tenant units, such as AETC, JPRA, DRMO, ANG, and Army, may use their respective shield or emblems. When using adhesive backed stickers for these shields or emblems, trim to the outline of the shield or emblem only.
D. THE AMERICANS WITH DISABILITIES ACT
FA462025R0001
Attachment 3 - 2025 Base Design Guide Data Sheets http://www.astm.org/Standards/D4956.htm http://mutcd.fhwa.dot.gov/ http://www.wbdg.org/ccb/DOD/UFC/ufc_3_120_01.pdf
1. Parking Stalls
a. All parking lot striping shall be white. Do not provide handicapped symbols or wording to the parking surface of parking stalls.
b. Handicapped parking access aisles will be striped, white by diagonal stripes.
E. EXTERIOR IDENTIFICATION SIGNS
1. Military Identification Signs:
a. Military (Building) Identification Sign
i. All building identification signs shall be free standing.
ii. Signs shall be Charleston Industries, Inc., Architectural Signage Systems, Series 325 Post and Panel System, Standard Design.
iii. Signs will be double-faced and oriented perpendicular to the roadway to permit reading by traffic moving in both directions.
iv. Provide full street address below the unit name.
v. Provide address lettering heights equal to the name of the organization.
vi. Sign colors shall be white letters on “National Park Service Brown” background.
Background, sign back, and post color shall match.
vii. Posts shall be 2-1/2” x 3-1/4” with 3’ buried in a 12” diameter by 3’-6” deep concrete footing.
viii. Existing SERE School building identification signs are installed on brick bases. All future signs shall match main base (installed on posts).
b. Building Number Sign Type
i. Only show the building number without displaying “Building Number” wordage.
ii. Locate sign on side elevation at approximately 5’-4” above ground. Adjust the placement of the sign to fit within the brick or block coursing where possible. Use only one sign per building.
iii. Sign colors shall be white letters on “National Park Service Brown” Pantone, PMS469c color background.
2. Community Identification Signs:
a. Use Military (Building) Identification Sign when identifying community facilities as opposed to the Community Facilities Signs.
b. Facilities with Services Activities (per AMC Services Signage Policy Supplement):
i. Facilities that house more than one Services activity will have all collocated activities listed on the exterior sign.
ii. Illuminated entrance signage is limited to one exterior illuminated sign per facility, located at or near the main entrance to the facility/operation.
iii. Entrance door signage is limited to facility name and hours of operation.
c. ACRB approval is required for all community and services activity identification signs.
F. DIRECTION SIGNS
1. Do not attach additional signs, such as the “H” for “Hospital” or “Tree City USA” to posts supporting another sign.
2. Direction Signs
FA462025R0001
a. Sign colors shall be white letters, arrows, rules and borders (reflectivity mandatory) on
“National Park Service Brown” background.
3. Street Name Sign
a. Provide one street name sign (for each street) at each street intersection.
b. Sign locations shall be consistent with other intersections in area and installed above traffic control signs. Mount both street name signs on single post.
c. Sign panel material shall be aluminum with a minimum thickness of 0.100”.
d. All street name signs are to include a 4” AMC shield to the left of the street name.
e. Sign colors and materials shall be as specified in the MUTCD.
4. Direction Signs Type
a. Vehicular directional and way finding signs shall be as detailed in the MUTCD.
b. Pedestrian directional signs shall follow UFC 3-120-01.
G. REGULATORY SIGNS
1. Traffic Control Signs
a. Traffic control sign face layout and colors shall be in accordance with the MUTCD.
b. Sign back and post color shall be painted to match Sherwin Williams SW #2070 “Spanish Moss.”
c. Reflective sheeting shall be warranted to meet or exceed MUTCD Table 2A-3 Minimum Maintained Retro-reflectivity Levels for ten years. Black is non-reflective.
d. If MUTCD sign size is inconsistent with other signs of the same type on base, obtain ACRB approval.
e. Sign panel material shall be aluminum with minimum thickness:
Horizontal width less than 20” 0.063”
Horizontal width between 20” and 36” inclusive 0.080”
Horizontal width over 36” 0.125”
Notes:
1 - The side dimension for a diamond shaped warning sign is considered to be the maximum horizontal dimension.
2 - Freestanding signs on the flightline (within the controlled area) shall be 0.100” minimum thickness.
f. Either non-perforated 2-1/2” square or 2-3/8” outside diameter round metal posts may be used. Round posts require special mounting brackets to maintain orientation of sign panels, bolting through round post is not permitted.
2. Handicapped Parking Signs:
a. Handicapped Parking Signs shall be freestanding unless approved by the Architectural Compatibility Review Board (ACRB).
b. Use Parking Regulation Sign for designation of handicapped parking stalls.
c. Do not display any “Fines” wordage or panels to handicapped signs.
d. Sign face colors shall be white symbol, letters, and border on “National Park Service Brown” background.
FA462025R0001
e. Sign back and post color shall be painted to match Sherwin Williams SW #2070 “Spanish
Moss.”
f. For van accessible spaces, provide the same, but substitute the wording “Van Accessible” for “Reserved Parking.”
g. Signs shall be pole mounted. Use the clear height of 5’-0” to the bottom of the panel unless safety dictates use of the 7’-0” height. When handicapped parking spaces are adjacent to reserved parking spaces, install handicapped parking signs at same height as reserved parking signs.
h. Handicapped parking signposts shall be non-perforated 2” square metal tubing.
3. Reserved Parking Signs:
a. Reserved Parking Signs shall be freestanding unless approved by the ACRB.
b. Curb markings shall not be used.
c. Use Parking Regulation Sign for designation of reserved parking stalls.
d. Sign face colors shall be white letters and border on “National Park Service Brown” background.
e. Sign back and post color shall be painted to match Sherwin Williams SW #2070 “Spanish Moss.”
f. Signs shall be pole mounted. Curb markings shall not be used.
g. Reserved parking signposts shall be non-perforated 2” square metal tubing.
h. The following reserved parking locations are authorized:
i. Squadron-level facilities may have one reserved parking sign for each of the following positions: Squadron Commander, Deputy (Ops Officer), First Sergeant, and Chief Master Sergeants.
ii. Wing Commander: Reserved parking signs for the wing commander are authorized at Wing Headquarters, Command Post, Fitness Center, Officer/Enlisted Club, Commissary, and Base Exchange.
iii. Limited customer service or visitor spaces and government-owned vehicle spaces are authorized: Number and location(s) shall be approved by the ACRB.
iv. Honor Guard: One spot at the Shoppette and one spot at the Base Exchange.
v. Car-Pool: Use requires approval by the ACRB.
H. MOTIVATION SIGNS
1. Exterior signs displaying unit emblems, mottoes, or personal names are not permitted.
2. Use of motivation signs shall be approved by the ACRB.
I. WALL MOUNTED SIGNS
1. Use of wall mounted signs is discouraged.
2. Except for the Building Number Sign or required hazard placards, use of wall mounted signs shall be approved by the ACRB.
J. SPECIFICATIONS AND DETAILS
1. Submit shop drawing of each sign and post/base for approval by 92 CES/CENM prior to manufacture.
2. Do not mix metals. For example, use aluminum bolts with aluminum stock.
3. Assembly bolts and brackets shall match the surface color where attached.
FA462025R0001
4. Exterior Signs shall be designed for nighttime visibility.
a. All sign background, legend, symbol, and border colors shall be retroreflective except for black which shall be opaque.
b. Reflective sheeting shall meet ASTM D4956 Type I.
5. For exterior signs not specified elsewhere in this data sheet, the minimum aluminum panel thickness shall be 0.063”.
6. Sign Posts/Bases:
a. Use concrete footings.
b. The use of wood posts is not permitted.
c. Steel posts, when used, shall be galvanized.
d. Posts shall not be perforated.
SECTION 110000 – EQUIPMENT
A. PERMITTING REQUIREMENTS
1. Refer to Section A.3, Environmental, to determine permitting requirements for equipment that includes, but is not limited to: paint booths, sawdust collectors, bag houses, and cyclones.
B. Equipment Installation requirements
1. All equipment mounting brackets shall be secure using finish screws that are color-coded to match the mounting brackets.
2. Any damage to the walls and ceilings during installation of any equipment shall be professionally repaired to match the same texture and color of the surrounding area. Damaged ceiling tiles shall be replaced with matching tiles.
3. Interior conduit shall be run inside walls, above ceilings or in crawl spaces/basement areas.
Cable/wires run in ceilings that are used for return air plenums shall be run in rigid conduit or are “plenum-rated”. Flush mounted cut in boxes shall be used for all new power/data points. Surface mounted conduit and boxes are prohibited except in utility rooms.
4. All power cords and data lines shall exit walls and ceilings at a point as close to the equipment as possible. All data lines shall enter walls in boxes with color coded faceplates that match the type originally installed in the facility.
5. No conduit, wires, cable, etc. are allowed to be attached to the exterior walls or roofs of buildings except in extreme circumstances. Building penetrations shall be below grade whenever possible.
If it is not possible to enter buildings below grade, conduit shall enter the building as close to grade as practical. All exposed exterior conduit shall be painted to match the exterior of the facility.
6. All equipment installations that require supporting electrical work or other facility modifications must be approved by 92CES on an AF Form 332 PRIOR to purchasing the equipment. A drawing/sketch shall be attached to the AF Form 332 that shows the location of all equipment that is proposed to be installed and depicts the location of any new electrical or communication requirements. All electrical work that is provided as part of the equipment installation shall conform to the National Electrical Code.
7. Any equipment installation requiring penetration of fire walls shall be protected with a material or system of the same hourly rating that is listed by UL, FM, or a NRTL.
FA462025R0001
SECTION 140000 – CONVEYING EQUIPMENT
A. ELEVATORS
1. Specifications shall require contractors installing elevators to include a 1-year service and maintenance agreement included in the construction contract for all new elevators. (This is in addition to the standard, one-year construction warranty).
SECTION 210000 – FIRE SUPPRESSION
A. GENERAL DESIGN REQUIREMENTS
1. Design for all new construction and major projects shall comply with, but not limited to:
a. UFC 3-600-01, Fire Protection Engineering for Facilities
b. All applicable Tri-Service Fire Protection Engineering Working Group (TSFPEWG) Guides
c. All Applicable NFPA standards, except where modified by UFC 3-600-01
d. All applicable Fairchild specific requirements
e. The Designer shall confirm that this guidance has not been superseded by any subsequent DoD directives.
2. Entire facility has automatic fire detection and/or sprinkler fire suppression system.
B. KITCHEN EQUIPMENT
1. All suppression systems used for the protection of commercial cooking operations shall be wet chemical systems IAW NFPA 17A and shall be designed as “overlapping” type.
C. WET-PIPE SYSTEMS
1. An electronic water flow switch (vane paddle type) shall be installed for the purpose of indicating a fire condition and be adjustable to delay the signal to the fire alarm panel up to at least one minute.
2. Water flow pressure switches and retard switches are not required.
D. DRY-PIPE SYSTEMS
1. The air system side shall be maintained by an Air Pump: Supervisor Air Panel, Model F112, UL Listed 892A, the pump being a Vacuum-Pressure, Model # 400-1901, manufactured by Barnat Co., Berrington, IL 60010, or equal.
E. PREACTION SYSTEMS
1. The chamber, valves and assembly shall be a Gem Multimatic, Model A-4; a Grinnell Duomatic, or approved equivalent.
2. No water flow pressure switches or retard switches on the system.
F. FIRE HYDRANTS
1. Fire hydrants shall be Dry barrel and suitable for winter conditions. 5 inch Storz adapters must be attached to the largest diameter opening of all new fire hydrant installations.
2. Fire hydrants shall be identified by color, based upon NFPA 291.
G. KEYS
1. All fire equipment cabinets on Fairchild AFB shall be keyed alike.
H. MISCELLANEOUS REQUIREMENTS
FA462025R0001
1. The Inspectors Test Valve, if not located with riser, must not be hidden and remain accessible to maintenance personnel.
2. All fire sprinkler systems shall have a PIV shut off valve.
3. All hydraulic and general information placards will be metal and information shall be permanently stamped
4. Fire suppression systems shall have an external electric bell to indicate water flow by the fire riser room.
5. All tamper switch arms on OS&Y valve stems shall be in the grove of the valve stem for proper alignment.
6. All rooms containing Fire Suppression equipment shall be labeled at the door.
SECTION 220000 – PLUMBING, GENERAL PURPOSE
A. WATER MAIN CHECK-VALVES
1. Watermain check valves shall be externally weighted, non-slam style.
B. BACKFLOW PREVENTION
1. Backflow assemblies are required at the water service entrance to buildings. Internal backflow assemblies are required at boiler make-up connections and any other location where the source of potential contamination through cross-connections is present. Specify the appropriate level of protection for the level of hazard.
2. All permanently installed backflow prevention assemblies shall be manufactured by Febco or Wilkins and shall, at time of installation, reside on the current publication of Washington State Department of Health – Division of Environmental Health – Office of Drinking Water’s Publication 331-137, Backflow Prevention Assemblies Approved for Installation in Washington State.
C. CATHODIC PROTECTION
1. See FAIRCHILD AIR FORCE BASE DESIGN GUIDE Section 264200 for cathodic protection Requirements.
D. WELDING
1. See FAIRCHILD AIR FORCE BASE GUIDE SPECIFICATION Section 013520, Paragraph B.2 for welding requirements.
E. PIPING
1. Do not specify grooved pipe and fittings for domestic water systems.
2. If copper piping is specified on hot or cold domestic…