233400 02-15 HVAC FANS.docx

DOCX document 25 KB Posted

Attached to
Z2DA--Proj #: 629-18-127, Remodel Pharmacy for USP 800
Solicitation number
36C25621R0013
Issued by

About this file

This document package includes a federal contract solicitation and related technical specifications for heating, ventilation and air conditioning (HVAC) fan installation.

The solicitation is for remodeling a pharmacy at the Southeast Louisiana Veterans Health Care System in New Orleans to meet new USP 800 compounding standards, including building a new segregated compounding area, with a project value between $1 million and $5 million. The procurement is reserved exclusively for service-disabled veteran-owned small businesses. The technical specifications cover centrifugal fans, utility fans, materials, corrosion protection, vibration control, testing and other HVAC fan requirements. Products include cabinet fans, centrifugal fans, variable speed motor controllers and accessories. The contractor must provide all labor, equipment, and supervision for fan installation per the specifications.

View the file

Other files

File Type Posted
36C25621R0013 0002.docx DOCX document
Sign in Sheet - Pharmacy Remodel Project.pdf PDF
36C25621R0013 0001.pdf PDF
054000 Cold-Formed Metal Framing.docx DOCX document
013323 Shop Drawings.docx DOCX document
262921 01-17 ENCLOSED SWITCHES AND CIRCUIT BREAKERS.docx DOCX document
230593 02-15 TESTING ADJUSTING AND BALANCING FOR HVAC.docx DOCX document
000110 TOC.docx DOCX document
EXHIBIT C SUBCONTRACTOR INFORMATION AND CONSENT.docx DOCX document
General Decision LA 20190041 05-31-2019 Orleans Parish LA Building.pdf PDF
224000 09-15 PLUMBING FIXTURES.docx DOCX document
EXHIBIT A PERFORMANCE RELEVANCY SURVEY (1).docx DOCX document
260526 01-17 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS.docx DOCX document
017419 Construction Waste Management.doc DOC document
102600 Wall and Door Protection.docx DOCX document
220711 09-19 PLUMBING INSULATION.docx DOCX document
234000 2-12 HVAC AIR CLEANING DEVICES.doc DOC document
230541 02-15 NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT.docx DOCX document
230711 02-15 HVAC AND BOILER PLANT INSULATION.docx DOCX document
072113 Thermal Insulation.docx DOCX document
233100 3-13 HVAC DUCTS AND CASINGS .docx DOCX document
Architectural Final.pdf PDF
087113 ADO.docx DOCX document
088000 Glazing.docx DOCX document
230800 11-16 COMMISSIONING OF HVAC SYSTEMS.docx DOCX document
260519 01-17 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES.docx DOCX document
092900 Gypsum Board.docx DOCX document
221300 09-15 FACILITY SANITARY AND VENT PIPING.docx DOCX document
230511 8-17 COMMON WORK RESULTS FOR HVAC.docx DOCX document
000115 List of Drawings.docx DOCX document
092216 Non-Structural Metal Framing.docx DOCX document
Fire Protection Final.pdf PDF
099100 Painting.docx DOCX document
232500 02-15 HVAC WATER TREATMENT.docx DOCX document
Exhibit B Past and Present Performance Questionnaire.docx DOCX document
233700 02-15 AIR OUTLETS AND INLETS.docx DOCX document
087100 Door Hardware.docx DOCX document
081113 HM Doors and Frames.docx DOCX document
051200 Structural Steel.docx DOCX document
079200 Joint Sealants.docx DOCX document
262726 01-18 WIRING DEVICES.docx DOCX document
36C25621R0013_2.docx DOCX document
010000 General Requirements.docx DOCX document
075423 Thermoplastic Polyolefin Roofing.docx DOCX document
220523 09-15 GENERAL-DUTY VALVES FOR PLUMBING PIPING.docx DOCX document
260511 01-16 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS .docx DOCX document
096723-30 Resinous Decorative Mortar Flooring.docx DOCX document
078400 Firestopping.docx DOCX document
230923 9-11 DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC.doc DOC document
230512 08-17 GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT.docx DOCX document
Show 40 more

Latest 50 of 77 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Renovate Pharmacy for USP 800 Requirements 02-01-15 VAMC New Orleans, LA

SECTION 23 34 00

HVAC FANS

PART 1 GENERAL

1.1 DESCRIPTION

A.Fans for heating, ventilating and air conditioning.
B.Product Definitions: AMCA Publication 99, Standard l66.

1.2 RELATED WORK

A.Section 01 00 00, GENERAL REQUIREMENTS.
B.Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
C.Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
D.Section 23 05 12, GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT.
E.Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT.
F.Section 23 05 93, TESTING, ADJUSTING, AND BALANCING FOR HVAC.
G.Section 23 09 23, DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC.
H.Section 23 73 00, INDOOR CENTRAL-STATION AIR-HANDLING UNITS.
I.Section 23 82 16, AIR COILS.
J.Section 26 29 11, MOTOR CONTROLLERS.

1.3 QUALITY ASSURANCE

A.Refer to paragraph, QUALITY ASSURANCE, in Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
B.Fans and power ventilators shall be listed in the current edition of AMCA 262, and shall bear the AMCA performance seal.
C.Operating Limits for Centrifugal Fans: AMCA 99 (Class I, II, and III).
D.Fans and power ventilators shall comply with the following standards:
l.Testing and Rating: AMCA 2l0.
2.Sound Rating: AMCA 300.
E.Vibration Tolerance for Fans and Power Ventilators: Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT.
F.Performance Criteria:
l.The fan schedule shall show the design air volume and static pressure. Select the fan motor HP by increasing the fan BHP by 10 percent to account for the drive losses and field conditions.
2.Select the fan operating point as follows:
a.Forward Curve and Axial Flow Fans: Right hand side of peak pressure point
b.Air Foil, Backward Inclined, or Tubular: At or near the peak static efficiency
G.Safety Criteria: Provide manufacturer's standard screen on fan inlet and discharge where exposed to operating and maintenance personnel.
H.Corrosion Protection:
1.Except for fans in fume hood exhaust service, all steel shall be millgalvanized, or phosphatized and coated with minimum two coats, corrosion resistant enamel paint. Manufacturers paint and paint system shall meet the minimum specifications of: ASTM D1735 water fog; ASTM B117 salt spray; ASTM D3359 adhesion; and ASTM G152 and G153 for carbon arc light apparatus for exposure of non-metallic material.
2.Fans for general purpose fume hoods, or chemical hoods, and radioisotope hoods shall be constructed of materials compatible with the chemicals being transported in the air through the fan.

1.4 SUBMITTALS

A.Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES.
B.Manufacturers Literature and Data:
l.Fan sections, motors and drives.
2.Centrifugal fans, motors, drives, accessories and coatings.
a.Utility fans and vent sets.
C.Certified Sound power levels for each fan.
D.Motor ratings types, electrical characteristics and accessories.
E.Belt guards.
F.Maintenance and Operating manuals in accordance with Section 01 00 00, GENERAL REQUIREMENTS.
G.Certified fan performance curves for each fan showing cubic feet per minute (CFM) versus static pressure, efficiency, and horsepower for design point of operation.

1.5 APPLICABLE PUBLICATIONS

A.The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B.Air Movement and Control Association International, Inc. (AMCA):
992016Standards Handbook
262-02AMCA Directory of Agricultural Products with Certified Ratings
3002014Reverberant Room Method for Sound Testing of Fans
C.American Society for Testing and Materials (ASTM):
B1172016Standard Practice for Operating Salt Spray (Fog) Apparatus
D17352014Standard Practice for Testing Water Resistance of Coatings Using Water Fog Apparatus
D33592017Standard Test Methods for Measuring Adhesion by Tape Test
G152-2013Standard Practice for Operating Open Flame Carbon Arc Light Apparatus for Exposure of Nonmetallic Materials
G153-2013Standard Practice for Operating Enclosed Carbon Arc Light Apparatus for Exposure of Nonmetallic Materials

1.6 extra materials A. Provide one additional set of belts for all belt-driven fans.

PART 2 PRODUCTS

2.1 FAN SECTION (Cabinet Fan)

A. Refer to specification Section 23 74 13, PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS.

2.2 CENTRIFUGAL FANS

A.Standards and Performance Criteria: Refer to Paragraph, QUALITY ASSURANCE. Record factory vibration test results on the fan or furnish to the Contractor.
B.Fan arrangement, unless noted or approved otherwise:
l.DWDl fans: Arrangement 3.
2.SWSl fans: Arrangement l, 3, 9 or l0.
C.Construction: Wheel diameters and outlet areas shall be in accordance with AMCA standards.
l.Housing: Low carbon steel, arc welded throughout, braced and supported by structural channel or angle iron to prevent vibration or pulsation, flanged outlet, inlet fully streamlined. Provide lifting clips, and casing drain. Provide manufacturer's standard access door. Provide 12.5 mm (1/2 inches) wire mesh screens for fan inlets without duct connections.
2.Wheel: Steel plate with die formed blades welded or riveted in place, factory balanced statically and dynamically.
3.Shaft: Designed to operate at no more than 70 percent of the first critical speed at the top of the speed range of the fans class.
4.Bearings: Heavy duty ball or roller type sized to produce a Bl0 life of not less than 50,000 hours, and an average fatigue life of 200,000 hours. Extend filled lubrication tubes for interior bearings or ducted units to outside of housing.
5.Belts: Oil resistant, non-sparking and non-static.
6.Belt Drives: Factory installed with final alignment belt adjustment made after installation.
7.Motors and Fan Wheel Pulleys: Adjustable pitch for use with motors through 15HP, fixed pitch for use with motors larger than 15HP. Select pulleys so that pitch adjustment is at the middle of the adjustment range at fan design conditions.
8.Motor, adjustable motor base, drive and guard: Furnish from factory with fan. Refer to Section 23 05 11, COMMON WORK RESULTS FOR HVAC for specifications. Provide protective sheet metal enclosure for fans located outdoors.
9.Furnish variable speed fan motor controllers where shown on the drawings. Refer to Section 26 29 11, MOTOR CONTROLLERS. Refer to Section 23 05 11, COMMON WORK RESULTS FOR HVAC for controller/motor combination requirements.
D.Utility Fans, Vent Sets and Small Capacity Fans: Class l design, arc welded housing, spun intake cone. Applicable construction specification, paragraphs 2.2.A and 2.2.C, for centrifugal fans shall apply for wheel diameters 300 mm (l2 inches) and larger. Requirement for AMCA seal is waived for wheel diameters less than 300 mm (l2 inches) and housings may be cast iron.

PART 3 EXECUTION

3.1 INSTALLATION

A.Install fan, motor and drive in accordance with manufacturer's instructions.
B.Align fan and motor sheaves to allow belts to run true and straight.
C.Bolt equipment to curbs with galvanized lag bolts.
D.Install vibration control devices as shown on drawings and specified in Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT.

3.2 PREOPERATION MAINTENANCE

A.Lubricate bearings, pulleys, belts and other moving parts with manufacturer recommended lubricants.
B.Rotate impeller by hand and check for shifting during shipment and check all bolts, collars, and other parts for tightness.
C.Clean fan interiors to remove foreign material and construction dirt and dust.

3.3 STARTUP AND INSTRUCTIONS

A.Verify operation of motor, drive system and fan wheel according to the drawings and specifications.
B.Check vibration and correct as necessary for air balance work.
C.After air balancing is complete and permanent sheaves are in place perform necessary field mechanical balancing to meet vibration tolerance in Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT.

E N D 23 34 00 - 5

File details come from the government source that posted it. Updated .