About this file

This document is an architectural drawing (Sheet AB200) detailing translucent wall panel specifications for a boathouse project, specifically for a Coast Guard facility at Base Seattle. The specifications outline precise technical requirements for the translucent wall panels, including performance standards such as light transmission, weather resistance, and material properties. Key technical details include:

Panel specifications mandate a sheet thickness of 0.06 inches, flexural strength of 13,500 pounds per square inch, and rigorous performance criteria over a 10-year period. The panels must maintain less than 10% light transmission change, minimal yellowing, and meet specific fire safety standards (ASTM E84 flame spread < 25, smoke developed < 450). Structural requirements include using stainless steel self-tapping fasteners with seal washers, and installation must conform to manufacturer instructions and design wind pressure specifications referenced on structural sheet SB001. The drawings show multiple elevations of a boathouse structure, including west, north, south, and east views, indicating a comprehensive architectural plan for the facility.

View the file

Other files

File Type Posted
Amendment 09_Drawing CN101-CN102 Markups_Revised Dredge Placement Areas.pdf PDF
Amendment 09_General Wage Decision WA20250125 14Mar2025.pdf PDF
Amendment 09 5.2.25.pdf PDF
Amendment 09_Debris Survey Technical Memo_PPI 197.pdf PDF
Amendment 10_5.6.25.pdf PDF
70Z05025R43000001_Amendment 08 4.25.25.pdf PDF
70Z05025R43000001_Amendment 07 4.17.25.pdf PDF
70Z05025R43000001_06_ 06 4.14.25.pdf PDF
NMACC Site Visit_27Feb2025 (Final).pdf PDF
FPAS Rated Order Letter to Contractors_Amendment 04.pdf PDF
Amendment 03FPAS-SILC-NMACC III Electrical Equipment 2025_03_11_sign.pdf PDF
Amendment 03Base Seattle Boat Haulout - As Builts.pdf PDF
2025.02_BA_USCG_BaseSeattle.pdf PDF
SF 30 4.2.2025 Amendment 04.pdf PDF
Continuation Sheets_Amendment 4.pdf PDF
Amendment 03 Seattle PH1A Continuation Sheets 03.pdf PDF
Amendment 2 13Mar25.pdf PDF
TOA CERCLA Price Form Amendment 04.pdf PDF
USCG Base Seattle IDP Flow Chart.pdf PDF
Amendment 2 Continuation Pages.pdf PDF
Amendment 03SF 30 3.26.25.pdf PDF
FPAS-Electrical Equipment 2025_03_11_sign Amendment 04.pdf PDF
Amendment 2 Cover Page.pdf PDF
Amendment 05 4.4.25.pdf PDF
Base Seattle CERCLA PSC Homeport PH1A - Pre Proposal Site Visit - Attendees.pdf PDF
Amendment 01 3.5.25.pdf PDF
TOA CERCLA 2.27.25.pdf PDF
FAR Class Deviation 25-02 Waiver of PLA Requirements.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TRANSLUCENT WALL PANEL SPECIFICATIONS

MANUFACTURER'S DATA SHEETS SHALL BE SUBMITTED FOR REVIEW AND

APPROVAL. SUBMITTALS SHALL INCLUDE LAYOUT DRAWINGS AND MUST BE

REVIEWED AND APPROVED BY COR PRIOR TO FABRICATION.

PANEL COLOR AND DIFFUSED LIGHT TRANSMISSION PER ASTM D 1494 SHALL BE

STANDARD AS SELECTED BY COR.

PANEL PROFILE SHALL MATCH PROFILE OF METAL WALL PANELS AND SHALL

MEET ALL SPECIFIED DESIGN REQUIREMENTS. REFER TO STRUCTURAL SHEET

SB001 FOR STRUCTURAL PERFORMANCE INCLUDING DESIGN WIND PRESSURES.

FLEXURAL STRENGTH, WHEN TESTED IN ACCORDANCE WITH ASTM D 790: 13,500

POUNDS PER SQUARE INCH.

SHEET THICKNESS: 0.06 INCH NOMINAL, PLUS OR MINUS 5 PERCENT.

ACCESSORIES SHALL BE PROVIDED AND INSTALLED THAT INCLUDES BUT NOT

LIMITED TO FLASHING, TRIM, CLOSURES, SEALANT, FASTENERS, AND OTHER

ITEMS AS REQUIRED.

PERFORMANCE:

A. LIGHT TRANSMISSION: CHANGE NOT TO EXCEED 10 PERCENT OVER 10

YEARS.

B. WEATHER RESISTANCE, WHEN TESTED FOR 3,000 HOURS IN

ACCORDANCE WITH ASTM G 155:

1. YELLOWING INTENSITY: CHANGE NOT TO EXCEED A DELTA OF 5 IN

10 YEARS.

2. HAZE: CHANGE NOT TO EXCEED 5 PERCENT IN 10 YEARS.

3. LESS THAN 5% LOSS OF TENSILE STRENGTH WHEN TESTED TO

ASTM D638.

4. PROTECTIVE UV LAYER: INTACT AFTER TESTING PERIOD.

5. ASTM E84 FLAME SPREAD < 25 AND SMOKE DEVELOPED < 450

EQUAL CLASS A.

6. ASTM D635 RATE OF BURNING = CLASS CC2 RATING.

STRUCTURAL FASTENERS SHALL BE STAINLESS STEEL, SELF TAPPING WITH SEAL

WASHERS. SIDE LAP AND FLASHING FASTENERS SHALL BE STAINLESS STEEL SB2

GROMMETS. ALL FASTENERS TO BE INSTALLED PER MANUFACTURER'S

INSTRUCTIONS. REFER TO STRUCTURAL SHEET SB001 FOR FASTENING PATTERN.

INSTALLATION OF TRANSLUCENT PANELS SHALL BE INSTALLED IN ACCORDANCE

WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS, DRAWINGS AND

DESIGN WIND PRESSURES STATED ON STRUCTURAL SHEET SB001.

1.

2.

3.

4.

5.

7.

8.

9.

6.

File details come from the government source that posted it. Updated .