The attachment package establishes requirements for Infrastructure Condition Assessment Program (ICAP) implementation following Condition Based Maintenance Management (CBMM) principles. Key deliverables include facility inventory documentation, site maps, asset tagging guidance, and comprehensive condition assessments across multiple building systems and equipment categories. The technical library inventory references installation facility location maps, utility maps, and electrical single-line diagrams dated through July 2025, with floor plans to be provided at contract award. Contractor responsibilities include three required recurring meetings: weekly Work Induction Board and Outstanding Work Order Status Review meetings, and monthly Customer Project Status Review meetings, all conducted via Microsoft Teams. The attachments provide detailed direct condition rating guidance for 50+ meter groups covering HVAC systems (boilers, chillers, air handling units, cooling towers, packaged units, split systems), electrical infrastructure (switchgear, transformers, panelboards, generators, UPS systems), doors, pumps, heat exchangers, and communication/alarm systems. Each meter group specifies individual components with three-tier condition ratings (Green/Amber/Red) based on operational functionality, damage levels, corrosion, and maintenance requirements. The General Direct Condition Rating Guidance defines sustainability needs and rating definitions ranging from Green (+) indicating full functionality with only preventive maintenance required, through Red (-) indicating complete component degradation with minimal salvageable value.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION J
DOCUMENTS, EXHIBITS, AND OTHER ATTACHMENTS
TABLE OF CONTENTS
ATTACHMENT NUMBER ATTACHMENT TITLE
J-1501000-01 Definitions and Acronyms
J-1501000-02 References and Technical Documents
J-1501000-03 Facility Inventory
J-1501000-04 Site Maps
J-1501000-05 Required Meetings
J-1501000-06 Asset Tagging Guidance
J-1501000-07 Assets Requiring Condition Assessment
J-1501000-08 Meter Group Descriptions and Direct Condition Rating Guidance
J-1501000-09 General Direct Condition Rating Guidance
J-1501000-10 Inventory of Technical Library
ATTACHMENT J-1501000-01
DEFINITIONS AND ACRONYMS
Condition Based Maintenance Management
A maintenance philosophy that encompasses a condition management cycle that is sustained throughout the entire life-cycle of a facility and its constituent component sections, or assets.
Facilities Life Cycle A facilities life cycle is divided into four stages, requirements (planning and design), acquisition (construction and acceptance), stewardship (operations, maintenance and repair), and disposal.
Facilities Maintenance Management
The planning, prioritizing, organizing, controlling, reporting, evaluating, and adjusting of facilities maintenance operations to support the CNO/NAVFAC facilities policy and objectives and satisfy customers’ facility needs. Defined by the International Facility Management Association as “the practice of coordinating the physical workplace with the people and work of the organization.”
Infrastructure Condition Assessment Program
A foundational component of Condition Based Maintenance Management (CBMM).
ICAP comprises three of the four CBMM quadrants: Inventory, Assessment, and Analysis.
Life-Cycle Costs A form of economic analysis that considers the total cost of owning, operating, and maintaining a building or system over its useful life.
Real Property Land and improvements to land (i.e., facilities). It includes equipment affixed and built into the facility as an integral part of the facility (such as heating systems), but not movable equipment (e.g., plant equipment, industrial equipment, buoys).
Restoration Restoration of real property to such a condition that it can be used for its intended purpose. Includes repair or replacement work to restore facilities damaged by inadequate sustainment, excessive age, natural disaster, fire, accident or other causes.
Sustainment Maintenance and repair activities necessary to keep a typical inventory of facilities in “normal working condition”. Sustainment includes regularly scheduled maintenance as well as cyclical major repairs or replacement of components that occur periodically over the expected service life of the facilities.
Uniformat Classification
A standard classification of building components established by the National Institute of Standards and Technology.
Acronym Title BFR Basic Facility Requirements CBMM Condition Based Maintenance Management ICAP Infrastructure Condition Assessment Program IMP Integrated Maintenance Program MDI Mission Dependency Index MILCON Military Construction PM Preventive Maintenance POAM Plan of Action and Milestones RSIP Regional Shore Infrastructure Plan
ATTACHMENT J-1501000-02
REFERENCES AND TECHNICAL DOCUMENTS
Reference Title OPNAVINST 11010.20 Navy Facilities Projects
OPNAVINST 11000.16 Command Responsibility for Shore Activity Land and Facilities NAVFACINST 11010.45 Regional Planning Instruction (Site Approval Process) DODD 6055.9 DoD Explosives Safety Management and the DoD Explosives Safety Board UFC 2-000-5N Facility Planning Criteria for Navy/Marine Corps Shore Installations NAVFAC P-78 Real Property Inventory Procedures Manual OPNAVINST 11011.10 Utilization of Navy Real Property SECNAVINST 11011.47 Acquisition, Management, and Disposal of Real Property and Real Property
Interests by the Department of the Navy
ATTACHMENT J-1501000-03
FACILITIES INVENTORY
See separate excel file titled, “J-1501000-03 Facility Property Inventory”.
ATTACHMENT J-1501000-04
SITE MAPS
See separate excel file titled, “J-1501000-04 Site Maps”.
ATTACHMENT J-1501000-05
REQUIRED MEETINGS
Meeting Title Location Average Duration Frequency
Work Induction Board Microsoft TEAMS 1 hour Weekly Outstanding Work Order Status Review
Microsoft TEAMS 1 hour Weekly
Customer Project Status Review
Microsoft TEAMS 1 hour Monthly
ATTACHMENT J-1501000-06
ASSET TAGGING GUIDANCE
See separate excel file titled, “J-1501000-06 Asset Tagging Guidance”.
ATTACHMENT J-1501000-07
ASSETS REQUIRING CONDITION ASSESSMENT
See separate excel file titled, “J-1501000-07 Assets Requiring Condition Assessment”.
ATTACHMENT J-1501000-08
METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE
B2030410 - Overhead Doors Meter & Description Direct Condition Rating Guidance Condition CR-5200 - Record the condition of the Controls
GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational
CR-5250 - Record the condition of the Door
GREEN: Door has minimal damage and corrosion, is square and securely fastened AMBER: Door has noticeable damage and corrosion, may be slightly displaced, but does not affect door operation or safety RED: Door has significant damage and/or corrosion, noticeably displaced, and may be structurally unsound or affect door operation
CR-5415 - Record the condition of the Guides
GREEN: Guides/Stops/Rollers/Pulleys show no signs of wear or damage, and are properly secured and aligned AMBER: Guides/Stops/Rollers/Pulleys show slight wear, and/or may be slightly loose or misaligned RED: Guides/Stops/Rollers/Pulleys have noticeable damage or wear, and are insecurely fastened and/or misaligned
CR-5505 - Record the condition of the Motor
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired
B2030901 - Hangar Doors
CR-5050 - Record the condition of the Brakes
GREEN: Brakes have minimal wear AMBER: Brakes have noticeable wear, may exhibit unusual noise, but are still operational RED: Brakes have significant wear, excessive noise, or may not function properly
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5250 - Record the condition of the Door
GREEN: Door has minimal damage and corrosion, is square and securely fastened AMBER: Door has noticeable damage and corrosion, may be slightly displaced, but does not affect door operation or safety RED: Door has significant damage and/or corrosion, noticeably displaced, and may be structurally unsound or affect door operation
CR-5415 - Record the condition of the Guides
GREEN: Guides/Stops/Rollers/Pulleys show no signs of wear or damage, and are properly secured and aligned AMBER: Guides/Stops/Rollers/Pulleys show slight wear, and/or may be slightly loose or misaligned RED: Guides/Stops/Rollers/Pulleys have noticeable damage or wear, and are insecurely fastened and/or misaligned
CR-5505 - Record the condition of the Motor
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
D3020130 - Boiler, Cast Iron, Hot Water, Gas
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound RED: Burners have significant damage or corrosion, may be loose or displaced, improper flame, and is not operationally sound
GREEN: Controls function properly
CR-5365 - Record the condition of the Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes RED: Firebox has significant damage or corrosion, cracks or holes may be present
CR-5370 - Record the condition of the Flue
GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational RED: Flue has significant damage and corrosion, noticeably loose, misaligned, or missing, and/or operationally impaired
CR-5380 - Record the condition of the Fuel System
GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational AMBER: Fuel System has noticeable damage or corrosion, but free of leaks, fully operational RED: Fuel System has significant damage or corrosion, significant leaking, and/or is operationally impaired
CR-5530 - Record the
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs
CR-5540 - Record the condition of the Pressure Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured
CR-5690 - Record the
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding RED: Wiring is significantly deteriorated or frayed, connection are loose, or risk of unintentional grounding
D3020134 - Boiler, Cast Iron, Steam, Gas
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound
GREEN: Controls function properly
Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes
CR-5520 - Record the
Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
D3020136 - Boiler, Cast Iron, Hot Water, Gas/Oil
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound
GREEN: Controls function properly
Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes
System
GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational AMBER: Fuel System has noticeable damage or corrosion, but free of leaks, fully operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3020138 - Boiler, Cast Iron, Steam, Gas/Oil
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound
GREEN: Controls function properly
CR-5345 - Record the condition of the Feed Water System
GREEN: Feed Water System has no damage or leaks, fully operational AMBER: Feed Water System has noticeable damage or corrosion, may have slight leaks but still operational RED: Feed Water System has significant damage or corrosion, noticeable leaks, and does not function properly
Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes
GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
D3020901 - Boiler, Cast Iron, HW, Oil
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound
GREEN: Controls function properly
Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes
GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational
System
GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational AMBER: Fuel System has noticeable damage or corrosion, but free of leaks, fully operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3020902 - Boiler, Cast Iron, Steam, Oil
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound
GREEN: Controls function properly
Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes
Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
D3030130 - Chiller, Reciprocating, Water Cooled
CR-5140 - Record the condition of the Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired
CR-5155 - Record the
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired
GREEN: Controls function properly
CR-5295 - Record the
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing
CR-5305 - Record the
Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the evaporator/coils, operationally impaired
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
CR-5565 - Record the condition of the Receiver Tank
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
D3030135 - Chiller, Reciprocating, Air Cooled
CR-5140 - Record the condition of the Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
CR-5175 - Record the
Condenser Fan(s) Assembly
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
GREEN: Controls function properly
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Tank
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3030140 - Chiller, Centrifugal, Water Cooled
CR-5110 - Record the condition of the Centrifugal Motor
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
CR-5140 - Record the
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
CR-5210 - Record the
Controls/Sensors
GREEN: Controls function properly
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Tank
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
D3030145 - Chiller, Gas Absorption, Water Cooled
CR-5000 - Record the condition of the Absorber
GREEN: Absorber has minimal damage and corrosion, but no leaks AMBER: Absorber has noticeable damage and corrosion, but minimal leaks and is still operational RED: Absorber has significant damage and corrosion, and noticeable leaks, operationally impaired
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
GREEN: Controls function properly
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
CR-5430 - Record the condition of the Heat Generator
GREEN: Heating Element has little to no damage or corrosion, and is fully operational AMBER: Heating Element has noticeable damage or corrosion, but still operational RED: Heating Element has significant damage or corrosion, Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
CR-5555 - Record the
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
D3030150 - Chiller, Steam Absorption, Water Cooled
CR-5000 - Record the condition of the Absorber
GREEN: Absorber has minimal damage and corrosion, but no leaks AMBER: Absorber has noticeable damage and corrosion, but minimal leaks and is still operational RED: Absorber has significant damage and corrosion, and noticeable leaks, operationally impaired
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
GREEN: Controls function properly
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
CR-5430 - Record the condition of the Heat Generator
GREEN: Heating Element has little to no damage or corrosion, and is fully operational AMBER: Heating Element has noticeable damage or corrosion, but still operational RED: Heating Element has significant damage or corrosion, Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
CR-5555 - Record the
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
D3030310 - Cooling Tower, Galvanized
CR-5025 - Record the condition of the Basin/Sump
GREEN: Sump has minimal damage or corrosion, no leaking AMBER: Sump has noticeable damage or corrosion, but no leaking RED: Sump has significant damage or corrosion, and noticeable leaking, operationally impaired
CR-5280 - Record the
Electrodes
GREEN: Conductivity Electrodes have minimal damage and corrosion, secure connections and fully functional AMBER: Conductivity Electrodes have noticeable damage and corrosion, some loose connections but still functional RED: Conductivity Electrodes have significant damage and corrosion, loose or missing connections, operationally impaired
CR-5325 - Record the condition of the Fan Assembly
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired
CR-5350 - Record the condition of the Fill Material
GREEN: Filter has minimal to no dirt and debris, free of damage AMBER: Filter shows noticeable signs of debris, but little to no damage allowing unobstructed flow RED: Air Filter clogged with dirt and debris, or shows signs of damage such as, punctures, tears, rips
Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
ATTACHMENT J-150100008
D3030320 - Cooling Tower, Fiberglass
CR-5025 - Record the condition of the Basin/Sump
GREEN: Sump has minimal damage or corrosion, no leaking AMBER: Sump has noticeable damage or corrosion, but no leaking
Electrodes
GREEN: Conductivity Electrodes have minimal damage and corrosion, secure connections and fully functional AMBER: Conductivity Electrodes have noticeable damage and corrosion, some loose connections but still functional
Assembly
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Material
GREEN: Filter has minimal to no dirt and debris, free of damage AMBER: Filter shows noticeable signs of debris, but little to no damage allowing unobstructed flow
Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3030330 - Cooling Tower, Stainless Steel
CR-5025 - Record the condition of the Basin/Sump
GREEN: Sump has minimal damage or corrosion, no leaking AMBER: Sump has noticeable damage or corrosion, but no leaking
Electrodes
GREEN: Conductivity Electrodes have minimal damage and corrosion, secure connections and fully functional AMBER: Conductivity Electrodes have noticeable damage and corrosion, some loose connections but still functional
Assembly
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Material
GREEN: Filter has minimal to no dirt and debris, free of damage AMBER: Filter shows noticeable signs of debris, but little to no damage allowing unobstructed flow
Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3030902 - Condenser, DX, Evaporative
CR-5325 - Record the condition of the Fan Assembly
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
CR-5495 - Record the condition of the Louvers
GREEN: Louvers have minimal damage and corrosion, fully secured AMBER: Louvers have noticeable damage and corrosion, may be loose but still operational RED: Louvers have significant damage and corrosion, may be loose, missing, and/or operationally impaired
CR-5515 - Record the condition of the Nozzles
GREEN: Nozzles show no signs of damage, corrosion, or clogging, fully operational AMBER: Nozzles have some damage, corrosion, or clogs, noticeable obstruction of flow, but operational RED: Nozzles have significant damage and corrosion, severely obstructed flow, operationally impaired
CR-5615 - Record the condition of the Sump Pump
GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3030903 - Packaged DX Refrigerant System
CR-5140 - Record the condition of the Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser Fan(s) Assembly
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
CR-5185 - Record the
Condensing Coils
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.
GREEN: Controls function properly
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3040106 - Air Handling Unit, Field Fabricated
CR-5120 - Record the condition of the Coils (Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
CR-5125 - Record the condition of the Coils (Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
CR-5145 - Record the
Condensate Piping
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Controls/Sensors
GREEN: Controls function properly
CR-5235 - Record the condition of the Dampers
GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational RED: Damper has significant damage and corrosion, noticeably loose, CR-5260 - Record the condition of the Drain Pan
GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks RED: Drain Pan has significant damage or corrosion, and noticeable leaks
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
CR-5330 - Record the
Assy
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3040110 - Air Handling Unit, Central Station
CR-5120 - Record the condition of the Coils (Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
GREEN: Controls function properly
GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational
Pan
GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
CR-5340 - Record the condition of the Fan(s) Assembly
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
GREEN: Louvers have minimal damage and corrosion, fully secured AMBER: Louvers have noticeable damage and corrosion, may be loose but still operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3040114 - Air Handling Unit, Rooftop
CR-5120 - Record the condition of the Coils (Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
GREEN: Controls function properly
GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational
Pan
GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
CR-5340 - Record the condition of the Fan(s) Assembly
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
GREEN: Louvers have minimal damage and corrosion, fully secured AMBER: Louvers have noticeable damage and corrosion, may be loose but still operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3040220 - Fan System, Centrifugal In-Line
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Assy
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3040230 - Fan System, Utility Set
CR-5330 - Record the condition of the Fan Assy
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
CR-5630 - Record the condition of the Switches Controls
GREEN: Switches function properly AMBER: None RED: Switches do not function properly
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3040240 - Fan System, Roof Exhaust
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Assy
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3040330 - Circulating Pump, End Suction
CR-5045 - Record the condition of the Booster Pump, w/ Oil Reservoir
GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired
D3040340 - Circulating Pump, Double Suction
CR-5045 - Record the condition of the Booster Pump, w/ Oil Reservoir
GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired
D3040610 - Heat Exchanger, Plate Type
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5375 - Record the
Frame/Supports
GREEN: Supports have minimal damage and corrosion, are fully stable and secure AMBER: Supports have noticeable damage and corrosion, but still structurally stable and secure RED: Supports have significant damage and corrosion, and/or unstable or not secured
CR-5465 - Record the
Insulation
GREEN: Insulation has minimal deterioration, and is mostly in place where necessary AMBER: Insulation has noticeable deterioration, portions may be loose or displaced, but mostly intact RED: Insulation is significantly damaged, or large portions are displaced or missing
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
CR-5570 - Record the condition of the Relief Valve
GREEN: Valve has little to no damage or corrosion, is fully operational AMBER: Valve shows some damage or corrosion, valve functions but may require calibration RED: Valve has significant damage or corrosion, is operationally impaired
CR-5590 - Record the condition of the Steam Modulating Valve
GREEN: Valve has little to no damage or corrosion, is fully operational AMBER: Valve shows some damage or corrosion, valve functions but may require calibration
D3040620 - Heat Exchanger, Shell Tube
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5375 - Record the
Frame/Supports
GREEN: Supports have minimal damage and corrosion, are fully stable and secure AMBER: Supports have noticeable damage and corrosion, but still structurally stable and secure RED: Supports have significant damage and corrosion, and/or unstable or not secured
CR-5465 - Record the
Insulation
GREEN: Insulation has minimal deterioration, and is mostly in place where necessary AMBER: Insulation has noticeable deterioration, portions may be loose or displaced, but mostly intact RED: Insulation is significantly damaged, or large portions are displaced or missing
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
CR-5570 - Record the condition of the Relief Valve
GREEN: Valve has little to no damage or corrosion, is fully operational AMBER: Valve shows some damage or corrosion, valve functions but may require calibration
CR-5590 - Record the condition of the Steam Modulating Valve
GREEN: Valve has little to no damage or corrosion, is fully operational AMBER: Valve shows some damage or corrosion, valve functions but may require calibration
D3050170 - Split Systems With Air Cooled Condensing Units
CR-5120 - Record the condition of the Coils (Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired
Condenser Fan(s) Assembly
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
GREEN: Controls function properly
Pan
GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks RED: Drain Pan has significant damage or corrosion, and noticeable leaks
CR-5460 - Record the condition of the Indoor Fan Motor Assembly
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding RED: Wiring is significantly deteriorated or frayed, connection are loose, or risk of unintentional grounding
D3050185 - Computer Room Cooling Units
CR-5120 - Record the condition of the Coils (Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
CR-5150 - Record the
Condensate Pump
GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired
Controls/Sensors
GREEN: Controls function properly
Pan
GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Assy
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
CR-5450 - Record the
Humidifier
GREEN: Pan has minimal damage or corrosion AMBER: Pan has noticeable damage or corrosion, but no leaks RED: Pan has significant damage or corrosion, and noticeable leaks
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3050201 - Packaged A/C, Air Cooled, Elec Heat
CR-5120 - Record the condition of the Coils (Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
Condenser Fan(s) Assembly
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
GREEN: Controls function properly
Pan
GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks
CR-5275 - Record the condition of the Duct Connectors
GREEN: Ductwork has little to no damage or corrosion, insulation is intact and there are no holes, leaks, or blockages AMBER: Ductwork has noticeable damage or corrosion, but minimal leaks or blockages RED: Ductwork has significant damage or corrosion, holes, punctures, leaks, or blockages. Operation is severely impaired
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
D3050201 - Packaged A/C, Air Cooled, Elec Heat
CR-5330 - Record the condition of the Fan Assy
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are…