S102.pdf
PDF 133 KB Posted
- Attached to
- Building 7 Boiler #2 Replacement
- Solicitation number
- 12-223-SOL-00177
About this file
J-1 Drawings S102
View the file
Other files
| File | Type | Posted |
|---|---|---|
| amendment 3.pdf | ||
| NCTR Air Permit.pdf | ||
| attachment 2- list of attendees.pdf | ||
| amendment 2.pdf | ||
| amendment 1.pdf | ||
| attachment 1- list of attendees.pdf | ||
| M203.pdf | ||
| M404.pdf | ||
| M102.pdf | ||
| M200.pdf | ||
| E106.pdf | ||
| M403.pdf | ||
| M104.pdf | ||
| M305.pdf | ||
| M304.pdf | ||
| M402.pdf | ||
| M501.pdf | ||
| M306.pdf | ||
| M401.pdf | ||
| E103.pdf | ||
| M303.pdf | ||
| M702.pdf | ||
| M302.pdf | ||
| M202.pdf | ||
| E202.pdf | ||
| M103.pdf | ||
| M201.pdf | ||
| M101.pdf | ||
| M601.pdf | ||
| M204.pdf | ||
| E201.pdf | ||
| M703.pdf | ||
| E104.pdf | ||
| 01120018 Add 01 Specs 080312.pdf | ||
| 12-223-SOL-00177.pdf | ||
| M100.pdf | ||
| E301.pdf | ||
| S101.pdf | ||
| M301.pdf | ||
| E101.pdf | ||
| G100.pdf | ||
| E102.pdf | ||
| E105.pdf | ||
| M701.pdf |
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIN FLR
0' - 0"
MEZZANIE
12' - 0"
SECOND FLOOR
24' - 0"
1 1.4 2 2.4 3 3.4 4
EXISTING BEAM TO
BE RELOCATED ABOVE
NEW LOCATION OF EXISTING
BEAM BELOW
EXISTING ANGLE
BRACING TO BE
ADJUSTED WHEN
EXISTING BEAM IS
RELOCATED (TYP)
EXISTING BEAM EXISTING BEAM EXISTING BEAM
E X
IS
T
IN
G
C O
LU
M
N
E X
IS
T
IN
G
C O
LU
M
N
E X
IS
T
IN
G
C O
LU
M
N
E X
IS
T
IN
G
C O
LU
M
N
E X
IS
T
IN
G
C O
LU
M
N
E X
IS
T
IN
G
C O
LU
M
N
'-0
'-7
/2
(F
IE
LD
V
E R
IF
Y
2'
-4
/2
LOCATION OF
EXISTING BEAM
FIN FLR
0' - 0"
MEZZANIE
12' - 0"
SECOND FLOOR
24' - 0"
1 1.4 2 2.4 3 3.4 4
EXISTING
2- L3 1/2x3x5/16
(TYP)
EXISTING
2- L3 1/2x2 1/2x5/16
EXISTING W12x40
EXISTING W12x40
EDGE OF EXISTING
OPNG
(+/-) 10'-8" EXISTING OPNG
9'-0 3/4" 12'-0" NEW LOUVER OPNG (CLR)
(+/-) 1"
EDGE OF EXISTING
LOUVER
EXISTING W12x40
LOCATION
ADD TEMPORARY
BRACING DURING
BOILER 2 INSTALLATION
'-0
EXISTING BEAM EXISTING BEAM EXISTING BEAM
E X
IS
T
IN
G
C O
LU
M
N
E X
IS
T
IN
G
C O
LU
M
N
E X
IS
T
IN
G
C O
LU
M
N
E X
IS
T
IN
G
C O
LU
M
N
1'-4"
S102
'-0
2'
-0
12'-0"
EXISTING HSS12X4X1/4
TO SUPPORT COILING
DOOR
ADD TEMPORARY
BRACING DURING
BOILER 2 INSTALLATION
6' -6
NEW HSS12X4X1/4
OVER NEW LOUVER
ADD W12x26 BEAM FOR
TEMPORARY BRACING
DURING BOILER 2
INSTALLATION
ADD TEMPORARY GUSSET
PLATE TO MATCH EXISTING
GUSSET PLATE (TYP)
"A"
SECTION "A" SECTION "B"
"B" H
1' -7
CONT BENT PL1/2"
11"
3"
FIELD VERIFY
WIDTH OF
EXISTING BLOCK
CL HSS & SILL
HSS12x4
EXISTING
WINDOW SILL
EXISTING
WINDOW
GALV PL3/8x9 x 1'-4"
TO SUPPORT
EXISTING BRICK
13'-0"
2"
CONT BENT PL
EA SIDE OF OPNG
ATTACH BENT PL TO EXISTING
MASONRY w/ HILTI HIT HY 20
1/2" DIA THREADED HIT-I INSERT
ANCHORS (3 3/8" EMBEDMENT)
@ EVERY BLOCK. CENTERED ON
EXISTING BLOCK
GALV HSS12x4x1/4
EXISTING BLOCK
1'-4"
3/16
3/16
ADJUST DEPENDING ON
WIDTH OF EXISTING BLOCK
NTS
12'-0" CLR
13'-0"
2"
TME, INC.
No. 178
CO
RP
OR
ATE REG I STRA T
I ON
ARKA NSA S - E NG I NEER
ISSUE DATE:
SHEET NUMBER:
PROJECT NUMBER:
5800 EVERGREEN DRIVE
LITTLE ROCK,
ARKANSAS
72205-1757
Phone: (501) 666-6776 Fax: (501) 663-8888 tme@tmecorp.com
SHEET TITLE:
ENGINEER SEAL
CORPORATE SEAL
MARK DATE DESCRIPTION
1 08/03/12 ADDENDUM #1
Je ffe rs on
L ab or at or ie s F oo d an d
D ru g A dm in is tr at io n
N
C T
R R d Je ffe rs on , A
R
S102
ELEVATIONS AND
DETAILS
06-26-12
FDA-SOI-06-00268
B ui ld in g
B oi le r #2
R ep la ce m en t
BOILER 2 INSTALLATION NOTES:
1. BEFORE BEGINNING STRUCTURAL WORK, THE CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS AND SHALL NOTIFY THE STRUCTURAL ENGINEER OF RECORD OF ANY CONDITIONS ENCOUNTERED
CONTRADICTORY TO THOSE SHOWN ON THE STRUCTURAL CONTRACT DOCUMENTS.
2. EXISTING W12x40 STEEL BEAM AND ANGLE BRACING IS TO BE TEMPORARILY REMOVED IN ORDER TO ACCOMODATE THE BOILER 2 INSTALLATION. THE W12x40 STEEL BEAM AND ANGLE BRACING WILL BE RE-INSTALLED AT THEIR ORIGINAL
POSITION (DEPICTED ON 01/S102) ONCE BOILER 2 IS INSIDE THE BUILDING.
3. BEFORE W12x40 AND ANGLE BRACING IS TEMPORARILY REMOVED BETWEEN GRIDS 2 & 3 THE CONTRACTOR SHALL ADD IDENTICAL BRACING IN ADJACENT BAY BETWEEN GRIDS 1 & 2 (AS SHOWN ON ELEVATION 01). THIS BRACING IS REQUIRED FOR THE OVERALL LATERAL STABILITY OF THE BUILDING. ONCE BOILER 2 HAS BEEN INSTALLED AND ORIGINAL BRACING BETWEEN GRIDS 2 & 3 IS RE-INSTALLED, ONLY THEN IS IT ALLOWABLE TO REMOVE BRACING
BETWEEN GRIDS 1 & 2.
4. CONTRACTOR TO PROVIDE TEMPORARY BRACING TO COMPENSATE FOR THE REMOVAL OF EXISTING BEAMS DURING CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR THE TEMPORARY BRACING AND/OR SHORING OF THE STRUCTURE DURING CONSTRUCTION. THE STRUCTURE IS NOT STABLE UNTIL ALL ELEMENTS ARE CONNECTED IN PLACE. THE DESIGN ADEQUACY AND SAFETY OF ERECTION BRACING, FORMWORK, SHORING, TEMPORARY SUPPORTS, ETC. AND THE MEANS, METHODS, TECHNIQUES AND SEQUENCE OF CONSTRUCTION ARE SOLE
RESPONIBILITY OF THE CONTRACTOR.
5. THE STRUCTURAL ENGINEER OF RECORD WILL REVIEW THE EXISTING BEAMS AND DECIDE IF IT IS ACCEPTABLE FOR THE EXISTING BEAMS TO BE CONNECTED BACK TO THE EXISTING COLUMNS BEFORE THE LOUVER OPENING IS INSTALLED. IF THE EXISTING W12X40 BEAM & ANGLE BRACING ARE DEEMED UNUSABLE NEW BEAMS WILL HAVE TO BE FABRICATED & ERECTED TO REPLACE THE EXISTING BEAMS. CONTRACTOR SHALL PROVIDE PRICING FOR NEW
STEEL MEMBERS IN THE BASE BID.
6. IF NEW STEEL BEAMS ARE REQUIRED (SEE NOTE 5 ABOVE) WIDE FLANGE SHAPES SHALL BE ASTM A992 GRADE 50.
ALL OTHER MISCELLANEOUS STEEL SHALL BE ASTM A36 UNLESS NOTED OTHERWISE.
7. ALL STRUCTURAL BOLTS CONNECTING STRUCTURAL STEEL SHALL BE ASTM A325 TYPE 1 WITH THREADS ALLOWED IN
THE SHEAR PLANE.
8. CONTRACTOR TO TEMPORARILY BRACE MASONRY WALL ONCE W12x40 IS MOVED FROM ORIGINAL LOCATION.
(BRACE WALL AT ORIGINAL W12x40 LOCATION) MASONRY WALL IS TO BRACED UNTIL W12x40 IS RELOCATED AND LATERAL TIES ARE PROVIDED TO BRACE MASONRY BACK TO W12x40. LATERAL TIES TO CONSIST OF BENT PL1/4x4 x 0'-7" (LLH) THAT IS WELDED TO BOTTOM FLANGE OF EXISTING BEAM AND ATTACHED TO EXISTING MASONRY w/ HILTI HY20 1/2" DIA THREADED HIT-1 INSERT ANCHORS (3 3/8" EMBEDMENT) TO MATCH EXISTING
LATERAL TIE SPACING.
9. CONTRACTOR TO REPLACE RIVET CONNECTIONS AT EXISTING BRACING LOCATIONS WITH SLIP CRITICAL BOLTS.
SIZE OF BOLT TO MATCH EXISTING BOLT HOLE SIZE.
BOILER 2 INSTALLATION
1/4" = 1'-0"
02 FRAMING ELEVATION ALONG GRID G
BOILER 2 INSTALLATION
1/4" = 1'-0"
01 FRAMING ELEVATION ALONG GRID H
FRAMING ALONG GRID G NOTES:
1. BEFORE BEGINNING STRUCTURAL WORK, THE CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS AND SHALL NOTIFY THE STRUCTURAL ENGINEER OF RECORD OF ANY CONDITIONS ENCOUNTERED
CONTRADICTORY TO THOSE SHOWN ON THE STRUCTURAL CONTRACT DOCUMENTS.
2. EXISTING LOW BEAMS AT ELEVATION (+/-)12'-7 1/2" (FIELD VERIFY) ARE TO BE RELOCATED IN ORDER TO ACCOMODATE
NEW OPENING FOR BOILER 2 INSTALLATION.
3. SET BOTTOM OF BEAMS 2'-0" ABOVE NEW OPENING.
4. ADJUST ANGLE BRACING AS REQUIRED TO FIT NEW BRACING ALIGNMENT.
5. CONTRACTOR TO PROVIDE TEMPORARY BRACING TO COMPENSATE FOR THE REMOVAL OF EXISTING BEAMS DURING CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR THE TEMPORARY BRACING AND/OR SHORING OF THE STRUCTURE DURING CONSTRUCTION. THE STRUCTURE IS NOT STABLE UNTIL ALL ELEMENTS ARE CONNECTED IN PLACE. THE DESIGN ADEQUACY AND SAFETY OF ERECTION BRACING, FORMWORK, SHORING, TEMPORARY SUPPORTS, ETC. AND THE MEANS, METHODS, TECHNIQUES AND SEQUENCE OF CONSTRUCTION ARE SOLE
RESPONIBILITY OF THE CONTRACTOR.
6. THE STRUCTURAL ENGINEER OF RECORD WILL REVIEW THE EXISTING BEAMS AND DECIDE IF IT IS ACCEPTABLE FOR THE EXISTING BEAMS TO BE CONNECTED BACK TO THE EXISTING COLUMNS BEFORE THE LOUVER OPENING IS INSTALLED. IF THE EXISTING W12X40 BEAM & ANGLE BRACING ARE DEEMED UNUSABLE NEW BEAMS WILL HAVE TO BE FABRICATED & ERECTED TO REPLACE THE EXISTING BEAMS. CONTRACTOR SHALL PROVIDE PRICING FOR NEW
STEEL MEMBERS IN THE BASE BID.
7. IF NEW STEEL BEAMS ARE REQUIRED (SEE NOTE 6 ABOVE) WIDE FLANGE SHAPES SHALL BE ASTM A992 GRADE 50.
ALL OTHER MISCELLANEOUS STEEL SHALL BE ASTM A36 UNLESS NOTED OTHERWISE.
8. ALL STRUCTURAL BOLTS CONNECTING STRUCTURAL STEEL SHALL BE ASTM A325 TYPE 1 WITH THREADS ALLOWED IN
THE SHEAR PLANE.
1" = 1'-0"
3 DETAIL AT MASONRY WALL SUPPORT
BID SET
File details come from the government source that posted it. Updated .