M101.pdf
PDF 811 KB Posted
- Attached to
- Building 7 Boiler #2 Replacement
- Solicitation number
- 12-223-SOL-00177
About this file
J-1 Drawings M101
View the file
Other files
| File | Type | Posted |
|---|---|---|
| amendment 3.pdf | ||
| NCTR Air Permit.pdf | ||
| attachment 2- list of attendees.pdf | ||
| amendment 2.pdf | ||
| amendment 1.pdf | ||
| attachment 1- list of attendees.pdf | ||
| S102.pdf | ||
| M304.pdf | ||
| M402.pdf | ||
| M501.pdf | ||
| M306.pdf | ||
| M401.pdf | ||
| E103.pdf | ||
| M303.pdf | ||
| M702.pdf | ||
| M302.pdf | ||
| M203.pdf | ||
| M404.pdf | ||
| M102.pdf | ||
| M200.pdf | ||
| E106.pdf | ||
| M403.pdf | ||
| M104.pdf | ||
| M305.pdf | ||
| M202.pdf | ||
| E202.pdf | ||
| M103.pdf | ||
| M201.pdf | ||
| M601.pdf | ||
| M204.pdf | ||
| E201.pdf | ||
| M703.pdf | ||
| E104.pdf | ||
| 01120018 Add 01 Specs 080312.pdf | ||
| 12-223-SOL-00177.pdf | ||
| M100.pdf | ||
| E301.pdf | ||
| S101.pdf | ||
| M301.pdf | ||
| E101.pdf | ||
| G100.pdf | ||
| E102.pdf | ||
| E105.pdf | ||
| M701.pdf |
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXISTING
BOILER
FEED
PUMP
EXISTING
BOILER
FEED
PUMP
EXISTING
BOILER
FEED
PUMP
EXISTING
BOILER
CONTROL
PANEL
EXISTING
AIR
STORAGE
TANK
EXISTING 2" FUEL OIL
PIPING FOS/FOR
6" S 15
6" S 15
6" S 15
10" S 15
3" SR
6" SR
6" BD DOWN TO
BLOWDOWN TANK
CPS-1
BDHX-1
EXISTING
CHEMICAL
TREATMENT
EXISTING
WATER TUBE
BOILER 2
TO BE
REMOVED
EXISTING
WATER TUBE
BOILER 1
3" S15
1" DCW
BS-1
EXISTING
FIRE TUBE
BOILER 1
CST-1
2" F
O S
4" DCW
8" S100
FOS-1
2" SR
2" BD
4" BFW
4 3.4 3 2.4 1.4 1
H
E
D
B
A
REMOVE EXISTING LOUVER AND GLASS FOR
INSTALLATION OF NEW BOILER #2. REMOVE
EXISTING X-BRACING. RELOCATE X-BRACING PER
STRUCTURAL DRAWINGS. AFTER NEW BOILER #2
IS IN AND PLACED. INSTALL NEW LOUVER TO
REPLACE EXISTING LOUVER, GLASS AND PORTION
OF REMOVED WALL.
EXISTING BOILER #2 AND ASSOCIATED
EQUIPMENT TO BE REMOVED UNDER BOILER 2
INSTALLATION.
EXISTING STRUCTURAL SUPPORT COLUMN TO
REMAIN. PROTECT DURING BOILER DEMOLITION.
EXISTING NATURAL GAS PIPES, FUEL OIL SUPPLY
AND RETURN PIPING IN TRENCH SHALL REMAIN TO
SERVE EXISTING WATER TUBE BOILER.
VENT PIPE TO BE CUT AND TEMPORARILY
REMOVED FROM BLOW-OFF TANK AND
REINSTALLED AFTER BOILER #2 HAS BEEN
MOVED INTO BUILDING. CUTLINE BELOW
SURFACE OF PIT COVERS. SEE DETAIL #2 ON THIS
SHEET.
REMOVE AND CAP HIGH PRESSURE NATURAL GAS
LINE IN TRENCH.
REMOVE PORTION OF WALL TO THE COLUMN AS
REQUIRED TO MOVE BOILER #2 INTO THE BLDG.
M101
4" NG
6" BD
3" S15
3" S15
6" BD
1" DCW
3" BD
6" BD
4" VTR
UNIT
HEATER
UNIT
HEATER
UNIT
HEATER
UNIT
HEATER
3/4" FOR
1" FOS
SEE GENERAL
NOTE #1
SEE GENERAL NOTE #1
SEE GENERAL NOTE #19
6" SR
3" BD
2" BD
3" NG
1" BD
8" S100
3" NG
3" BFW
2" V
4" NG
6" NG
FOP-1
EXISTING 6" BD TO BE REMOVED.
ALL EXISTING PIPING TO BE REMOVED.
EXISTING STEAM UNIT HEATER TO BE REMOVED.
REMOVE ALL ASSOCIATED CONTROLS AND
SUPPORTS. REMOVE ALL ASSOCIATED PIPING
AND CAP PIPING AT POINT OF DEMOLITION.
EXISTING BOILER TO REMAIN.
EXISTING 30 PSI NATURAL GAS PIPE TO EXISTING
WATER TUBE BOILER TO BE REMOVED AND
CAPPED INSIDE THE EXISTING TRENCH.
EXISTING FUEL OIL PIPE DOWN TO TRENCH TO
REMAIN.
EXISTING FUEL OIL PUMP SERVING EXISTING
WATER TUBE BOILER TO REMAIN.
EXISTING FUEL OIL PUMP SERVING EXISTING AND
NEW FIRE TUBE BOILER TO REMAIN.
ADDITIVE OPTION 1: REMOVE ABANDONED PIPING
ASSOCIATED WITH EXISTING FEED WATER
SYSTEM.
ADDITIVE OPTION 2: REMOVE EXISTING
FEEDWATER PUMPS AND ALL ASSOCIATED
FEEDWATER PIPING, CONCRETE, ETC., PATCH
FLOOR AND SMOOTH FINISHED SURFACE.
ADDITIVE OPTION 3: REMOVE EXISTING
FEEDWATER PIPING IN TRENCH.
EXISTING WATER SOFTENER TANKS TO REMAIN.
EXISTING AIR COMPRESSOR TO REMAIN.
4"SCW UP
TO DA TANK
ABOVE
3" NG
4" BFW
6" S15
4" BFW
GENERAL NOTES:
1. CONTRACTOR SHALL PROVIDE PRICING
FOR OPTIONS 1 THRU 8 AS LISTED ON
THIS DRAWING.
2. ALL EXISTING EQUIPMENT, PIPING,
VALVES TO REMAIN UNLESS
OTHERWISE NOTED.
DEMOLITION KEYES NOTES:
17EXISTING CONDENSATE
RETURN PUMPS
17EXISTING CHEMICAL
FEED PUMP PADS
FIRST FLOOR
0' - 0"
SECOND FLOOR
24' - 0"
FAN PLATORM
36' - 0"
ROOF
56' - 0"
32.4
FAN PLATFORM
36' - 0"
MEZZANINE
12' - 0"
4" V
6" VTR
6" VTR
BlOW-OFF
TANK
PIT COVERS
4" BD
PIPE SUPPORT
TO BE REMOVED
AND REUSED
2" VTR
6" VTR
1 1
BOILER INSTALLATION SYSTEM SCHEDULE
PROJECT PHASE SCOPE OF WORK - MAJOR EQUIPMENT
1). INSTALL NEW FIRE TUBE BOILER #2 AND 2-STAGE ECONOMIZER.
2). INSTALL THREE NEW EXHAUST FANS.
1). REMOVE EXISTING WATER TUBE BOILER #2, ALL ASSOCIATED PIPING BACK TO MAINS, AND ALL ASSOCIATED EQUIPMENT, INDUCED DRAFT
FAN, AND COMBUSTION AIR FAN.
OPTION 1: REMOVE ABANDONED DEAERATOR TANK AND ALL ASSOCIATED PIPING.
OPTION 2: REMOVE EXISTING FEEDWATER PUMPS AND ALL ASSOCIATED FEEDWATER PIPING ABOVE SLAB.
OPTION 3: REMOVE EXISTING FEEDWATER PIPING IN TRENCH.
OPTION 4: NEW STEAM UNIT HEATERS AND ALL S15 STEAM PIPING FEEDING NEW STEAM UNIT HEATERS.
OPTION 5: REMOTE MONITORING OF THE BOILERS, SURGE TANK, AND DEAERATOR TANK AT BUILDING 50.
OPTION 6: REMOTE MONITORING OF THE BOILER CONTROL SYSTEM AT BOILER MANUFACTURE'S TECHNICAL SERVICE FACILITY.
OPTION 7: RELOCATE EXISTING FLOW METER INSTALLED ON CAMPUS STEAM CONDENSATE STEAM RETURN PIPE.
OPTION 8: PROVIDE PVC JACKET FOR ALL NON-STEAM AND STEAM CONDENSATE PIPING (I.E. FEED WATER, DOMESTIC WATER, ECONOMIZER
PIPING FOR BOTH NEW AND EXISTING BOILER).
BOILER 2
INSTALLATION
DEMOLITION
BOILER 2
INSTALLATION
NEW WORK
ADDITIVE
OPTIONS
ISSUE DATE:
SHEET NUMBER:
PROJECT NUMBER:
5800 EVERGREEN DRIVE
LITTLE ROCK,
ARKANSAS
72205-1757
Phone: (501) 666-6776 Fax: (501) 663-8888 tme@tmecorp.com
SHEET TITLE:
ENGINEER SEAL
CORPORATE SEAL
MARK DATE DESCRIPTION
Je ffe rs on
L ab or at or ie s F oo d an d
D ru g A dm in is tr at io n
N
C T
R R d Je ffe rs on , A
R
M101
BOILER 2 INSTALLATION -
FIRST FLOOR PLAN -
MECHANICAL DEMOLITION
06-26-12
FDA-SOI-06-00268
B ui ld in g
B oi le r
R ep la ce m en t
1/4" = 1’−0"
BOILER 2 INSTALLATION − FIRST FLOOR PLAN − MECHANICAL DEMOLITION
1/4" = 1’−0"
SECTION − EXTERIOR BLOW−OFF TANK
AND VENT DEMOLITION
1 08/03/12 ADDENDUM #1
BID SET
File details come from the government source that posted it. Updated .