This document is a technical design drawing and specification sheet for a sanitary lift station installation at Tinker Air Force Base, Oklahoma City, prepared by Burns & McDonnell for the U.S. Army Corps of Engineers Tulsa District under contract W912BV-16-C-0029.
The lift station design includes a 6-foot diameter fiberglass reinforced plastic (FRP) wet well with a 4.5-foot square valve vault, both constructed to withstand 300 PSF live loads and designed for confined space entry compliance. Key construction requirements specify that the wet well backfill must be compacted to 95% maximum dry density and that all dimensions and fitting sizes must be verified with the equipment manufacturer. The wet well must undergo exfiltration testing, with allowable infiltration not exceeding 1.14 gallons per day per vertical foot, and must conform to ASTM D 3753. The specification requires specific signage on both the wet well and valve vault hatches using reinforced fiberglass with engraved lettering and aluminum pop-rivets, including confined space entry warnings and Class I, Division 1 portable ventilation requirements. Additional components include discharge and vent piping, check valves, ball valves, plug valves, an air relief valve, a yard hydrant connection to a 10-inch site water main, and pipe support systems with stainless steel fasteners and welded support brackets. All electrical conduit routing, control panel specifications, and stilling well requirements are referenced on separate electrical sheets.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LIFT STATION GENERAL NOTES:
1. ALL DIMENSIONS, AND FITTING SIZES, TO BE VERIFIED WITH EQUIPMENT
MANUFACTURER BY CONTRACTOR.
2. WET WELL AND VALVE VAULT TOP SHALL BE DESIGNED BY EQUIPMENT
MANUFACTURER FOR 300 PSF LIVE LOAD.
3. WET WELL BACKFILL SHALL BE COMPACTED TO 95% OF MAXIMUM DRY
DENSITY.
4. SIGNAGE:
A. MOUNT SIGN ON UNDERSIDE OF HATCH FOR WET WELL AND VALVE
VAULT.
B. PROVIDE SIGNAGE OF REINFORCED FIBERGLASS, 1/8" THICKNESS,
SPECIFICALLY DESIGNED FOR EXTERIOR USE.
C. COPY SHALL BE ENGRAVED INTO 3-PLY LAMINATE CONSTRUCTION,
EXPOSING CONTRASTING COLOR CORE.
D. COLORS SHALL BE SELECTED FROM MANUFACTURER'S STANDARDS.
E. SIGN SHALL HAVE 1" HIGH LETTERING USING STANDARD, BOLD,
CONDENSED, UPPERCASE STYLE LETTERS.
F. MOUNTING SYSTEM SHALL BE WITH ALL ALUMINUM POP-RIVETS.
G. MOUNT SIGN THAT SAYS, "WET WELL AND VALVE VAULT REQUIRE
CONFINED SPACE ENTRY PERMIT" ON THE UNI-STRUT RACK FOR THE
LIFT STATION CONTROLS ALONG WITH FOLLOWING INFORMATION.
WARNING: CLASS I, DIV. 1 PORTABLE VENTILATION REQUIRED WHEN
OCCUPIED. VAULT AIR SHALL BE PURGED BEFORE ENTERING. PERSONAL
BREATHING AIR APPARATUS SHALL BE USED WHEN ENTERING VAULT.
5. EXFILTRATION TESTING OF WET WELL SHALL BE PERFORMED BY
CONTRACTOR AND SHALL BE TESTED SEPARATELY FROM THE PIPE.
A. WET WELL SHALL BE TESTED BY PLUGGING ALL OPENINGS IN A
WATERTIGHT MANNER WHICH WILL WITHSTAND THE HYDROSTATIC
PRESSURE WHEN WET WELL IS FILLED WITH WATER.
B. TESTING SHALL COMMENCE 12 HOURS AFTER WET WELL HAS
CONTAINED THE TEST WATER.
C. WET WELL HAVING A DEPTH GREATER THAN 25' SHALL BE TESTED
FOR ONLY 25' HEAD OF WATER. MANHOLES 25' DEEP OR LESS SHALL
BE TESTED FULL OF WATER.
D. EXFILTRATION SHALL NOT EXCEED 1.14 GALLONS PER DAY PER
VERTICAL FOOT OF WET WELL.
E. DEWATER WET WELL UPON COMPLETION OF TESTING.
6. FRP WETWELL AND VALVE VAULT SHALL CONFORM TO ASTM D 3753.
7. FOR CONTROL PANEL, CONDUIT ROUTING, STILLING WELL, AND OTHER
ELECTRICAL REQUIREMENTS REFER TO ELECTRICAL SHEETS.
8. CONTRACTOR SHALL VERIFY WITH MANUFACTURER REINFORCEMENT
WILL NOT INTERFERE WITH ANTI-FLOTATION FLANGE.
9. LOCATE PS-2 AT MIDPOINT OF VERTICAL LINE.
3'-6" x 3'-6" MIN
NOTE 1
NOTE 8
ALUMINUM
1 CF #57
WASHED STONE
SIPHON BREAK
1. HOSE BIB SHALL CCOMMODATE
STANDARD 3/4" GARDEN HOSE.
2. LOCATE BETWEEN IWLS1 AND
SSLS1.
NOTES:
3' -0
" M
IN
BU
R Y
1' -6
" M
IN
IM
U
M
ACCESS
1'-6" SQUARE 8" THICK CONCRETE
SLAB
TOP OF
SLAB
6"
6"
HATCH
8" FROM SSMH-1I
INV. EL. 1261.89
ALUMINUM
ACCESS
HATCH
GROUND ELEV.
LIFT-OUT CHAIN
WITH 1/4" SST
LIFTING BAIL
HWL ALARM ON 1261.89'
PUMP OFF 1258.89'
LOW WATER ALARM 1257.89'
2" GUIDE RAILS,
SCHEDULE 40 SST
BOTTOM EL 1256.39'
#6 @ 12 EW EF
2-#6 W/30 LS
4" DIP DISCHARGE PIPE
TOP MOUNT
4"
VENT PIPE
INSECT
SCREEN
RIM ELEV. 1273.71
GROUND ELEV.
4"
CONDUIT STUB
(ROTATED FOR
CLARITY)
1" INSULATED WATER PIPE SHUT
OFF VALVE AT BOTTOM TO
PREVENT FREEZING.
REDUCER
EL. 1265.67
3'-0"
STD 90° HOOK
(TYP)
#5 DOWELS @ 12 EF
#5 (TYP)
1' -6
6'-0"
3'-0" 3'-0"
15'-0"
4'-6" SQUARE (MIN)
NOTE 1
4" CAM LOK FITTING
WITH DUST CAP
BLIND FLANGE
TAP FOR 3" SPOOL
4" CHECK
VALVE (CV)
4"
DISMANTLING
JOINT (DJ)
AIR RELIEF
VALVE
1"
GATEVALVE
4" BALL
VALVE
4" PLUG
VALVE (PV)
PS-1
4" DIA.
FLGxFLG
SPOOL
4"x4" TEE
4" TEE
PS-1
3" ANTI-FLOATATION
FLANGE (VERIFY SIZE
WITH MANUFACTURER)
#5@12 EW EF
#5 DOWELS @ 12 EF (TYP)
2" C
C (T
YP
3" C
C (T
YP
2" CC
(TYP)
EL = 1265.67
#5 (TYP)
CL EL. 1267.67
4" DI DISCHARGE FLANGE
1' -6
" 2' -6
DIP HDPE
OR
PVC
RIM ELEV. 1273.74
SST FASTENERS
GROUND ELEV.
FLAP
VALVE
2" (T
YP
4' -6
LIFT OUT
ASSEMBLY
2" C
C (T
YP
3" ANTI-FLOATATION
FLANGE (VERIFY SIZE
WITH MANUFACTURER)
6'-0" DIAMETER WET WELL
ALUMINUM ACCESS
HATCH (SEE NOTE 1)
CONDUIT STUBS
(SEE ELECTRICAL DRAWINGS)
8" FROM SSMH-1I
TOP MOUNT
VENT PIPE
BALL VALVE OPERATOR
3" CAM
LOCK FITTING
WITH DUST CAP
4"
4" DRAIN PIPE
CV DJ 4" PV
CV DJ PV 4"
4"
6' -0
SE
E N
O
TE
3'-1 1/2" SEE NOTE 1
1' -3
SE
E N
O
TE
VALVE VAULT
SSVV1
6' -0
2'
-3
VALVE
VAULT
0.
PUMP ON 1260.89'
PS-2 (NOTE 9)
4'-0"
2" CC (TYP)
2" C
C (T
YP
SEE PLANS FOR PIPE
SIZE, AND LOCATION
RISER PIPE CLAMP
1 X 1X 14 WELDED
LUG (TYP OF 4)
L3 X 3 X 14, WELDED
BETWEEN SUPPORT BRACKETS
STAINLESS STEEL,
WELDED PIPE SUPPORT
BRACKET (LOCATE AS
REQD TO PROVIDE
PROPER SUPPORT MIN.
SIZE L3 X 3 X 1/4)
4"Ø SST BOLT
MOUNTING PLATFORM 1
BY FRP WET WELL
MANUFACTURER
VA
R
IE
S
SEE THIS DRAWING FOR
PIPE SIZE, CL ELEVATION
AND PIPE SUPPORT LOCATION.
PIPE OD, SEE PLANS
ADJUST PIPE SADDLE
SUPPORT (SEE NOTES)
THE REDUCER BUSHING
AND NIPPLE (SIZE AS
REQUIRED)
SCH 40 STEEL PIPE, SIZE
DETERMINED BY PIPE SADDLE
NOTE:
1. WHERE PIPE SUPPORT IS INDICATED TO BE LOCATED
UNDER VALVE, PROVIDE ADJUSTABLE PLATE SUPPORT
IN LIEU OF SADDLE SUPPORT.
10"
INSTRUMENT ACCESS
HATCH (SEE NOTE 1)
A
CU-512
2"
CC (TYP)
4"
DRAIN PIPE
4"
1/4" TAP WITH
ISOLATION BALL VALVE
AIR RELIEF
12" TAPERED
CONCRETE FILLET
12" (TYP)
FRP WALL
3" C
C
1 1/2" TYP
1 1/2" TYP
2' -3
2'-3"2'-3"
8'-0"
3'-0"
3' -0
(T
YP
7'-0" 4'-0" 2'-3"2'-3"
3/4"Ø SST BOLT
MOUNTING PLATFORM
1 BY FRP WET WELL
MANUFACTURER
7'-0"
WET WELL - SSLS 1
WET WELL
LIFT STATION SSLS 1
PIPE SUPPORT PS-2
YARD HYDRANT
PIPE SUPPORT PS-1
VALVE VAULT
SSVV1
VALVE VAULT BASE PLAN
SCALE: NTS
SANITARY SEWER LIFT STATIONA1
#6 DOWELS @ 12 EF (TYP)
PLAN VIEW
SEE VALVE VAULT
BASE PLAN
SLAB BARS NOT SHOWN FOR CLARITY
CONNECT TO
10" SITE
WATER MAIN
LOCATION POINT ON PLANS AND
CU600 TABLE
LOCATION POINT ON
PLANS AND CU600 TABLE
M
IN
IM
U
M
A
BO
VE
G R
AD
E
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
TU
LS
A D
IS
TR
IC
T
TU
LS
A, O
KL
AH
O M
A
BU
R
N S
M
C D
O N
N
EL
L
W
AR
D
P
AR
KW
AY
KA
N
SA
S
C
IT
Y, M
O
US Army Corps of Engineers Tulsa District
M
AR
K D
ES
C
R
IP
TI
O
N
SHEET
IDENTIFICATION
D
AT
E
AP
PR
SO
LI
C
IT
AT
IO
N N
O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SB
M
T
BY
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
C O
N
TR
AC
T
N O
5 6
D
C
A
B
1 2 3 4
E
"X
C O
PY
R
IG
H
T
B
U R
N S
M cD O
N N
EL
L
EN
G
IN
EE
R
IN
G C
O M
PA
N
Y, IN
C
KC
-4
6A D
EP
O
T M
AI
N
T C
O M
PL
EX
S U
PP
O
R T
IN
FR
A.
O
KL
AH
O
M A
C
IT
Y, O
KL
AH
O M
A
TI
N
KE
R A
IR
F
O R
C E
BA
SE
W W
YK
CU
0-
CU
6.D
W G
PD
C
:W W
YK
FY
:1
SHEET
IF SHEET IS LESS THAN 42 X 30
REDUCED PRINT - USE GRAPHIC SCALE
D
C
A
B
E
5 61 2 3 4
AS-BUILT (CWG)
M
AY
W
2B V-
-C
-0
CU512
SA
N
IT
AR
Y
LI
FT
S
TA
TI
O N
D
ET
AI
LS
K.
W
AR
TA
D . M
U
ET
IN
G
R . B
AR
U
TH
K.
W
AR
TA
1:
7/ 1/
| Sheets and Views |
| CU512 |
File details come from the government source that posted it. Updated .