Copy_of_Asbestos_DataRequest_20160315.pdf
PDF 441 KB Posted
- Solicitation number
- W912DS-17-R-0001
About this file
W912DS-17-R-0001-0005 ABESTOS DATA REQUEST
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Building
No.
RPUID Build Date Asbestos Survey Asbestos Survey Date Asbestos Sampling Location ID
Building
Floor Asbestos Sampling Location Description
Asbestos
Surveyed?
Asbestos
Present?
Asbestos Material Type
Asbestor Material
Condition Asbestos Material Form
Asbestos
Mineral
Asbestos
Percentage (%) Asbestos Product Asbestos Material Location Type
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-001 1 Electrical penetration sealer sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Mechanical Room
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-002 1 Electrical penetration sealer sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Mechanical Room
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-003 1 Vibration isolator sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Mechanical Room
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-004 1 Vibration isolator sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Mechanical Room
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-005 1 Pipe end cap thermal insulation, paper/foil wrap, and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Mechanical Room
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-006 1 Pipe end cap thermal insulation, paper/foil wrap, and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Mechanical Room
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-007 1 Southwest office drywall and joint compound sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Office
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-008 1 Drywall and joint compound. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Mechanical Room
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-009 1 Northwest cove base and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Storage Room
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-010 1 Southwest office cove base and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Office
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-011 1 Southwest 12x12 Floor material - genericoor tile and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Office
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-012 1 Southwest office 12x12 Floor material - genericoor tile and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Office
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-013 1 Attic access insulation and paper/tar wrap sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Attic
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-014 1 Attic access thermal insulation and paper/tar wrap sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Attic
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-015 1 Northwest storage wall panel mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Storage Room
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-016 1 Northwest storage wall panelling mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Storage Room
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-017 1 West side window glazing sampled. 675 linear feet. Yes Yes Window frame/other No Damage (Mild) Nonfriable Chrysotile 2 Sprayed on Window
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-018 1 South side window glazing sampled. 675 linear feet. Positive Stop, assumed same results as sample 513-017. Yes Yes Window frame/other No Damage (Mild) Nonfriable Chrysotile 2 Sprayed on Window
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-019 1 North side entryway wainscoating mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Other
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-020 1 Latrine wainscoating mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Lavatory
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-101 2 East Shed roof rubber membrane, paper/foil wrap, and foam insulation sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Roof
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-102 2 East shed roof rubber membrane, paper/foil wrap, and foam insulation sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Roof
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-103 2 Under SSR fabric, membrane, and tar sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Roof
513 311225 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 513-104 2 Under SSR fabric, membrane, and tar sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Roof
513 311225 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 513-97-001 1 Room G wallboards 20 cellulose 2 glass fiber 75 nfb/filler 3 paint Yes No Wallboard Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
513 311225 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 513-98-001 1 Room C ceiling boards 15 cellulose 2 glass fiber 80 nfb/filler 3 paint Yes No Ceiling - Board Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
513 311225 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 513-99-001 1 Room E joint compound 20 cellulose 2 glass fiber 8 plaster 70 nfb/filler Yes No Wall/other Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
513 311225 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 513-38-001 1 Room C Floor material - genericoor tiles 1 cellulose 55 aggregate 43 pvc 1 bitumen Yes No Floor material - generic Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
513 311225 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 513-95-001 2 Roof sheathing 30 cellulose 30 aggregate 40 botumen Yes No Roofing material Not Applicable Not Applicable Not Applicable 0 Sheet Roof
514 304727 07/01/1977 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 514-TBD No Potential
514 311226 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 514-97-001 1 Room K wallboards 20 cellulose 1 glass fiber 76 nfb/filler 3 paint Yes No Wallboard Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
514 311226 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 514-98-001 1 Room I ceiling boards 20 cellulose 2 glass fiber 75 nfb/filler 3 paint Yes No Ceiling - Board Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
514 311226 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 514-99-001 1 Room J joint compound 20 cellulose 1 glass fiber 30 plaster 49 nfb/filler Yes No Wall/other Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
514 311226 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 514-38-001 1 Room B Floor material - genericoor tiles 1 cellulose 50 aggregate 1 bitumen 48 pvc Yes No Floor material - generic Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
514 311226 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 514-105-001 1 Room I acoustical ceiling tiles 25 cellulose 50 mineral wool 5 nfb/filler 1 paint 20 perlite Yes No Ceiling - Textual Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-001 1 Southwest corner window glazing sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Window
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-002 1 East corner window glazing sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Window
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-003 1 Room 2 drywall and joint compound sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-004 1 Room 1 drywall and joint compound sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-005 1 Room 2 isolator material sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-006 1 Room 2 isolator material sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-007 1 Room 2 HVAC putty sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-008 1 Room 2 HVAC Putty sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-009 1 Room 2 thermal insulation, paper/foil wrap, and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-010 1 Room 2 thermal insulation, paper/foil wrap, and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-011 1 Room 4 Floor material - genericoor tile (3%Ch) and mastic sampled. 3400 square feet. Yes Yes Floor material - generic No Damage (Mild) Nonfriable Chrysotile 3 Sheet General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-012 1 Room 10 Floor material - genericoor tile (3%Ch) and mastic sampled. 3400 square feet. Yes Yes Floor material - generic No Damage (Mild) Nonfriable Chrysotile 3 Sheet General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-013 1 Room 3 Floor material - genericoor tile and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-014 1 Room 3 Floor material - genericoor tile and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-015 1 Room 1 sink undercoating sampled Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-016 1 Room 1 sink undercoating sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-017 1 Room 5 2x4 ceiling tile sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-018 1 Room 7 2x4 ceiling tile sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-019 1 Room 7 carpet and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-020 1 Room 7 Carpet and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-101 2 Under SSR fabric, vinyl wrap, and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Roof
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-102 2 Under SSR fabric sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Roof
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-103 2 Under SSR fabric, yinyl, and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Roof
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-104 2 East entrance Roofing shingles. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Roof
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-105 2 East entrance roofing shingles sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Roof
515 311227 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 515-Floor material - genericUE 1 South wall Floor material - genericue insulation with metal jacket sampled. ASSUMED POSITIVE. 30 linear feet. No Potential Duct - Aircell insulation No Damage (Mild) Friable Not Applicable 0 Sheet Outside
515 311227 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 515-97-001 1 Room C wallboards 18 cellulose 1 glass fiber 79 nfb/filler 2 paint Yes No Wallboard Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
515 311227 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 515-99-001 1 Room H joint compound 25 cellulose 1 glass fiber 40 plaster 30 nfb/filler 5 paint Yes No Wall/other Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
515 311227 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 515-95-001 2 Roof sheathing 7 glass fiber 25 aggergate 68 bitumen Yes No Roofing material Not Applicable Not Applicable Not Applicable 0 Sheet Roof
515 311227 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 515-38-001 1 Room C Floor material - genericoor tiles 5 chrysotile 50 aggregate 45 pvc 1 bitumen Yes Yes Floor material - generic No Damage (Mild) Nonfriable Chrysotile 5 Sheet General - Room
515 311227 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 515-15-001 1 Room I joint insulation 60 chrysotile 20 synthetic fiber 20 nfb/filler Yes Yes Pipe insulation - cooling water No Damage (Mild) Nonfriable Chrysotile 60 Sheet General - Room
515 311227 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 515-07-001 1 Room I transite panels 20 chrysotile 80 nfb/filler Yes Yes Wall - transite No Damage (Mild) Nonfriable Chrysotile 20 Sheet General - Room
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-001 1 North side window glazing sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Outside
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-002 1 South side window glazing sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Outside
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-003 1 East end wall drywall sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Other
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-004 1 West end ceiling sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Other
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-005 1 East end wall fiberboard sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Other
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-006 1 Northwest corner fiber board sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Other
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-007 1 East end Door core insulation - fire doors Northside interior Door core insulation - fire door frame caulking. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Other
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-008 1 East end Door core insulation - fire doors Southside interior Door core insulation - fire door frame caulking sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Other
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-009 1 East wall west end drywall and texture sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Other
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-010 1 North wall east end drywall and texture sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Other
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-011 1 West end fiber board sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable CraWall - unspecified type_space
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-012 1 West end fiber board sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable CraWall - unspecified type_space
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-013 1 West end east section Floor material - genericoor tile (5%Ch) and mastic (5%Ch) sampled. 1400 square feet. Yes Yes Floor material - generic Damaged (Moderate) Nonfriable Chrysotile 10 Sheet Other
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-014 2 West end of east section Floor material - genericoor tile (5%Ch) and mastic (5%Ch) sampled. 1400 square feet. Yes Yes Floor material - generic Damaged (Moderate) Nonfriable Chrysotile 10 Sheet Other
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-101 2 Under SSR vinyl wrap. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Roof
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-102 2 Under SSR vinyl wrap. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Roof
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-TRANS 1 West end Transite Panels. ASSUMED POSITIVE. No Potential Wall - unspecified type Damaged (Moderate) Nonfriable Not Applicable 0 Sheet Other
540 311240 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 540-ROOF 2 West end asphalt shingles and transite debris pile. ASSUMED POSITIVE. 50 square feet. No Potential Roofing material Damaged (Moderate) Nonfriable Not Applicable 0 Other Roof
540 311240 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 540-97-001 1 Mess Hall wall boards 25 cellulose 73 nfb/filler 2 paint Yes No Wallboard Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
540 311240 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 540-98-001 1 Mess Hall ceiling boards 25 cellulose 73 nfb/filler 2 paint Yes No Ceiling - Board Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
540 311240 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 540-95-001 2 Roof Sheathing 30 cellulose 25 aggregate 45 bitumen Yes No Roofing material Not Applicable Not Applicable Not Applicable 0 Sheet Roof
540 311240 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 540-38-001 1 Mess Hall Floor material - genericoor tiles 3 chrysotile 20 aggregate 26 nfb/filler 50 pvc 1 bitumen Yes Yes Floor material - generic No Damage (Mild) Nonfriable Chrysotile 3 Sheet General - Room
540 311240 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 540-107-001 1 Mess Hall asbestos board 45 chrysotile 35 cellulose 20 nfb/filler Yes Yes Attic Insulator No Damage (Mild) Nonfriable Chrysotile 45 Sheet Cafeteria
540 311240 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 540-07-001 1 Kitchen transite panel 35 chrysotile 65 nfb/filler Yes Yes Wall - transite No Damage (Mild) Nonfriable Chrysotile 45 Sheet Cafeteria
541 304727 07/01/1977 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 541-TBD No Potential
541 311241 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 541-99-001 1 Room I joint compound 1 cellulose 97 nfb/filler 3 paint Yes No Wall/other Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
541 311241 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 541-38-001 1 Room I Floor material - genericoor tiles 10 chrysotile 18 aggregate 20 nfb/filler 50 pvc 2 bitumen Yes Yes Floor material - generic No Damage (Mild) Nonfriable Chrysotile 10 Sheet General - Room
542 304727 07/01/1977 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 542-TBD No Potential
542 311242 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 542-98-001 1 Room A ceiling baords 30 cellulose 3 glass fiber 66 nfb/filler 1 paint Yes No Ceiling - Board Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
542 311242 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 542-97-001 1 Room A wall baords 30 cellulose 3 glass fiber 65 nfb/filler 2 paint Yes No Wallboard Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-001 1 Room 5 wall mastic sampled Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-002 1 Room 5 wall mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-003 1 Room 7 ceiling drywall and texture sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-004 1 Room 3 drywall and texture sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-005 1 Room 2 cove base and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-006 1 Room 1 cove base and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-007 1 Tread and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Stairwell
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-008 1 stair tread and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Stairwell
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-009 1 Room 2 12x12 Floor material - genericoor tile and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-010 1 Room 1 12x12 Floor material - genericoor tile and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-011 1 Room 3 HVAC debris sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-012 1 Room 3 HVAC debris sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-013 1 Room 3 vibration isolator sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-014 1 Room 3 vibration isolators sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-015 1 Room 3 thermal insulation, paper/foil wrap, and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-016 1 Room 3 thermal insulation, paper/foil wrap, and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-017 1 West end window cover caulking. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Window
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-018 1 West end window cover caulking sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Window
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-019 1 Room 8 12x12 Floor material - genericoor tile and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-020 1 Room 7 12x12 Floor material - genericoor tile and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-021 1 Room 7 cove base and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-022 1 Room 8 cove base and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-023 1 Room 8 12x12 ceiling tile sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-024 1 Room 7 12x12 ceiling tile Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-025 1 Room 5 2x2 ceiling tile sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-026 1 Room 5 2x2 ceiling tile sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-027 1 Room 8 wall paneling mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-028 1 Wall paneling mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-101 2 Roofing shingles and tar parper sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Roof
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-102 2 Roofing shingles and tar paper sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Roof
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-103 2 Chimney sealer sampled. 1 square feet Yes Yes Roofing material No Damage (Mild) Nonfriable Chrysotile 10 Molded Roof Copy of Asbestos_DataRequest_20160315.xlsx
RPUID Build Date Asbestos Survey Asbestos Survey Date Asbestos Sampling Location ID
Building
Floor Asbestos Sampling Location Description
Asbestos
Surveyed?
Asbestos
Present?
Asbestos Material Type
Asbestor Material
Condition Asbestos Material Form
Asbestos
Mineral
Asbestos
Percentage (%) Asbestos Product Asbestos Material Location Type
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-104 2 Chimney sealer sampled. 1 square foot. Yes Yes Roofing material No Damage (Mild) Nonfriable Chrysotile 10 Molded Roof
543 311243 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 543-Floor material - genericUE 2 Chimney Floor material - genericue insulation with metal jacket. ASSUMED POSITIVE. 30 linear feet. No Potential Roofing material No Damage (Mild) Friable Not Applicable 0 Sheet Roof
543 311243 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 543-97-001 1 Room c wall baordS 25 cellulose 73 nfb/filler 2 paint Yes No Wallboard Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
543 311243 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 543-49-001 1 Steps between Floor material - genericoors linoleum 19 nfb/filler 1 glue 80 pvc Yes No Floor material - generic Not Applicable Not Applicable Not Applicable 0 Sheet Stairwell
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-001 1 East side window glazing (x20) sampled. Yes Yes Window frame/wood No Damage (Mild) Nonfriable Chrysotile 5 Sprayed on Window
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-002 1 North side window glazing sampled (x20). Positive Stop, assumed same results as sample 544-001. Yes Yes Window jamb/other No Damage (Mild) Nonfriable Chrysotile 5 Sprayed on Window
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-003 1 Room 5 HVAC Duct insulation, paper/foil, and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-004 1 Room 5 HVAC duct insulation, paper/foil, and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-005 1 Room 5 isolator material sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-006 1 Room 5 isolator material sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-007 1 Room 5 Drywall, joint compound, and texture sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-008 1 Room 6 drywall and joint compound/texture sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-009 1 Room 5 putty sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-010 1 Room 5 putty sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-011 1 Room 1 cove base and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-012 1 Room 3 cove base and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-013 1 Room 4 non-skid strip and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-014 1 Room 4 non-skid strips and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable General - Room
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-015 1 Room 6 Floor material - genericoor tile(5%Ch) and mastic(5%Ch) sampled. 1300 square feet. Yes Yes Floor material - generic No Damage (Mild) Nonfriable Chrysotile 10 Sheet General - Room
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-016 1 Room 6 Floor material - genericoor tile (5%Ch) and mastic (5%Ch) sampled. 1300 square feet. Yes Yes Floor material - generic No Damage (Mild) Nonfriable Chrysotile 10 Sheet General - Room
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-101 1 Roofing shingles and vapor barrier sampled. Yes No Not Applicable No Damage (Mild) Not Applicable Not Applicable 0 Not Applicable Roof
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-102 2 Roofing shingles and vapor barrier sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Roof
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-103 2 Chimney/vent sealer sampled. 3 linear feet. Yes Yes Roofing material No Damage (Mild) Nonfriable Chrysotile 10 Molded Roof
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-104 2 Chimney/vent sealer sampled. Positive stop, assumed same results as sample 544-103. 3 linear feet. Yes Yes Roofing material No Damage (Mild) Nonfriable Chrysotile 10 Molded Roof
544 311244 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 544-Floor material - genericUE 2 Chimney Floor material - genericue insulation with metal jacket . ASSUMED POSITIVE. 15 linear feet. No Potential Roofing material No Damage (Mild) Friable Not Applicable 0 Sheet Roof
544 311244 07/01/1942 1997 ACM Survey (HUB) 19970501 544-01 1 Floor material - genericoor tile. Cellulose 1. Yes No Floor material - generic No Damage (Mild) Nonfriable Chrysotile 0 Sheet General - Room
544 311244 07/01/1942 1997 ACM Survey (HUB) 19970501 544-02 1 Floor material - genericoor tile. Cellulose 1. Yes No Floor material - generic No Damage (Mild) Nonfriable Chrysotile 0 Sheet General - Room
544 311244 07/01/1942 1997 ACM Survey (HUB) 19970501 544-03 1 Floor material - genericoor tile. Chrysolite 1 Cellulose 1. Yes Yes Floor material - generic No Damage (Mild) Nonfriable Chrysotile 1 Sheet General - Room
544 311244 07/01/1942 1997 ACM Survey (HUB) 19970501 544-04 1 Sheetrock. Cellulose 1 and Glass fiber 5 Yes No Wall - sheetrock No Damage (Mild) Nonfriable Chrysotile 0 Sheet General - Room
544 311244 07/01/1942 1997 ACM Survey (HUB) 19970501 544-05 1 Sheetrock. Cellulose 1 and Glass fiber 5 Yes No Wall - sheetrock No Damage (Mild) Nonfriable Chrysotile 0 Sheet General - Room
544 311244 07/01/1942 1997 ACM Survey (HUB) 19970501 544-06 1 Sheetrock. Cellulose 1 and Glass fiber 5 Yes No Wall - sheetrock No Damage (Mild) Nonfriable Chrysotile 0 Sheet General - Room
544 311244 07/01/1942 1997 ACM Survey (HUB) 19970501 544-07 1 Floor material - genericoor mastic. Cellulose 3 and Chrysolite 3 Yes Yes Floor material - generic No Damage (Mild) Nonfriable Chrysotile 3 Sheet General - Room
544 311244 07/01/1942 1997 ACM Survey (HUB) 19970501 544-08 1 Floor material - genericoor mastic No No Floor material - generic Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
544 311244 07/01/1942 1997 ACM Survey (HUB) 19970501 544-R01 2 Roofing Shingles. Cellulose 10-20 Mineral Chip 30-35 Organic Binder ** Opaques 15-20 Yes No Roofing materialSH No Damage (Mild) Nonfriable Chrysotile 0 Sheet Roof
544 311244 07/01/1942 1997 ACM Survey (HUB) 19970501 544-R02 2 Roofing Shingles. Cellulose 10-20 Mineral Chip 30-35 Organic Binder ** Opaques 15-20 Yes No Roofing materialSH No Damage (Mild) Nonfriable Chrysotile 0 Sheet Roof
544 311244 07/01/1942 1997 ACM Survey (HUB) 19970501 544-R03 2 Roofing Shingles. Cellulose 10-20 Mineral Chip 30-35 Organic Binder ** Opaques 15-20 Yes No Roofing materialSH No Damage (Mild) Nonfriable Chrysotile 0 Sheet Roof
544 311244 07/01/1942 1997 ACM Survey (HUB) 19970501 544-R04 2 Roofing Floor material - genericashing. Chrysolite 25-30 Mineral Chip 20-25 Organic Binder ** Opaques 20-25 Yes Yes Roofing materialFloor material - genericS No Damage (Mild) Nonfriable Chrysotile 30 Sheet Roof
544 311244 07/01/1942 1997 ACM Survey (HUB) 19970501 544-R05 2 Roofing Floor material - genericashing Yes No Roofing materialFloor material - genericS Not Applicable Not Applicable Not Applicable 0 Sheet Roof
544 311244 07/01/1942 1997 ACM Survey (HUB) 19970501 544-R06 2 Roofing Floor material - genericashing Yes No Roofing materialFloor material - genericS Not Applicable Not Applicable Not Applicable 0 Sheet Roof
545 311245 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 545-001 1 West end interior partition drywall and joint compound sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Other
545 311245 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 545-002 1 East end exterior drywall and joint compound sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Other
545 311245 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 545-003 1 East end 12x12 Floor material - genericoor tile (3%Ch) and mastic (5%Ch). 1296 square feet. Yes Yes Floor material - generic Damaged (Moderate) Nonfriable Chrysotile 8 Sheet Other
545 311245 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 545-004 1 Center 12x12 Floor material - genericoor tile (3%Ch) and mastic (5%Ch) sampled. 1296 square feet. Positive stop, assumed same results as 545-003. Yes Yes Floor material - generic Damaged (Moderate) Nonfriable Chrysotile 8 Sheet Other
545 311245 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 545-005 1 Stainless steel sink west end undercoating sampled. 8 square feet. Yes Yes Other No Damage (Mild) Nonfriable Chrysotile 3 Sprayed on Other
545 311245 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 545-006 1 Stainless steel sink west end undercoating sampled. Positive stop, assumed same results as sampled 545-005. 8 square feet. Yes Yes Other No Damage (Mild) Nonfriable Chrysotile 3 Sprayed on Other
545 311245 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 545-007 1 Exterior east end window glazing sampled. 1280 linear feet. Yes No Not Applicable Damaged (Moderate) Not Applicable Not Applicable 0 Not Applicable Window
545 311245 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 545-008 1 Exterior southwest corner window glazing sampled. 1280 linear feet. Yes Yes Window jamb/other Damaged (Moderate) Nonfriable Chrysotile 2 Sprayed on Window
545 311245 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 545-009 1 South wall tile and mortar sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Other
545 311245 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 545-010 1 South wall tile and mortar sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Other
545 311245 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 545-101 2 Roofing shingles and tar papers sampled Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Roof
545 311245 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 545-102 1 Roofing shingles and tar papers sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Roof
545 311245 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 545-103 2 Vent sealer sampled. 50 linear feet. Yes Yes Roofing material No Damage (Mild) Nonfriable Chrysotile 10 Molded Roof
545 311245 07/01/1942 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 545-104 1 Vent sealer sampled. Positive stop, assumed same results as sample 545-103. 50 linear feet. Yes Yes Roofing material No Damage (Mild) Nonfriable Chrysotile 10 Molded Roof
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-R01 2 Roofing shingles. Cellulose 5 Mineral Chip 10 Organic Binder ** Yes No Roofing materialSH No Damage (Mild) Nonfriable Chrysotile 0 Sheet Roof
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-R02 2 Roofing shingles. Cellulose 5 Mineral Chip 10 Organic Binder ** Yes No Roofing materialSH No Damage (Mild) Nonfriable Chrysotile 0 Sheet Roof
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-R03 2 Roofing shingles. Cellulose 5 Mineral Chip 10 Organic Binder ** Yes No Roofing materialSH No Damage (Mild) Nonfriable Chrysotile 0 Sheet Roof
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-R04 2 Roofing Floor material - genericashing. Chrysolite 2 Cellulose 5 Mineral Chip 10 Organic Binder ** Yes Yes Roofing materialFloor material - genericS No Damage (Mild) Nonfriable Chrysotile 2 Sheet Roof
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-R05 2 Roofing Floor material - genericashing No No Roofing materialFloor material - genericS Not Applicable Not Applicable Not Applicable 0 Sheet Roof
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-R06 2 Roofing Floor material - genericashing No No Roofing materialFloor material - genericS Not Applicable Not Applicable Not Applicable 0 Sheet Roof
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-01 1 Roofing shingles. Cellulose trace Mineral Chip 70-80 Organic Binder ** Yes No Floor material - generic No Damage (Mild) Nonfriable Chrysotile 0 Sheet General - Room
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-02 1 Roofing shingles. Cellulose trace Mineral Chip 70-80 Organic Binder ** Yes No Floor material - generic No Damage (Mild) Nonfriable Chrysotile 0 Sheet General - Room
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-03 1 Roofing shingles. Cellulose trace Mineral Chip 70-80 Organic Binder ** Yes No Floor material - generic No Damage (Mild) Nonfriable Chrysotile 0 Sheet General - Room
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-04 1 First Hatch. Cellulose 10-15 Gypsum 85-90 Yes No Wall - sheetrock No Damage (Mild) Nonfriable Chrysotile 0 Sheet Other
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-05 1 Area Sheetrock. Cellulose 10-15 Gypsum 85-90 Yes No Wall - sheetrock No Damage (Mild) Nonfriable Chrysotile 0 Sheet General - Room
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-06 1 Area Sheetrock. Cellulose 10-15 Gypsum 85-90 Yes No Wall - sheetrock No Damage (Mild) Nonfriable Chrysotile 0 Sheet General - Room
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-07 1 Under Metal Heat Sheild. Chrysolite 40-45 Cellulose 30-35 Mineral Chip 20-30 Yes Yes Other No Damage (Mild) Nonfriable Chrysotile 45 Sheet Cafeteria
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-08 1 Under Metal Heat Sheild. Chrysolite 40-45 Cellulose 30-35 Mineral Chip 20-30 No No Other Not Applicable Not Applicable Not Applicable 0 Sheet Cafeteria
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-09 1 Under Metal Heat Sheild. Chrysolite 40-45 Cellulose 30-35 Mineral Chip 20-30 No No Other Not Applicable Not Applicable Not Applicable 0 Sheet Cafeteria
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-10 1 Floor material - genericoor Mastic. Chrysolite 01-05 Cellulose 05-10 Mineral Chip 05-10 Organic Binder ** Yes Yes Floor material - generic No Damage (Mild) Nonfriable Chrysotile 5 Sheet General - Room
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-11 1 Floor material - genericoor Mastic. Chrysolite 01-05 Cellulose 05-10 Mineral Chip 05-10 Organic Binder ** No No Floor material - generic Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
545 311245 07/01/1942 1997 ACM Survey (HUB) 19970501 545-12 1 Floor material - genericoor Mastic. Chrysolite 01-05 Cellulose 05-10 Mineral Chip 05-10 Organic Binder ** No No Floor material - generic Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
550 304727 07/01/1977 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 550-TBD No Potential
550 315043 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 550-98-001 1 Kitchen ceiling boards 36 cellulose 60 nfb/filler 4 paint Yes No Ceiling - Board Not Applicable Not Applicable Not Applicable 0 Sheet Cafeteria
550 315043 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 550-95-001 2 Roof sheathing 30 cellulose 20 aggregate 50 bitumen Yes No Roofing material Not Applicable Not Applicable Not Applicable 0 Sheet Roof
550 315043 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 550-38-001 1 Mess Hall Floor material - genericoor tiles 2 chrysotile 1 cellulose 40 aggregate 2 nfb/filler 55 pvc 1 bitumen Yes Yes Floor material - generic No Damage (Mild) Nonfriable Chrysotile 2 Sheet Cafeteria
551 304727 07/01/1977 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 551-TBD No Potential
551 315044 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 551-99-001 1 Room X joint compound 25 cellulose 3 glass fiber 72 nfb/filler Yes No Wall/other Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
551 315044 07/01/1941 1990 ACM Survey - ATI (DAKF36-89-D-0034) 19900406 551-97-001 1 Room V wall boards 30 cellulose 4 glass fiber 65 nfb/filler 1 paint Yes No Wallboard Not Applicable Not Applicable Not Applicable 0 Sheet General - Room
552 315045 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 552-001 1 North side window caulking sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Window
552 315045 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 552-002 1 South side window caulking and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Window
552 315045 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 552-003 1 Isolator material sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Mechanical Room
552 315045 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 552-004 1 Isolator material sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Mechanical Room
552 315045 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 552-005 1 Paper/foil wrap and mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Mechanical Room
552 315045 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026) 20111128 552-006 1 Pipe insulation mastic sampled. Yes No Not Applicable Not Applicable Not Applicable Not Applicable 0 Not Applicable Mechanical Room
552 315045 07/01/1941 2011 Pre-Demolition Survey Report (W912DY-11-D-0026)…