MCAF FIGHTER ALERT FACILITY, JBPHH, OAHU, HAWAII KNMD 043004
PROJECT TABLE OF CONTENTS
DIVISION 01 - GENERAL REQUIREMENTS
01 32 00 PROJECT SCHEDULE
01 33 00 SUBMITTAL PROCEDURES
01 33 29 SUSTAINABILITY REPORTING
01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS
01 45 00 RMS3 - CONTRACTOR MODE (RMS3/CM)
01 45 04 CONTRACTOR QUALITY CONTROL
01 45 35 SPECIAL INSPECTIONS
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS
01 57 20 ENVIRONMENTAL PROTECTION
01 62 35 RECYCLED / RECOVERED MATERIALS
01 78 00 CLOSEOUT SUBMITTALS
01 78 23 OPERATION AND MAINTENANCE DATA
01 90 00 MISCELLANEOUS PROVISIONS
01 91 00.15 TOTAL BUILDING COMMISSIONING
DIVISION 02 - EXISTING CONDITIONS
02 41 00 DEMOLITION AND DECONSTRUCTION
02 61 13 EXCAVATION AND HANDLING OF CONTAMINATED MATERIAL
02 82 16.00 20 ENGINEERING CONTROL OF ASBESTOS CONTAINING MATERIALS
02 83 13.00 20 LEAD IN CONSTRUCTION
02 84 16 HANDLING OF LIGHTING BALLASTS AND LAMPS CONTAINING PCBs
AND MERCURY
DIVISION 03 - CONCRETE
03 11 13.00 10 STRUCTURAL CAST-IN-PLACE CONCRETE FORMING
03 20 00.00 10 CONCRETE REINFORCING
03 30 00.00 10 CAST-IN-PLACE CONCRETE
03 35 00.00 10 CONCRETE FINISHING
03 39 00.00 10 CONCRETE CURING
DIVISION 04 - MASONRY
04 20 00 UNIT MASONRY
DIVISION 05 - METALS
05 05 23.13 10 ULTRASONIC INSPECTION OF WELDMENTS
05 12 00 STRUCTURAL STEEL
05 30 00 STEEL DECKS
05 40 00 COLD-FORMED METAL FRAMING
05 50 13 MISCELLANEOUS METAL FABRICATIONS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
06 20 00 FINISH CARPENTRY
06 41 16.00 10 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
06 61 16 SOLID SURFACING FABRICATIONS
PROJECT TABLE OF CONTENTS Page 1
(DELETED) (DELETED)
(Am-0003)
DOD GPC NC Survey V1.2 © 2015-2017 GREEN BUILDING INITIATIVE, INC. ALL RIGHTS RESERVED.
Project Team Survey 61 - 90% Design Submittals ASHRAE 189.1-2014 ASHRAE 90.1-2013
Guiding Principle Requirement Select Your Answer i.a i.a.1 i.a.1.1
Not Applicable i.a.1.2
Not Applicable i.a.1.3
Not Applicable
Link 1:
Link 2:
1.a 1.a.1
1.a.1.1 Yes
No LCCA was performend because there's no HVAC in the base bid package.
1.a.2 1.a.2.1
Partially
1 EMPLOY INTEGRATED DESIGN PRINCIPLES
Sustainable Locations UFC 1-200-02, Paragraph 2-2.1.2 Evaluation for Design Strategies Evaluate site and building components for determination on passive &/or natural design strategies.
The building is designed with both long sides open for natural ventilation.
Life-Cycle Cost
Analysis
What was the finding of the Life-Cycle Cost Analysis
(LCCA)?
Meet requirements of UFC 2-100-01 Installation Master Planning.
UFC 1-200-02, Paragraph 2-2.1.3 Evaluation of the Site
Prepare the LCCA in accordance with CFR Title 10 Part 436, Subpart A and NIST Handbook 135 "Life-Cycle Costing Manual for the Federal Energy Management Program ."
In the base bid configuration, the building is open on both long sides with no HVAC. The only HVAC would be an 11,000 Btu DX split system for the Foam Room if the hangar door option is exercised
Prepare the LCCA using the Building Life-Cycle Costing (BLCC) program from NIST.
Use the implied long-term inflation rate and discount rates identified in the Annual supplement to NIST Handbook 135.
http://energy.gov/eere/femp/building-life-cycle-cost-programs https://www.ecfr.gov/cgi-bin/text-idx?SID=1772217352e2b3956b37b48739ebd676&mc=true&node=pt10.3.436&rgn=div5
UFC 1-200-02, Paragraph 1-7: Life-Cycle Cost Analysis (LCCA)
LCCAs comparing individual component or system alternatives comply with UFC 1-200-02, Paragraph 1-7.3 (LCCA Individual Component or System Alternatives Analysis).
Item # Enter Required Documentation & Comments
i. LIFE-CYCLE COST ANALYSIS (LCCA) LCCA Format
1(Am-0003)
SECTION 01 33 29 ATTACHMENT 2
TPC CHECKLIST
1.a.3
1.a.3.1 Partially
1.a.3.2 Yes
1.a.3.3 Partially
1.a.3.4 Partially
1.a.3.5 Not Applicable
1.b 1.b.1
1.b.1.1
Partially
1.b.2 1.b.2.1
Yes
UFC 1-200-02, Paragraph 2-2.1.1 Integrated Planning Submit meeting notes, project goals, and design charrette matrix and decisions Showing established goals for siting, energy, water, materials, indoor environmental quality, and other comprehensive design goals.
Meetings were held to discuss and select the site layout.
Follow the steps of design optimization for the Integrated Design Charrette Process in ASHRAE 189.1 Section F1.1.1 (Charrette Process).
Submit list of stakeholders.
Four possible building orientation/configuration options were considered but many of the functional considerations had to take precendence over the sustainability id ti
This is a secured area. Only aircraft operators and maintenance personnel should be approaching the building.
UFC 1-200-02, Paragraph 2-2.1.4 Site Integration and Design of the Building Meet the following requirements during the planning and design process.
Site design elements ensure safe and convenient pedestrian access.
Incorporate results of site analysis into design, with focus on orientation, configuration, and massing.
Integrated Design UFC 1-200-02, Paragraph 2-2.1: Integrated Design
Orient building to maximize energy efficiency, passive solar, and daylighting potential.
Incorporate high performance and sustainable systems into design.
The nature of the function of the building isn't one that's conducive to voluntary physical activity due to aircraft and other vehicular traffic in
Design promotes opportunities for occupants to voluntarily increase physical activity.
Four different building orientations/configurations were considered however, the site was very constrained Some of the constraintsAll lighting is high-efficiency LED lighting. Building is naturally ventilated.
2(Am-0003)
1.c
1.c.1
1.c.1.1
Yes
1.c.1.2
Yes
1.c.1.3 Yes
1.c.1.4
Yes
1.c.1.5
Yes
1.c.1.6 Yes
1.c.1.7 Yes
1.c.1.8 Yes
1.c.1.9 Not Applicable
DOD GPC NC Survey V1.2 © 2015-2017 GREEN BUILDING INITIATIVE, INC. ALL RIGHTS RESERVED.
Submit the contract documentation requirements of ASHRAE 189.1 Section 10.3.1.2.6 Documentation.
Submit the contract documentation requirements of ASHRAE 189.1 Section 10.3.1.2.2 Activities Prior to Building Occupancy.
Submit an electronic O&M Manual (hard copy optional).
Commissioning
UFC 1-200-02, Paragraph 2-2.2: Commissioning Complete all nine (9) requirements (as applicable).
Exception: For medical treatment facilities, refer to UFC 4-510-01 Military Medical Facilities for commissioning requirements.
Air Force projects only: The Project Delivery team must determine the level of commissioning activities required.
Submit the design documentation requirements of ASHRAE 189.1 Section 10.3.1.2.1 Activities Prior to Building Permit.
The CxA has conducted a focused OPR review of the contract documents at or near 50% design completion.
Submit the contract documentation requirements of ASHRAE 189.1 Section 10.3.1.2.4 Systems.
Submit the contract documentation requirements of ASHRAE 189.1 Section 10.3.1.2.5 Building Envelope Airtightness.
The CxA has conducted a second, focused OPR review of the final contract documents.
Submit the contract documentation requirements of ASHRAE 189.1 Section 10.3.1.2.3 Post-Occupancy Activities.
3(Am-0003)
ASSESSOR USE ONLY Assessor Comments
Has the requirement been met?
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
1.a Sustainable Locations i.a LCCA Format
I. LIFE-CYCLE COST ANALYSIS (LCCA)
1 EMPLOY INTEGRATED DESIGN PRINCIPLES
4(Am-0003)
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
1.b Integrated Design
5(Am-0003)
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
1.c Commissioning
6(Am-0003)
Guiding Principle Requirement Select Your Answer
2.a
2.a.1 Commercial & Multi-Family
2.a.1.A 2.a.1.A.1
Not Applicable
2.a.1.A.2
Not Applicable
2.a.1.A.3 Not Applicable
2.a.1.B 2.a.1.B.1
Not Applicable
2.a.1.B.2
Not Applicable
2.a.1.C
(pick from drop down list)
2.a.1.C.1 (pick from drop down list)
2.a.1.C.2
2.a.1.C.2.i
( mark with X to select)
2.a.1.C.2.ii
( mark with X to select)
2.a.1.C.2.iii
( mark with X to select)
2.a.1.C.2.iv
( mark with X to select)
iv) If none of the above reductions are LCCE, design to achieve an energy consumption level at the highest level of energy efficiency that is LCCE.
Not applicable. New Construction.
ii) Reduce measured building energy use by at least 20% below FY 2015 energy use baseline.
Not applicable. New Construction.
iii) Reduce modeled energy use (from all sources including renewable energy) by 20% compared to the ASHRAE 90.1 baseline building design.
Not applicable. New Construction.
Submit energy model showing the proposed building alternatives to achieve at least 30% - less if LCCE -energy consumption reduction from IECC baseline (Section 405, Simulated Performance Alternative).
UFC 1-200-02, Paragraph 2-3.1.3 Renovations - OPTION C Renovation Type - Will this renovation replace everything above the foundation?
Not applicable. New Construction.
If replacing everything above the foundation:
Apply either UFC 2-3.1.1 or 2-3.1.2 as applicable.
Not applicable. New Construction.
Determine energy consumption levels for ASHRAE Baseline Building and proposed building alternatives.
UFC 1-200-02, Paragraph 2-3.1.2 Low-Rise Residential Buildings - OPTION B Meet the requirements of International Energy Conservation Code (IECC).
Meet the requirements of ASHRAE 90.1 Energy Standard for Buildings Except Low-Rise Residential Buildings.
The building wasn't modeled because there are no HVAC systems in the base bid.
For all other renovations, choose from one of the following four (4) options by marking an X in the pink cell:
i) Reduce measured building energy use by at least 30%, below FY 2003 energy use baseline.
Not applicable. New Construction.
UFC 1-200-02, Paragraph 2-3.1.1 Commercial and Multi-Family High-Rise Residential Buildings - OPTION A
Building Type - Select the building type most applicable to your project. Then complete only the appropriate requirement (Option) below.
Item # Enter Required Documentation & Comments
2 OPTIMIZE ENERGY PERFORMANCE
Energy Efficiency
Submit energy model showing the proposed building model to achieve at least 30% - less if LCCE - energy consumption reduction from ASHRAE 90.1 baseline.
7(Am-0003)
LCCA was not performed since no HVAC in the base bid.
Not applicable
Not applicable
2.a.2
2.a.2.1 Not Applicable
Link 1:
Link 2:
2.a.3
2.a.3.1 Not Applicable
2.b
2.b.1
2.b.1.1
Not Applicable
2.b.1.2 Not Applicable
No LCCA performed because first-cost budget constraints precluded PV and/or solar hot ater0%
Not applicable http://www.energystar.gov https://energy.gov/eere/femp/federal�energy�management�program
UFC 1-200-02, Paragraph 2-3.1.5 Standby Powered Devices
UFC 1-200-02, Paragraph 2-3.2: On-Site Renewable Energy Complete LCCA, both specific requirements, and tracking fields 1 - 4 (as applicable).
NAVFAC only: In addition to above, complete tracking field 5.
Submit Life Cycle Cost Analysis for on-site renewable energy (minimum quantity per ASHRAE 189.1 Section 7.4.1.1).
Rooftop PV and/or hot water systems were not feasible due to first-cost budget constraints and the fact that a glare study had not been done to
Submit documentation for on-site renewable energy system(s).
Tracking 5 Navy only: What is the Installation-level solution to renewable energy systems for this project?
Tracking 3 What is the system's total capacity for renewable thermal energy?
Tracking 4 List renewable energy technology
Tracking 1 What percentage of energy will come from the renewable energy system(s)?
Tracking 2 What is the system's total capacity for renewable electric energy?
Life-Cycle Cost
Analysis
What was the finding of the Life-Cycle Cost Analysis
(LCCA)?
Renewable and Clean Energy
Provide commercially available, off-the-shelf products that use no more than 1 watt in standby mode.
There are no appliance or equipment beign provided under this project.
COMPLETE EACH REQUIREMENT BELOW.
UFC 1-200-02, Paragraph 2-3.1.4 Energy Efficient Products Select energy consuming products and equipment with Energy Star or FEMP designation.
No energyconsuming
Tracking 1 What is the current energy consumption reduction percentage?
Tracking 2 Energy Use Intensity (EUI) (kBTU/Sq. Ft./Year per building)
Enter LCCA and tracking data below, regardless of OPTION selected above.
Life-Cycle
Cost Analysis
What was the finding of the Life-Cycle Cost Analysis
(LCCA)?
8(Am-0003)
2.b.2
2.b.2.1 Not Applicable
Not applicable
Not applicable
2.c
2.c.1
2.c.1.1 Partially
2.c.1.2 Not Applicable
2.c.1.3 Not Applicable
2.c.1.4 Partially
2.c.1.5 Partially
DOD GPC NC Survey V1.2 © 2015-2017 GREEN BUILDING INITIATIVE, INC. ALL RIGHTS RESERVED.
Is steam metered at the building level?
Submit documentation of electric meter at each building connected to base-wide monitoring system.
Sheet M-802
Submit documentation of utility meters for all other sources at each building, connected to the base-wide monitoring system.
The Alert Shelter is fed from the Crew Quarters Building, which has its own meter. The Crew Quarters building's meter is connected to the base wide
Metering
UFC 1-200-02, Paragraph 2-3.4 Metering Requirements 2.c.1.1 - 3: Choose "Yes" for each utility available at the project site, and "Not applicable" for utilities not available.
Requirements 2.c.1.4 - 5: Select "Not applicable if there is no centralized system.
Is electricity metered at the building level? The Alert Shelter is fed from the Crew Quarters Building, which has its own
Is natural gas metered at the building level?
Life-Cycle Cost
Analysis
What was the finding of the Life-Cycle Cost Analysis
(LCCA)?
Tracking 1 What percentage of the hot water demand is being met through the installation of solar hot water heaters?
UFC 1-200-02, Paragraph 2-3.2.1 Solar Domestic Hot Water (SDHW) Purchase and install solar domestic hot water system where life cycle cost effective.
Solar hot water heating was not provided due to first-cost budget constraints.
9(Am-0003)
Has the requirement been met?
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
2 OPTIMIZE ENERGY PERFORMANCE
2.a Energy Efficiency
10(Am-0003)
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
(pick from drop down list)
2.b Renewable and Clean Energy
11(Am-0003)
Has the requirement been met?
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
2.c Metering
12(Am-0003)
Guiding Principle Requirement Select Your Answer
3.a 3.a.1
3.a.1.1
Not Applicable
3.a.1.2 Not Applicable
3.a.1.3 Not Applicable
Not applicable
Not applicable
3.a.2 3.a.2.1
Not Applicable
3.b
3.b.1
3.b.1.1 Not Applicable
3.b.1.2
Not Applicable
3.b.1.3
Not Applicable
Not applicable.
3.b.2
UFC 1-200-02, Paragraph 2-4.1: Indoor Water Submit documentation of compliance with ASHRAE 189.1 Section 6.3.2 (Building Water Use Reduction), which incorporates USEPA WaterSense-labeled products.
The only plumbing in the building consists of two emergency eyewash/showers. Because this is a health and safety feature, adequae water flow is critical.
Submit documentation of compliance with ASHRAE 189.1 Section 6.4.2 (Building Water Use Reduction).
Submit documentation of compliance with ASHRAE 189.1 Section 6.4.3 (Special Water Features).
No Special Water Features in this project
Submit documentation showing no potable water is used for new landscaping.
No landcaping.
UFC 1-200-02, Paragraph 2-4.1.1 Indoor Water Metering Submit documentation for water meter(s) at each building, connected to base-wide monitoring system.
Item # Enter Required Documentation & Comments
3 PROTECT AND CONSERVE WATER
Indoor Water Use
Life-Cycle Cost
Analysis
What was the finding of the Life-Cycle Cost Analysis
(LCCA)?
Tracking 1 NAVFAC ONLY: Water Use Intensity (GAL/Sq. Ft./Year/building)
There are only two emergency eyewash/shower stations in the building's plumbing system. Regular
Outdoor Water Use
UFC 1-200-02, Paragraph 2-4.2.1 Water for Landscaping Complete LCCA and all three (3) requirements (as applicable).
For existing systems, if a building has a single water meter: Submit documentation of 20% indoor and outdoor potable water use reduction. Calculate water savings results to baseline building using EPA's WaterSense landscape water budget tool version 1.01 or later.
New Building
Require irrigation contractors to be certified through a WaterSense labeled program, or by another industry-recognized, credentialing program.
No landscaping
Life-Cycle Cost
Analysis
What was the finding of the Life-Cycle Cost Analysis
(LCCA)?
No landscaping
UFC 1-200-02, Paragraph 2-4.2.2 Outdoor Water Metering For existing irrigation systems using potable water and serving more than 25,000 sq. ft. of landscape.
13(Am-0003)
3.b.2.1 Not Applicable
3.c 3.c.1
3.c.1.1
Not Applicable
3.d
3.d.1
3.d.1.1 Not Applicable
3.d.1.2
Not Applicable
3.d.1.3 Not Applicable
DOD GPC NC Survey V1.2 © 2015-2017 GREEN BUILDING INITIATIVE, INC. ALL RIGHTS RESERVED.
UFC 3-210-10 Low Impact Development Complete requirements 3.d.1.1 and 3.d.1.2 (as applicable).
NAVFAC only: In addition to above, complete 3.d.1.3
Alternative Water UFC 1-200-02, Paragraph 2-4.3 Alternative Water Submit documentation of water efficient landscape and irrigation strategies, such as water reuse and the use of harvested rainwater.
No landscaping
Stormwater Management
Submit documentation for separate water meters for outdoor water use.
No landcaping.
Are the requirements of UFC 3-210-10 Low Impact Development applicable to this project?
Although the site meets the criteria in paragraph 1-4 of UFC 3-10-10, application of full LID principles is technically infeasible per Paragraph 2Submit documentation (see ToolTip, all documentation is required) to validate the as-built LID-integrated management practices meet the design requirements, per UFC 3-210-10 paragraph 2-2.4.
For NAVFAC only, does the project require NAVY LID policy?
14(Am-0003)
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
3 PROTECT AND CONSERVE WATER
3.a Indoor Water Use
3.b Outdoor Water Use
15(Am-0003)
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
3.d Stormwater Management
3.c Alternative Water
16(Am-0003)
Guiding Principle Requirement Select Your Answer
4.a 4.a.1
4.a.1.1 Not Applicable
4.a.1.2
Not Applicable
4.a.1.3
Yes
4.b 4.b.1
4.b.1.1 Not Applicable
4.b.1.2 Not Applicable
4.b.1.3
Not Applicable
4.b.2 4.b.2.1
Partially
4.b.2.2
Not Applicable
4.c 4.c.1 4.c.1
Yes
4.c.1.2 Not Applicable
If Medical Treatment Facility: Meet the requirements of UFC 4-510-01 Medical Military Facilities.
Not a medical facility
UFC 1-200-02, Paragraph 2-5.3.1: Moisture Control Meet the requirements of ASHRAE 189.1 Section
10.3.1.5. Include and implement these requirements in
the IAQ construction management plan.
Material handling/storage requirements are in the specficiations.
Meet the requirements of UFC 3-410-01, Chapter 3, Sections 3-2 and 3-3 (Ventilation Air).
Building is not conditioned.
All regularly occupied spaces located on the exterior wall have vision fenestration.
No regularly occupied spaces in the building.
UFC 3-530-01 Interior & Exterior Lighting Systems and Controls Provide automated lighting controls in accordance with UFC 3-530-01 Interior and Exterior Lighting Systems and Controls, Sections 2-2 Lighting Controls (Interior) and 4-3 Lighting Controls (Exterior).
The Civil Engineering Squadron, who will be maintaining the facilities, was against daylight responsive dimmers due to long-term maintenance concerns. A timeclock is being
Indoor Air Quality
All classrooms and offices have daylighting. No classrooms or offices in the building.
Meet the requirements of ASHRAE 189.1 Section 8.4.1.2 (Minimum Sidelighting effective Aperture for Office Spaces and Classrooms) OR Section 8.5.1.2 (Usable Daylight Illuminance in Office Spaces and Classrooms).
No classrroms or office in the building.
UFC 1-200-02, Paragraph 2-5.2: Daylighting and Lighting Controls
Meet the requirements of UFC 3-410-01 Heating, Ventilating, and Air Conditioning Systems.
No HVAC in the base bid of this building. The only AC will be a 11 000 Btu unit to cool the equipment
If Medical Treatment Facility: Meet the requirements of UFC 4-510-01 Medical Military Facilities.
This is not a medical treatment facility.
Show proof that passive ventilation and thermal comfort methods are allowed and encouraged.
The long side of both buildings are open for ventilation. There is no HVAC in the base bid of this building.
Daylighting and Lighting Controls
UFC 1-200-02, Paragraph 2-5.1: Ventilation and Thermal Comfort
Item # Enter Required Documentation & Comments
4 ENHANCE INDOOR ENVIRONMENTAL QUALITY
Ventilation and Thermal Comfort
17(Am-0003)
4.c.1.3
4.c.2 4.c.2.1
Yes
4.c.3 4.c.3.1
Not Applicable
4.c.3.2
Not Applicable
4.c.4 4.c.4.1
Yes
4.d 4.d.1
4.d.1.1 Yes
DOD GPC NC Survey V1.2 © 2015-2017 GREEN BUILDING INITIATIVE, INC. ALL RIGHTS RESERVED.
Occupant Health and Wellness UFC 1-200-02, Paragraph 2-5.4 Occupant Health and Wellness During Integrated Design Process, identify efforts to promote opportunities for occupant physical activity.
An exercise room and locker rooms are provided in the Crew Quarters building where the "Alert" personnel
For new construction and for renovation of unoccupied existing buildings, meet the requirements of ASHRAE 189.1 Section 10.3.1.4 Indoor Air Quality (IAQ) Construction Management.
There are no HVAC systems in the base bid and the building sides are mostly open. There's no need for a flushout or indoor air monitoring.
For renovation of occupied existing buildings, meet the requirements of SMACNA IAQ Guidelines for Occupied Buildings Under Construction , 2nd edition
ANSI/SMACNA 008-2008.
UFC 1-200-02, Paragraph 2-5.3.4 Environmental Tobacco Smoke Control Meet the requirements of ASHRAE 189.1 Section 8.3.1 Manage environmental tobacco smoke.
Meet the requirements of UFC 3-101-01 Architecture, Chapter 3, Building Envelope Requirements. Submit design details complying with moisture control requirements.
The two long sides of the building are mostly open. The building envelope isn't designed to be air-tight.
UFC 1-200-02, Paragraph 2-5.3.2 Reduce Volatile Organic Compounds (VOC) (Low-Emitting Materials) Meet the requirements of ASHRAE 189.1 Section 8.4.2 Materials (Prescriptive Option).
VOC limitation requirements have been inserted to all of the pertinent sections in the Specifications.
UFC 1-200-02, Paragraph 2-5.3.3 Protect Indoor Air Quality during Construction
18(Am-0003)
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
(pick from drop down list)
4 ENHANCE INDOOR ENVIRONMENTAL QUALITY
4.a Ventilation and Thermal Comfort
4.b Daylighting and Lighting Controls
4.c Indoor Air Quality
19(Am-0003)
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
4.d Occupant Health and Wellness
20(Am-0003)
Guiding Principle Requirement Select Your Answer
5.a 5.a.1
5.a.1.1 Yes
5.a.1.2 Yes
5.a.2 5.a.2.1
Yes
5.a.2.2
Yes
5.a.3 5.a.3.1
Not Applicable
5.a.3.2
Not Applicable
5.a.3.3
Yes
5.b 5.b.1
5.b.1.1
Not Applicable
5.b.2 5.b.2.1
Yes
DOD GPC NC Survey V1.2 © 2015-2017 GREEN BUILDING INITIATIVE, INC. ALL RIGHTS RESERVED.
UFC 1-200-02, Paragraph 2-6.2.2 Waste Diversion Divert a minimum of 60% (DoD requirement) of non-hazardous construction and demolition waste from landfills.
Comply with UFC 3-600-01 Fire Protection Engineering for Facilities for allowable chemicals in fire suppression systems.
UFC 3-600-01 refers to UFC 4-211-01 for Aircraft Maintenance Hangars.
UFC 4-211-01 allows foam fire suppression systems, which is what's
Waste Diversion and Materials Management UFC 1-200-02, Paragraph 2-6.2.1 Storage of Recyclables Meet the requirements of ASHRAE 189.1 Section 9.3.4.1:
Provide an area that serves the entire building and is dedicated to the collection and storage of materials for recycling.
The maintenance hangar is not a normally occupied space. When not actively maintaining an aircraft, the maintenance personnel will be in the Ready Alert Building.
Provide written narrative detailing research, analysis, and final determination of exclusion or inclusion of considered bio-based products in project.
Research of EPA website
UFC 1-200-02, Paragraph 2-6.1.3 Ozone Depleting Compounds Provide written narrative detailing research, analysis, and final determination of exclusion or inclusion of considered environmentally preferable products in project.
Base contract does not include any air conditoning
Meet the requirements of ASHRAE 189.1 Section 9.3.3:
Do not use CFC-based refrigerants in HVAC&R Systems.
Base contract does not include any air conditoning
Comply with RCRA Section 6002, per EPA's Comprehensive Procurement Guideline website.
Requirements were included in each pertinent section of the Specifications.
For EPA-designated products, specify products meeting or exceeding EPA's recycled content recommendations.
Requirements were included in each pertinent section of the Specifications.
UFC 1-200-02, Paragraph 2-6.1.2 Biologically-Based Products Specify products composed of the highest percentage of biobased content consistent with the USDA BioPreferred Program if products meet performance and are available at a reasonable cost.
Requirements were included in each pertinent section of the Specifications.
UFC 1-200-02, Paragraph 2-6.1.1 Recycled Content
Item # Enter Required Documentation & Comments
5 REDUCE ENVIRONMENTAL IMPACT OF MATERIALS
Material Content and Performance
21(Am-0003)
(pick from drop down list)
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
(pick from drop down list)
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
Has the requirement been met?
(pick from drop down list)
5 REDUCE ENVIRONMENTAL IMPACT OF MATERIALS
5.a Material Content and Performance
5.b Waste Diversion and Materials Management
22(Am-0003)
Guiding Principle Requirement Select Your Answer
6.a 6.a.1
6.a.1.1 Not Applicable
6.a.1.2 Not Applicable
DOD GPC NC Survey V1.2 © 2015-2017 GREEN BUILDING INITIATIVE, INC. ALL RIGHTS RESERVED.
Is or will there be a climate change projection and/or determination of acceptable risk for this project?
If located in a floodplain of concern: Provide design solutions which mitigate floodplain impact and impact on building function and occupants.
Project is near a floodplain but the building was purposely cited to avoid encroachment into the floodplain.
UFC 1-200-02, Paragraph 2-7 Address Climate Change Risk
Item # Enter Required Documentation & Comments
6 ASSESS AND CONSIDER CLIMATE CHANGE RISKS
Address Climate Change Risks
23(Am-0003)
(pick from drop down list)
(pick from drop down list)
6 ASSESS AND CONSIDER CLIMATE CHANGE RISKS
6.a Address Climate Change Risks
24(Am-0003)
DOD�GPC�NC�Survey�V1.2 ©�2015�2017�GREEN�BUILDING�INITIATIVE,�INC.�ALL�RIGHTS�RESERVED.
Survey�Assessment�Area Criteria Project�Team�Response Assessor�Response i.a.1.1 Not�Applicable No�Answer i.a.1.2 Not�Applicable No�Answer i.a.1.3 Not�Applicable No�Answer
1.a.1.1 Yes No�Answer Life�Cycle�Cost�Analysis No�LCCA�was�performend�because�there's�no�HVNo�Answer
1.a.2.1 Partially No�Answer
1.a.3.1 Partially No�Answer 1.a.3.2 Yes No�Answer 1.a.3.3 Partially No�Answer 1.a.3.4 Partially No�Answer 1.a.3.5 Not�Applicable No�Answer
1.b.1.1 Partially No�Answer
1.b.2.1 Yes No�Answer
1.c.1.1 Yes No�Answer 1.c.1.2 Yes No�Answer 1.c.1.3 Yes No�Answer 1.c.1.4 Yes No�Answer 1.c.1.5 Yes No�Answer 1.c.1.6 Yes No�Answer 1.c.1.7 Yes No�Answer 1.c.1.8 Yes No�Answer 1.c.1.9 Not�Applicable No�Answer
1.c.1�UFC�1�200�02,�Paragraph�2�2.2:��Commissioning i.a�LCCA�Format i.a.1�UFC�1�200�02,�Paragraph�1�7:�Life�Cycle�Cost�Analysis�(LCCA)
EM
PL
O Y�
IN
TE
G
RA
TE
D�
DE
SI
G N �P
RI
N
CI
PL
ES
1.a�Sustainable�Locations 1.a.1�UFC�1�200�02,�Paragraph�2�2.1.2�Evaluation�for�Design�Strategies
1.a.2�UFC�1�200�02,�Paragraph�2�2.1.3�Evaluation�of�the�Site
1.a.3�UFC�1�200�02,�Paragraph�2�2.1.4�Site�Integration�and�Design�of�the�Building
1.b�Integrated�Design 1.b.1�UFC�1�200�02,�Paragraph�2�2.1:��Integrated�Design
1.b.2�UFC�1�200�02,�Paragraph�2�2.1.1�Integrated�Planning
1.c�Commissioning
LC
CA
25(Am-0003)
2.a.1�Building�Type Commercial�&�Multi�Family No�Answer
2.a.1.A.1 Not�Applicable No�Answer 2.a.1.A.2 Not�Applicable No�Answer 2.a.1.A.3 Not�Applicable No�Answer
2.a.1.B.1 Not�Applicable No�Answer 2.a.1.B.2 Not�Applicable No�Answer Renovation�Type No�Answer No�Answer
2.a.1.C.1 No�Answer No�Answer
2.a.1.C.2.i (mark�with�X�to�select) No�Answer 2.a.1.C.2.ii (mark�with�X�to�select) No�Answer 2.a.1.C.2.iii (mark�with�X�to�select) No�Answer 2.a.1.C.2.iv (mark�with�X�to�select) No�Answer Life�Cycle�Cost�Analysis LCCA�was�not�performed�since�no�HVAC�in�the�bNo�Answer Tracking�1 Not�applicable No�Answer Tracking�2 Not�applicable No�Answer
2.a.2.1 Not�Applicable No�Answer
2.a.3.1 Not�Applicable No�Answer
2.b.1.1 Not�Applicable No�Answer 2.b.1.2 Not�Applicable No�Answer Life�Cycle�Cost�Analysis No�LCCA�performed�because�first�cost�budget�coNo�Answer Tracking�1 0% No�Answer Tracking�2 No�Answer No�Answer Tracking�3 No�Answer No�Answer Tracking�4 Not�applicable No�Answer Tracking�5 No�Answer No�Answer
2.b.2.1 Not�Applicable No�Answer Life�Cycle�Cost�Analysis Not�applicable No�Answer Tracking�1 Not�applicable No�Answer
O
PT
IM
IZ
E�
EN
ER
G Y�
PE
RF
O
RM
AN
CE
2.a�Energy�Efficiency
2.a.1.A�UFC�1�200�02,�Paragraph�2�3.1.1�Commercial�and�Multi�Family�High�Rise�Residential�Buildings���OPTION�A
2.a.1.B�UFC�1�200�02,�Paragraph�2�3.1.2�Low�Rise�Residential�Buildings���OPTION�B
2.a.1.C�UFC�1�200�02,�Paragraph�2�3.1.3�Renovations���OPTION�C
2.a.1.C.2�For�all�other�renovations,�choose�from�one�of�the�following�four�(4)�options�by�marking�an�X�in�the�pink�cell:
2.a.2�UFC�1�200�02,�Paragraph�2�3.1.4�Energy�Efficient�Products
2.a.3�UFC�1�200�02,�Paragraph�2�3.1.5�Standby�Powered�Devices
2.b�Renewable�and�Clean�Energy 2.b.1�UFC�1�200�02,�Paragraph�2�3.2:��On�Site�Renewable�Energy
2.b.2�UFC�1�200�02,�Paragraph�2�3.2.1�Solar�Domestic�Hot�Water�(SDHW)
26(Am-0003)
2.c.1.1 Partially No�Answer 2.c.1.2 Not�Applicable No�Answer 2.c.1.3 Not�Applicable No�Answer 2.c.1.4 Partially No�Answer 2.c.1.5 Partially No�Answer
3.a.1.1 Not�Applicable No�Answer 3.a.1.2 Not�Applicable No�Answer 3.a.1.3 Not�Applicable No�Answer Life�Cycle�Cost�Analysis Not�applicable No�Answer Tracking�1 Not�applicable No�Answer
3.a.2.1 Not�Applicable No�Answer
3.b.1.1 Not�Applicable No�Answer 3.b.1.2 Not�Applicable No�Answer 3.b.1.3 Not�Applicable No�Answer Life�Cycle�Cost�Analysis Not�applicable.�� No�Answer
3.b.2.1 Not�Applicable No�Answer
3.c.1.1 Not�Applicable No�Answer
3.d.1.1 Not�Applicable No�Answer 3.d.1.2 Not�Applicable No�Answer 3.d.1.3 Not�Applicable No�Answer
4.a.1.1 Not�Applicable No�Answer 4.a.1.2 Not�Applicable No�Answer 4.a.1.3 Yes No�Answer
4.b.1.1 Not�Applicable No�Answer 4.b.1.2 Not�Applicable No�Answer 4.b.1.3 Not�Applicable No�Answer
4.b.2.1 Partially No�Answer 4.b.2.2 Not�Applicable No�AnswerRO
N M
EN
TA
L� Q U
AL
IT
Y
4.a�Ventilation�and�Thermal�Comfort
3.b.1�UFC�1�200�02,�Paragraph�2�4.2.1�Water�for�Landscaping
3.b.2�UFC�1�200�02,�Paragraph�2�4.2.2�Outdoor�Water�Metering
3.c�Alternative�Water 3.c.1�UFC�1�200�02,�Paragraph�2�4.3�Alternative�Water
3.d�Stormwater�Management 3.d.1�UFC�3�210�10�Low�Impact�Development
4.a.1�UFC�1�200�02,�Paragraph�2�5.1:�Ventilation�and�Thermal�Comfort
4.b�Daylighting�and�Lighting�Controls 4.b.1�UFC�1�200�02,�Paragraph�2�5.2:�Daylighting�and�Lighting�Controls
4.b.2�UFC�3�530�01�Interior�&�Exterior�Lighting�Systems�and�Controls
PR
O
TE
CT
�A N D�
CO
N
SE
RV
E� W
AT
ER
3.a�Indoor�Water�Use 3.a.1�UFC�1�200�02,�Paragraph�2�4.1:�Indoor�Water
3.a.2�UFC�1�200�02,�Paragraph�2�4.1.1�Indoor�Water�Metering
3.b�Outdoor�Water�Use
2.c�Metering 2.c.1�UFC�1�200�02,�Paragraph�2�3.4�Metering
27(Am-0003)
4.c.1 Yes No�Answer 4.c.1.2 Not�Applicable No�Answer 4.c.1.3 Not�Applicable No�Answer
4.c.2.1 Yes No�Answer
4.c.3.1 Not�Applicable No�Answer 4.c.3.2 Not�Applicable No�Answer
4.c.4.1 Yes No�Answer
4.d.1.1 Yes No�Answer
5.a.1.1 Yes No�Answer 5.a.1.2 Yes No�Answer
5.a.2.1 Yes No�Answer 5.a.2.2 Yes No�Answer
5.a.3.1 Not�Applicable No�Answer 5.a.3.2 Not�Applicable No�Answer 5.a.3.3 Yes No�Answer
5.b.1.1 Not�Applicable No�Answer
5.b.2.1 Yes No�Answer
6.a.1.1 Not�Applicable No�Answer
6.a.1.2 Not�Applicable No�Answer
DOD�GPC�NC�Survey�V1.2 ©�2015�2017�GREEN�BUILDING�INITIATIVE,�INC.�ALL�RIGHTS�RESERVED.
5.b.2�UFC�1�200�02,�Paragraph�2�6.2.2�Waste�Diversion
AS
SE
SS
�A N D�
CO
N
SI
DE
R�
CL
IM
AT
E�
CH
AN
G E�
RI
SK
S 6.a�Address�Climate�Change�Risks
6.a.1�UFC�1�200�02,�Paragraph�2�7�Address�Climate�Change�Risk
4.c.4�UFC�1�200�02,�Paragraph�2�5.3.4�Environmental�Tobacco�Smoke�Control
4.d�Occupant�Health�and�Wellness 4.d.1�UFC�1�200�02,�Paragraph�2�5.4�Occupant�Health�and�Wellness
RE
DU
CE
�E N
VI
RO
N M
EN
TA
L�
IM
PA
CT
�O F� M
AT
ER
IA
LS
5.a�Material�Content�and�Performance 5.a.1�UFC�1�200�02,�Paragraph�2�6.1.1�Recycled�Content
5.a.2�UFC�1�200�02,�Paragraph�2�6.1.2�Biologically�Based�Products
5.a.3�UFC�1�200�02,�Paragraph�2�6.1.3�Ozone�Depleting�Compounds
5.b�Waste�Diversion�and�Materials�Management 5.b.1�UFC�1�200�02,�Paragraph�2�6.2.1�Storage�of�Recyclables
EN
HA
N
CE
�IN
DO
O R�
EN
VI
R
4.c.1�UFC�1�200�02,�Paragraph�2�5.3.1:�Moisture�Control
4.c.2�UFC�1�200�02,�Paragraph�2�5.3.2�Reduce�Volatile�Organic�Compounds�(VOC)�(Low�Emitting�Materials)
4.c.3�UFC�1�200�02,�Paragraph�2�5.3.3�Protect�Indoor�Air�Quality�during�Construction
4.c�Indoor�Air�Quality
28(Am-0003)
Guiding Principle Requirement Select Your Answer ASSESSOR USE ONLY Assessor Comments i.a i.a.1 Has the requirement been met?
i.a.1.1
Not Applicable (pick from drop down list) i.a.1.2
Not Applicable (pick from drop down list) i.a.1.3
Yes (pick from drop down list)
Link 1:
Link 2:
1.a 1.a.1 Has the requirement been met?
1.a.1.1 Partially (pick from drop down list)
The most LCC effective air conditioning system for this application is a system incorporating a high efficiency air cooled chiller.
1.a.2 Has the requirement been met?
1.a.2.1
Partially (pick from drop down list)
UFC 1-200-02, Paragraph 1-7: Life-Cycle Cost Analysis (LCCA)
LCCAs comparing individual component or system alternatives comply with UFC 1-200-02, Paragraph 1-7.3 (LCCA Individual Component or System Alternatives Analysis).
AC LCCA attached in Sustainability Notebook
Item # Enter Required Documentation & Comments
i. LIFE-CYCLE COST ANALYSIS (LCCA) LCCA Format
Meet requirements of UFC 2-100-01 Installation Master Planning.
The project involves replacing existing buildings with new facilities in the same general vicinity. The entire area
UFC 1-200-02, Paragraph 2-2.1.3 Evaluation of the Site
Prepare the LCCA in accordance with CFR Title 10 Part 436, Subpart A and NIST Handbook 135 "Life-Cycle Costing Manual for the Federal Energy Management Program ."
Prepare the LCCA using the Building Life-Cycle Costing (BLCC) program from NIST.
Use the implied long-term inflation rate and discount rates identified in the Annual supplement to NIST Handbook 135.
http://energy.gov/eere/femp/building-life-cycle-cost-programs https://www.ecfr.gov/cgi-bin/text-idx?SID=1772217352e2b3956b37b48739ebd676&mc=true&node=pt10.3.436&rgn=div5
1 EMPLOY INTEGRATED DESIGN PRINCIPLES
Sustainable Locations UFC 1-200-02, Paragraph 2-2.1.2 Evaluation for Design Strategies Evaluate site and building components for determination on passive &/or natural design strategies.
There were numerous functional and safety issues that precluded flexibility in the siting of the buildings.
Life-Cycle Cost
Analysis
What was the finding of the Life-Cycle Cost Analysis
(LCCA)?
1.a Sustainable Locations i.a LCCA Format
I. LIFE-CYCLE COST ANALYSIS (LCCA)
1 EMPLOY INTEGRATED DESIGN PRINCIPLES
29(Am-0003)
1.a.3 Has the requirement been met?
Yes (pick from drop down list)
1.a.3.2 Yes (pick from drop down list)
1.a.3.3 Not Applicable (pick from drop down list)
1.a.3.4 Yes (pick from drop down list)
1.a.3.5 Partially (pick from drop down list)
1.b 1.b.1 Has the requirement been met?
1.b.1.1
Yes (pick from drop down list)
1.b.2 Has the requirement been met?
1.b.2.1
Yes (pick from drop down list)
Follow the steps of design optimization for the Integrated Design Charrette Process in ASHRAE 189.1 Section F1.1.1 (Charrette Process).
Submit list of stakeholders.
The charrette report (331 pages) and the Design Analysis (925 pages) are incorporated by reference but not attachment due to their length.
There were numeorus functional and safety considerations in the siting of the building. See charrette minutes in the Sustainability Notebook thatReference is made to the charrette meeting minutes cited in Item 1.a.3.1.
There were numerous mission-critical site constraints that dictated the
UFC 1-200-02, Paragraph 2-2.1.4 Site Integration and Design of the Building Meet the following requirements during the planning and design process.
Site design elements ensure safe and convenient pedestrian access.
Incorporate results of site analysis into design, with focus on orientation, configuration, and massing.
Integrated Design UFC 1-200-02, Paragraph 2-2.1: Integrated Design
Orient building to maximize energy efficiency, passive solar, and daylighting potential.
Incorporate high performance and sustainable systems into design.
The nature of the functions at the site are not conducive to people walking around the building. One of the reasons the Crew Quarters is located
Design promotes opportunities for occupants to voluntarily increase physical activity.
Daylighting via windows was provided to the extent feasible. However, the wall assemblies facing the hangar were subject to minimum blast Refer to charrette minutes in this section of the Sustainability Notebook.
Subsequent to the charrette, it was determined that low impact design
UFC 1-200-02, Paragraph 2-2.1.1 Integrated Planning Submit meeting notes, project goals, and design charrette matrix and decisions Showing established goals for siting, energy, water, materials, indoor environmental quality, and other comprehensive design goals.
Refer to Charrette Report and Design Analysis.
1.b Integrated Design
30(Am-0003)
1.c.1 Has the requirement been met?
1.c.1.1
Yes (pick from drop down list)
1.c.1.2
Yes (pick from drop down list)
1.c.1.3 Yes (pick from drop down list)
1.c.1.4
Yes (pick from drop down list)
1.c.1.5
Yes (pick from drop down list)
1.c.1.6 Yes (pick from drop down list)
1.c.1.7 Yes (pick from drop down list)
1.c.1.8 Yes (pick from drop down list)
1.c.1.9 Not Applicable (pick from drop down list)
DOD GPC NC Survey V1.2 © 2015-2017 GREEN BUILDING INITIATIVE, INC. ALL RIGHTS RESERVED.
Submit an electronic O&M Manual (hard copy optional). To be provided by the Contractor during the construction phase
Refer to attached Design Phase Commissioning Plan.
Commissioning
UFC 1-200-02, Paragraph 2-2.2: Commissioning Complete all nine (9) requirements (as applicable).
Exception: For medical treatment facilities, refer to UFC 4-510-01 Military Medical Facilities for commissioning requirements.
Air Force projects only: The Project Delivery team must determine the level of commissioning activities required.
Submit the design documentation requirements of ASHRAE 189.1 Section 10.3.1.2.1 Activities Prior to Building Permit.
Refer to attached Design Phase Commissioning Plan.
The CxA has conducted a focused OPR review of the contract documents at or near 50% design completion.
Submit the contract documentation requirements of ASHRAE 189.1 Section 10.3.1.2.4 Systems.
Refer to attached Design Phase Commissioning Plan.
Submit the contract documentation requirements of ASHRAE 189.1 Section 10.3.1.2.5 Building Envelope Airtightness.
Refer to attached Design Phase Commissioning Plan.
The CxA has conducted a second, focused OPR review of the final contract documents.
Refer to attached Design Phase Commissioning Plan.
Refer to attached Design Phase Commissioning Plan.
Submit the contract documentation requirements of ASHRAE 189.1 Section 10.3.1.2.3 Post-Occupancy Activities.
Refer to attached Design Phase Commissioning Plan.
Submit the contract documentation requirements of ASHRAE 189.1 Section 10.3.1.2.6 Documentation.
Submit the contract documentation requirements of ASHRAE 189.1 Section 10.3.1.2.2 Activities Prior to Building Occupancy.
Refer to attached Design Phase Commissioning Plan.
1.c Commissioning
31(Am-0003)
Guiding Principle Requirement Select Your Answer ASSESSOR USE ONLY Assessor Comments
2.a
2.a.1 Commercial & Multi-Family (pick from drop down list)
2.a.1.A Has the requirement been met?
2.a.1.A.1
Partially (pick from drop down list)
2.a.1.A.2
Not Applicable (pick from drop down list)
2.a.1.A.3 Yes (pick from drop down list)
2.a.1.B Has the requirement been met?
2.a.1.B.1
Not Applicable (pick from drop down list)
2.a.1.B.2
Not Applicable (pick from drop down list)
2.a.1.C Has the requirement been met?
(pick from drop down list) (pick from drop down list)
2.a.1.C.1 (pick from drop down list) (pick from drop down list)
2.a.1.C.2 Has the requirement been met?
2.a.1.C.2.i
( mark with X to select) (pick from drop down list)
2.a.1.C.2.ii
( mark with X to select) (pick from drop down list)
2.a.1.C.2.iii
( mark with X to select) (pick from drop down list)
2.a.1.C.2.iv
( mark with X to select) (pick from drop down list)
Has the requirement been met?
LCCA was performed for the air conditoning system. The most LCC efficient system is a system using a high efficiency4.87%
74.291
2.a.2 Has the requirement been met?
2.a.2.1 Yes (pick from drop down list)
Link 1:
Link 2:
2.a.3 Has the requirement been met?
2.a.3.1 Not Applicable (pick from drop down list)
2.b
2.b.1 Has the requirement been met?
2.b.1.1
Not Applicable (pick from drop down list)
UFC 1-200-02, Paragraph 2-3.1.1 Commercial and Multi-Family High-Rise Residential Buildings - OPTION A
Building Type - Select the building type most applicable to your project. Then complete only the appropriate requirement (Option) below.
Item # Enter Required Documentation & Comments
2 OPTIMIZE ENERGY PERFORMANCE
Energy Efficiency
Submit energy model showing the proposed building model to achieve at least 30% - less if LCCE - energy consumption reduction from ASHRAE 90.1 baseline.
Base energy consumptions was 163,164 kWh. Proposed consumption is 155,218 kWh for a 4.87% reduction. Without PV, it's not
Determine energy consumption levels for ASHRAE Baseline Building and proposed building alternatives.
Base energy consumptions was 163,164 kWh. Proposed consumption is 155,218 kWh for a 4.87%
UFC 1-200-02, Paragraph 2-3.1.2 Low-Rise Residential Buildings - OPTION B Meet the requirements of International Energy Conservation Code (IECC).
Meet the requirements of ASHRAE 90.1 Energy Standard for Buildings Except Low-Rise Residential Buildings.
Base energy consumptions was 163,164 kWh. Proposed consumption is 155,218 kWh for a 4.87% red ction Witho t PV it's not
For all other renovations, choose from one of the following four (4) options by marking an X in the pink cell:
i) Reduce measured building energy use by at least 30%, below FY 2003 energy use baseline.
Not applicable. New Construction.
Tracking 1 What is the current energy consumption reduction percentage?
Tracking 2 Energy Use Intensity (EUI) (kBTU/Sq. Ft./Year per building)
Enter LCCA and tracking data below, regardless of OPTION selected above.
Life-Cycle
Cost Analysis
What was the finding of the Life-Cycle Cost Analysis
(LCCA)?
Renewable and Clean Energy
Provide commercially available, off-the-shelf products that use no more than 1 watt in standby mode.
Appliances are not being furnished under this project.
COMPLETE EACH REQUIREMENT BELOW.
UFC 1-200-02, Paragraph 2-3.1.4 Energy Efficient Products Select energy consuming products and equipment with Energy Star or FEMP designation.
Water heaters are required to be Energy Star compliant (refer to Spec Section 22 00 00, Section 2.11.1).
Appliances are not in contract.
UFC 1-200-02, Paragraph 2-3.2: On-Site Renewable Energy Complete LCCA, both specific requirements, and tracking fields 1 - 4 (as applicable).
NAVFAC only: In addition to above, complete tracking field 5.
Submit Life Cycle Cost Analysis for on-site renewable energy (minimum quantity per ASHRAE 189.1 Section 7.4.1.1).
Rooftop PV and/or hot water systems were not feasible due to first-cost budget constraints.
iv) If none of the above reductions are LCCE, design to achieve an energy consumption level at the highest level of energy efficiency that is LCCE.
Not applicable. New Construction.
2 OPTIMIZE ENERGY PERFORMANCE
2.a Energy Efficiency
2.b Renewable and Clean Energy http://www.energystar.gov https://energy.gov/eere/femp/federal�energy�management�program
UFC 1-200-02, Paragraph 2-3.1.5 Standby Powered Devices
ii) Reduce measured building energy use by at least 20% below FY 2015 energy use baseline.
Not applicable. New Construction.
iii) Reduce modeled energy use (from all sources including renewable energy) by 20% compared to the ASHRAE 90.1 baseline building design.
Not applicable. New Construction.
Submit energy model showing the proposed building alternatives to achieve at least 30% - less if LCCE -energy consumption reduction from IECC baseline (Section 405, Simulated Performance Alternative).
UFC 1-200-02, Paragraph 2-3.1.3 Renovations - OPTION C Renovation Type - Will this renovation replace everything above the foundation?
Not applicable. New Construction.
If replacing everything above the foundation:
Apply either UFC 2-3.1.1 or 2-3.1.2 as applicable.
Not applicable. New Construction.
32(Am-0003)
2.b.1.2 Not Applicable (pick from drop down list)
No LCCA performed because first-cost budget constraints precluded PV and/or solar hot water0%
Not applicable
2.b.2 Has the requirement been met?
2.b.2.1 Not Applicable (pick from drop down list)
Not applicable
Not applicable
2.c
2.c.1 Has the requirement been met?
2.c.1.1 Yes (pick from drop down list)
2.c.1.2 Not Applicable (pick from drop down list)
2.c.1.3 Not Applicable (pick from drop down list)
2.c.1.4 Yes (pick from drop down list)
2.c.1.5 Yes (pick from drop down list)
DOD GPC NC Survey V1.2 © 2015-2017 GREEN BUILDING INITIATIVE, INC. ALL RIGHTS RESERVED.
Life-Cycle Cost
Analysis
What was the finding of the Life-Cycle Cost Analysis
(LCCA)?
Tracking 3 What is the system's total capacity for renewable thermal energy?
Tracking 4 List renewable energy technology
Tracking 1 What percentage of energy will come from the renewable energy system(s)?
Tracking 2 What is the system's total capacity for renewable electric energy?
Life-Cycle Cost
Analysis
What was the finding of the Life-Cycle Cost Analysis
(LCCA)?
Tracking 1 What percentage of the hot water demand is being met through the installation of solar hot water heaters?
Tracking 5 Navy only: What is the Installation-level solution to renewable energy systems for this project?
UFC 1-200-02, Paragraph 2-3.2.1 Solar Domestic Hot Water (SDHW) Purchase and install solar domestic hot water system where life cycle cost effective.
Solar hot water heating was not provided due to first-cost budget constraints.
Submit documentation of utility meters for all other sources at each building, connected to the base-wide monitoring system.
Sheet M-802
Metering
UFC 1-200-02, Paragraph 2-3.4 Metering Requirements 2.c.1.1 - 3: Choose "Yes" for each utility available at the project site, and "Not applicable" for utilities not available.
Requirements 2.c.1.4 - 5: Select "Not applicable if there is no centralized system.
Is electricity metered at the building level? Sheet M-802
Is natural gas metered at the building level?
Submit documentation for on-site renewable energy system(s).
2.c Metering
Is steam metered at the building level?
Submit documentation of electric meter at each building connected to base-wide monitoring system.
Sheet M-802
33(Am-0003)
Guiding Principle Requirement Select Your Answer ASSESSOR USE ONLY Assessor Comments
3.a 3.a.1 Has the requirement been met?
3.a.1.1
Yes (pick from drop down list)
3.a.1.2 Yes (pick from drop down list)
3.a.1.3 Not Applicable (pick from drop down list)
Not applicable
Not applicable
3.a.2 Has the requirement been met?
3.a.2.1
Yes (pick from drop down list)
3.b
3.b.1 Has the requirement been met?
3.b.1.1 Yes (pick from drop down list)
3.b.1.2
Not Applicable (pick from drop down list)
3.b.1.3
Not Applicable (pick from drop down list)
Not applicable.
3.b.2
3.b.2.1 Not Applicable (pick from drop down list)
3.c 3.c.1 Has the requirement been met?
3.c.1.1
Yes (pick from drop down list)
3.d
3.d.1 Has the requirement been met?
3.d.1.1 Not Applicable (pick from drop down list)
3.d.1.2
Not Applicable (pick from drop down list)
3.d.1.3 Not Applicable (pick from drop down list)
DOD GPC NC Survey V1.2 © 2015-2017 GREEN BUILDING INITIATIVE, INC. ALL RIGHTS RESERVED.
Are the requirements of UFC 3-210-10 Low Impact Development applicable to this project?
Although the site meets the criteria in paragraph 1-4 of UFC 3-10-10, application of full LID principles is technically infeasible per Paragraph 2Submit documentation (see ToolTip, all documentation is required) to validate the as-built LID-integrated management practices meet the design requirements, per UFC 3-210-10 paragraph 2-2.4.
This is a design submission.
Construction team will coordinate the post construction documentation.
For NAVFAC only, does the project require NAVY LID policy?
Life-Cycle Cost
Analysis
What was the finding of the Life-Cycle Cost…