P-502_-_PLUMBING_DETAILS_Amend_001.pdf
PDF 146 KB Posted
- Attached to
- C-17 Corrosion Control and Fuel Cell Hangar
- Solicitation number
- W91242-18-B-0891
About this file
P-502
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRONIC
DEMAND
DRAIN VALVE
(TYP)
FLEXIBLE
CONNECTOR (TYP)
BALL
VALVE
(TYP)
500 GALLON VERTICAL
WET AIR RECEIVER
OIL INJECTED, VARIABLE SPEED,
AIR COOLED COMPRESSOR WITH
INTEGRAL DRYER 40 HP/185 CFM,
460 V (3 PH), 60 Hz
PRESSURE GAUGE
(TYPICAL)
SAFETY RELIEF
VALVE SET AT 150
PSI
200 GALLON VERTICAL
REMOTE AIR RECEIVER
SAFETY RELIEF VALVE
SET AT 150 PSI
3" COMPRESSED AIR TO CA
OUTLETS.
PORTABLE AIR
COMPRESSOR CONNECTOR
2" PORTABLE
AIR
COMPRESSOR
CONNECTION
INLET COALESCING
FILTERS (TYP)
HEATLESS REGENERATIVE
DRYER, MOUNTED ON
BREATHING AIR SYSTEM
SKID
HIGH EFFICIENCY
WATERSEPARATOR (TYP)
OUTLET DUST FILTER
(TYP)
TO BREATHING
AIR OUTLETS
3" BA
185 SCFM1 1/2" BA
2" BA
DUAL STAGE CARBON FIBER (TYP.)
2" 2" 2"
2"
2" BA
3"
REQUIRED TO HAVE HMI IN EACH
BOOTH CONTROL ROOM TO
OVERRIDE CA SHUT DOWN WHEN BA
PRESSURE IS DOWN AND PEOPLE
HAVE SAFELY EXITED THE BOOTHS.
PT
PRESSURE TRANSMITTER FOR
LOW ALARM AND LOW-LOW
LEVEL ALARM FUNCTIONS.
M
CONTROL VALVE TO CLOSE
WHEN PRESSURE DROPS
BELOW 75 PSIG (LOW-LOW
LEVEL) IN THE BREATHING
AIR SYSTEM.
AC-1 AC-2
CAR-1
BAS
BAS
BAP-1
CAR-2
3"
OIL INJECTED, VARIABLE SPEED,
AIR COOLED COMPRESSOR WITH
INTEGRAL DRYER 40 HP/185 CFM,
460 V (3 PH), 60 Hz
2"
4" HIGH HOUSEKEEPING PAD WITH 6"
CLEARNCE. COORDINATE PLACEMENT
WITH EQUIPMENT INSTALLED ON SITE
1 1
TYPE 1: STANDARD 1" CA DROP
TYPE 2: STANDARD 1" CA DROP FOR NON-LUBRICATED
AIR AND EQUIPMENT (FOR BA DROPS)
TYPE 3: SPARE DROP
12" DIRT LEG
REGULATOR/GAUGE
AIR LUBRICATOR
MANUAL DRAIN VALVE
12" DIRT LEG
TYP. PIPE SUPPORT
TO WALL OR
STRUCTURE
3/4" x 1/2"
CONCENTRIC
REDUCER
DRAIN VALVE
1" AIR DROP
BALL VALVE
QUICK COUPLER
CONNECTOR SIZE PER
SPEC. @ 48". SEE
ABOVE FOR PLAN VIEW
OPTIONAL HARD PIPE TO
PNEUMATIC EQUIPEMENT
AS REQUIRED
REGULATOR/GAUGE
ELEVATION
AIR FILTER
ELEVATION
TYPE 2 (BA)
PLAN
1" AIR DROP
BALL VALVE
TYPE 1 (CA)
AIR FILTER WALL
ELEVATION
MANUAL DRAIN
VALVE
BALL VALVE
12" DIRT LEG
1" AIR DROP
TYPE 3 (FUTURE)
NOTE: CONTRACTOR TO CONSULT OWNER'S
REPRESENTATIVE INCLUDING HANGAR USER
TECHNICAL PERSONNEL AND RECEIVE WRITTEN
AND APPROVED LIST DEFINING TYPE OF OUTLET
TO BE USED AT EACH LOCATION.
QUICK COUPLER
CONNECTOR SIZE PER
SPEC. @ 48" AFF
OPTIONAL HARD PIPE TO
PNEUMATIC EQUIPEMENT
AS REQUIRED
TYP. PIPE SUPPORT TO
WALL OR STRUCTURE
3/4" x 1/2"
CONCENTRIC
REDUCER
TYP. PIPE SUPPORT
TO WALL OR
STRUCTURE
3/4" x 1/2"
CONCENTRIC
REDUCER
3/4" PIPE CAP @ 48" AFF
3/4" 45° ELBOW
3/4" NIPPLE
3/4" BALL VALVE
AUTOMATIC MOISTURE
REMOVAL TRAP WITH
BOWL GUARD, PIPE TO
NEAREST HUB DRAIN (HD-1) OR
FLOOR DRAIN (FD-1).
COMPRESSED AIR MAIN
FINISHED FLOOR
1/2" STAY-OPEN BALL
VALVE
PUSH FLAG HANDLE
11/4" TEPID
WATER
STAINLESS
STEEL BOWL
PULL ROD
SHOWER HEAD
1" (STAY OPEN) BALL VALVE
GLOBE AND ELECTRIC HORN
MOUNT ON WALL AT 8'-6"± ABOVE
FINISHED FLOOR, REFERENCE
PLANS FOR LOCATIONS
THERMOSTATIC MIXING VALVE
REFERENCE DRAWING P-401
FOR CONTINUATION
1" CW
0°
1" HW
MV
IAINNFCOQUEIAEENTSCI
G E
O G
R A
PH
I AE PENE T
R A
M U
S
A I
R
N A T I O N A L
G
U A
R D
C I
V
I L
E N G I N E E R
I N
G
FJRP
159062
145TH AIRLIFT WING
NORTH CAROLINA AIR NATIONAL GUARD
CHARLOTTE-DOUGLAS IAP, NORTH CAROLINA
SCALE
DESIGNED BY
REVIEWED BY
DATE
AE PROJ. NO.
DRAWN BY
SHEET
PROJECT NO.
NCANG CIVIL ENGINEERING
REVISIONS
INITIALDESCRIPTIONDATEREV
CHARLOTTE-DOUGLAS IAP CHARLOTTE, NORTH CAROLINA
F6W71900
C-17 CORROSION CONTROL & FUEL CELL HANGAR
54321
D C
B A
08/17/2018As indicated
/3
/2
:5
:3
P
M B
IM
/U
S
N o rt h C a ro lin a A ir N a ti o n a l G u a rd
/N C
A N
G
C
H a n g a r
P L
U M
B
V
.r v t
P-502
J. STAMPER
N. MITCHELL
N. MITCHELL
PLUMBING
C-17 HANGAR
PLUMBING DETAILS
NTSC1
COMPRESSED AIR PIPING DIAGRAM
SCHEMATIC
NTSB2
COMPRESSED AIR OUTLET DETAIL
NTSB1
AUTOMATIC COMPRESSED AIR DRAIN DETAIL NOT TO SCALEB4
EMERGENCY EYEWASH & SHOWER
1 10/4/2018 AMENDMENT 001 JJS
| NCANG - C17 Hangar - PLUMB_ V17 |
| P-502 - PLUMBING DETAILS |
File details come from the government source that posted it.