M
T
TT
T
X
M M
RETURN
AIR
F
DP
SUPPLY FAN
SUPPLY
AIR
D
X
WALL MOIUNTED
THERMOSTAT
M
RELIEF
AIR
OUTDOOR
AIR
N.C.
N.C.
F
PDI
DP
SS CS
FROM
FACP
CM
SUPPLY FAN
TS
S
TO
FACP
TS
TO NEXT AGC
XX
FROM PREVIOUS AGC
UNIT MANUFACTURER'S FACTORY INSTALLED CONTROLLER
RETURN
AIR
SUPPLY
AIR
M
CD
CD
D
X
ED
SS CS
DI
SS CS
E
H
ED CI
TS
F
PDI
DP
DI
ENERGY RECOVERY
WHEEL
EXHAUST
FAN
PART OF AAC/ASC
TO NEXT AAC/ASC
XX
FROM PREVIOUS AAC/ASC
SS
DO AI
TS
160A
AI
TS
160B
TS
OA
AI
HS
OA
AI DI
SW
PART OF AAC/ASC
TO NEXT AAC/ASC
XX
FROM PREVIOUS AAC/ASC
AX
DI
WATER
METER
ELECTRIC
METER
AX
DI
GAS
METER
WALL MOUNTED
THERMOSTAT
ELECTRIC
UNIT HEATER
OUTDOOR
AIR
INTAKE
N.C.
M
N.C.
EXHAUST FAN
EXHAUST
AIR
M
CD
DI
CD
DI
WALL MOUNTED
THERMOSTAT
N.C.
EXHAUST FAN
EXHAUST
AIR
M
CD
DI
WALL MOUNTED
THERMOSTAT
CV
PART OF AAC/ASC
TO NEXT AAC/ASC
XX
FROM PREVIOUS AAC/ASC
TO BREATHING
AIR OUTLETS
M
BA
AO
PT
COMPRESSED AIR
TO CA OUTLETS
CA
AI
KEYNOTES
1 MOTOR STARTER/FAN DISCONNECT..
2 INTERLOCK FAN WITH FIRE ALARM SYSTEM THROUGH
CONTROL MODULE (CM) TO STOP AHU WHEN ANY DUCT
SMOKE DETECTOR ASSOCIATED WITH FAN SENSES
PARTICLES OF COMBUSTION. THIS INTERLOCK SHALL
BE HARD WIRED AND NOT PERFORMED THROUGH BAS.
CM AND DUCT SMOKE DETECTOR FURNISHED AND
INSTALLED UNDER DIVISION 28.
3 PROVIDE INTERLOCK WIRING BETWEEN FAN AND
ASSOCIATED ISOLATION DAMPER. WHEN FAN IS
COMMANDED TO START IN EITHER HAND OR AUTO MODE,
DAMPER SHALL OPEN. ONCE DAMPER IS PROVEN OPEN
BY ASSOCIATED END SWITCH, FAN SHALL START. DAMPER
SHALL CLOSE WHEN THE FAN STOPS.
GENERAL NOTES
A. REFER TO SHEET M-001 FOR SYMBOLS AND ABBREVIATIONS.
B. SEE DIVISION 23, DIRECT DIGITAL CONTROL FOR HVAC,
FOR SEQUENCE OF OPERATION.
C. DUCT SMOKE DETECTORS AND CONTROL MODULES
PROVIDED AND CONNECTED TO FIRE ALARM SYSTEM BY
DIVISION 28. SEE DIVISION 28, FIRE ALARM, FOR
ADDITIONAL INFORMATION.
ALL DESTRATIFICATION FANS IN HANGAR SHALL BE
CONTROLLED BY A SINGLE COMMAND FROM BAS.
DESTRATIFICATION FANS WILL BE POWERED BY A SINGLE
CIRCUIT. COORDINATE WITH DIV 26 AND PROVIDE
NECESSARY CONTROL DEVICES AND WIRING FOR FAN
CONTROL AS NECESSARY.
8 PROVIDE SPACE TEMPERATURE SENSORS IN HANGAR
WHERE INDICATED ON FLOOR PLANS. INSTALL ONE
SENSOR 5 FEET ABOVE FINISHED FLOOR AND THE OTHER
SENSOR 40 FEET ABOVE FINISHED FLOOR.
9 ENERGY RECOVERY UNIT, DOAS-01, WILL BE PROVIDED
WITH UNIT MANUFACTURER'S PACKAGED CONTROLS
INCLUDING BACNET-COMPATIBLE CONTROLLER,
SENSORS AND OTHER CONTROL DEVICES. CONTROLLER
SHALL BE CONNECTED TO BAS NETWORK USING BACNET
MS/TP AND INTEGRATED INTO BAS FOR REMOTE
CONTROL AND MONITORING. SEE LIST OF CONTROL AND
MONITORING POINTS IN BAS POINT FUNCTION SCHEDULE.
CONNECT PULSE OUTPUT SIGNAL FROM GAS AND WATER
METERS TO BAS.
ELECTRIC METER SHALL BE CONNECTED TO BAS VIA
NETWORK INTERFACE USING BACNET. MAP OVER AND
INTEGRATE METERING INFORMATION INTO BAS.
TYPICAL AIR DISTRIBUTION EMERGENCY SHUT DOWN
SWITCHES. INSTALL EACH SWITCH WITH HINGED CLEAR
COVER, WARNING SIGN AND TAG WHERE INDICATED ON
FLOOR PLANS. WHEN SWITCH IS ACTIVATED, ALL AIR SIDE
MECHANICAL EQUIPMENT CONTROLLED BY BAS SHALL BE
SHUT DOWN.
NTSB3
SPLIT SYSTEM HEAT PUMP - CONTROL DIAGRAM
IDU-01, IDU-02 AND IDU-03
NTSC1
ENERGY RECOVERY UNIT - CONTORL DIAGRAM
DOAS-01 NTSC3
DESTRATIFICATION FANS - CONTORL DIAGRAM
TYPICAL
NTSB2
MISCELLANEOUS POINTS
NTSA2
PUMP HOUSE - VENTILATION FAN
EF-01P NTSA3
PUMP HOUSE - ELECTRIC UNIT HEATER
UH-01 AND UH-02NTSA1
EXHAUST FAN - CONTROL DIAGRAM
EF-13
NTSB1
TYPICAL BREATHING AIR/COMPRESSED AIR PRESSURE CONTROL
IAINNFCOQUEIAEENTSCI
G E
O G
R A
PH
I AE PENE T
R A
M U
S
A I
R
N A T I O N A L
G
U A
R D
C I
V
I L
E N G I N E E R
I N
G
FJRP
159062
145TH AIRLIFT WING
NORTH CAROLINA AIR NATIONAL GUARD
CHARLOTTE-DOUGLAS IAP, NORTH CAROLINA
SCALE
DESIGNED BY
REVIEWED BY
DATE
AE PROJ. NO.
DRAWN BY
SHEET
PROJECT NO.
NCANG CIVIL ENGINEERING
REVISIONS
INITIALDESCRIPTIONDATEREV
CHARLOTTE-DOUGLAS IAP CHARLOTTE, NORTH CAROLINA
F6W71900
C-17 CORROSION CONTROL & FUEL CELL HANGAR
54321
D C
B A
08/17/2018
/3
/2
:5
:4
P
M B
IM
/U
S
N o rt h C a ro lin a
A ir N a ti o n a l G u a rd /N
C A
N G
C
H a n g a r
M
E C
H V
.r v t
M-702
J. STAMPER
S. KOWALCZYK
S. KOWALCZYK
MECHANICAL
HVAC
CONTROL DIAGRAMS
1 10/4/2018 AMENDMENT 001 JJS
| NCANG - C17 Hangar - MECH_V17 |
| M-702 - HVAC CONTROL DIAGRAMS |