Text version
C-17 CORROSION
CONTROL & FUEL CELL
HANGAR
A. SHEET ILLUSTRATES EXISTING AND PROPOSED WATER MAINS AND FIRE
HYDRANTS LOCATIONS, FOR REFERENCE ONLY. THE HYDRANT
IDENTIFICATION NUMBERS ARE SHOWN. REFER TO CIVIL PLANS FOR
ADDITIONAL INFORMATION.
GENERAL NOTES
FLOOR PLAN KEYED NOTES
IAINNFCOQUEIAEENTSCI
GEOGR APH I A E PENE TR AM
US
A I R
N A T I ON A L
GU AR
D
C I V I L
E N G I N E E R I N G
N
FJRP
159062
145TH AIRLIFT WING
NORTH CAROLINA AIR NATIONAL GUARD
CHARLOTTE-DOUGLAS IAP, NORTH CAROLINA
SCALE
DESIGNED BY
REVIEWED BY
DATE
AE PROJ. NO.
DRAWN BY
SHEET
PROJECT NO.
NCANG CIVIL ENGINEERING
REVISIONS
INITIALDESCRIPTIONDATEREV
CHARLOTTE-DOUGLAS IAP CHARLOTTE, NORTH CAROLINA
F6W71900
C-17 CORROSION CONTROL & FUEL CELL HANGAR
54321
D C
B A
08/17/2018As indicated
/2
/2
4:
:0
PM
BI
M
U
S
- N or th
C ar ol in a Ai r N at io na l G ua rd /N
C A
N G
C
H an ga r - F
IR
E_
V
.rv t
FX-100
J.BEALS
M.OWENS
J.McLAUGHLIN
FIRE SUPPRESSION
OVERALL SITE PLAN
PROPOSED HYDRANT
3/64" = 1'-0"A1 FIRE SUPPRESSION OVERALL SITE PLAN
INCOMING FIRE WATER MAIN
FROM PUMP HOUSE AND
INCOMING DOMESTIC WATER
PUMP HOUSE
EXISTING WATER
TANK
GAUGE HYDRANT
FLOW HYDRANT
FUTURE CONNECTION TO
HANGAR 51
INCOMING FIRE WATER MAIN
FROM PUMP HOUSE AND
INCOMING DOMESTIC WATER
1 THE PROJECT SCOPE INCLUDES SUPPLYING THE NEW FIRE SUPPRESSION
SYSTEMS FROM THE EXISTING 280,000 GALLON WATER STORAGE TANK.
PERFORM THE FOLLOWING REPAIRS/ENHANCEMENTS TO THE EXISTING
TANK PRIOR TO CONNECTING THE NEW FIRE PUMP:
• INSTALL THERMOMETER AT GROUND LEVEL.
• INSTALL PRESSURE GAUGE AT GROUND LEVEL THAT READS FEET AND
PSI.
• INSTALL A FROST-PROOF DRAIN WITH LOCKING DEVICE.
• CLEAN TANK NAME PLATE AND REINSTALL IT.
• PROVIDE STAINLESS STEEL BOLTS FOR MANWAYS.
• CLEAN AND LUBRICATE ALL MOVING PARTS OF THE LIQUID LEVEL
INDICATOR AND PROVIDE GAUGE THAT READS IN FEET AND PSI.
• PROVIDE AN OSHA AND AWWA APPROVED SHELL LADDER WITH A
CABLE TYPE LADDER SAFETY CLIMB DEVICE AND POST A FALL
PROTECTION REQUIRED SIGN.
• EXTEND THE OVERFLOW DOWN THE EXTERIOR TO GRADE WITH
PROPER STANDOFFS, AND A FLAPPER VALVE AND SCREEN.
• EXTEND THE EXISTING HANDRAIL SYSTEM AROUND THE ROOF OF THE
TANK AND COMPLETE WITH TOEBOARD AND INTERMEDIATE RAILL.
• PROVIDE A SECONDARY 36" ROOF MANWAY WITH CONFIED SPACE
ENTRY SIGN AND EXTERIOR PLATFORM.
• PROVIDE NEW LOCK FOR EXISTING MANWAY.
• REPLACE THE EXISTING ROOF VENT WITH A VACUUM-PRESSURE,
FROST PROOF VENT AND SCREEN.
• CLEAN AND PAINT EXISTING INTERIOR LADDER.
1 10/4/2018 REBID MFO