CONCRETE CURB AND GUTTER DETAIL
ADA ACCESSIBLE CURB RAMP DETAIL
EXISTING SURFACE
COURSE TO BE MILLED
1.5" AND OVERLAY NEW
SURFACE COURSE
CONTRACTOR SHALL
SAW-CUT EDGE AND
MAKE SURE NO WATER
IS TRAPPED
EXISTING SURFACE
COURSE
EXISTING PAVEMENT
12" MIN.
PROP. BIT. SURFACE
COURSE
PROP. BASE COURSE
EXISTING INTERMEDIATE
ASPHALT CONCRETE
EXISTING BASE - ASPHALT
CONCRETE
MATCH EXISTING CROSS SLOPE
PAVEMENT OVERLAY DETAIL
IAINNFCOQUEIAEENTSCI
GEOGRAPH I AE PENE TR AM
US
A I R
N A T I O N A L
GU AR
D
C I V I L
E N G I N E E R I N G
FJRP
159062
145TH AIRLIFT WING
NORTH CAROLINA AIR NATIONAL GUARD
CHARLOTTE-DOUGLAS IAP, NORTH CAROLINA
SCALE
DESIGNED BY
REVIEWED BY
DATE
AE PROJ. NO.
DRAWN BY
SHEET
PROJECT NO.
NCANG CIVIL ENGINEERING
REVISIONS
INITIALDESCRIPTIONDATEREV
CHARLOTTE-DOUGLAS IAP CHARLOTTE, NORTH CAROLINA
F6W71900
C-17 CORROSION CONTROL & FUEL CELL HANGAR
54321
B
/1
6/
:4 9:
P
M
:\p w or ki ng
\g bn a\ cr ow le ra \d
1\
-5
.d g
08/17/2018 C-502
CIVIL
CONSTRUCTION DETAILS
A. WILLIAMSON
A. WILLIAMSON
D. DEIBLE
NTS
1. REMOVE A SPADE FULL OF SOIL (APPROXIMATELY 2" DEEP) FROM WHERE THE BASE POST WILL BE LOCATED.
2. DRIVE THE BASE POST IN THE CENTER OF THE HOLE JUST CREATED, TO WITHIN 4" OF GRADE LEVEL.
3. PLACE ONE BOLT AND FLAT WASHER IN THE TOP HOLE OF THE BASE POST. (IF THE TOP HOLE ON THE BASE POST, OR
THE BOLT TO 20 FT. LBS. OF TORQUE. REPEAT THIS PROCESS FOR THE LOWER BOLT.
4. NEST THE TOP POST OVER THE PROTRUDING BOLTS ON THE BASE POST. PLACE A SELF-LOCKING FLANGE NUT ON EACH
BOLT AND TIGHTEN SECURELY TO 20 FT. LBS. OF TORQUE.
5. REPLACE SOIL REMOVED IN STEP 1.
THE BOTTOM HOLE ON THE TOP POST IS LESS THAN 3/4" FROM END OF THE POST USE THE SECOND AND SIXTH HOLES.)
6. IN TRIPLE POST INSTALLATIONS USING 4 LB./FT. POSTS IN WEAK SOIL, A 1'-0"W x 6"H SOIL PLATE IS REQUIRED.
2. THE SILVER ANODIZED BAR SPACER IS FOR USE WITH 2, 2.5 AND 2.75 LB./FT. RIB-BAK POST GRADE SP-80 ONLY.
4. INSTALLATION PROCEDURES SHALL BE IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.
3. THE GOLD ANODIZED BAR SPACER IS FOR USE WITH 3 AND 4 LB./FT. RIB-BAK POST GRADE SP-80 ONLY.
TOP VIEW
STUB
DIRECTION
RECOMMENDED TORQUE VALUES:
BOLTS TO THREADED BAR SPACER
SELF-LOCKING FLANGE NUT TO BOLTS
20 FT. LBS.
20 FT. LBS.
HEIGHT
OF TRAFFIC
3/8" 1"
WITH THE THREADED BAR SPACER ALIGNED WITH TOP HOLE ON THE BACK SIDE OF THE BASE POST, SECURELY TIGHTEN
MAX.
Ø HOLE
O.C.
MAX.7'-0"
7'-0" MIN. (RURAL AREAS)
MIN. (URBAN AREAS)5'-0"
3'-0"
(BRACE NO LONGER THAN
USE BRACING FOR SIGN WIDTH
CURB
ROADWAY
(1) 4 LB./FT.
BASE POST TO BE SAME
WEIGHT PER FOOT AS
TOP POST (4'-6" LENGTH)
RIB-BAK U-CHANNEL SIGN POST
4"
(SEE DETAIL "A")
1. SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTION OF THE SPECIFICATIONS.
WIDTH OF SIGN)
INSTALLATION PROCEDURE:
FRONT VIEW
DETAIL "A"
RIGHT SIDE VIEW
SIGN MOUNTING DETAIL
CURB TRANSITION
XX XX XX XX
EXPANSION JOINT
1" DIA. X 1'-6" LONG SMOOTH
DOWEL @ 12" O.C. (3 MIN. @ MIDDEPTH)
BUILDING FOUNDATION
REFER TO STRUCTURAL
PLANS FOR DETAILS
COMPACTED SUBGRADE
SIDEWALK
LEAN CONCRETE FILL
BELOW SIDEWALK AT
BUILDING DOOR LOCATIONS.
EXTEND 2'-0" BEYOND
ENDGE OF DOOR AT EACH
SIDE.
FLOOR SLAB
CONCRETE LANDING DETAIL
4'-0"
42" MIN.
8"
1'-0"
\A1;1'-0"10" AGGREGATE
BASE COURSE
12.5" RIGID CONCRETE PAVEMENT
20" MIN.
OVERLAP
3"
6"
MIN.
6" DIA UNDERDRAIN
PIPE
AASHTO M-288, CL-2
FILTRATION GEOTEXTILE
DRAINAGE COURSE
NOTES:
1. FOR CONCRETE PAVEMENTS LOCATE THE PIPE IN VICINITY OF A JOINT.
2. SEE C501 FOR PAVEMENT SECTION DETAILS.
SUBGRADE
PAVEMENT UNDERDRAIN
N.T.S.
10" AGGREGATE
DRAINAGE COURSE
XX XX XX XX
1" DIA. X 1'-6" LONG SMOOTH
DOWEL @ 12" O.C. (3 MIN. @ MIDDEPTH)
BUILDING FOUNDATION
REFER TO STRUCTURAL
PLANS FOR DETAILS
COMPACTED SUBGRADE
CONCRETE SIDEWALK
LEAN CONCRETE FILL
BELOW SIDEWALK AT
BUILDING DOOR LOCATIONS.
EXTEND 2'-0" BEYOND
ENDGE OF DOOR AT EACH
SIDE.
FLOOR SLAB
7A
CONCRETE STOOP DETAIL
4'-0"
42" MIN.
8"
1'-0"
APRON
14"
1 AMENDMENT 003 RAC11/12/18
CS-100
Layout1
CS-101
Layout1
C-502
Layout1
U
E
UGE
UGEUGEUGE
2140720.02EM//PKF
736.90HVAC
803736.83HVAC
821736.39HVAC
822736.37HVAC
731.99HVAC
732.19HVAC
731.54HVAC
2809735.42HVAC
2819736.86HVAC
2820736.83HVAC
2436705.41HW1+7//CONC
2437705.47HW1//CONC 2438705.44HW1 RECT//CONC
873728.68INV//6" RCP
874728.71INV//6" RCP
726.42INV//6" RCP
922726.41INV//6" RCP
942730.37INV//12" D.IRON
1457726.81INV//6" RCP
1458726.70INV//6" RCP
2044725.44INV//6" RCP
2045725.58INV//6" RCP
2515702.98INV//RCP 18"
3851730.48MW
578734.37STEP1+7//METAL
736.09STEP1//METAL
580736.06STEP1 RECT//METAL
724.28STEP10+7//CONC
729.58STEP10//CONC
729.54STEP10 RECT//CONC
WWWWWW
W
UGEUGE
GAS
AS
W W W W W W W W W W W W W
W W W W W
N
TXF
LD
PED
HERCULES BLVD
{ASPHALT PAVEMENT}
H
R
LE
S
LV
{A
LT
V
T}
TX
F
BLDG
TX
BLDG 4
BLDG 66
BLDG 65
BLDG 62
BLDG 51
N:538785.20 E:1423259.74
Z:733.41
N:539157.21 E:1423934.77 Z:725.94
N:538908.87 E:1423506.88 Z:730.37
N:538727.23 E:1424021.29
Z:726.43
CONTROL PT 2
CONTROL PT 6
CONTROL PT 7
CONTROL PT 5
W W W
5589693.21HW1+7//CONC
5590693.20HW1//CONC
5591693.10HW1//CONC
5592693.09HW1 CLO//CONC
5264695.41INV//15" RCP
5567683.84INV//IN
5568683.91INV//IN
5569683.95INV//IN
5570683.40INV//IN
5593690.92INV//RCP 15"
5729685.91INV//15" CPP
5776684.74INV//15" CPP
15"RCP
{\Q15;C.MYRTLE}
YIELD SIGN
STREET SIGN
{\Q15;ASPHALT}
CONC. SIDEWALK
5' BRICK S
CREEN WA
LL{\Q15;12" RCP}CI 2408
DI 1113
{\Q 15;
12"
RC
P}
{\Q15;18" RCP}
{\Q15;1
2" DIP}
;12 " R
CP
CB 2326
TIMBER RET. WALL
15;
24"
RC
P}
DI
;S
HR
UB
BE
RY
{\Q15;GRAVEL}
C-17 CORROSION
CONTROL & FUEL CELL
HANGAR
EXISTING
HANGAR 51
SQUADRON
OPERATIONS
FACILITY
RIGID CONCRETE
PAVEMENT AIRCRAFT
APRON
EXISTING
HANGAR 4
WB-40INDOT 2013 (US)
(c) 2014 Transoft Solutions, Inc. All rights reserved.
B-
INDO
T 20 13 (U
S)
(c) 2014 T ransoft So lutions, In
c. All right s reserved
Aircraft TugCusto m(c) 2014 Transoft Solutions, Inc. All rig hts reserved.
ir c ft T u u s to m
(c) 20
14 Tr ansof t Solu tions, Inc. A ll righ ts res erved rwall rwall
AIR
PO
RT
DR
IVEHERCU
LES BL
VD
rwall
CONC. RETA
INING WALL
Payne Blvd n li s te d r iv e
Stairs
Payne Avenue
WING-TIP
CLEARANCE
45 1 7
LO
LOS
LOS LO
SLO
LOS LO
LOS LOS LOS LOS LOS LOS LOS
LOS LOS
S LOS LOS LOS
LOS LOS LOS
PUMP HOUSE
0 50 100 A1
OVERALL SITE LAYOUT PLAN
SHEET NOTES
LEGEND
CS-100
OVERALL SITE LAYOUT PLAN
R. CROWLEY
1" = 50'
BUILDING FOOTPRINT
RIGID CONCRETE AIRCRAFT APRON
RIGID CONCRETE PAVEMENT/SIDEWALK
HEAVY DUTY ASPHALT PAVEMENT
STANDARD DUTY ASPHALT PAVEMENT
GEOGR APH I A E PENE TR AM
G U AR
E N G I N E E R
I N
-1
1. ALL DIMENSIONS ARE TO FACE OF CURB, EDGE OF PAVEMENT, OR
CORNER OF FENCE, UNLESS NOTED OTHERWISE.
2. BUILDING COORDINATES ARE TO EXTERIOR CORNER OF BUILDING.
3. ALL DIMENSIONS ARE PERPENDICULAR TO ONE ANOTHER, UNLESS
NOTED OTHERWISE.
4. ALL PAVEMENT AND CONCRETE CURB & GUTTER SHALL MEET EXISTING IN
LINE AND AT GRADE.
1 AMENDMENT 003 RAC11/12/18
CS-100
Layout1
CS-101
Layout1
C-502
Layout1
0 30 60
SITE LAYOUT PLAN
KEY NOTES
STANDARD DUTY ASPHALT PAVEMENT. SEE DETAIL 6 ON SHEET C-501.
HEAVY DUTY ASPHALT PAVEMENT. SEE DETAIL 1 ON SHEET C-501.
CONCRETE SIDEWALK. SEE DETAIL 3 ON SHEET C-501.
RIGID CONCRETE PAVEMENT. SEE DETAIL 2 ON SHEET C-501.
RIGID CONCRETE AIRCRAFT APRON. SEE DETAIL 7 ON SHEET C-501.
SURFACE MOUNTED VEHICLE BARRIER PROVIDED BY THE
GOVERNMENT.
7 FT HIGH CHAIN LINK FENCE WITH 1' OUTRIGGER. SEE DETAIL 4 ON SHEET
C-501. [REFER TO SHEET NOTE 8.]
25' WIDE CANTILEVERED SLIDING GATE. SEE DETAIL 8 ON SHEET C-501.
[REFER TO SHEET NOTE 9.]
6" HIGH CONCRETE CURB & GUTTER. SEE DETAIL 1 ON SHEET C-502.
NOT USED
LEGEND
CS-101
SITE LAYOUT PLAN
1" = 30'
BUILDING FOOTPRINT
RIGID CONCRETE AIRCRAFT APRON
RIGID CONCRETE PAVEMENT/SIDEWALK
HEAVY DUTY ASPHALT PAVEMENT
STANDARD DUTY ASPHALT PAVEMENT
GEOGR APH I A E PENE TR
AM
G U AR
I N
-1
SHEET NOTES
1. ALL DIMENSIONS ARE TO FACE OF CURB, EDGE OF PAVEMENT, OR
CORNER OF FENCE, UNLESS NOTED OTHERWISE.
2. BUILDING COORDINATES ARE TO EXTERIOR CORNER OF BUILDING.
3. ALL DIMENSIONS ARE PERPENDICULAR TO ONE ANOTHER, UNLESS
NOTED OTHERWISE.
4. ALL PAVEMENT AND CONCRETE CURB & GUTTER SHALL MEET EXISTING IN
LINE AND AT GRADE.
5. ALL CURB RADII ARE 5 FEET, UNLESS NOTED OTHERWISE.
6. ALL CONCRETE SIDEWALKS SET AT 5 FEET IN WIDTH, UNLESS NOTED
OTHERWISE.
7. PROVIDE A CONCRETE LANDING IN ACCORDANCE WITH DETAIL 7 ON
SHEET C-502 AT ALL DOOR ENTRANCES. LANDING SHALL BE 5' BY 5',
UNLESS NOTED OTHERWISE.
8. OPTIONAL LINE ITEM: IN LIEU OF CHAIN LINK FENCE WITH 1' OUTRIGGER,
PROVIDE ORNAMENTAL FENCE MOUNTED ON CONCRETE KNEE WALL IN
ACCORDANCE WITH DETAILS 2 AND 3 ON SHEET C-504.
9. OPTIONAL LINE ITEM: IN LIEU OF CHAIN LINK SLIDING GATE, PROVIDE
ORNAMENTAL SLIDING GATE IN ACCORDANCE WITH DETAIL 1 ON SHEET
C-504.
11 STOP SIGN
NO PARKING SIGN. SIGNS SHALL BE SPACED AT 100 FEET ON
CENTER ALONG HERCULES BLVD.
13 NOT USED
BUILDING COORDINATE TABLE
ID DESCRIPTION NORTHING EASTING
A HANGAR SOUTHWEST BLDG CORNER 538,805.79 1,423,690.12
B HANGAR NORTHEAST BLDG CORNER 539,035.51 1,423,949.22
E PUMP HOUSE NORTHWEST CORNER 538,829.41 1,423,580.32
F PUMP HOUSE SOUTHEAST CORNER 538,820.59 1,423,628.92
14 ADA ACCESSIBLE CURB RAMP. REFER TO DETAIL 5 ON SHEET C502.
OPTIONAL LINE ITEM:
1. THE INSTALLATION OF A 7'-0" HIGH FENCE CONSISTING OF A
3'-0" HIGH CAST IN PLACE CONCRETE KNEE WALL WITH A 4'-0"
HIGH AT/FP COMPLIANT ORNAMENTAL FENCE ABOVE. SEE
DETAILS ON SHEET C-504.
2. THE 7'-0" HIGH CHAIN LINK FENCE SHALL BE PROVIDED AS
PART OF THE BASE BID. 1 AMENDMENT 003 RAC11/12/18
GRASSED SLOPE
STEPS
ASPHALT
LOT
18"
STD
C&
CONC SIDEWALK
LD
GA
BI
ON
BAS
KET
CONC DITCH
CONC
RAMP
RET W
ALL
LOT
MWELL
TW:705.14
TW:709.06
TW:712.75
TW:721.40
TW:726
.46
TW:716.60
TW:723
.54
TW:714.75
TW:704.54
5' CONC WALK
CONC WALK
CONC W
ALK
CROSSWALK
O
LK
LV
{A
LT
T}
CONTAINER
GRASS
4' CO
NC W
ALK
BLDG 52
DIESEL TANK
BLDG 66
BLDG 65
BLDG 51
732.27
730.91
728.35
728.40
730.01
730.02
JERSEY BARRIERS (TYP)
N:539157.21 E:1423934.77 Z:725.94
N:538908.87 E:1423506.88 Z:730.37
N:538727.23 E:1424021.29
Z:726.43
CONTROL PT 6
CONTROL PT 7
CONTROL PT 5
9 72
8 72
6 72
TC:721.77
TC:726.96
TC:727.22
TC:7
27.17
TC
:72
6.9
:7
.0
.1
.4
.6
.8
.6
.1
.7
.4
.2
.3
TC:727.11
TC:716.66
TC:717.14
TC:718.88
TC:720.00
TC:720.94
TC:722.45
TC:722.96
TC:723.56
TC:724.82
TC:725.23
TC:725.62
TC:725.24
TW:724.89
TW:723.66
TW:718.86
TW:714.71
TW:701.67
TW:711.77
TW:719.97
15"RCP
5 69
:70
2.3
1.3
0.5
:6
0.2
1.3
TC:696.41
TC:697.01
TC:697.69
TC:698.71
TC:701.18
TC:700.39
TC:701.23
TC:701.12
TC:701.34
TC:701.48
TC:696.63
TC:697.70
TC:694.58
TC:692.25
TC:689.56
TC:687.20
TC:685.85
EP:685.54
EP:686.61
EP:687.53
EP:690.08
EP:692.49
EP:694.61
EP:696.56
EP:697.43
BC:701.07
EC:702.36
EP:703.66
EP:703.00
BC:703.42
BC:702.94
BC:703.78
BC:7
02.9
C-17 CORROSION
CONTROL & FUEL CELL
HANGAR
112.3'
.1'
'TERMINATE
CURB & GUTTER
AND FENCE LINE
AT BLDG CORNER
R=40' Δ=104.4°
LC=73.1'
rw al l
70.9'
.2'
60'27.9'
1.5
3'8.7' 24 .5'
6'
5'
1.
2'
10'
10'
5' 43.6°46.4°
R=44' Δ=46.4°
LC=34.6'
.8
.8'
MEET EXISTING
SIDEWALK AND
CURB & GUTTER
IN LINE AND AT GRADE
REFER TO SHEET CS-401
'ENLARGED SITE LAYOUT PLAN'
45°
TERMINATE FENCE LINE
ASPHALT PAVEMENT TO MEET
EX. SIDEWALK IN LINE & AT
GRADE (TYP)
126.4'10'
234'
MEET EX. CONCRETE SIDEWALK AND
CURB & GUTTER IN LINE AND AT GRADE
TERMINATE FENCE LINE
PUMP
HOUSE
.9
TERMINATE
FENCE LINE
AT BLDG FACE
REFER TO SHEET CS-401
'ENLARGED SITE LAYOUT PLAN'
23.5'
CS-100
Layout1
CS-101
Layout1
C-502
Layout1
J
JJ
S SS
A. REFER TO SHEET E-001 FOR LEGEND, ABBREVIATIONS, AND NOTES.
B. REFER TO E700 SERIES DRAWINGS FOR PANELBOARD SCHEDULES.
C. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR EQUIPMENT
LOCATION.
D. REFER TO E-500 SERIES DRAWING FOR SUPPLEMENTAL DETAILS.
E. CONTRACTOR SHALL OFFSET OUTLET BOXES ON OPPOSITE SIDES OF
COMMON WALL TO PREVENT SOUND TRANSMISSION BETWEEN ADJOINING
ROOMS. BACK TO BACK BOXES SHALL NOT BE PERMITTED.
F. REFER TO E-600 SERIES DRAWINGS FOR SINGLE LINE DIAGRAMS. REFER
TO MECHANICAL EQUIPMENT SCHEDULES AND PANEL SCHEDULES FOR
ADDITIONAL ELECTRICAL REQUIREMENTS.
G. CONTRACTOR SHALL INSTALL ALL PANELS AND ELECTRICAL EQUIPMENT
TO MEET THE CLEARANCE REQUIREMENTS OF THE NEC SECTION NEC
110.26(A).
H. PROVIDE EXPANSION FITTINGS/COUPLINGS AT ALL ABOVE CEILING
CONDUITS RUNS AT EXPANSION JOINTS. REFER TO SPECIFICATIONS.
J. REFERENCE SHEET E-002 AREA CLASSIFICATION PLAN. ALL EQUIPMENT AND
WIRING WITHIN A HAZARDOUS (CLASSIFIED) LOCATION SHALL BE IN
ACCORDANCE WITH THE FOLLOWING: NEC ARTICLE 501 FOR CLASS 1, DIV 1
OR DIV 2 LOCATIONS AND GROUP CLASSIFICATIONS WHERE SPECIFIED; NEC
ARTICLE 502 FOR CLASS 2, DIV 1 OR DIV 2 LOCATIONS AND GROUP
CLASSIFICATIONS WHERE SPECIFIED.
GENERAL NOTES
RECEIVING AND
STAGING
H139
COMPOSITE
SHOP
H138
COMPOSITE
SHOP
H137
WOMEN
H133
STENCIL ROOM
H136
MEN
H131
CORRIDOR
H135
WOMEN SHOWER
/ LOCKERS
H134
MEN SHOWER /
LOCKERS
H132
SP SR1
WPG
G G
HR1 -1,9,10 9
HR1 -2,3,4 2
H1
HE.9
G.5
HC.8
HC.6
HC.4
HC.2
3.8
G.1 H.1
WPG WPG
SR1 -8
SR1 -11
GG
SR1 -14
SR1 -15
SR1 -17 17
GG
SR1 -20,21
21 20
SR1 -18
SR1 -1
SR1 -2
SP -1,3,5
SP -2,4,6
SP -7,9,11
EF-07
SR1 -23
14 SR1 -19
SR1 -16
HR2 -16,18,20
HR2 -9,11,13
HR2 -10,12,14
SR1 -22
CC2A
CC1A
MP2 -25,27,29
5 4
HR2 -5
HR2 -4
HR2 -6
PWO-3
HR1 -27
SR1 -26
SR1 -28
SR1 -30
HR2 -32
SR1 -27
MHP -10
MHP -11
SR2
SGB
25MP2 -13,15,17
VAV-2-02
VAV-2-04
VAV-2-05
VAV-2-03
SP -26
SP -24
SP -25
SP -22
PP2 -20
PP2 -22
PP2 -22
TYP
ELECTRICAL
ROOM
H167
HEF EQUIPMENT
H168
WORKSTAND /
EQUIPMENT
STORAGE
H165
STAIR 02
HS102
TR
H166
CORRIDOR
H169
WPG WPG WPG
ODU-01
ODU-02
IDU-01
m
CU-03
HR1 -11,12
HFA -1
HFA -6
HFA -4
HFA -2
HR1 -7,8,9
HR1 -4,5,6
HR1 -1,2,3
1HA
HB
HA.5
HA.1
H6
H5
H4
H3
H2
HFA -3
E-401 B1
E-401
WPG WPG
HR1 -13
EF-11
EF-06
EF-08
EF-01
MP1 -14,16,18
MP1 -7,9,11
MP1 -13,15,17
TR1 -5,7
PP1 -7,9
15 14
PP1 -24
CONTINUE
TO ODU-01
PWO-1
HR1 -25
PP1 -27
HR1 -29
HR1 -32
HR1 -34
HR1 -34
HR1 -31
DF-01
FED THRU SEPARATE
BUSSING AHEAD OF
THE MAIN SERVICE.
PP1 -21
WATER
mMP1 -20
PP1 -22
EF-13
m PP1 -20
N A T I ON A L
08/17/2018 1/8" = 1'-0"
4/
:1 3:
- N th ar ol in a
Ai r N at io na l G ua rd
/N
AN
an ga r -
_V
.rv t
EP103
M.CAHILL
E.YINGLING
C-17 HANGAR
PARTIAL POWER PLAN - AREA B AND C
1/8" = 1'-0"A1 PARTIAL POWER PLAN - AREA B
1/8" = 1'-0"A3 PARTIAL POWER PLAN - AREA C
KEY PLAN
KEYNOTES
1 CONNECT ELECTRONIC TRAP PRIMER. COORDINATE LOCATION WITH PLUMBING DRAWINGS.
2 CONNECT FMCP. REFER TO FIRE ALARM DRAWINGS FOR ADDITIONAL INFORMATION.
3 CONNECT NAC. REFER TO FIRE ALARM DRAWINGS FOR ADDITIONAL INFORMATION.
4 CONNECT ERS. REFER TO FIRE ALARM DRAWINGS FOR ADDITIONAL INFORMATION.
5 PROVIDE DISCONNECT SWITCH FOR MOTORIZED OVERHEAD DOORS. COORDINATE ADDITIONAL
ELECTRICAL REQUIREMENTS WITH MANUFACTURER PRIOR TO ROUGH-IN.
6 GFCI RECEPTACLE FOR ELECTRIC WATER COOLER (EWC). MOUNT AT 20" AFF IN WATER COOLER
HOUSING. COORDINATE LOCATION PRIOR TO ROUGH-IN.
7 PROVIDE NEMA 3R DISCONNECT SWITCH FOR MONORAIL HOIST. COORDINATE ADDITIONAL
8 PROVIDE JUNCTION BOX FOR SECURITY DOOR POWER. COORDINATE WITH SECURITY CONTRACTOR
ANY ADDITIONAL ELECTRICAL REQUIREMENTS PRIOR TO ROUGH-IN.
9 PROVIDE JUNCTION BOX FOR SECURITY CAMERA POWER. MOUNT ADJACENT TO CAMERA SIGNAL
JUNCTION BOX. COORDINATE WITH SECURITY DRAWINGS FOR EXACT MOUNTING HEIGHT.
10 PROVIDE JUNCTION BOX FOR OVERHEAD MOTORIZED DOOR CONTROL. COORDINATE ADDITIONAL
11 JUNCTION BOX SHOWN FOR REFERENCE ONLY. ELECTRICAL CONNECTIONS ARE TO BE FURNISHED
AND INSTALLED BY PAINT BOOTH MANUFACTURER.
12 JUNCTION BOX SHOWN FOR REFERENCE ONLY. ELECTRICAL CONNECTIONS ARE TO BE FURNISHED
AND INSTALLED BY SANDING BOOTH MANUFACTURER.
13 JUNCTION BOX SHOWN FOR REFERENCE ONLY. ELECTRICAL CONNECTIONS ARE TO BE FURNISHED
AND INSTALLED BY AIR SHOWER MANUFACTURER.
14 JUNCTION BOX SHOWN FOR REFERENCE ONLY. ELECTRICAL CONNECTIONS ARE TO BE FURNISHED
AND INSTALLED BY PAINT MIXING ROOM MANUFACTURER.
15 OUTLETS IN THIS AREA SHALL BE MOUNTED AT 24" TO CENTER OF BOX.
16 PROVIDE JUNCTION BOX FOR POWER WASH OUTLET. COORDINATE ADDITIONAL ELECTRICAL
REQUIREMENTS WITH MANUFACTURER PRIOR TO ROUGH-IN.
17 PROVIDE NEMA 3R DISCONNECT SWITCH FOR EXHAUST FAN. COORDINATE ADDITIONAL ELECTRICAL
REQUIREMENTS WITH MANUFACTURER PRIOR TO ROUGH-IN.
18 PROVIDE NEMA 3R DISCONNECT SWITCH FOR HANGAR DOOR CONTROLLERS. CIRCUIT CONTINUES
TO JUNCATION BOX IN DOOR POCKET. COORDINATE ADDITIONAL ELECTRICAL REQUIREMENTS WITH
MANUFACTURER PRIOR TO ROUGH-IN.
19 PROVIDE JUNCTION BOX MOUNTED AT 64'-0" AFF FOR HANGAR DOOR CONTROLLER POWER.
20 CONNECT RSCP. REFER TO FIRE ALARM DRAWINGS FOR ADDITIONAL INFORMATION.
21 FURNISH AND INSTALL WALL MOUNTED REMOTE CONTROLLER WITH FAN OR MAKEUP AIR UNIT
ON/OFF SWITCH AND HOSE REEL UP/DOWN SWITCH, ONE FOR EACH MOTORIZED EXHAUST HOSE
REEL AND ONE FOR EACH SUPPLY AIR HOSE REEL. COORDINATE MOUNTING HEIGHT AND LOCATION.
CONTROLLERS MAY BE STACKED IN GROUPS AND SHALL BE LABELED WITH THE IDENTIFICATION OF EACH REEL, MATCHING THE IDENTIFICATION LABEL ON THE OVERHEAD REEL, WHICH SHALL BE READABLE FROM THE FLOOR. REMOTE CONTROLLER SHALL BE PROVIDED WITH HOSE REEL. REFER TO SPECIFICATION 23 33 00 - SECTION 2.13.B4, AIR DUCT CORD REELS. PROVIDE WIRING AS
REQUIRED FROM THE MANUFACTURER.
22 FURNISH AND INSTALL WALL MOUNTED REMOTE UP/DOWN SWITCH, ONE FOR EACH MOTORIZED
COMPRESSED AIR HOSE REEL AND ONE FOR EACH BREATHING AIR HOSE REEL. COORDINATE
MOUNTING HEIGHT AND LOCATION. SWITCHES MAY BE STACKED IN GROUPS AND SHALL BE
LABELED WITH THE IDENTIFICATION OF EACH REEL, MATCHING THE IDENTIFICATION LABEL ON THE OVERHEAD REEL, WHICH SHALL BE READABLE FROM THE FLOOR. REMOTE CONTROLLER SHALL BE PROVIDED WITH HOSE REEL. REFER TO SPECIFICATION 22 15 13 - SECTION 2.9.B, ELECTRIC
AUTOMATIC REMOTE CONTROLLED REELS. PROVIDE WIRING AS REQUIRED FROM THE
MANUFACTURER.
23 FURNISH AND INSTALL WALL MOUNTED REMOTE UP/DOWN SWITCH, ONE FOR EACH MOTORIZED
RECEPTACLE CORD REEL. COORDINATE MONTING HEIGHT AND LOCATION. SWITCHES MAY BE
STACKED IN GROUPS AND SHALL BE LABELED WITH THE IDENTIFICATION OF EACH REEL, MATCHING
THE IDENTIFICATION LABEL ON THE OVERHEAD REEL WHICH SHALL BE READABLE FROM THE
FLOOR. REMOTE UP/DOWN SWITCH SHALL BE PROVIDED WITH THE RECEPTACLE CORD REEL.
REFER TO SPECIFICATION 26 27 26 - SECTION 2.1H, POWER CORD REELS. PROVIDE WIRING AS
REQUIRED FROM THE MANUFACTURER.
24 PROVIDE JUNCTION BOX FOR EMERGENCY EYEWASH/SHOWER ALARM. COORDINATE MOUNTING
HEIGHT AND LOCATION ON SITE AND COORDINATE ADDITIONAL ELECTRICAL REQUIREMENTS WITH
MANUFACTURER PRIOR TO ROUGH-IN.
25 PROVIDE ELECTRICAL GROUND BAR. REFER TO DETAIL B1/E-503 AND BUILDING GROUND RISER
DIAGRAM ON A1/E-602.
26 FURNISH AND INSTALL NEMA 4X JUNCTION BOX FOR WATER AND GAS METER 120V POWER. PROVIDE
3/4" SEAL TITE WITH 3#12 TO METER. COORDINATE WITH METER FOR EXACT INSTALLATION
REQUIREMENTS.
27 PROVIDE JUNCTION BOX FOR HYDROBLAST SOLUTION MIX STATION. COORDINATE ADDITIONAL
28 PROVIDE JUNCTION BOX FOR DDC PANEL POWER. COORDINATE WITH MECHANICAL CONTRACTOR
ANY ADDITIONAL ELECTRICAL REQUIREMENTS PRIOR TO ROUGH-IN.
29 PROVIDE JUNCTION BOX FOR MECHANICAL CONTROL PANEL POWER. COORDINATE WITH
MECHANICAL CONTRACTOR ANY ADDITIONAL ELECTRICAL REQUIREMENTS PRIOR TO ROUGH-IN.
30 DISCONNECT SWITCH FOR VAV BOXES POWER. CORDINATE ANY ADDITIONAL ELECTRICAL
REQUIREMENTS WITH HVAC CONTRACTOR.
31 FURNISH AND INSTALL MOTOR RATED SWITCH TO ROOF STRUCTURE NEAR DESTRATIFICATION FAN.
COORDINATE MOUTING LOCATION AND ANY ADDITIONAL ELECTRICAL REQUIREMENTS WITH
MANUFACTURE PRIOR TO ROUGH-IN.
1/8" = 1'-0"
24'4' 8' 16'
1 11/14/2018 AMENDMENT 003 ELY
Sheets
EP103 - C-17 HANGAR PARTIAL POWER PLAN - AREA B AND C
EP108 - C-17 HANGAR PARTIAL ROOF POWER PLAN - AREA B
VFD
H1
HE.9 G.5
HC.8
HC.6
HC.4
HC.2
3.8
G.1 H.1
MAU-05MAU-06
RTU-02
SP -14,16,18
SR1 -24
SR1 -25
1 2
3 4
GV-2GV-1
A. REFER TO SHEET E-001 FOR LEGEND, ABBREVIATIONS, AND NOTES.
B. REFER TO E700 SERIES DRAWINGS FOR PANELBOARD SCHEDULES.
C. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR EQUIPMENT
LOCATION.
D. REFER TO E-500 SERIES DRAWING FOR SUPPLEMENTAL DETAILS.
E. CONTRACTOR SHALL OFFSET OUTLET BOXES ON OPPOSITE SIDES OF
COMMON WALL TO PREVENT SOUND TRANSMISSION BETWEEN ADJOINING
ROOMS. BACK TO BACK BOXES SHALL NOT BE PERMITTED.
F. REFER TO E-600 SERIES DRAWINGS FOR SINGLE LINE DIAGRAMS. REFER
TO MECHANICAL EQUIPMENT SCHEDULES AND PANEL SCHEDULES FOR
ADDITIONAL ELECTRICAL REQUIREMENTS.
G. CONTRACTOR SHALL INSTALL ALL PANELS AND ELECTRICAL EQUIPMENT
TO MEET THE CLEARANCE REQUIREMENTS OF THE NEC SECTION NEC
110.26(A).
H. PROVIDE EXPANSION FITTINGS/COUPLINGS AT ALL ABOVE CEILING
CONDUITS RUNS AT EXPANSION JOINTS. REFER TO SPECIFICATIONS.
J. REFERENCE SHEET E-002 AREA CLASSIFICATION PLAN. ALL EQUIPMENT AND
WIRING WITHIN A HAZARDOUS (CLASSIFIED) LOCATION SHALL BE IN
ACCORDANCE WITH THE FOLLOWING: NEC ARTICLE 501 FOR CLASS 1, DIV 1
OR DIV 2 LOCATIONS AND GROUP CLASSIFICATIONS WHERE SPECIFIED; NEC
ARTICLE 502 FOR CLASS 2, DIV 1 OR DIV 2 LOCATIONS AND GROUP
CLASSIFICATIONS WHERE SPECIFIED.
GENERAL NOTES
08/17/2018 1/8" = 1'-0"
4/
:1 3:
- N
Ai r N
AN
r -
.rv t
EP108
M.CAHILL
PARTIAL ROOF POWER - AREA B
1/8" = 1'-0"A2 PARTIAL ROOF POWER PLAN - AREA B
KEY PLAN
KEYNOTES
1 MOUNT VFD TO UNISTRUT STRUCTURE TO RTU. COORDINATE LOCATION OF VFD WITH RTU SERVICE
PANELS. PROVIDE A NEMA 4X RATED ENCLOSURE FOR VFD.
2 MOUNT WEATHER RESISTANT GFCI RECEPTACLE TO SKIN OF ROOF MOUNTED MECHANICAL
EQUIPMENT. COORDINATE LOCATION WITH MANUFACTURER PRIOR TO ROUGH-IN.
3 MAU-6 TO BE FURNISHED AND INSTALLED BY SANDING BOOTH CONTRACTOR. SHOWN FOR
REFERENCE ONLY.
4 MAU-5 TO BE FURNISHED AND INSTALLED BY PAINT BOOTH CONTRACTOR. SHOWN FOR REFERENCE
ONLY.
5 PAINT BOOTH COMPRESSOR / CONDENSER TO BE FURNISHED AND INSTALLED BY PAINT BOOTH
CONTRACTOR. SHOWN FOR REFERENCE ONLY.
1/8" = 1'-0"
24'4' 8' 16'
1 11/14/2018 AMENDMENT 003 ELY
Sheets
EP103 - C-17 HANGAR PARTIAL POWER PLAN - AREA B AND C
EP108 - C-17 HANGAR PARTIAL ROOF POWER PLAN - AREA B
LOUVER SCHEDULE
MARK
MANUFACTURER MODEL
ASSOCIATED
UNIT
L-1 RUSKIN ELF6375DXD EF-05, EF-06
VELOCITY
(FPM)
10,000
AIR FLOW
(CFM)
FREE AREA
(SQ. FT)
17.89
LENGTH (IN.)
WIDTH (IN.)
PRESSURE
DROP (IN. WC)
0.05
BASIS OF DESIGN SIZE
NOTES
PENETRATION
1. REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATION AND ELEVATION.
2. PROVIDE WITH LOW LEAKAGE MOTORIZED CONTROL DAMPER. CONTROL DAMPER LEAKAGE SHALL NOT EXCEED 3 CFM /SQ. FT.
3. INTERLOCK EXHAUST FANS EF-05, EF-06, EF-07 WITH LOUVER L-6.
L-2 RUSKIN ELF6375DXD EF-07 10,000 627 15.94 40960.06 1023
L-3 RUSKIN ELF6375DXD EF-02, EF-04, EF 09 31,450 804 39.11 701360.09 1023
L-4 RUSKIN ELF6375DXD MAU-01 30,000 767 39.11 701360.09 1023
L-5 RUSKIN ELF6375DXD MAU-02, MAU-04 30,000 796 37.68 422280.10 1023 1,2
1,2
L-6 RUSKIN ELF6375DXD 15,000 387 38.78 342880.02 1023 1,2EF-05, EF-06, EF-07
TYPE
EXHAUST
INTAKE
L-7 RUSKIN ELF6375DXD 1,200 408 2.94 24360.03 1023 1,2MAU-03 INTAKE
L-8 RUSKIN ELF6375DXD 1,200 131 9.14 40600.001 1023 1,2EF-03, POWER WASH EXHAUST
L-9 RUSKIN ELF6375DXD 450 370 1.22 16240.02 1023 1,2EF-13 EXHAUST
L-10 RUSKIN ELF6375DXD 450 370 1.22 16240.02 1023 1,2- INTAKE
GRAVITY VENTILATOR SCHEDULE
PLAN
BASIS OF DESIGN
AIRFLOW
THROAT SIZE AREA
(SQ FT)
THROAT VELOCITY
FT/MIN
MAX PRESSURE DROP
(IN. WG)
SIZE (IN X IN)
WEIGHTS (LBS)
GV-1 GREENHECK FGI 2500 5.44 459.2 0.1 49 X 48 132 ALL NOTES APPLY
GV-2 GREENHECK FGR 2500 5.44 459.2 0.1 48 X 38 113 ALL NOTES APPLY
AREA
SERVED
CURRING OVEN
CURRING OVEN
LOUVER SCHEDULE - FIRE PUMP BUILDING
ASSOCIATED
UNIT
AIR FLOW
FREE AREA
(SQ. FT) LENGTH (IN.)WIDTH (IN.)
PRESSURE
DROP (IN. WC)
BASIS OF DESIGN SIZE
PENETRATION
1. REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATION AND ELEVATION.
2. PROVIDE WITH LOW LEAKAGE MOTORIZED CONTROL DAMPER.
3. PROVIDE WITH LOW LEAKAGE CONTROL DAMPER. CONROL DAMPER LEAKAGE SHALL NOT EXCEED 3 CFM /SQ. FT.
L-1P RUSKIN ELF6375DXD EF-01FP 975 46 32.72 24360.01 1023 1,2,3OUTSIDE AIR
O
GR
APH I A E PENE TR
AM
GU
AR
I
L
/9
/2
1:
:0
IM
ir r
.r vt
M-602
J. STAMPER
S. KOWALCZYK
S. KOWALCZYK
MECHANICAL
HVAC SCHEDULES
HOSE REEL EXHAUST AIR SCHEDULE
CFM
DIAMETER
(IN.)
HOSE LENGTH
(FT)
MOTOR DATA
WEIGHT (LBS)MANUFACTURER MODEL HP VOLTAGE FREQUENCY PHASE
HRE-01 MONOXIVENT XL-24-5 600 10 55' - 0" 1/2 460 60 3 630
HRE-02 MONOXIVENT XL-24-5 600 10 55' - 0" 1/2 460 60 3 630
HRE-03 MONOXIVENT XL-24-5 600 10 55' - 0" 1/2 460 60 3 630
HRE-04 MONOXIVENT XL-24-5 600 10 55' - 0" 1/2 460 60 3 630
HOSE REEL SUPPLY AIR SCHEDULE
CFM
DIAMETER
(IN.)
HOSE
LENGTH (FT)
MOTOR DATA WEIGHT
(LBS)MANUFACTURER MODEL HP VOLTAGE FREQUENCY PHASE
HRS-01 MONOXIVENT XL-24-5 600 10 55' - 0" 1/2 460 60 3 630
HRS-02 MONOXIVENT XL-24-5 600 10 55' - 0" 1/2 460 60 3 630
HRS-03 MONOXIVENT XL-24-5 600 10 55' - 0" 1/2 460 60 3 630
HRS-04 MONOXIVENT XL-24-5 600 10 55' - 0" 1/2 460 60 3 630
HRS-05 MONOXIVENT XL-24-5 600 10 55' - 0" 1/2 460 60 3 630
MINI SPLIT COOLING ONLY OUTDOOR CONDENSING UNIT SCHEDULE (ODU)
MARK SERVING
COOLING CAPACITY
(BTUH) SEER
ELECTRICAL DATA
OPERATING
WEIGHT (lbs) REFRIGERANT NOTESMANUFACTURER MODEL VOLTAGE (V) PHASE FREQUENCY (Hz)
MCA
(A)
MOCP
(A)
ODU-01 IDU-01 TOSHIBA CARRIER RAS-12EACV-UL 12,000 23 208 1 60 13.00 20.00 95.00 R-410 1,2,3,5 ODU-02 IDU-02 TOSHIBA CARRIER RAS-12EACV-UL 12,000 23 208 1 60 13.00 20.00 95.00 R-410 1,2,3,5 ODU-03 IDU-03 TOSHIBA CARRIER RAS-22EACV-UL 22,000 15.5 208 1 60 15.00 25.00 100.00 R-410 1,2,3,4
1. REFER TO STRUCTURAL DRAWINGS FOR CONDENSING UNIT SUPPORT
2. REFRIGERANT PIPING SHALL BE SIZED AS RECOMMENDED BY MANUFACTURER.
3. CAPACITY RATED FOR 96°F AMBIENT CONDITIONS.
MINI SPLIT COOLING ONLY INDOOR UNIT SCHEDULE (IDU)
BASIS OF DESIGN AIRFLOW ELECTRICAL DATA OPERATING
WEIGHT (lbs) NOTESMANUFACTURER MODEL MAX. CFM MIN. CFM SEER VOLTAGE (V) PHASE FREQUENCY (Hz) IDU-01 H168 HEF EQUIPMENT TOSHIBA CARRIER RAS-12EKCV-UL 406 219 23.00 208 1 60 25.00 1,2
IDU-02 H166 TR TOSHIBA CARRIER RAS-12EKCV-UL 406 219 23.00 208 1 60 25.00 1,2
IDU-03 H128 TER TOSHIBA CARRIER RAS-22EKCV-UL 636 388 15.50 208 1 60 35.00 1,2
1. INDOOR UNIT TO BE PROVIDED WITH CONDENSATE PUMP.
2. REFRIGERANT PIPING SHALL BE SIZED AS RECOMMENDED BY MANUFACTURER.
DESTRATIFICATION FAN SCHEDULE
MAX CFM WEIGHT MCA V/P/HZ
COVERAGE
AREA (SQ. FT) MAX RPM QUANTITY NOTESMANUFACTURER MODEL
DF-01 AIRIUS A-60-EC 1770 22 1.3 277/1/60 2000 1770 8 1,2,3,4
DF-02 AIRIUS A-100-EC 3358 45 2.5 277/1/60 2500 1690 9 1,2,3,4
1. MOUNTING HEIGHT IS TO THE BASE OF THE FAN ABOVE FINISHED FLOOR.
2. FANS SHALL BE PROVIDED WITH EC MOTORS.
3. FANS SHALL BE CONTROLLABLE VIA BAS WITH 0-10 Vdc.
4. REFERENCE B3/M-502 FOR MOUNTING AND INSTALLATION DETAILS.
1. ALL VENTILATORS SHALL BE PROVIDED WITH BIRDSCREENS.
2. PROVIDE BACKDRAFT DAMPERS FOR ALL INTAKE VENTILATORS.
3. TOPS OF ALL VENTILATORS SHALL BE SOUND DEADENED AND
INSULATED FOR NOISE CONTROL.
SUPPLY AIR DEVICE SCHEDULE
MARK MODULE SIZE NECK SIZE MIN. FLOW MAX FLOW. BORDER TYPE PATTERN
NOTESMANUFACTURER MODEL
S1B 24x24 6 0 157 LAY-IN 4-WAY TITUS OMNI-AA 1,2,3 S1C 24x24 8 157 279 LAY-IN 4-WAY TITUS OMNI-AA 1,2,3 S1D 24x24 10 279 436 LAY-IN 4-WAY TITUS OMNI-AA 1,2,3
S2A 6X6 6X6 0 114 WALL-MOUNTED 1-WAY TITUS 300FS 1,2,3
S3A 40X15 SEE PLANS 0 4000 DUCT MOUNTED 45 DEGREE TILT TITUS SD-L 1,2,3
S3B 12X10 SEE PLANS 0 462 DUCT MOUNTED 45 DEGREE TILT TITUS S300F 1,2,3
S4A 96X6 1-SLOT 8 0 170 LAY-IN 2-WAY TITUS ML-37 1,2,3
RETURN AND EXHAUST AIR DEVICE SCHEDULE
MARK MODULE SIZE NECK SIZE MIN. FLOW MAX. FLOW BORDER TYPE
NOTESMANUFACTURER MODEL
E1A 24x24 6X6 0 175 LAY-IN TITUS PAR-AA 1,2,3 E1C 24x24 10X10 267 350 GYP. BOARD TITUS PAR-AA 1,2,3
E2A 12X12 6X6 0 175 GYP. BOARD TITUS PAR-AA 1,2,3
E2B 12X12 10X10 270 350 GYP. BOARD TITUS PAR-AA 1,2,3
E3A 38X38 38X38 0 13000 DUCT MOUNTED TITUS 350FS 1,2,3
E3B 12X12 12X12 0 615 DUCT MOUNTED TITUS 350FS 1,2,3
E3C 48X46 48X46 0 10400 DUCT MOUNTED TITUS 350FS 1,2,3
R1A 24x24 6X6 0 175 LAY-IN TITUS PAR-AA 1,2,3 R1B 24x24 8X8 175 270 LAY-IN TITUS PAR-AA 1,2,3 R1C 24x24 10X10 271 400 LAY-IN TITUS PAR-AA 1,2,3 R1D 24x24 15X15 500 1094 LAY-IN TITUS PAR-AA 1,2,3
R1E 12X10 12X12 0 500 LAY-IN TITUS PAR-AA 1,2,3
R1F 12X12 10X10 270 350 LAY-IN TITUS PAR-AA 1,2,3
R3A 96X6 1-SLOT 6 0 170 LAY-IN TITUS ML-37 1,2,3
R4A 32X26 32X26 0 615 DUCT MOUNTED TITUS 350FS 1,2,3
T1A 10X10 10 0 114 WALL-MOUNTED TITUS 300FS 1,2,3
T1B 14X14 14 0 650 WALL-MOUNTED TITUS 300FS 1,2,3
1. COORDINATE DIFFUSER FRAME WITH ARCHITECTURAL CEILING TYPE PRIOR TO BEGINNING OF WORK.
2. REFER TO DIVISION 23 SPECIFICATIONS FOR ADDITIONAL DIFFUSER/REGISTER REQUIREMENTS.
3. COORDINATE AND VERIFY QUANTITY, TYPE, MOUNTING, AND AIRFLOWS WITH APPROVED SHOP DRAWINGS.
1. COORDINATE DIFFUSER FRAME WITH ARCHITECTURAL CEILING TYPE PRIOR TO BEGINNING OF WORK.
2. REFER TO DIVISION 23 SPECIFICATIONS FOR ADDITIONAL DIFFUSER/REGISTER REQUIREMENTS.
3. COORDINATE AND VERIFY QUANTITY, TYPE, MOUNTING, AND AIRFLOWS WITH APPROVED SHOP DRAWINGS.
4. CONDENSING UNIT SHALL BE MOUNTED ON EQUIPMENT CURB. COORDINATE WITH
ROOFING REQUIREMENTS. FLASH CURB INTO ROOFING MEMBRANE PER ROOF
SYSTEM MANUFACTURER'S INSTALLATION DETAILS. REFERENCE DETAIL A3/M-501.
5. CONDENSING UNIT SHALL BE MOUNTED ON GRADE. REFERENCE DETAILL A4/M-502.
EXHAUST FAN SCHEDULE - FIRE PUMP BUILDING
MARK SERVING TYPE CFM
ESP
(IN-WG) DRIVE TYPE
WEIGHT
(LBS)
FAN
RPM
MOTOR DATA BASIS OF DESIGN
NOTESVOLTAGE PHASE FREQUENCY MANUFACTURER MODEL
EF-01FP C-17 FIRE PUMP BUILDING WALL-MOUNTED 750 0.25 DIRECT 50 1350 115 1 60 GREENHECK SE1-12-432-G 1,2,3,4
1. PROVIDE DISCONNECT SWITCH IN ACCORDANCE WITH NEC REQUIREMENTS.
2. ALL FANS SHALL BE U.L LISTED AND LABELED.
3. ALL FANS SHALL BE SUPPLIED BY ONE MANUFACTURER UNLESS NOTED OTHERWISE.
4. PROVIDE WITH BIRDSCREEN.
UNIT HEATER SCHEDULE - FIRE PUMP BUILDING
HEATING
KW
ELECTRICAL DATA WEIGHT
(LBS) NOTESMANUFACTURER MODEL V PH Hz
UH-01 C-17 FIRE PUMP BUILDING QMARK MUH-07-4 HORIZONTAL 7.5 480 3 60 38 1,2
UH-02 C-17 FIRE PUMP BUILDING QMARK MUH-07-4 HORIZONTAL 7.5 480 3 60 38 1,2
1. PROVIDE WITH AUTOMATIC RESET LINEAR THERMAL-CUT-OUT FOR ELEMENT PROTECTION.
2. MOUNT UNIT HEATERS ON WALL SUPPORT AND ANGLE AT 45° DEGREE TOWARDS THE FLOOR.
1 11/09/2018 AMENDMENT #003 NKM
Sheets
M-602 - C-17 HANGAR HVAC SCHEDULES