This document outlines requirements for a federal contract to provide office space and facilities management services for the Defense Logistics Agency Aviation Operations Center in Richmond, Virginia. The contractor will be responsible for furnishing a 1,500 square foot office space with specific requirements including a reception area, break room with refrigerator and bottled water dispenser, storage room, two restrooms, 420 square foot conference room, central work area, and dedicated communications room. The contractor must also provide category 6 cabling to workstations and a T-1 line connecting the communications room to the Norfolk District, in addition to IT equipment for the room including a six-foot rack and adequate power, lighting and cooling.
View the file
Other files
Show 40 more
Latest 50 of 127 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DLA OPS CENTER PHASE 2 W91236-17-D-002
DEFENSE SUPPLY CENTER RICHMOND (DSCR), RICHMOND, VA
refrigerator, and bottled water services with a dispenser that dispenses cold and hot water.
c. Provide a storage room of 48 square feet area with a door, door knob, and keyed lock.
d. Provide Two restrooms (1 each for men and women). Each restroom shall have a sink, toilet fixtures, and a wall mounted urinal in the men's room. Restrooms shall be complete with hot and cold water, wall mounted soap dispenser, and a wall mounted paper towel dispenser.
Contractor shall be responsible for all connections to the privatized utilities (sewer and water) shall be provided in accordance with all applicable codes and installation requirements. The Contractor will provide all toilet paper and paper towels.
e. The conference room shall be 420 square feet (minimum) area and shall have cabling for data and phone lines with communication outlets incorporating RJ45 connectors. All communication outlets shall be terminated back to the communications room and tested for straight through connectivity. Two data and two phone connections shall be provided in each wall of the conference room. Adequate electricity for the conference room shall also be provided.
f. The centrally located work area shall be provided with category 6 cabling for fax machines, B&W and color printers, copier, digital senders, and a mail area adjacent to the filing area. The Contractor shall provide a multifunction copier/fax/printer/scanner of manufacture as required by the Contracting Officer to be compatible with connectivity on a Government field office network.
g. The dedicated communications room shall be a walled room provided with door, door knob, and keyed lock and be adequately sized for the IT equipment shown in attached "Communications Room" sketch.
h. Provide open work area providing adequate area for (8) 100 square foot modular work spaces and ADA compliant circulation space.
In addition the office shall be supplied with the following items:
a. Provide a T-1 line for IT equipment (see attached "Communications Room" sketch) for connection back to Norfolk District in the dedicated communications room with a 6ft Rack for mounted IT equipment and adequate power, lighting and cooling for the room. Installed at each workstation shall be (2) category 5e or category 6 cables, unshielded twisted pair (UTP) plenum rated 24 AWG extended frequency LAN cable (one for voice and one for data) to include two RJ45 and faceplate jacks. All cable runs shall be continuous from the communications room to the workstation faceplate jack. Data cables shall be terminated to a patch panel rack that can hold 70-90 data lines in the communications room and all data cables shall be tested for category 5e or category 6 compliance with a cable test set. Any cables that fail testing shall be repaired or replaced and re-tested for compliance. Voice cable shall be terminated on either "66" blocks or "110" blocks for 70-90 voice lines. All voice cables installed shall be tested for open, split, reversed, shorted or mis-wired pairs. All data and voice cabling shall be properly labeled at both ends of the wire and labeled on the face of the patch panel and the data jack faceplate.
SECTION 01 50 02.00 50 Page 6