About this file

Revised E-9 Drawings

View the file

Other files for this federal contract opportunity

Other files attached to CLR039b Long Range Discrimination Radar Construction Package #2 ECF, Clear AFS, AK, newest first.
File Type Posted
01_19_30_02_29_Attachment_g.pdf PDF
01_50_00_02_00_Attachment_a.pdf PDF
01_19_30_02_29_Attachment_a.pdf PDF
01_19_30_02_29_Attachment_f.pdf PDF
05_40_00.02_00.pdf PDF
08_44_23.02_00.pdf PDF
G-100003E_Location_and_Vicinity_Map.pdf PDF
01_19_30.02_29.pdf PDF
01_11_00.02_00.pdf PDF
28_23_23.02_10.pdf PDF
09_29_00.02_00.pdf PDF
23_05_93.02_00.pdf PDF
01_45_35.02_00.pdf PDF
W911KB18R0006_AM_3.pdf PDF
Schedule_of_Drawings_AM__3_Sheet_1.pdf PDF
01_50_00.02_00.pdf PDF
Final_Presentation--Pre-Proposal_Site_Visit--20180515_Slide_5_Date_Corrections.pdf PDF
01_33_29.02_00.pdf PDF
Revised_E-1_Drawings.pdf PDF
T-100701E_TELECOM_CABLE_SCHEDULE_MISSION_SUPPORT_-_RACEWAYS.pdf PDF
34_71_13.02_16.pdf PDF
26_21_00.02_00.pdf PDF
Revised_M_Drawings.pdf PDF
Revised_TY_Drawings.pdf PDF
EG100101E_SITE_PLAN_-_GROUNDING.pdf PDF
Revised_T_Drawings.pdf PDF
Revised_Security_Drawings.pdf PDF
08_88_36.02_00.pdf PDF
G-100005E_Contractor_Laydown_Areas.pdf PDF
Site_Visit_Sign_In_Sheet.pdf PDF
W911KB18R0006_AM_2.pdf PDF
28_20_01.02_10.pdf PDF
Revised_Site_Plan_Drawings.pdf PDF
26_21_00.02_00.pdf PDF
Final_Presentation--Pre-Proposal_Site_Visit--20180515.pdf PDF
C_Drawing_revisions.pdf PDF
Revised_E_Drawings.pdf PDF
A_Drawing_Revisions.pdf PDF
28_20_00.02_00.pdf PDF
Revised_E-9_Drawings.pdf PDF
33_71_02.02_00.pdf PDF
EG100101E_-_SITE_PLAN_-_GROUNDING.pdf PDF
W911KB18R0006_AM_1.pdf PDF
JA_for_Vindictor_LRDR_ECF_Redacted.pdf PDF
CLR_LRDR_CP2_Rev2_RTA_Drawings_22x34.pdf PDF
CP2_RTA_SPECS_V2_CLR039_18-0410.pdf PDF
SPECS_V2-4_CLR039_18-0410.pdf PDF
CP2_RTA_SPECS_V4_CLR039_18-0410.pdf PDF
W911KB18R0006.pdf PDF
CP2_RTA_SPECS_V3_CLR039_18-0410.pdf PDF
Show all 50

CLR039b Long Range Discrimination Radar Construction Package #2 ECF, Clear AFS, AK has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

38' - 10"

' - 3

D

OA

OA

OA

P C

OAOA

D D

P C

P C

J J

J

J

J

B

B

J

AC

A1X

A1

BX

BX

B1X

A1

A1X

A1

A1XA

DX

DX

F

SA

X

X

SA

LC-90361002

LC-90361003

EXIT LOBBY

ENTRY LOBBY

ENTRY CONTROL

COMM/MECH/ELEC

JC

B

B1X

LC-90361001

DP-90361002-8

TOILET

B1 a a a b c c c b bb b c a

A1 c

TO LC-90361001

TO LC-90361002

TO LC-90361003

SA

DP-90361002-10

DX-B

DX-B

DP-90361002-7

PP-90361001-34

DP-90361002-25

DP-90361002-26

RLY 90367001

RLY 90367002

VIA LC-90361001

SA

DX

DX

+16'-0" AFG

+12'-0" AFG

+12'-0" AFG

+16'-0" AFG

D E

P

A R

T M

E N

T O

F D

E F

E

N S

E

MISSIL

E D

E F

E N

S E

A

GENCY

D ra w in g

F il e N a m e

D w g S c a le

P lo t S c a le

D a te

D ra w n

R E

S

ID

E N

T E

N G

IN

E

E R

P R

IM

E

C O

N T

R A

C T

O R

S u b m it te d

D e s ig n e d

R e v ie w e d

U .S

A

R M

Y E

N G

IN

E

E R

D

IS

T R

IC

T

A N

C H

O R

A G

E A

L A

S K

A

C O

R P

S O

F E

N G

IN

E

E R

S

D a te

S T

A T

E C

IT

Y

C O

N T

R A

C T

O R

C O

N T

R A

C T

N O

R e c o m m e n d e d

A p p ro v e d

Reference number:

HGFEDCBA

A S

N O

T E

D

P L O

T T

E D

O N

US Army Corps of Engineers ®

Alaska District

M D

A

C L R b

P D

C I N

C

E N

G

IN

E E

R S

G

A M

B E

L L S

T S

U

IT

E

A N

C H

O R

A G

E

A K

A N

C

-7

-3

A

E C

C

N O

T F

O R

C O

N S

T R

U C

T

IO

N

/1

/2

:0

:3

P

M C

U s e rs

\b ri a n a rm a g o s t\ D o c u m e n ts

\C L R

L R

D R

E

C F

E

-D M b ri a n a rm a g o s t.

rv t

AM#3 E-903101E

F L O

O R

P L A

N

L

IG

H T

IN

G

L O

N G

R A

N G

E D

IS

C

R

IM

IN

A

T

IO

N R

A D

A R

C L E

A R

A F

S A

L A

S K

A

R D

P

:1

C

LR

_L R

D R

_ E C

F _E

-D M

J D

S

B H

W K

B -1

-R

-0

.0 .0

C O

N S

T R

U C

T

IO

N P

A C

K A

G E

V O

L U

M E

R

D P

A F

-1

- 3

-0

SCALE:

3/8" = 1' - 0"

4' 2' 4' 6' 3/8" = 1'-0"1

FLOOR PLAN - LIGHTING

PLAN NORTH

1. INSTALL REMOTE BATTERY UNIT ABOVE CEILING

ADJACENT TO EXTERIOR WALL PENETRATIONS.

2. PROVIDE SINGLE EXTERIOR WALL PENETRATION TO

PHOTOCELLS MOUNTED TO OUTSIDE WALL AT BASE OF

PARAPET.

3. DIMMING CONTROL STATIONS ALLOW OVERRIDE OF

LUMINAIRES IN THE ENTRY LOBBY, EXIT LOBBY AND

ENTRY CONTROL ROOM.

4. OCCUPANCY SWITCH WITH DPST CONTROLS FOR

CONTROL OF TOILET ROOM LUMINAIRES AND BUILDING

VENTILATION.

5. OCCUPANCY SWITCH WITH DPST CONTROLS FOR

CONTROL OF ENTRY CONTROL ROOM LUMINAIRES AND

BUILDING VENTILATION.

SHEET NOTES X

S y m

A c ti o n

D e s c ri p ti o n

D a te

A p p v d

A

M E

N D

M E

N T

/1

B

K H

3 3

38' - 10"

' - 3

G

G

W P

W P

J

J

J

J

J

J

J

M

M

J J

J

J

W P

M

J

J

J

J

J

J JW

P

W P

J

AC

WH-90312001

DP-90361002

IDB-90367002

IDB-90367001

UPS-90367002

DO

DO

DO

LC-90361002

LC-90361003

DP-90361001

PP-90361001

T-90361002

DS-90361001

EXIT LOBBY

ENTRY LOBBY

ENTRY CONTROL

COMM/MECH/ELEC

JC

B

CUH-90322002

FTH-90322002

FTH-90322003

FTH-90322004

FTH-90322001

AIC-90341001

EF-90341002

AIC-90341002

EF-90341001

MTR-90361001

LC-90361001

HC-90341001

PHC-90341001

FACP-90353001

T-90361001

HC-90361001

CUH-90322001

P-90352001

PP-90361001-3

PP-90361001-24,26

PP-90361001-28,30

DP-90361002-1,3,5

DP-90361002-2,4,6

PP-90361001-2

UPS-90367002-2

UPS-90367002-1

PP-90361001-9

PP-90361001-7

PP-90361002-6

PP-90361001-4

PP-90361001-14,16

PP-90361001-21,23

PP-90361001-5

TOILET

PP-90361002-8,10

PP-90361002-13,15

UPS-90363001

PP-90361002-5

PP-90361001-17,19

PP-90361002-20,22

PP-90361002-17,19

DP-90361001-5

PP-90361001-40,42,44

PP-90361002

PP-90361002-2,4

PP-90361002-16,18

PP-90361002-21,23

PP-90361002-9,11

PP-90361001-32

FAA-90353001

RLY 90367001

RLY 90367002

PP-90361001-1

PP-90361002-25

PP-90361001-36,38

ACU-90332001

P-90312001

AHU-90341001

DP-90361002-27,29,31

HEAT TRACE ROOF DRAIN

PP-90361001-8

BMS-90363001

PP-90361001-15

PP-90361001-6

PP-90361002-30

NG-90352001

PP-90361002-1

PP-90361002-31,33

PP-90361002-24,26

PP-90361002-3

+84"

AC B

PP-90361002-1

COND-90333002

COND-90333001

PP-90361002-12,14

PP-90361002-27,29

PP-90361001-10

D E

P

A R

T M

E N

T O

F D

E F

E

N S

E

MISSIL

E D

E F

E N

S E

A

GENCY

D ra w in g

F il e N a m e

D w g S c a le

P lo t S c a le

D a te

D ra w n

R E

S

ID

E N

T E

N G

IN

E

E R

P R

IM

E

C O

N T

R A

C T

O R

S u b m it te d

D e s ig n e d

R e v ie w e d

U .S

A

R M

Y E

N G

IN

E

E R

D

IS

T R

IC

T

A N

C H

O R

A G

E A

L A

S K

A

C O

R P

S O

F E

N G

IN

E

E R

S

D a te

S T

A T

E C

IT

Y

C O

N T

R A

C T

O R

C O

N T

R A

C T

N O

R e c o m m e n d e d

A p p ro v e d

Reference number:

HGFEDCBA

A S

N O

T E

D

P L O

T T

E D

O N

US Army Corps of Engineers ®

Alaska District

M D

A

C L R b

P D

C I N

C

E N

G

IN

E E

R S

G

A M

B E

L L S

T S

U

IT

E

C H

O R

A G

E

A K

A N

C

-7

-3

A

E C

C

N O

T F

O R

C O

N S

T R

U C

T

IO

N

/1

/2

:5

:0

A

M C

U s e rs

\b ri a n a rm a g o s t\ D o c u m e n ts

\C L R

L R

D R

E

C F

E

-D M b ri a n a rm a g o s t.

rv t

AM#3 E-903111E

F L O

O R

P L A

N

P O

W E

R

L O

N G

R A

N G

E D

IS

C

R

IM

IN

A

T

IO

N R

A D

A R

C L E

A R

A F

S A

L A

S K

A

R D

P

:1

C

LR

_L R

D R

_ E C

F_ E

-D M

J D

S

B H

W K

B -1

-R

-0

.0 .0

C O

N S

T R

U C

T

IO

N P

A C

K A

G E

V O

L U

M E

R

D P

A F

-1

- 3

-0

SCALE:

3/8" = 1' - 0"

4' 2' 4' 6' 3/8" = 1'-0"1

FLOOR PLAN - POWER

1. PROVIDE 2 - 1/2" C. STUBBED UP TO LOCATIONS NEAR

RECEPTACLES AT BASE OF TELECOM RACK.

2. ROOF DRAIN HEAT TRACE, SEE E-903502E.

3. ROOF DRAIN OVERFLOW HEAT TRACE. SEE E-903502E.

4. VENT THROUGH ROOF HEAT TRACE CONNECTION. SEE

E-903502E.

5. SANITARY SEWER HEAT TRACE. SEE C-100507E FOR

DETAILS AND EXTENT OF ROUTING.

6. WATER SERVICE HEAT TRACE. SEE C-100507E FOR

DETAILS AND EXTENT OF ROUTING. SEE E-100401E FOR

WATER SERVICE END OF LINE TERMINATIONS AT MCF

(BLDG 900).

7. SPRINKLER SERVICE HEAT TRACE. SEE C-100507E FOR

DETAILS AND EXTENT OF ROUTING.

8. EXHAUST FAN EF-90341001 AND TOILET ROOM

LUMINAIRES CONTROLLED BY OCCUPANCY SWITCH

WITH DPST CONTROLS, SEE E-903101E.

9. PROVIDE WALL SWITCH FOR MANUAL CONTROL OF

DYNAMIC WINDOWS. MOUNT AT +60" AFF AND

COORDINATE WITH OTHER DEVICES IN THIS AREA.

PROVIDE LABEL ON COVER PLATE "WINDOW TINTING".

10. INSTALL HIGH/LOW/OFF SWITCH FURNISHED BY OTHERS

AT +60" AFF FOR CONTROL OF AIC-9031001 AND AIC-903-

1002.

11. PROVIDE POWER CONNECTION TO ROOF HATCH HEAT

TRACE (INTEGRAL TO HATCH FROM MANUFACTURER).

COORDINATE WITH ARCHITECTURAL. PROVIDE WITH

LOCAL PILOT LIGHT SWITCH AS CONTROL AND

DISCONNECTING MEANS.

12. PROVIDE 120V POWER TO DYNAMIC WINDOW

CONTROLLER. PROVIDE LOW VOLTAGE CABLING

BETWEEN CONTROLLER AND EACH BANK OF DYNAMIC

WINDOWS. REFER TO DIVISION 8 FOR ADDITIONAL

INFORMATION.

13. PROVIDE MINIMUM OF 100kA SURGE CURRENT

PROTECTION IN A NEMA 1 ENCLOSURE (SPD-90361001).

COORDINATE CLEARANCES AND MOUNTING WITH OTHER

TRADES.

SHEET NOTES X

1/8" = 1'-0"2

ROOF PLAN - POWER

SCALE:

0 8' 16'

1/8" = 1' - 0"

8' 16'

PLAN NORTH PLAN NORTH

S y m

A c ti o n

D e s c ri p ti o n

D a te

A p p v d

A

M E

N D

M E

N T

/1

B

K H

A

M E

N D

M E

N T

/1

B

K H

2 2

2 2

3 3

/3

125/3

300/3

ALL FEEDER CONDUCTORS SHALL BE COPPER.

3 - 12 AWG, 1 - 10 AWG GND, 3/4" C.

4 - 2 AWG, 1 - 8 AWG GND, 1-1/2" C.

3 - 1 AWG, 1 - 6 AWG GND, 2" C.

4 - 4/0 AWG, 1 - 4 AWG GND, 2-1/2" C.

2 SETS: 3 - 4/0 AWG, 1 - 4/0 AWG GND, 4" C.

FEEDER SCHEDULE

PP-90361001

208Y/120V

225 AMP MCB

T-90361002

75KVA

480∆:208Y/120V

NEMA 1, CU

WINDINGS

DP-90361001

480Y/277V

400AF/300AT MCB

CP-2E

ENTRY CONTROL FACILITY (BLDG. 903)

125/3

T-90361001

225KVA

480∆:480Y/277V

NEMA 1 CU WINDINGS

+2.5% SECONDARY TAP

2 SETS: 4 - 4/0 AWG + 1 - 4/0 AWG GND, 2-1/2" C.400A

N G

DS-90361001

400 AMP

300 AMP

FUSE NEMA

4X

ENCLOSURE

A

INTEGRATED POWER CENTER

100/3

/3

A

PP-10061001

208Y/120V

100 AMP MCB

NEMA 3R

70 3 - 4 AWG, 1 - 10 AWG GND, 1" C.

T-10061001

45KVA

480∆:208Y/120V

NEMA 3R, CU

WINDINGS

DP-90361002

480Y/277V

125 AMP MLO

125A

M MTR-90361001

CP-1B

TO EP-90061001

PP-90361002

208Y/100V

100 AMP MLO

100/3

15/3

20 HC-90341001

20/2

TO FIELD DISTRIBUTION

BOXES (FDB), TYPICAL OF 4

400AF

MCF (BLDG. 900)

PIPE ENTRY 1B

300AT

2E

100AF

15AT

1E

600AF

400AT

100AF

15AT

3E

100AF

30AT

4E

TO CP-1B

LOADS

TO CP-1B

LOADS

TO CP-1B

LOADS

EP-90061002

480V, 600A

(E) EHH-10061101

(HANDHOLE ONLY)

EHH-10061102

225 4 - 4/0 AWG, 1 - 4 AWG GND, 2-1/2" C.

175 3 - 2/0 AWG, 1 - 6 AWG GND, 2" C.

125A 4 - 1 AWG, 1 - 6 AWG GND, 2" C.

5 FOR GROUNDING SIZES

AND CONNECTIONS, SEE

EG100601E AND EG903112E

15/1

5E 6E

20/2 20/2

MPZB5S40F

NFA SHED (WEST)

MPZ

5KVA

480V:120/240V

20/1

20/1

4 DUPLEX

SHED LTG

MPZ5S40F

NFA SHED (EAST)

MPZ

5KVA

480V:120/240V

20/1

20/1

4 DUPLEX

SHED LTG

/2

/2

202 2 - 8 AWG, 1 - 10 AWG GND, 2" C.

202A

202A 4 - 8 AWG, 2 - 10 AWG GND, 2" C

7202202

D E

P

A R

T M

E N

T O

F D

E F

E

N S

E

MISSIL

E D

E F

E N

S E

A

GENCY

D ra w in g

F il e N a m e

D w g S c a le

P lo t S c a le

D a te

D ra w n

R E

S

ID

E N

T E

N G

IN

E

E R

P R

IM

E

C O

N T

R A

C T

O R

S u b m it te d

D e s ig n e d

R e v ie w e d

U .S

A

R M

Y E

N G

IN

E

E R

D

IS

T R

IC

T

A N

C H

O R

A G

E A

L A

S K

A

C O

R P

S O

F E

N G

IN

E

E R

S

D a te

S T

A T

E C

IT

Y

C O

N T

R A

C T

O R

C O

N T

R A

C T

N O

R e c o m m e n d e d

A p p ro v e d

Reference number:

HGFEDCBA

A S

N O

T E

D

P L O

T T

E D

O N

US Army Corps of Engineers ®

Alaska District

M D

A

C L R b

P D

C I N

C

E N

G

IN

E E

R S

G

A M

B E

L L S

T S

U

IT

E

C H

O R

A G

E

A K

A N

C

-7

-3

A

E C

C

N O

T F

O R

C O

N S

T R

U C

T

IO

N

/1

/2

:0

:3

P

M C

U s e rs

\b ri a n a rm a g o s t\ D o c u m e n ts

\C L R

L R

D R

E

C F

E

-D M b ri a n a rm a g o s t.

rv t

AM#3 E-903601E

D

IA

G R

A M

P

O W

E R

O N

E -L

IN

E

L O

N G

R A

N G

E D

IS

C

R

IM

IN

A

T

IO

N R

A D

A R

C L E

A R

A F

S A

L A

S K

A

R D

P

:1

C

LR

_L R

D R

_ E C

F _E

-D M

J D

S

B H

W K

B -1

-R

-0

.0 .0

C O

N S

T R

U C

T

IO

N P

A C

K A

G E

V O

L U

M E

R

D P

A F

-1

- 3

-0

NO SCALE1

POWER ONE-LINE DIAGRAM

1. SEPARATELY DERIVED GROUNDING SYSTEM, BOND TO

SERVICE GROUND BAR. SEE EG100501E.

2. SEPARATELY DERIVED GROUNDING SYSTEM. PROVIDE

GROUND CONNECTION TO (2) 20' x 3/4" GROUND RODS.

3. METER SHALL BE MONITORED BY THE BMS SYSTEM.

4. FEEDER UPSIZED TO ADJUST FOR VOLTAGE DROP.

5. PROVIDE CONDUCTORS FROM BREAKER IN EP-90061002

TO THE ECF BUILDING AS SHOWN. RACEWAY IS

EXISTING FROM EP-90061002 TO EHH-10061101. PROVIDE

RACEWAY ALONG OTHER SECTION FOR A COMPLETE

FEEDER.

6. PROVIDE 200W STRIP HEATER INSIDE PANELBOARD

ENCLOSURE.

7. PROVIDE SURGE SUPPRESSION AHEAD OF ECF MAIN

DISTRIBUTION PANEL.

SHEET NOTES X

S y m

A c ti o n

D e s c ri p ti o n

D a te

A p p v d

A

M E

N D

M E

N T

/1

B

K H

A

M E

N D

M E

N T

/1

B

K H

3 3

3 3

3 3

D E

P

A R

T M

E N

T O

F D

E F

E

N S

E

MISSIL

E D

E F

E N

S E

A

GENCY

D ra w in g

F il e N a m e

D w g S c a le

P lo t S c a le

D a te

D ra w n

R E

S

ID

E N

T E

N G

IN

E

E R

P R

IM

E

C O

N T

R A

C T

O R

S u b m it te d

D e s ig n e d

R e v ie w e d

U .S

A

R M

Y E

N G

IN

E

E R

D

IS

T R

IC

T

A N

C H

O R

A G

E A

L A

S K

A

C O

R P

S O

F E

N G

IN

E

E R

S

D a te

S T

A T

E C

IT

Y

C O

N T

R A

C T

O R

C O

N T

R A

C T

N O

R e c o m m e n d e d

A p p ro v e d

Reference number:

HGFEDCBA

A S

N O

T E

D

P L O

T T

E D

O N

US Army Corps of Engineers ®

Alaska District

M D

A

C L R b

P D

C I N

C

E N

G

IN

E E

R S

G

A M

B E

L L S

T S

U

IT

E

C H

O R

A G

E

A K

A N

C

-7

-3

A

E C

C

N O

T F

O R

C O

N S

T R

U C

T

IO

N

/1

/2

:5

:0

A

M C

U s e rs

\b ri a n a rm a g o s t\ D o c u m e n ts

\C L R

L R

D R

E

C F

E

-D M b ri a n a rm a g o s t.

rv t

AM#3 E-903701E

P A

N E

L S

C H

E D

U L E

S

L O

N G

R A

N G

E D

IS

C

R

IM

IN

A

T

IO

N R

A D

A R

C L E

A R

A F

S A

L A

S K

A

R D

P

:1

C

LR

_L R

D R

_ E C

F _E

-D M

J D

S

B H

W K

B -1

-R

-0

.0 .0

C O

N S

T R

U C

T

IO

N P

A C

K A

G E

V O

L U

M E

R

D P

A F

-1

- 3

-0

9 OTHER = 3900 VA 100% 3900 VA

8 SPARE = 0 VA 100% 0 VA

7 NON-COINCIDENTAL = 12300 VA 0% 123 VA

6 MISC. CONTINUOUS = 0 VA 125% 0 VA

5 MISC. NON-CONTINUOUS = 46520 VA 100% 46520 VA

4 LARGEST MOTOR = 0 VA 125% 0 VA TOTAL EST DEMAND: 180 A

3 MOTORS = 3948 VA 100% 3948 VA TOTAL CONN: 215 A

2 RECEPTACLES = 10780 VA 10K+50% 10390 VA TOTAL EST DEMAND: 65 kVA CIRCUIT BREAKER AND WIRES AS REQUIRED.

1 LIGHTING = 50 VA 125% 63 VA TOTAL CONN LOAD: 77 kVA 1. COORDINATE WITH CIVIL CONTRACTOR FOR EXACT ELECTRIC GATE LOAD AND UPSIZE

LOAD SUMMARY AND CODE

DEFINITIONS

CONNECTED

LOAD

NEC

ESTIMATED

DEMAND

PANEL TOTALS NOTES:

PERCENT: 10 % -2 % -11 %

PHASE BALANCE: A-B A-C B-C

TOTAL AMPS: 223 A 200 A 229 A

TOTAL LOAD: 26436 VA 24009 VA 27053 VA

-- SPACE W/ HARDWARE -- -- 53 0 0 54 -- -- SPACE W/ HARDWARE --

-- SPARE 20 A 1 51 0 0 52 -- -- SPACE W/ HARDWARE --

-- SPARE 20 A 1 49 0 0 50 1 20 A SPARE --

-- SPARE 20 A 1 47 0 0 48 1 20 A SPARE --

-- SPARE 20 A 1 45 0 0 46 1 20 A SPARE --

-- SPARE 20 A 1 43 0 800 44 -- -- -- --

-- SPARE 20 A 1 41 0 800 42 -- -- -- --

-- -- -- -- 39 960 800 40 3 15 A PHC-90341001 RM 104 9

5 CRASH GATE 1 20 A 2 37 960 1800 38 -- -- -- --

-- -- -- -- 35 2500 1800 36 2 20 A ACU-9033201 ...

-- -- -- -- 33 2500 50 34 1 15 A LC-90361001 - SECURITY 1

7 ELECTRIC GATE, EXTERIOR 1 30 A 3 31 2500 500 32 1 20 A FAA, RM 105 9

-- -- -- -- 29 2500 1000 30 -- -- -- --

-- -- -- -- 27 2500 1000 28 2 20 A CUH-90322002 RM 103 ...

5 ELECTRIC GATE, EXTERIOR 1 30 A 3 25 2500 1000 26 -- -- -- --

-- -- -- -- 23 2000 1000 24 2 20 A CUH-90322001 RM 106 ...

5 FTH-90322001 EXIT LOBBY 102 30 A 2 21 2000 11043 22 -- -- -- --

-- -- -- -- 19 2500 9900 20 -- -- -- --

5 FTH-90322002 EXIT LOBBY 102 30 A 2 17 2500 10233 18 3 100 A PP-90361002 ...

9 BMS-9063001 20 A 1 15 0 1500 16 -- -- -- --

5 GATE HEATER 1 20 A 1 13 1000 1500 14 2 20 A WH-90312001 TOILET /JC 103 2

5 CRASH GATE HEATER 1 20 A 1 11 1000 1000 12 1 20 A 1 GATE HEATER 5

2 RCPT COMM/MECH/ELEC 104 20 A 1 9 720 360 10 1 20 A RCPT, ROOF 2

2 RCPT RM 105, 104 20 A 1 7 720 180 8 1 20 A RCPT ENTRY CONTROL 105 2

2 COMM RACK COMM/MECH/ELEC 104 20 A 1 5 360 360 6 1 20 A RCPT ENTRY LOBBY 101 2

3 EF-90341002 TOILET /JC 103 20 A 1 3 76 500 4 1 20 A DOOR OPERATORS RM 102, 101 9

3 EF-90341001 20 A 1 1 76 500 2 1 20 A FACP-90361001 ENTRY LOBBY 101 9

L

O

A

D

CIRCUIT DESCRIPTION

NOTE

S

AMPS P CKT A B C A B C CKT P AMPS

NOTE

S

CIRCUIT DESCRIPTION

L

O

A

D

MAIN: MCB, 225A, ET, LSIG CIRCUITS: 54 LOCATION: COMM/MECH/ELEC 104

BUS AMPS: 225 A MIN AIC RATING: 10,000 MOUNTING: SURFACE

VOLTAGE: 208Y/120 SPECIFICATION TYPE: BPB ENCLOSURE: TYPE 1

PANELBOARD PP-90361001

9 OTHER = 12000 VA 100% 12000 VA

8 SPARE = 0 VA 100% 0 VA

7 NON-COINCIDENTAL = 0 VA 0% 0 VA

6 MISC. CONTINUOUS = 0 VA 125% 0 VA 6. PROVIDE MOV SURGE SUPPRESSION ON SITE LIGHTING CIRCUITS PER UFC 3-530-01.

5 MISC. NON-CONTINUOUS = 22600 VA 100% 22600 VA 5. PROVIDE HANDLE LOCK-ON DEVICE.

4 LARGEST MOTOR = 0 VA 125% 0 VA TOTAL EST DEMAND: 77 A 4. PROVIDE HANDLE LOCK-OFF PROVISIONS.

3 MOTORS = 1800 VA 100% 1800 VA TOTAL CONN: 71 A 3. AFCI BREAKER.

2 RECEPTACLES = 0 VA 10K+50% 0 VA TOTAL EST DEMAND: 64 kVA 2. GFPE BREAKER (30mA).

1 LIGHTING = 22315 VA 125% 27894 VA TOTAL CONN LOAD: 59 kVA 1. GFCI BREAKER (5mA).

LOAD SUMMARY AND CODE

DEFINITIONS

CONNECTED

LOAD

NEC

ESTIMATED

DEMAND

PANEL TOTALS NOTES:

PERCENT: 9 % -6 % 3 %

PHASE BALANCE: A-B A-C B-C

TOTAL AMPS: 67 A 74 A 72 A

TOTAL LOAD: 18536 VA 20429 VA 19750 VA

41 0 42 -- -- SPACE W/ HARDWARE --

1 LTG - FENCED AREA PERIMETER - SECTOR 6 6 20 A 1 39 2010 0 40 -- -- SPACE W/ HARDWARE --

1 LTG - FENCED AREA PERIMETER - SECTOR 4-5 6 20 A 1 37 2010 0 38 -- -- SPACE W/ HARDWARE --

1 LTG - FENCED AREA PERIMETER - SECTOR 2-3 6 20 A 1 35 2546 0 36 -- -- SPACE W/ HARDWARE --

1 LTG - FENCED AREA PERIMETER - SECTOR 1 6 20 A 1 33 2010 0 34 -- -- SPACE W/ HARDWARE --

-- -- -- -- 31 600 0 32 -- -- SPACE W/ HARDWARE --

-- -- -- -- 29 600 0 30 -- -- SPACE W/ HARDWARE --

3 AHU-90341001 15 A 3 27 600 0 28 -- -- SPACE W/ HARDWARE --

1 LC-90361002 - SITE 6 15 A 1 25 50 50 26 1 15 A 6 LC-90361003 - ROADWAY 1

-- -- -- -- 23 1005 1556 24 1 20 A 6 LTG - ROADWAY 1

1 LTG - FENCED AREA PERIMETER - SECTOR 7-10 6 20 A 2 21 1005 2400 22 1 20 A 6 LTG - SUBSTATION 1

-- -- 6 -- -- 19 2010 364 20 1 20 A 6 LTG - ECF PARKING LOT 1

1 LTG - FENCED AREA PRMTR. - SECTOR 11-14 6 20 A 2 17 2010 1500 18 -- -- -- --

-- -- -- -- 15 1500 1500 16 2 20 A 5 FDB-10067004 9

9 FDB-10067003 5 20 A 2 13 1500 1500 14 -- -- -- --

-- -- -- -- 11 1500 1500 12 2 20 A 5 FDB-10067002 9

9 FDB-10067001 5 20 A 2 9 1500 373 10 1 20 A LTG ECF INTERIOR SECURED AREA 1

... LTG ECF EXT. & FNCD. AREA PRMTR.-SECT. 15 6 20 A 1 7 2850 72 8 1 20 A LTG ECF INTERIOR UNSECURED AREA 1

-- -- -- -- 5 3767 3767 6 -- -- -- --

-- -- -- -- 3 3767 3767 4 -- -- -- --

... AIC-90341002 20 A 3 1 3767 3767 2 3 20 A 4 AIC-90341001 ...

L

O

A

D

CIRCUIT DESCRIPTION

NOTE

S

AMPS P CKT A B C A B C CKT P AMPS

NOTE

S

CIRCUIT DESCRIPTION

L

O

A

D

MAIN: MLO CIRCUITS: 42 LOCATION: COMM/MECH/ELEC 104

BUS AMPS: 125 A MIN AIC RATING: 18,000 MOUNTING: SURFACE

VOLTAGE: 480Y/277 SPECIFICATION TYPE: BPB ENCLOSURE: TYPE 1

PANELBOARD DP-90361002

9 OTHER = 0 VA 100% 0 VA

8 SPARE = 0 VA 100% 0 VA

7 NON-COINCIDENTAL = 1200 VA 0% 12 VA

6 MISC. CONTINUOUS = 0 VA 125% 0 VA

5 MISC. NON-CONTINUOUS = 21100 VA 100% 21100 VA

4 LARGEST MOTOR = 0 VA 125% 0 VA TOTAL EST DEMAND: 83 A

3 MOTORS = 3796 VA 100% 3796 VA TOTAL CONN: 87 A

2 RECEPTACLES = 5080 VA 10K+50% 5080 VA TOTAL EST DEMAND: 30 kVA

1 LIGHTING = 0 VA 125% 0 VA TOTAL CONN LOAD: 31 kVA 1. GFPE BREAKER (30mA).

LOAD SUMMARY AND CODE

DEFINITIONS

CONNECTED

LOAD

NEC

ESTIMATED

DEMAND

PANEL TOTALS NOTES:

PERCENT: 3 % -7 % -10 %

PHASE BALANCE: A-B A-C B-C

TOTAL AMPS: 86 A 83 A 92 A

TOTAL LOAD: 10233 VA 9900 VA 11043 VA

-- SPACE W/ HARDWARE -- -- 41 0 0 42 -- -- SPACE W/ HARDWARE --

-- -- -- -- 39 600 0 40 -- -- SPACE W/ HARDWARE --

5 HEAT TRACE - SPRINKLER SERVICE 1 20 A 2 37 600 0 38 1 20 A SPARE --

-- SPARE 20 A 1 35 0 0 36 1 20 A SPARE --

-- -- -- -- 33 250 0 34 1 20 A SPARE --

5 HEAT TRACE- WATER SERVICE 1 20 A 2 31 250 0 32 1 20 A SPARE --

-- -- -- -- 29 100 1200 30 1 20 A NG-90352001 RM 104 ...

3 COND-9033001 20 A 2 27 100 0 28 -- -- SPACE W/ HARDWARE --

9 IPID'S 28VDC POWER SUPPLY RM 104 20 A 1 25 0 600 26 -- -- -- --

-- -- -- -- 23 1500 600 24 2 20 A 1 HEAT TRACE - SANITARY SEWER 5

5 HEAT TRACE- WATER SERVICE 1 40 A 2 21 1500 2750 22 -- -- -- --

-- -- -- -- 19 2250 2750 20 2 40 A FTH-90322003 ENTRY LOBBY 101 5

5 FTH-90322004 ENTRY LOBBY 101 30 A 2 17 2250 1500 18 -- -- -- --

-- -- -- -- 15 1250 1500 16 2 40 A 1 HEAT TRACE- WATER SERVICE 5

2 UPS-90367002 COMM/MECH/ELEC 104 20 A 2 13 1250 1183 14 -- -- -- --

-- -- -- -- 11 400 1183 12 2 20 A COND-90333002 3

5 HEAT TRACE - SANITARY SEWER 1 20 A 2 9 400 750 10 -- -- -- --

-- SPARE 20 A 1 7 0 750 8 2 20 A UPS-90361001 COMM/MECH/ELEC 104 2

3 P-90352001, P-90312001 JC 106 15 A 1 5 1230 1080 6 1 20 A RCPT RM 107, 106, 102 2

5 WINDOW TINTING 20 A 1 3 500 300 4 -- -- -- --

... HEAT TRACE - ROOF DRAIN 1 20 A 1 1 300 300 2 2 20 A 1 HEAT TRACE - SPRINKLER SERVICE 5

L

O

A

D

CIRCUIT DESCRIPTION

NOTE

S

AMPS P CKT

CONNECTED VA

PH A PH B PH C

CONNECTED VA

PH A PH B PH C

CKT P AMPS

NOTE

S

CIRCUIT DESCRIPTION

L

O

A

D

MAIN: MLO CIRCUITS: 42 LOCATION: COMM/MECH/ELEC 104

BUS AMPS: 100 A MIN AIC RATING: 10,000 MOUNTING: SURFACE

VOLTAGE: 208Y/120 SPECIFICATION TYPE: BPB ENCLOSURE: Type 1

PANELBOARD PP-90361002

9 OTHER = 25400 VA 100% 25400 VA

8 SPARE = 0 VA 100% 0 VA

7 NON-COINCIDENTAL = 12300 VA 0% 123 VA

6 MISC. CONTINUOUS = 0 VA 125% 0 VA

5 MISC. NON-CONTINUOUS = 70620 VA 100% 70620 VA

4 LARGEST MOTOR = 0 VA 125% 0 VA TOTAL EST DEMAND: 202 A

3 MOTORS = 5748 VA 100% 5748 VA TOTAL CONN: 240 A

2 RECEPTACLES = 61360 VA 10K+50% 35680 VA TOTAL EST DEMAND: 168 kVA

1 LIGHTING = 24375 VA 125% 30469 VA TOTAL CONN LOAD: 200 kVA

LOAD SUMMARY AND CODE

DEFINITIONS

CONNECTED

LOAD

NEC

ESTIMATED

DEMAND

PANEL TOTALS NOTES:

6 60 A 60 A 3 TMT SPD-90361001 1000 1000 1000 9

5 15 A 60 A 3 TMT HC-90341001 ENTRY CONTROL 105 2167 2167 2167 9

4 125 A 250 A 3 ET LSIG DP-90361002 18536 20429 19750 1; 2; 5; 3; 9

3 100 A 100 A 3 TMT T-10061001 20010 18180 15900 1; 2; 5

2 125 A 250 A 3 ET LSIG T-90361002 26436 24009 27053 1; 2; 7; 5; 3; 9

1 300 A 400 A 3 ET LSIG MAIN -- -- -- --

CKT AMPS FRAME P TRIP FEATURES LOAD DESCRIPTION NOTES

CONNECTED VA

PH A PH B PH C

LOAD

MAIN: MCB LOCATION: COMM/MECH/ELEC 104

BUS AMPS: 400 A MIN AIC RATING: 18,000 MOUNTING: SURFACE

VOLTAGE: 480Y/277 SPECIFICATION TYPE: DPB ENCLOSURE: TYPE 1

DISTRIBUTION PANELBOARD DP-90361001

S y m

A c ti o n

D e s c ri p ti o n

D a te

A p p v d

A

M E

N D

M E

N T

/1

B

K H

A

M E

N D

M E

N T

/1

B

K H

2 2

2 2

Sheets
E-100701E - ELECTRICAL SCHEDULES
E-903101E - FLOOR PLAN - LIGHTING
E-903111E - FLOOR PLAN - POWER
E-903601E - DIAGRAM - POWER ONE-LINE
E-903111E - FLOOR PLAN - POWER.pdf
Sheets
E-903111E - FLOOR PLAN - POWER
E-903701E - PANEL SCHEDULES
E-903601E - DIAGRAM - POWER ONE-LINE.pdf
Sheets
E-100701E - ELECTRICAL SCHEDULES
E-903101E - FLOOR PLAN - LIGHTING
E-903111E - FLOOR PLAN - POWER
E-903601E - DIAGRAM - POWER ONE-LINE
E-903701E - PANEL SCHEDULES.pdf
Sheets
E-903111E - FLOOR PLAN - POWER
E-903701E - PANEL SCHEDULES