26_21_00.02_00.pdf
PDF 66 KB Posted
- Attached to
- CLR039b Long Range Discrimination Radar Construction Package #2 ECF, Clear AFS, AK Federal contract opportunity
- Solicitation number
- W911KB18R0006
About this file
26 21 00.02 00
View the file
Other files for this federal contract opportunity
Show all 50
CLR039b Long Range Discrimination Radar Construction Package #2 ECF, Clear AFS, AK has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CP#2 Long Range Discrimination Radar (LRDR) CLR039b LRDR Complex Security - Clear AFS, Alaska AM#3
SECTION 26 21 00.02 00
EXTERIOR DISTRIBUTION SYSTEM
02/14
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM B1 (2013) Standard Specification for Hard-Drawn Copper Wire
ASTM B8 (2011) Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft
ASTM D709 (2013) Laminated Thermosetting Materials
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms
IEEE 515 (2011) Standard for the Testing, Design, Installation, and Maintenance of Electrical Resistance Heat Tracing for Industrial Applications
IEEE C2 (2012; Errata 2012; INT 1-4 2012; INT 5-7 2013; INT 8-10 2014; INT 11 2015) National Electrical Safety Code
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
NETA ATS (2013) Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
ANSI C80.1 (2005) American National Standard for Electrical Rigid Steel Conduit (ERSC)
NEMA 250 (2014) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA FU 1 (2012) Low Voltage Cartridge Fuses
NEMA ICS 1 (2000; R 2015) Standard for Industrial Control and Systems: General Requirements
NEMA ICS 6 (1993; R 2011) Enclosures
SECTION 26 21 00.02 00 Page 1
NEMA KS 1 (2013) Enclosed and Miscellaneous Distribution Equipment Switches (600 V Maximum)
NEMA RN 1 (2005; R 2013) Polyvinyl-Chloride (PVC) Externally Coated Galvanized Rigid Steel Conduit and Intermediate Metal Conduit
NEMA ST 20 (1992; R 1997) Standard for Dry-Type Transformers for General Applications
NEMA TC 14 (2002) Standard for Reinforced Thermosetting Resin Conduit (RTRC) and Fittings
NEMA TC 3 (2015) Standard for Polyvinyl Chloride (PVC) Fittings for Use With Rigid PVC Conduit and Tubing
NEMA TP 1 (2002) Guide for Determining Energy Efficiency for Distribution Transformers
NEMA WD 1 (1999; R 2005; R 2010) Standard for General Color Requirements for Wiring Devices
NEMA WD 6 (2012) Wiring Devices Dimensions Specifications
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2014; AMD 1 2013; Errata 1 2013; AMD 2 2013; Errata 2 2013; AMD 3 2014; Errata 3-4 2014; AMD 4-6 2014) National Electrical Code
NFPA 70E (2015; ERTA 1 2015) Standard for Electrical Safety in the Workplace
UNDERWRITERS LABORATORIES (UL)
UL 1242 (2006; Reprint Mar 2014) Standard for Electrical Intermediate Metal Conduit -- Steel
UL 1561 (2011; Reprint Jun 2015) Dry-Type General Purpose and Power Transformers
UL 1660 (2014) Liquid-Tight Flexible Nonmetallic Conduit
UL 198M (2003; Reprint Feb 2013) Standard for Mine-Duty Fuses
UL 360 (2013; Reprint Jan 2015) Liquid-Tight Flexible Steel Conduit
UL 4248-1 (2007; Reprint Oct 2013) UL Standard for
SECTION 26 21 00.02 00 Page 2
Safety Fuseholders - Part 1: General Requirements
UL 4248-12 (2007; Reprint Dec 2012) UL Standard for Safety Fuseholders - Part 12: Class R
UL 467 (2013; Reprint Jun 2017) UL Standard for Safety Grounding and Bonding Equipment
UL 486A-486B (2013; Reprint Feb 2014) Wire Connectors
UL 486C (2013; Reprint Feb 2014) Splicing Wire Connectors
UL 489 (2013; Reprint Mar 2014) Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-Breaker Enclosures
UL 498 (2012; Reprint Oct 2014) Attachment Plugs and Receptacles
UL 50 (2015) UL Standard for Safety Enclosures for Electrical Equipment, Non-Environmental Considerations
UL 510 (2005; Reprint Jul 2013) Polyvinyl Chloride, Polyethylene and Rubber Insulating Tape
UL 514B (2012; Reprint Nov 2014) Conduit, Tubing and Cable Fittings
UL 6 (2007; Reprint Nov 2014) Electrical Rigid Metal Conduit-Steel
UL 67 (2009; Reprint Apr 2015) Standard for Panelboards
UL 854 (2004; Reprint Nov 2014) Standard for Service-Entrance Cables
UL 869A (2006) Reference Standard for Service Equipment
UL 943 (2006; Reprint Jun 2012) Ground-Fault Circuit-Interrupters
1.2 DEFINITIONS
Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, are as defined in
IEEE 100 .
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.
SECTION 26 21 00.02 00 Page 3
Submittals with an "S" are for inclusion in the Sustainability Notebook, in conformance to Section 01 33 29.02 00 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00.02 00.
SD-02 Shop Drawings
Panelboards; G
Transformers; G
AM#2... Fiberglass Shelter; G ...AM#2
Include wiring diagrams and installation details of equipment indicating proposed location, layout and arrangement, control panels, accessories, and other items that must be shown to ensure a coordinated installation. Identify circuit terminals on wiring diagrams and indicate the internal wiring for each item of equipment and the interconnection between each item of equipment.
Indicate on the drawings adequate clearance for operation, maintenance, and replacement of operating equipment devices.
Self-Regulating Heat Trace; G
Include control diagrams, carrier pipe to conduit connection details and lighted end-seal mounting and support details.
SD-03 Product Data
Panelboards; G
Receptacles;
Circuit breakers; G
Switches;
Transformers; G
Intelligent Parking Lot Controller; G
Include performance and characteristic curves.
Self-Regulating Heat Trace; G
Including cables, controlling switches and contactors, pilot lights and related accessories. Include manufacturer's post-installation testing requirements.
AM#2... Fiberglass Shelter; G
Include wind and snow loading calculations with product information. ...AM#2
SD-06 Test Reports
600-volt wiring test; G
Transformer tests; G
SECTION 26 21 00.02 00 Page 4
Ground-fault receptacle test; G
Heat Trace Megger Test
SD-07 Certificates
Fuses; G
SD-09 Manufacturer's Field Reports
Transformer factory tests
SD-10 Operation and Maintenance Data
Electrical Systems, Data Package 5; G
Submit operation and maintenance data in accordance with Section 01 78 23.02 00, OPERATION AND MAINTENANCE DATA and as specified herein.
1.4 QUALITY ASSURANCE
1.4.1 Fuses
Submit coordination data as specified in paragraph, FUSES of this section.
1.4.2 Regulatory Requirements
In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "shall" or "must" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Provide equipment, materials, installation, and workmanship in accordance with the mandatory and advisory provisions of NFPA 70 unless more stringent requirements are specified or indicated.
1.4.3 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship and:
a. Have been in satisfactory commercial or industrial use for 2 years prior to bid opening including applications of equipment and materials under similar circumstances and of similar size.
b. Have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.
c. Where two or more items of the same class of equipment are required, provide products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.
1.4.3.1 Alternative Qualifications
Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than
SECTION 26 21 00.02 00 Page 5
6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.
1.4.3.2 Material and Equipment Manufacturing Date
Products manufactured more than 3 years prior to date of delivery to site are not acceptable.
1.5 MAINTENANCE
1.5.1 Electrical Systems
Submit operation and maintenance manuals for electrical systems that provide basic data relating to the design, operation, and maintenance of the electrical distribution system for the building. Include the following:
a. Single line diagram of the "as-built" building electrical system.
b. Schematic diagram of electrical control system (other than HVAC, covered elsewhere).
c. Manufacturers' operating and maintenance manuals on active electrical equipment.
1.6 WARRANTY
Provide equipment items supported by service organizations that are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.
1.7 SEISMIC REQUIREMENTS
Provide seismic details conforming to Section 26 05 48.02 10, SEISMIC
PROTECTION FOR ELECTRICAL EQUIPMENT.
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
As a minimum, meet requirements of UL, where UL standards are established for those items, and requirements of NFPA 70 for all materials, equipment, and devices.
2.2 CONDUIT AND FITTINGS
Conform to the following:
2.2.1 Rigid Metallic Conduit
2.2.1.1 Rigid, Threaded Zinc-Coated Steel Conduit
ANSI C80.1 , UL 6 .
2.2.2 Intermediate Metal Conduit (IMC)
UL 1242 , zinc-coated steel only.
SECTION 26 21 00.02 00 Page 6
2.2.3 Plastic-Coated Rigid Steel and IMC Conduit
NEMA RN 1, Type 40 (40 mils thick).
2.2.4 Liquid-Tight Flexible Metal Conduit
UL 360 .
2.2.5 Fittings for Flexible Metal Conduit
UL 514B . Ferrous fittings: cadmium- or zinc-coated in accordance with
UL 514B .
2.2.5.1 Fittings for Rigid Metal Conduit and IMC
Threaded-type. Split couplings unacceptable.
2.2.6 Fittings for Rigid Nonmetallic Conduit
NEMA TC 3 for PVC and NEMA TC 14 for fiberglass, and UL 514B .
2.2.7 HDPE Conduit
UL 1660 .
2.3 CABINETS, JUNCTION BOXES, AND PULL BOXES
Volume greater than 100 cubic inches, UL 50 , hot-dip, zinc-coated, if sheet steel.
2.3.1 Field Distribution Boxes with Internal Heater
See Section 33 71 02.02 00 UNDERGROUND ELECTRICAL DISTRIBUTION.
2.3.2 In-Grade Boxes
See Section 33 71 02.02 00 UNDERGROUND ELECTRICAL DISTRIBUTION.
2.3.3 At-Grade Enclosure
See Section 33 71 02.02 00 UNDERGROUND ELECTRICAL DISTRIBUTION.
2.4 WIRES AND CABLES
Provide wires and cables in accordance applicable requirements of NFPA 70 and UL for type of insulation, jacket, and conductor specified or indicated. Do not use wires and cables manufactured more than 12 months prior to date of delivery to site.
2.4.1 Conductors
Provide the following:
a. Conductor sizes and capacities shown are based on copper, unless indicated otherwise.
b. Conductors No. 8 AWG and larger diameter: stranded.
c. Conductors No. 10 AWG and smaller diameter: solid.
SECTION 26 21 00.02 00 Page 7
d. Conductors for remote control, alarm, and signal circuits, classes 1, 2, and 3: stranded unless specifically indicated otherwise.
e. All conductors: copper. Conductors indicated to be No. 6 AWG or smaller diameter: copper. Conductors indicated to be No. 4 AWG and larger diameter: copper.
2.4.1.1 Minimum Conductor Sizes
Provide minimum conductor size in accordance with the following:
a. Branch circuits: No. 12 AWG.
b. Class 1 remote-control and signal circuits: No. 14 AWG.
c. Class 2 low-energy, remote-control and signal circuits: No. 16 AWG.
d. Class 3 low-energy, remote-control, alarm and signal circuits: No. 22
AWG.
2.4.2 Color Coding
Provide color coding for service, feeder, branch, control, and signaling circuit conductors.
2.4.2.1 Ground and Neutral Conductors
Provide color coding of ground and neutral conductors as follows:
a. Grounding conductors: Green.
b. Neutral conductors: White.
c. Exception, where neutrals of more than one system are installed in same raceway or box, other neutrals color coding: white with a different colored (not green) stripe for each.
2.4.2.2 Ungrounded Conductors
Provide color coding of ungrounded conductors in different voltage systems as follows:
a. 208/120 volt, three-phase
(1) Phase A - black
(2) Phase B - red
(3) Phase C - blue
b. 480/277 volt, three-phase
(1) Phase A - brown
(2) Phase B - orange
(3) Phase C - yellow
SECTION 26 21 00.02 00 Page 8
2.4.3 Insulation
Unless specified or indicated otherwise or required by NFPA 70 , provide power and lighting wires rated for 600-volts, Type XHHW/XHHW-2.
2.4.4 Bonding Conductors
ASTM B1, solid bare copper wire for sizes No. 8 AWG and smaller diameter;
ASTM B8, Class B, stranded bare copper wire for sizes No. 6 AWG and larger diameter.
2.4.5 Service Entrance Cables
Service Entrance (SE) and Underground Service Entrance (USE) Cables, UL 854 .
2.4.6 Self-Regulating Heat Trace
Provide heat trace where shown on drawings. Heat trace cables shall be at least 10 watts per foot for underground locations and 12 watts per foot for heat trace at ECF (roof drains, VTRs, and wall discharge) unless noted otherwise. Provide with heat trace controls contactor, feed-in cables, mounting accessories, lighted end-seals and other required accessories for a complete and functional installation. Provide heat trace from a single manufacturer. Basis of Design is Raychem LBTV for underground locations and Raychem ICESTOP for ECF locations.
Heat trace systems for pipes, valves, and fittings shall be in accordance with IEEE 515 and be UL-listed.
Provide self-regulating heaters consisting of 10 AWG tinned-copper bus wires for underground locations and 16 AWG tinner-copper bus wires for ECF locations embedded in parallel in a self-regulating polymer core that varies its power output to respond to temperature along its length.
Heater shall be able to be crossed over itself without overheating and must be approved before used directly on plastic pipe. Heater shall be covered by a radiation cross-linked modified polyolefin jacket.
Provide heater with self-regulating factor of at least 90 percent, in order to provide energy conservation and to prevent overheating.
Heat trace shall operate on either 120, 240, or 277 volts without the use of transformers.
2.5 SPLICES AND TERMINATION COMPONENTS
UL 486A-486B for wire connectors and UL 510 for insulating tapes.
Connectors for No. 10 AWG and smaller diameter wires: insulated, pressure-type in accordance with UL 486A-486B or UL 486C (twist-on splicing connector). Provide solderless terminal lugs on stranded conductors.
2.6 SWITCHES
2.6.1 Disconnect Switches
NEMA KS 1. Provide heavy duty-type switches where indicated, where switches are rated higher than 240 volts, and for double-throw switches.
Utilize Class R fuseholders and fuses for fused switches, unless indicated otherwise. Provide horsepower rated for switches serving as the
SECTION 26 21 00.02 00 Page 9 motor-disconnect means. Provide switches in NEMA 3R enclosure per NEMA ICS 6 unless indicated otherwise. If switch is required to be rated higher than 10kA SCCR, provide manufacturer-approved current-limiting fuses and fuse rejection clips to obtain the required rating.
2.7 FUSES
NEMA FU 1. Provide complete set of fuses for each fusible switch.
Coordinate time-current characteristics curves of fuses serving motors or connected in series with circuit breakers or other circuit protective devices for proper operation. Submit coordination data for approval.
Provide fuses with a voltage rating not less than circuit voltage and interrupting rating not less than the calculated maximum fault current and rating of the device in which the fuses are installed.
2.7.1 Fuseholders
Provide in accordance with UL 4248-1 .
2.7.2 Cartridge Fuses, Current Limiting Type (Class R)
UL 198M , Class RK-5. Provide only Class R associated fuseholders in accordance with UL 4248-12 .
2.7.3 Cartridge Fuses, High-Interrupting Capacity, Current Limiting Type (Classes J, L, and CC)
UL 198M , Class J for zero to 600 amperes, Class L for 601 to 6,000 amperes, and Class CC for zero to 30 amperes.
2.7.4 Cartridge Fuses, Current Limiting Type (Class T)
UL 198M , Class T for zero to 1,200 amperes, 300 volts; and zero to 800 amperes, 600 volts.
2.8 RECEPTACLES
Provide the following:
a. UL 498 , hard use (also designated heavy-duty), grounding-type.
b. Ratings and configurations: as indicated.
c. Bodies: ivory as per NEMA WD 1.
d. Face and body: thermoplastic supported on a metal mounting strap.
e. Dimensional requirements: per NEMA WD 6.
f. Screw-type, side-wired wiring terminals or of the solderless pressure type having suitable conductor-release arrangement.
g. Grounding pole connected to mounting strap.
h. The receptacle: containing triple-wipe power contacts and double or triple-wipe ground contacts.
SECTION 26 21 00.02 00 Page 10
2.8.1 Head Bolt Receptacles
Receptacles serving headbolt heaters are special purpose. Provide weatherproof receptacles with Intelligent Parking Lot Controller Model M210 or Government-approved substitute. Receptacle circuit shall be protected by GFCI circuit breaker. Provide two optical based portable programming units IPLC Data-Mates for owner use.
2.8.2 Weatherproof Receptacles
Provide receptacles, UL listed for use in "wet locations." Include cast metal box with gasketed, hinged, lockable and weatherproof while-in-use, die-cast metal/aluminum cover plate.
2.8.3 Ground-Fault Circuit Interrupter Receptacles
UL 943 , duplex type for mounting in standard outlet box. Provide device capable of detecting current leak of 6 milliamperes or greater and tripping per requirements of UL 943 for Class A ground-fault circuit interrupter devices. Provide screw-type, side-wired wiring terminals or pre-wired (pigtail) leads.
2.9 PANELBOARDS
Provide panelboards in accordance with the following:
a. UL 67 and UL 50 having a short-circuit current rating as indicated.
b. Panelboards for use as service disconnecting means: additionally conform to UL 869A .
c. Panelboards: circuit breaker-equipped.
d. Designed such that individual breakers can be removed without disturbing adjacent units or without loosening or removing supplemental insulation supplied as means of obtaining clearances as required by UL.
e. Where "space only" is indicated, make provisions for future installation of breakers.
f. Directories: indicate load served by each circuit in panelboard.
g. Panelboards: listed and labeled for their intended use.
h. Directories: indicate source of service (upstream panel) to panelboard.
i. Type directories and mount in holder behind transparent protective covering.
j. Panelboard nameplates: provided in accordance with paragraph FIELD
FABRICATED NAMEPLATES.
2.9.1 Enclosure
Provide panelboard enclosure in accordance with the following:
a. UL 50 .
SECTION 26 21 00.02 00 Page 11
b. Cabinets mounted outdoors or flush-mounted: hot-dipped galvanized after fabrication.
c. Cabinets: painted in accordance with paragraph PAINTING.
d. Outdoor cabinets: NEMA 3R raintight with conduit hubs welded to the cabinet.
e. Front edges of cabinets: form-flanged or fitted with structural shapes welded or riveted to the sheet steel, for supporting the panelboard front.
f. All cabinets: fabricated such that no part of any surface on the finished cabinet deviates from a true plane by more than 1/8 inch.
g. Holes: provided in the back of indoor surface-mounted cabinets, with outside spacers and inside stiffeners, for mounting the cabinets with a 1/2 inch clear space between the back of the cabinet and the wall surface.
h. Flush doors: mounted on hinges that expose only the hinge roll to view when the door is closed.
i. Each door: fitted with a combined catch and lock, except that doors over 24 inches long provided with a three-point latch having a knob with a T-handle, and a cylinder lock.
j. Keys: two provided with each lock, with all locks keyed alike.
k. Finished-head cap screws: provided for mounting the panelboard fronts on the cabinets.
l. Provide with internal heater.
2.9.2 Panelboard Buses
Support bus bars on bases independent of circuit breakers. Design main buses and back pans so that breakers may be changed without machining, drilling, or tapping. Provide isolated neutral bus in each panel for connection of circuit neutral conductors. Provide separate ground bus identified as equipment grounding bus per UL 67 for connecting grounding conductors; bond to steel cabinet.
2.9.2.1 Panelboard Neutrals for Non-Linear Loads
Provide in accordance with the following:.
a. UL listed, with panelboard type specifically UL heat rise tested for use on non-linear loads.
b. Panelboard: heat rise tested in accordance with UL 67 , except with the neutral assembly installed and carrying 200 percent of the phase bus current during testing.
c. Verification of the testing procedure: provided upon request.
d. Two neutral assemblies paralleled together with cable is not acceptable.
SECTION 26 21 00.02 00 Page 12
e. Nameplates for panelboard rated for use on non-linear loads: marked "SUITABLE FOR NON-LINEAR LOADS" and in accordance with paragraph FIELD
FABRICATED NAMEPLATES.
f. Provide a neutral label with instructions for wiring the neutral of panelboards rated for use on non-linear loads.
2.9.3 Circuit Breakers
UL 489 , thermal magnetic-type having a minimum short-circuit current rating equal to the short-circuit current rating of the panelboard in which the circuit breaker will be mounted. Breaker terminals: UL listed as suitable for type of conductor provided. Where indicated on the drawings, provide circuit breakers with shunt trip devices. Series rated circuit breakers and plug-in circuit breakers are unacceptable.
2.9.3.1 Multipole Breakers
Provide common trip-type with single operating handle. Design breaker such that overload in one pole automatically causes all poles to open.
Maintain phase sequence throughout each panel so that any three adjacent breaker poles are connected to Phases A, B, and C, respectively.
2.9.3.2 Circuit Breaker With Ground-Fault Circuit Interrupter
UL 943 and NFPA 70 . Provide with "push-to-test" button, visible indication of tripped condition, and ability to detect and trip on current imbalance of 6 milliamperes or greater per requirements of UL 943 for Class A ground-fault circuit interrupter.
2.9.3.3 Circuit Breakers at Field Distribution Box (FDB)
Provide DIN rail-mounted circuit breakers for security equipment within each FDB.
2.10 TRANSFORMERS
Provide transformers in accordance with the following:
a. NEMA ST 20 , general purpose, dry-type, self-cooled, ventilated.
b. Provide transformers in NEMA 3R enclosure.
c. Transformer insulation system:
(1) 220 degrees C insulation system for transformers 15 kVA and greater, with temperature rise not exceeding 150 degrees C under full-rated load in maximum ambient of 40 degrees C.
(2) 180 degrees C insulation for transformers rated 10 kVA and less, with temperature rise not exceeding 150 degrees C under full-rated load in maximum ambient of 40 degrees C.
d. Transformer of 115 degrees C temperature rise: capable of carrying continuously 115 percent of nameplate kVA without exceeding insulation rating.
SECTION 26 21 00.02 00 Page 13
e. Transformers: quiet type with maximum sound level at least 3 decibels less than NEMA standard level for transformer ratings indicated.
2.10.1 Specified Transformer Efficiency
Transformers, indicated and specified with: 480V primary, 80 degrees C or 115 degrees C temperature rise, kVA ratings of 37.5 to 100 for single phase or 30 to 500 for three phase, energy efficient type. Minimum efficiency, based on factory test results: not be less than NEMA Class 1 efficiency as defined by NEMA TP 1 .
2.10.2 Transformers With Non-Linear Loads
Provide transformers for non-linear loads in accordance with the following:
a. Transformer insulation: UL recognized 220 degrees C system. Neither the primary nor the secondary temperature is allowed to exceed 220 degrees C at any point in the coils while carrying their full rating of non-sinusoidal load.
b. Transformers are to be UL listed and labeled for K-13 K-Factor rating in accordance with UL 1561 .
c. Transformers evaluated by the UL K-Factor evaluation: listed for 115 degrees C average temperature rise only.
d. Transformers with K-Factor ratings with temperature rise of 150 degrees C rise are not acceptable.
e. K-Factor rated transformers impedance: allowed range of 3 percent to 5 percent, with a minimum reactance of 2 percent to prevent excessive neutral current when supplying loads with large amounts of third harmonic.
2.10.3 Outdoor Transformers
a. Dry type, size as shown on drawings.
b. Provide with NEMA 4X enclosure.
2.11 GROUNDING AND BONDING EQUIPMENT
2.11.1 Ground Rods
UL 467 . Ground rods: copper-clad steel, with minimum diameter of 3/4 inch and minimum length 20 feet. Sectional ground rods are permitted.
2.12 MANUFACTURER'S NAMEPLATE
Provide on each item of equipment a nameplate bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.
2.13 FIELD FABRICATED NAMEPLATES
Provide field fabricated nameplates in accordance with the following:
a. ASTM D709.
SECTION 26 21 00.02 00 Page 14
b. Provide laminated plastic nameplates for each equipment enclosure, relay, switch, and device; as specified or as indicated on the drawings.
c. Each nameplate inscription: identify the function and, when applicable, the position.
d. Nameplates: melamine plastic, 0.125 inch thick, white with black center core.
f. Surface: matte finish. Corners: square. Accurately align lettering and engrave into the core.
g. Minimum size of nameplates: one by 2.5 inches.
h. Lettering size and style: a minimum of 0.25 inch high normal block style.
2.14 WARNING SIGNS
Provide warning signs for arc flash protection in accordance with Section 26 28 01.02 10 COORDINATED POWER SYSTEM PROTECTION STUDY. Provide field installed signs to warn qualified persons of potential electric arc flash hazards when warning signs are not provided by the manufacturer. Provide marking that is clearly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment.
2.15 FACTORY APPLIED FINISH
Provide factory-applied finish on electrical equipment in accordance with the following:
a. NEMA 250 corrosion-resistance test and the additional requirements as specified herein.
b. Interior and exterior steel surfaces of equipment enclosures:
thoroughly cleaned followed by a rust-inhibitive phosphatizing or equivalent treatment prior to painting.
c. Exterior surfaces: free from holes, seams, dents, weld marks, loose scale or other imperfections.
d. Interior surfaces: receive not less than one coat of corrosion-resisting paint in accordance with the manufacturer's standard practice.
e. Exterior surfaces: primed, filled where necessary, and given not less than two coats baked enamel with semigloss finish.
f. Equipment located outdoors: ANSI Light Gray.
g. Provide manufacturer's coatings for touch-up work and as specified in paragraph FIELD APPLIED PAINTING.
SECTION 26 21 00.02 00 Page 15
2.16 SOURCE QUALITY CONTROL
2.16.1 Transformer Factory Tests
Submittal: include routine NEMA ST 20 transformer test results on each transformer and also provide the results of NEMA "design" and "prototype" tests that were made on transformers electrically and mechanically equal to those specified.
2.17 COORDINATED POWER SYSTEM PROTECTION
Prepare analyses as specified in Section 26 28 01.02 10 COORDINATED POWER
SYSTEM PROTECTION.
AM#2... 2.18 FIBERGLASS SHELTER
Provide walk-in shelter to house panel and connection points for Near Field Antenna (NFA) testing. Shelter shall be large enough to maintain NEC panel clearance as well as to allow a 6'-0" tall person to walk inside this building without striking equipment or ceiling mounted appurtenances. Shelter shall be construted of corrosion-resistant non-metallic materials with non-magnetic stainless steel hardware, and be able to support the snow and wind loads at Clear AFS. ...AM#2 AM#3...
Provide 6-inch continuously poured concrete slab floor extending 3-inches all sides beyond the shelter. Anchor shelter to slab in accordance with calculations. Finish floor level shall be 3 inches above finish grade.
Shelter door shall be 36 inches wide by 80 inches tall ...AM#3
PART 3 EXECUTION
3.1 INSTALLATION
Electrical installations, including weatherproof and hazardous locations and ducts, plenums and other air-handling spaces: conform to requirements of NFPA 70 and IEEE C2 and to requirements specified herein.
3.1.1 Underground Service
Underground service conductors and associated conduit: continuous from service entrance equipment to outdoor power system connection.
3.1.2 Service Entrance Identification
Service entrance disconnect devices, switches, and enclosures: labeled and identified as such.
3.1.2.1 Labels
Wherever work results in service entrance disconnect devices in more than one enclosure, as permitted by NFPA 70 , label each enclosure, new and existing, as one of several enclosures containing service entrance disconnect devices. Label, at minimum: indicate number of service disconnect devices housed by enclosure and indicate total number of enclosures that contain service disconnect devices. Provide laminated plastic labels conforming to paragraph FIELD FABRICATED NAMEPLATES. Use lettering of at least 0.25 inch in height, and engrave on black-on-white matte finish. Service entrance disconnect devices in more than one enclosure: provided only as permitted by NFPA 70 .
SECTION 26 21 00.02 00 Page 16
3.1.3 Wiring Methods
Provide insulated conductors installed in rigid steel conduit, or rigid nonmetallic conduit, except where specifically indicated or specified otherwise or required by NFPA 70 to be installed otherwise. Grounding conductor: separate from electrical system neutral conductor. Provide insulated green equipment grounding conductor for circuit(s) installed in conduit and raceways. Shared neutral, or multi-wire branch circuits, are not permitted with arc-fault circuit interrupters. Minimum conduit size:
1/2 inch in diameter for low voltage lighting and power circuits.
Vertical distribution in multiple story buildings: made with metal conduit in fire-rated shafts, with metal conduit extending through shafts for minimum distance of 6 inches.
3.1.3.1 Pull Wire
Install pull wires in empty conduits. Pull wire: plastic having minimum 200-pound force tensile strength. Leave minimum 36 inches of slack at each end of pull wire.
3.1.3.2 Heat Trace Installation
Heat trace shall be continuous between access points. Heat trace cable for underground piping shall run in channel per details and specifications. Heat trace cable for roof drains shall be installed per details and specifications.
3.1.4 Conduit Installation
Unless indicated otherwise, conceal conduit under floor slabs and within finished walls, ceilings, and floors. Keep conduit minimum 6 inches away from parallel runs of flues and steam or hot water pipes. Install conduit parallel with or at right angles to ceilings, walls, and structural members where located above accessible ceilings and where conduit will be visible after completion of project. Underground conduits for branch circuits and headbolt heater feeder shall be direct-buried HDPE unless indicated otherwise on the drawings.
3.1.4.1 Restrictions Applicable to Nonmetallic Conduit
a. PVC Schedule 40 and PVC Schedule 80
(1) Do not use in areas where subject to severe physical damage, including but not limited to, mechanical equipment rooms, electrical equipment rooms, hospitals, power plants, missile magazines, and other such areas.
(2) Do not use in hazardous (classified) areas.
(3) Do not use in fire pump rooms.
(4) Do not use in penetrating fire-rated walls or partitions, or fire-rated floors.
(5) Do not use above grade, except where allowed in this section for rising through floor slab or indicated otherwise.
(6) Do not use when the enclosed conductors must be shielded from the effects of High-altitude Electromagnetic Pulse (HEMP).
SECTION 26 21 00.02 00 Page 17
3.1.4.2 Restrictions Applicable to Flexible Conduit
Use only as specified in paragraph FLEXIBLE CONNECTIONS. Do not use when the enclosed conductors must be shielded from the effects of High-altitude Electromagnetic Pulse (HEMP).
3.1.4.3 Underground Conduit
Plastic-coated rigid steel; plastic-coated steel IMC; HDPE; PVC, Type EPC-40; or fiberglass. Convert nonmetallic conduit, other than PVC Schedule 40 or 80, to plastic-coated rigid, or IMC, steel conduit before rising through floor slab. Plastic coating: extend minimum 6 inches above floor.
3.1.4.4 Conduit Through Floor Slabs
Where conduits rise through floor slabs, do not allow curved portion of bends to be visible above finished slab.
3.1.4.5 Conduit Installed in Concrete Floor Slabs
Rigid steel; steel IMC; fiberglass, or PVC, Type EPC-40. Locate so as not to adversely affect structural strength of slabs. Install conduit within middle one-third of concrete slab. Do not stack conduits. Do not stack conduits more than two diameters high with minimum vertical separation of 6 inches. Space conduits horizontally not closer than three diameters, except at cabinet locations. Curved portions of bends must not be visible above finish slab. Increase slab thickness as necessary to provide minimum one inch cover over conduit. Where embedded conduits cross building and/or expansion joints, provide suitable watertight expansion/deflection fittings and bonding jumpers. Expansion/deflection fittings must allow horizontal and vertical movement of raceway. Conduit larger than one inch trade size: installed parallel with or at right angles to main reinforcement; when at right angles to reinforcement, install conduit close to one of supports of slab. Where nonmetallic conduit is used, convert raceway to plastic coated rigid steel or plastic coated steel IMC before rising above floor, unless specifically indicated.
3.1.4.6 Stub-Ups
Provide conduits stubbed up through concrete floor for connection to free-standing equipment with adjustable top or coupling threaded inside for plugs, set flush with finished floor. Extend conductors to equipment in rigid steel conduit, except that flexible metal conduit may be used 6 inches above floor. Where no equipment connections are made, install screwdriver-operated threaded flush plugs in conduit end.
3.1.4.7 Directional Changes in Conduit Runs
Make changes in direction of runs with symmetrical bends or cast-metal fittings. Make field-made bends and offsets with hickey or conduit-bending machine. Do not install crushed or deformed conduits.
Avoid trapped conduits. Prevent plaster, dirt, or trash from lodging in conduits, boxes, fittings, and equipment during construction. Free clogged conduits of obstructions.
SECTION 26 21 00.02 00 Page 18
3.1.4.8 Locknuts and Bushings
Fasten conduits to sheet metal boxes and cabinets with two locknuts where required by NFPA 70 , where insulated bushings are used, and where bushings cannot be brought into firm contact with the box; otherwise, use at least minimum single locknut and bushing. Provide locknuts with sharp edges for digging into wall of metal enclosures. Install bushings on ends of conduits, and provide insulating type where required by NFPA 70 .
3.1.4.9 Flexible Connections
Provide flexible steel conduit between 3 and 6 feet in length for recessed and semirecessed lighting fixtures; for equipment subject to vibration, noise transmission, or movement; and for motors. Install flexible conduit to allow 20 percent slack. Minimum flexible steel conduit size: 1/2 inch diameter. Provide liquidtight flexible conduit in wet and damp locations for equipment subject to vibration, noise transmission, movement or motors. Provide separate ground conductor across flexible connections.
3.1.5 Boxes, Outlets, and Supports
Provide boxes in wiring and raceway systems wherever required for pulling of wires, making connections, and mounting of devices or fixtures. Boxes for metallic raceways: cast-metal, hub-type when located in wet locations, when surface mounted on outside of exterior surfaces, and when specifically indicated. Boxes in other locations: sheet steel, except that aluminum boxes may be used with aluminum conduit, and nonmetallic boxes may be used with nonmetallic conduit system. Provide each box with volume required by NFPA 70 for number of conductors enclosed in box.
Boxes for mounting lighting fixtures: minimum 4 inches square, or octagonal, except that smaller boxes may be installed as required by fixture configurations, as approved. Boxes for use in masonry-block or tile walls: square-cornered, tile-type, or standard boxes having square-cornered, tile-type covers. Provide gaskets for cast-metal boxes installed in wet locations and boxes installed flush with outside of exterior surfaces. Provide separate boxes for flush or recessed fixtures when required by fixture terminal operating temperature; provide readily removable fixturesfor access to boxes unless ceiling access panels are provided. Support boxes and pendants for surface-mounted fixtures on suspended ceilings independently of ceiling supports. Fasten boxes and supports with wood screws on wood, with bolts and expansion shields on concrete or brick, with toggle bolts on hollow masonry units, and with machine screws or welded studs on steel. Threaded studs driven in by powder charge and provided with lockwashers and nuts or nail-type nylon anchors may be used in lieu of wood screws, expansion shields, or machine screws. In open overhead spaces, cast boxes threaded to raceways need not be separately supported except where used for fixture support; support sheet metal boxes directly from building structure or by bar hangers.
Where bar hangers are used, attach bar to raceways on opposite sides of box, and support raceway with approved-type fastener maximum 24 inches from box. When penetrating reinforced concrete members, avoid cutting reinforcing steel.
3.1.5.1 Boxes
Boxes for use with raceway systems: minimum 1 1/2 inches deep, except where shallower boxes required by structural conditions are approved.
Boxes for other than lighting fixture outlets: minimum 4 inches square, except that 4 by 2 inch boxes may be used where only one raceway enters
SECTION 26 21 00.02 00 Page 19 outlet.
3.1.5.2 Pull Boxes
Construct of at least minimum size required by NFPA 70 of code-gauge aluminum or galvanized sheet steel, except where cast-metal boxes are required in locations specified herein. Provide boxes with screw-fastened covers. Where several feeders pass through common pull box, tag feeders to indicate clearly electrical characteristics, circuit number, and panel designation.
3.1.6 Conductor Identification
Provide conductor identification within each enclosure where tap, splice, or termination is made. For conductors No. 6 AWG and smaller diameter, provide color coding by factory-applied, color-impregnated insulation.
For conductors No. 4 AWG and larger diameter, provide color coding by plastic-coated, self-sticking markers; colored nylon cable ties and plates; or heat shrink-type sleeves. Identify control circuit terminations in accordance with manufacturer's recommendations. Provide telecommunications system conductor identification as specified in Section
27 10 00.02 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEMS.
3.1.6.1 Marking Strips
Provide marking strips in accordance with the following:
a. Provide white or other light-colored plastic marking strips, fastened by screws to each terminal block, for wire designations.
b. Use permanent ink for the wire numbers
c. Provide reversible marking strips to permit marking both sides, or provide two marking strips with each block.
d. Size marking strips to accommodate the two sets of wire numbers.
e. Assign a device designation in accordance with NEMA ICS 1 to each device to which a connection is made. Mark each device terminal to which a connection is made with a distinct terminal marking corresponding to the wire designation used on the Contractor's schematic and connection diagrams.
f. The wire (terminal point) designations used on the Contractor's wiring diagrams and printed on terminal block marking strips may be according to the Contractor's standard practice; however, provide additional wire and cable designations for identification of remote (external) circuits for the Government's wire designations.
3.1.7 Splices
Make splices in accessible locations. Make splices in conductors No. 10 AWG and smaller diameter with insulated, pressure-type connector. Make splices in conductors No. 8 AWG and larger diameter with solderless connector, and cover with insulation material equivalent to conductor insulation.
SECTION 26 21 00.02 00 Page 20
3.1.8 Covers
Install with edges in continuous contact with finished wall surfaces without use of mats or similar devices. Plaster fillings are not permitted. Install plates with alignment tolerance of 1/16 inch. Use of sectional-type device plates are not permitted. Provide gasket for plates installed in wet locations.
3.1.9 Grounding and Bonding
See Section 26 20 00.02 00 INTERIOR DISTRIBUTION SYSTEM and 33 71 02.02 00 UNDERGROUND ELECTRICAL DISTRIBUTION for specific requirements.
3.2 FIELD FABRICATED NAMEPLATE MOUNTING
Provide number, location, and letter designation of nameplates as indicated. Fasten nameplates to the device with a minimum of two sheet-metal screws or two rivets.
3.3 WARNING SIGN MOUNTING
Provide the number of signs required to be readable from each accessible side. Space the signs in accordance with NFPA 70E.
3.4 FIELD APPLIED PAINTING
Paint electrical equipment as required to match finish of adjacent surfaces or to meet the indicated or specified safety criteria.
Painting: as specified in Section 09 90 00.02 00 PAINTS AND COATINGS.Where field painting of enclosures for panelboards or the like is specified to match adjacent surfaces, to correct damage to the manufacturer's factory applied coatings, or to meet the indicated or specified safety criteria, provide manufacturer's recommended coatings and apply in accordance to manufacturer's instructions.
3.5 FIELD QUALITY CONTROL
Furnish test equipment and personnel and submit written copies of test results. Give Contracting Officer 5 working days notice prior to tests.
3.5.1 Devices Subject to Manual Operation
Operate each device subject to manual operation at least five times, demonstrating satisfactory operation each time.
3.5.2 600-Volt Wiring Test
Test wiring rated 600 volt and less to verify that no short circuits or accidental grounds exist. Perform insulation resistance tests on wiring No. 6 AWG and larger diameter using instrument which applies voltage of approximately 500 volts to provide direct reading of resistance. Minimum resistance: 250,000 ohms.
3.5.3 Transformer Tests
Perform the standard, not optional, tests in accordance with the Inspection and Test Procedures for transformers, dry type, air-cooled, 600 volt and below; as specified in NETA ATS. Measure primary and secondary voltages for proper tap settings. Tests need not be performed by a
SECTION 26 21 00.02 00 Page 21 recognized independent testing firm or independent electrical consulting firm.
3.5.4 Ground-Fault Receptacle Test
Test ground-fault receptacles with a "load" (such as a plug in light) to verify that the "line" and "load" leads are not reversed.
3.5.5 Heat Trace Megger Test
Test heat trace in accordance with manufacturer's recommendations after arrival on site, pre- and post-installation to verify there are no faults within the cable installation.
AM#2... 3.6 FIBERGLASS SHELTER
Install and inspect shelter in accordance with manufacturer's recommendations. ...AM#2
-- End of Section --
SECTION 26 21 00.02 00 Page 22
File details come from the government source that posted it.