About this file

Revised Specification

View the file

Other files for this federal contract opportunity

Other files attached to CLR039b Long Range Discrimination Radar Construction Package #2 ECF, Clear AFS, AK, newest first.
File Type Posted
01_19_30_02_29_Attachment_f.pdf PDF
01_50_00_02_00_Attachment_a.pdf PDF
01_19_30_02_29_Attachment_a.pdf PDF
01_19_30_02_29_Attachment_g.pdf PDF
05_40_00.02_00.pdf PDF
08_44_23.02_00.pdf PDF
G-100003E_Location_and_Vicinity_Map.pdf PDF
01_19_30.02_29.pdf PDF
01_11_00.02_00.pdf PDF
28_23_23.02_10.pdf PDF
09_29_00.02_00.pdf PDF
Revised_M_Drawings.pdf PDF
Revised_TY_Drawings.pdf PDF
EG100101E_SITE_PLAN_-_GROUNDING.pdf PDF
Schedule_of_Drawings_AM__3_Sheet_2.pdf PDF
01_50_00.02_00.pdf PDF
Final_Presentation--Pre-Proposal_Site_Visit--20180515_Slide_5_Date_Corrections.pdf PDF
01_33_29.02_00.pdf PDF
Revised_E-1_Drawings.pdf PDF
T-100701E_TELECOM_CABLE_SCHEDULE_MISSION_SUPPORT_-_RACEWAYS.pdf PDF
34_71_13.02_16.pdf PDF
26_21_00.02_00.pdf PDF
Revised_E-9_Drawings.pdf PDF
23_05_93.02_00.pdf PDF
01_45_35.02_00.pdf PDF
W911KB18R0006_AM_3.pdf PDF
Revised_T_Drawings.pdf PDF
Revised_Security_Drawings.pdf PDF
G-100005E_Contractor_Laydown_Areas.pdf PDF
Site_Visit_Sign_In_Sheet.pdf PDF
W911KB18R0006_AM_2.pdf PDF
33_71_02.02_00.pdf PDF
EG100101E_-_SITE_PLAN_-_GROUNDING.pdf PDF
01_91_10.02_29.pdf PDF
28_23_23.02_10.pdf PDF
Final_Presentation--Pre-Proposal_Site_Visit--20180515.pdf PDF
C_Drawing_revisions.pdf PDF
Revised_E_Drawings.pdf PDF
A_Drawing_Revisions.pdf PDF
28_20_00.02_00.pdf PDF
Revised_E-9_Drawings.pdf PDF
28_20_01.02_10.pdf PDF
Revised_Site_Plan_Drawings.pdf PDF
W911KB18R0006_AM_1.pdf PDF
JA_for_Vindictor_LRDR_ECF_Redacted.pdf PDF
JA_Edwards_EST3_fire_Panel_CP_2_ECF_Redacted.pdf PDF
CLR_LRDR_CP2_Rev2_RTA_Drawings_22x34.pdf PDF
CP2_RTA_SPECS_V3_CLR039_18-0410.pdf PDF
CP2_RTA_SPECS_V4_CLR039_18-0410.pdf PDF
W911KB18R0006.pdf PDF
Show all 50

CLR039b Long Range Discrimination Radar Construction Package #2 ECF, Clear AFS, AK has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CP#2 Long Range Discrimination Radar (LRDR) CLR039b LRDR Complex Security - Clear AFS, Alaska AM#2

SECTION 08 88 36.02 00

DYNAMIC GLAZING

08/11

PART 1 GENERAL

1.1 SUSTAINABILITY REQUIREMENTS

The materials in this Specification section are part of the overall compliance with ( HPSB) "High Performance and Sustainable Buildings" "guiding principles for stainable new construction and major renovations". Refer to Specification Section 01 33 29.02 00 - SUSTAINABLE DESIGN REQUIREMENTS, and this Section for more information.

1.2 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)

ANSI Z97.1 (2009; Errata 2010) Safety Glazing Materials Used in Buildings - Safety Performance Specifications and Methods of Test

ASTM INTERNATIONAL (ASTM)

ASTM C1036 (2010; E 2012) Standard Specification for Flat Glass

ASTM C1172 (2014) Standard Specification for Laminated Architectural Flat Glass

ASTM C509 (2006; R 2011) Elastomeric Cellular Preformed Gasket and Sealing Material

ASTM C920 (2014a) Standard Specification for Elastomeric Joint Sealants

ASTM D395 (2014) Standard Test Methods for Rubber Property - Compression Set

ASTM E1300 (2012a; E 2012) Determining Load Resistance of Glass in Buildings

GLASS ASSOCIATION OF NORTH AMERICA (GANA)

GANA Glazing Manual (2004) Glazing Manual

GANA Sealant Manual (2008) Sealant Manual

HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS (HPSB)

HPSB (2008) Guiding Principles for Sustainable New Construction and Major Renovations

SECTION 08 88 36.02 00 Page 1

INSULATING GLASS MANUFACTURERS ALLIANCE (IGMA)

IGMA TB-3001 (2001) Guidelines for Sloped Glazing

IGMA TM-3000 (1990; R 2004) North American Glazing Guidelines for Sealed Insulating Glass Units for Commercial & Residential Use

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

16 CFR 1201 Safety Standard for Architectural Glazing Materials

1.3 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability Notebook, in conformance to Section 01 33 29.02 00 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00.02 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Installation; G, PR

Drawings showing complete details of the proposed setting methods, mullion details, edge blocking, size of openings, frame details, materials, and types and thickness of glass.

AM#2... Drawings showing cables, cable routing, components, location of connections, and wiring through frames. ...AM#2

SD-03 Product Data

Insulating Glass; G

Exterior Glazing - performance documentation for all glass types

Glazing Accessories, G

Manufacturer's descriptive product data, handling and storage recommendations, installation instructions, and cleaning instructions.

SD-04 Samples

Dynamic Glass; G

Sealant, G

Three samples of each indicated material.

SECTION 08 88 36.02 00 Page 2

SD-07 Certificates

Insulating Glass

Dynamic Glass, G

SD-08 Manufacturer's Instructions

Setting and Sealing Materials, G

Glass Setting, G

Submit glass manufacturer's recommendations for setting and sealing materials and for installation of each type of glazing material specified.

SD-11 Closeout Submittals

Sustainability Reporting; G, S

1.4 DEFINITIONS

Refer to Division 8 for industry standard glass and glazing definitions.

The following apply to this section:

a. Busbar: Electrically conductive metal strip to apply voltage across electrochromic surface of insulated glass units.

b. IGU Pigtail: Wire extending from individual special function insulating glass units.

c. Tinted: Dynamic tint state with a lower visible light transmission.

d. Clear: Dynamic tint state with highest visible light transmission.

e. Inboard Lite: Pane of IGU that faces interior of building.

f. Outboard Lite: Pane of IGU that faces exterior of building.

g. Laminated Glass: Two sheets of monolithic glass bonded together with plastic interlayer by heat and pressure.

h. Normal Thermal Movement: Resulting from ambient temperature range of 120 degrees F and from consequent temperature range within glass and glass framing members of 180 degrees F.

i. Laminated Glass Deterioration: Defects materially obstructing vision through glass including edge separation or delamination or loss of tinting function.

1.5 SYSTEM DESCRIPTION

Fabricate and install watertight and airtight glazing systems to withstand thermal movement and wind loading without glass breakage, gasket failure, deterioration of glazing accessories, or defects in the work. Glazed panels must comply with the safety standards, in accordance with ANSI Z97.1 , and comply with indicated wind/snow loading in accordance with ASTM E1300.

1.6 DELIVERY, STORAGE, AND HANDLING

Deliver products to the site in unopened containers, labeled plainly with manufacturers' names and brands. Store glass and setting materials in safe, enclosed dry locations and do not unpack until needed for installation. Handle and install materials in a manner that will protect

SECTION 08 88 36.02 00 Page 3 them from damage.

1.7 SUSTAINABILITY REPORTING

Materials in this technical specification may contribute towards contract compliance with sustainability requirements. See Section 01 33 29.02 00 SUSTAINABILITY REPORTING for project HPSB, low-emitting materials, recycled content, and HPSB documentation.

1.8 ENVIRONMENTAL REQUIREMENTS

Do not start glazing work until the outdoor temperature is above 40 degrees F and rising, unless procedures recommended by the glass manufacturer and approved by the Contracting Officer are made to warm the glass and rabbet surfaces. Provide ventilation to prevent condensation of moisture on glazing work during installation. Do not perform glazing work during damp or rainy weather.

1.9 WARRANTY

1.9.1 Warranty for Insulating Glass Units

Warranty insulating glass units against development of material obstruction to vision (such as dust, fogging of delamination glass, or film formation on the inner glass surfaces) caused by failure of the hermetic seal, other than through glass breakage or failure of electrochromatic coating to tint, for a 5-year period following acceptance of the work. Provide new units for any units failing to comply with terms of this warranty within 45 working days after receipt of notice from the Government.

1.10 SYSTEM START-UP/OWNER INSTRUCTIONS/COMMISSIONING

Provide start up, commissioning and Owner instructions to ensure system functions and is used properly.

PART 2 PRODUCTS

2.1 GLASS

ASTM C1036, unless specified otherwise. In doors and sidelights, provide safety glazing material conforming to 16 CFR 1201 .

2.1.1 Heat Absorbing Glass

Type I, Class 2 (heat and light reducing, Quality q3 (select), 1/4 inch thick, clear 50 percent minimum light transmittance, conforming to ASTM C1036. Provide electrochromatic coating on inside face at all exterior glass lites.

2.1.2 Laminated Glass

ASTM C1172, Kind LA fabricated from two nominal 1/8 inch pieces of Type I, Class 1, Quality q3, flat annealed transparent glass conforming to ASTM C1036. Flat glass must be laminated together with a minimum of 0.060 inch thick, clear polyvinyl butyral interlayer with a total nominal thickness of 1/4 inch.

SECTION 08 88 36.02 00 Page 4

2.2 DYNAMIC COATING

Electrochromatic coating that darkens with electrification. Darkness intensity variable. Provide controllers to control each elevation exposure of building independently.

2.3 INSULATING GLASS UNITS

2.3.1 Buildings

2.3.1.1 Insulated Dynamic Glass (Type "IDG")

The inner lite must be ASTM C1172, Kind "LA" laminated glass, Type I, Class 1 (transparent), quality q3. Center lite must be ASTM C1036, clear annealed flat glass Type I, Class 1 (transparent, Quality q3, 1/8 inch thick. The outer light must be ASTM C1036, heat-absorbing glass, Type I, Class 1 (transparent), Quality q3, with anti-reflective low-emissivity coating and dynamic coating on No. 2 surface (inside surface of exterior lite).

2.3.1.2 Insulated Dynamic Safety Glass (Type "IDS")

The inner lite must be ASTM C1172, Kind "LA" laminated glass, Type I, Class 1 (transparent), quality q3. Center lite must be ASTM C1036, clear annealed flat glass Type I, Class 1 (transparent, Quality q3, 1/8 inch thick. The outer light must be ASTM C1172, Kind "LA" laminated glass, Type I, Class 1 (transparent), Quality q3, with anti-reflective low-emissivity coating and dynamic coating on No. 4 surface (inside surface of exterior lite).

2.3.1.3 Insulated Dynamic Safety Glass (Type "IDD")

The inner lite must be ASTM C1172, Kind "LA" laminated glass, Type I, Class 1 (transparent), quality q3. The outer light must be ASTM C1172, Kind "LA" laminated glass, Type I, Class 1 (transparent), Quality q3, with anti-reflective low-emissivity coating and dynamic coating on No. 4 surface (inside surface of exterior lite).

2.4 SETTING AND SEALING MATERIALS

Provide as specified in the GANA Glazing Manual , IGMA TM-3000 , IGMA TB-3001 , and manufacturer's recommendations, unless specified otherwise herein. Do not use metal sash putty, nonskinning compounds, nonresilient preformed sealers, or impregnated preformed gaskets. Materials exposed to view and unpainted must be gray or neutral color.

2.4.1 Sealants

Provide elastomeric and structural sealants.

2.4.1.1 Elastomeric Sealant

ASTM C920, Type S, Grade NS, Class 12.5, Use G. Use for channel or stop glazing metal sash. Sealant must be chemically compatible with setting blocks, edge blocks, and sealing tapes, with sealants used in manufacture of insulating glass units. Color of sealant must be white.

SECTION 08 88 36.02 00 Page 5

2.4.2 Preformed Channels

Neoprene, vinyl, or rubber, as recommended by the glass manufacturer for the particular condition.

2.4.3 Setting Blocks and Edge Blocks

Closed-cell neoprene setting blocks must be dense extruded type conforming to ASTM C509 and ASTM D395, Method B, Shore A durometer between 70 and

90. Edge blocking must be Shore A durometer of 50 (plus or minus 5).

Provide silicone setting blocks when blocks are in contact with silicone sealant. Profiles, lengths and locations must be as required and recommended in writing by glass manufacturer. Block color must be black.

2.4.4 Glazing Gaskets

Glazing gaskets must be extruded with continuous integral locking projection designed to engage into metal glass holding members to provide a watertight seal during dynamic loading, building movements and thermal movements. Glazing gaskets for a single glazed opening must be continuous one-piece units with factory-fabricated injection-molded corners free of flashing and burrs. Glazing gaskets must be in lengths or units recommended by manufacturer to ensure against pull-back at corners.

Provide glazing gasket profiles as recommended by the manufacturer for the intended application.

2.4.4.1 Fixed Glazing Gaskets

Fixed glazing gaskets must be closed-cell (sponge) smooth extruded compression gaskets of cured elastomeric virgin neoprene compounds conforming to ASTM C509, Type 2, Option 1.

2.4.4.2 Aluminum Framing Glazing Gaskets

Glazing gaskets for aluminum framing must be permanent, elastic, non-shrinking, non-migrating, watertight and weathertight.

2.4.5 Accessories

Provide as required for a complete installation, including glazing points, clips, shims, angles, beads, and spacer strips. Provide noncorroding metal accessories. Provide primer-sealers and cleaners as recommended by the glass and sealant manufacturers.

AM#2... 2.5 CONTROLLERS AND ACCESSORIES

Provide controller to sense light coming from each elevation exposure monitoring ambient light levels and control each elevation exposure independently. Preprogram controller at factory to match initial calculated programming requirements based on sun angle, window location, and depth of light penetration. Provide switch located in Control Room to turn off dynamic glass coating to all elevations with one switch. Dynamic glazing to be able to shade to a maximum solar heat gain coefficient of

0.09. Where required for power and communications to equipment, provide POE Network switch or POE injector to power remote sensor. Network switch shall comply with approved equipment listing requirements of Section

01 91 10.02 29 CYBERSECURITY/RISK MANAGEMENT FRAMEWORK REQUIRMENTS.

Provide connectors and other equipment necessary for a complete installation. ...AM#2

SECTION 08 88 36.02 00 Page 6

PART 3 EXECUTION

Any materials that show visual evidence of biological growth due to the presence of moisture must not be installed on the building project.

3.1 PREPARATION

Preparation, unless otherwise specified or approved, must conform to applicable recommendations in the GANA Glazing Manual , GANA Sealant Manual , IGMA TB-3001 , IGMA TM-3000 , and manufacturer's recommendations. Verify wiring is in place for connection. Determine the sizes to provide the required edge clearances by measuring the actual opening to receive the glass. Leave labels in place until the installation is approved, except remove applied labels on insulating glass units as soon as glass is installed. Securely fix movable items or keep in a closed and locked position until glazing compound has thoroughly set.

3.2 GLASS SETTING

Shop glaze or field glaze items to be glazed using glass of the quality and thickness specified or indicated. Glazing, unless otherwise specified or approved, must conform to applicable recommendations in the GANA Glazing Manual , GANA Sealant Manual , IGMA TB-3001 , IGMA TM-3000 , and manufacturer's recommendations. Aluminum windows, may be glazed in conformance with one of the glazing methods described in the standards under which they are produced, except that face puttying with no bedding will not be permitted. Handle and install glazing materials in accordance with manufacturer's instructions. Use beads or stops which are furnished with items to be glazed to secure the glass in place. Verify products are properly installed, connected, and adjusted.

a. Use grommets during installation to protect wire when routing IGU pigtail through frame.

b. If IGU pigtail connector is damaged during installation, notify manufacturer and repair connector using manufacturer's approved method.

3.2.1 Sheet Glass

Cut and set with the visible lines or waves horizontal.

3.2.2 Insulating Glass Units

Do not grind, nip, or cut edges or corners of units after the units have left the factory. Springing, forcing, or twisting of units during setting will not be permitted. Handle units so as not to strike frames or other objects. Installation must conform to applicable recommendations of IGMA TB-3001 and IGMA TM-3000 .

3.3 CLEANING

Clean glass surfaces and remove labels, paint spots, putty, and other defacement as required to prevent staining. Glass must be clean at the time the work is accepted.

3.4 PROTECTION

Protect glass work immediately after installation. Identify glazed

SECTION 08 88 36.02 00 Page 7 openings with suitable warning tapes, cloth or paper flags, attached with non-staining adhesives. Place protective material far enough away from the coated glass to allow air to circulate to reduce heat buildup and moisture accumulation on the glass. Remove and replace glass units which are broken, chipped, cracked, abraded, or otherwise damaged during construction activities with new units.

a. Protection during testing: Comply with the following:

1) Do not use a high-voltage spark gas analyzer such as the

Sparklike Gasglass to evaluate gas content of View Dynamic Glass products.

2) Use of such device may damage film and controls, potentially voiding View Inc. product warranty.

3.5 COMMISSIONING

As part of the work of this section, perform the following:

a. Conduct visual inspection to verify insulating glass units and corresponding pigtail cables are installed in the right orientation as specified in the View IGU product data sheet.

b. Verify that all IGU pigtails are accessible for connection to the main trunk line.

c. Provide information requested by the commissioning agent for final commissioning documentation.

d. Provide measuring instruments and logging devices to record test data acquisition equipment to record data for complete range of testing during the required test period.

e. Evaluate any performance irregularities and recommend corrective action.

f. Provide means for the commissioning agent to access, visually observe, and confirm proper operation of the View Dynamic Glass system. AM#2...

Remote network access for commissioning will not be permitted.

Provide local equipment for programming and adjustments. ...AM#2