EIE326-RoomCriteria.pdf

PDF 203 KB Posted

Attached to
Design/Construct 168 Person Dormitory (EIE326), Eielson AFB, Alaska
Solicitation number
W911KB-14-R-0017
Issued by

About this file

Room Criteria

View the file

Other files

File Type Posted
AM_7.pdf PDF
Attachement_10_Energy Sustainability_Record_Card.xlsx XLSX spreadsheet
EIE326-01_19_10_00_29-2_7_AM_6.pdf PDF
EIE326-RoomCriteria_2014-05-05_AM_6.pdf PDF
EIE326_Proosal_Schedule__AM_6.pdf PDF
EIE326_RFP_TOC_2014-05-06_AM_6.pdf PDF
A_3_6_2_J A14-38_Delta_Controls_Redacted.pdf PDF
ProjNet_Bidder_Inquiry_Report.pdf PDF
01_19_10.00_29_2.4.14-Dryers.pdf PDF
A_3_6_2_J A_14-37_Cooper_Redacted.pdf PDF
AM_6.pdf PDF
A_3_6_2_J A_14-35_Knox_Redacted.pdf PDF
A_3_6_2_J A_14-34_BasisV_card_access_Redacted.pdf PDF
A_3_6_2_J A_14-36_Monaco_Redacted.pdf PDF
01_57_20.00_10_Attachment_N_2014-05-06_AM_6.pdf PDF
A_3_6_2_J A_14-33_Best_locks_Redacted.pdf PDF
EIE326-01_19_10_00_29-2_2_AM_5_Pages.pdf PDF
EIE326-RoomCriteria_AM_5.pdf PDF
EIE326-L101_Half_AM_5.pdf PDF
EIE326-01_19_10_00_29-2_8_AM_5_Pages.pdf PDF
AM_5.pdf PDF
APPNDX05-USGBC-CHP-Guidance-for-FTW-Project-AM_5.pdf PDF
EIE326-01_19_10_00_29-2_6.pdf PDF
EIE326-02_61_13_AM_5.pdf PDF
EIE326-01_19_10_00_29-2_4_AM_5_Pages.pdf PDF
EIE326-01_19_10_00_29-2_10_AM_5.pdf PDF
EIE326_D1_00_Half_AM_5.pdf PDF
EIE326-L102_Half_AM_5.pdf PDF
EIE326-01_19_10_00_29-2_9_AM_5_Pages.pdf PDF
A.2.11.3.1_SolicAmend_EIE326-AM4.pdf PDF
A.2.11.3.1_SolicAmend_EIE326-AM3.pdf PDF
EIE326_RFP_TAB2_2014-03-24.pdf PDF
EIE326_RFP_TAB3_2014-03-24.pdf PDF
EIE326_RFP_TAB1_2014-03-19.pdf PDF
RevisedSECTION_00_22_20.pdf PDF
Amendment__2.pdf PDF
AM_1.pdf PDF
Module-Aerial.jpg JPG image
EIE326_RFP.pdf PDF
EIE326_RFP_TAB4_drawings_2013-12-24.pdf PDF
Module-Aerial-3.jpg JPG image
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DORMITORY, 168 PN EIELSON AFB, AK

SECTION 01 19 10.00 29

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 100sf 8'-0" Wall:

Max. Net Area: 9'-0" Flr/Clng:

Door(s):

Window(s):

Casework: Base: Wall: Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

3'-0" min.; storage lockset; closer;

Mechanical / Plumbing

Not required

GWB, Paint Window Treatment:

n/a

Stattic Dissipative Tile

Electrical / Communication / Data One circuit per rack. Provide (2) double duplex outlet for TTB on designated circuit.

Fire Protection

Min. Ceiling Height:

Acoustics:

STC 50

None

Provide one data outlet.

Maintain specified temperature Positive pressure filitered per EIA/TIA 569, Equipment cooling

Not required

Linear fluorescent lighting. Provide 50fc minimum. Wall-mounted occupancy switch.

None

STC 55

Area Ceiling

Max. Ceiling Height:

MAIN COMMUNICATIONS

Primary Communications Utility entry point and distribution

Adjacencies: 1st Floor

Architectural none

Finishes

Rubber Base GWB, Paint

Sprinkler, Fire Alarm, & Mass Notification

W911KB-11-D-0003

EIE 326

Room Name Oty.

Common Areas Min. Max.

Main Arctic Entry 1 200 Lobby 1 250 Vending 1 128 Public Toilet - Accessible 1 65 100 Multi-purpose 1 344 Bulk Storage 1 638 Laundry 3 230 Janitor / House keeping 6 100

Dorm Module Shared Commons 42 288 Bedroom 168 131 Private Bathroom 168 39 Walk-in Closet 168 20

Dorm Management Dorm Management 1 500

Support Services Main Electrical 1 100 Electrical 6 100 Main Communications 1 100 Communications 5 100 Main Mechanical 1 Mechanical - Air Handlers 2 Elevator 1 Elevator Machine Room 1 Stair(s) 3 Circulation / Corridors

68,712

ROOM/AREA TABULATION

PR

O

G R

A M

A R

EA

S

Net Area - ft2

TOTAL GROSS AREA

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 250 sf 8'-0" Wall:

Max. Net Area: - 9'-0" Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Phone/Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

Terminal heating unit sized for 4 ACHRs

Not required Mechanical / Plumbing

Mailboxes; Card key kiosk; Intercom call box; FAP; Security Camera(s);

provide 168 mail boxes (6"w x 5" h x 15.5" d); provide one out going mail drop box; provide location for card key kiosk.

GWB, Paint

Min. Ceiling Height:

not required / not prohibited

GWB, Paint Window Treatment:

n/a Rubber Base

Fire Protection

Provide dry sprinkler or dry pipe system as required.

Sprinkler, Fire Alarm, & Mass Notification

Provide intercom system for communication between arctic entry and dorm management office.

None

Card swipe at interior door and CCTV coverage

Two duplex outlets: One convenience outlet and one duplex outlet for temp.

card machine

Not required Not required

None required

Two data outlets; Card machine and intercom phone to Dorm Mgr's Office

Electrical / Communication / Data Minimum illumination 20 fc. Linear fluorescent lighting switched at circuit breaker.

Walk of grating, Walk off carpet

Glazed Storefront, 3'-0" min.; Exit hardware; Card key access on interior door to Lobby

MAIN ARCTIC ENTRY

Architectural

Provides a buffering entry zone for access to the main lobby & location for mailboxes.

Lobby, Dorm Management

Ceiling

Max. Ceiling Height:

n/a

Acoustics:

STC 50

STC 55

Area

Adjacencies:

Finishes

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 200sf 9'-0" Wall:

Max. Net Area: - - Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

Glazed Storefront, 3'-0" min.; Exit hardware; access control on door to Main Arctic Entry

Mechanical / Plumbing

Not required

GWB, Paint Window Treatment:

Quarry Tile or Resilient flooring

Electrical / Communication / Data One duplex outlet on every wall.

Fire Protection

Min. Ceiling Height:

Acoustics:

STC 50

Provide coverage

One 2-port phone/data outlet.

Maintain specified temperature Yes

Not required

Linear fluorescent lighting switched at Dorm Mgr's office CCTV coverage

STC 55

Area Ceiling

Max. Ceiling Height:

n/a

LOBBY

Central Circulation zone, Transition from exterior to interior

Adjacencies: Main Arctic Entry, Dorm Management, Public Toilet, Multi-purpose

Architectural not required / not prohibited

Finishes

Quarry Tile or Rubber Base

GWB, Paint

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 128sf 8'-0" Wall:

Max. Net Area: - 9'-0" Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

n/a

Mechanical / Plumbing

Not required

GWB, Paint Window Treatment:

n/a

Match room it opens to.

None

Electrical / Communication / Data 2 double duplex outlets on each vending machine wall. Provide two circuits per double duplex outlet.

Fire Protection

Min. Ceiling Height:

Acoustics:

STC 50

Provide coverage

Provide a data outlet for each vending equipment.

Maintain specified temperaure Not required

Not required

Linear fluorescent lighting switched with lobby.

None

STC 55

Area Ceiling

Max. Ceiling Height:

n/a

VENDING

Area for the placement of vending machines.

Adjacencies: Lobby; Multipurpose;

Dorm Management;

Architectural n/a

Finishes

Rubber Base provide space for two vending machines. (GFGI)

GWB, Paint

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 65sf 8'-0" Wall:

Max. Net Area: 100sf 9'-0" Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

Fire Protection

Minimum illumination 20 fc. Provide fluorescent vanity fixture above mirror and linear fluorescent fixture on ceiling.

Control all lighting with ceiling-mounted occ. sensor.

Ceramic Tile or Resilient Flooring

None

Electrical / Communication / Data One GFCI receptacle by sink location

Min. Ceiling Height:

Acoustics:

STC 50

Provide coverage as required

None

Maintain specified temperature Yes, and exhaust to outdoors

Hot water, cold water, waste and vent

None

STC 55

Area Ceiling

Max. Ceiling Height:

n/a

3'-0" min.; privacy hardware w/ closer, PUBLIC TOILET - ACCESSIBLE

ADA Accessible toilet and sink for public use

Adjacencies: Lobby; Dorm management;

Multipurpose

Architectural n/a

Ceramic Tile to 5'-0" min.

Finishes

Ceramic Tile or Integral Cove mirror; soap dispenser; paper towel dispenser and waste receptacle; tp dispenser; grab bars;

GWB, Paint

Comply with all ABA required clearances, mounting heights, and ammenities.

Sprinkler, Fire Alarm, & Mass Notification

Mechanical / Plumbing toilet, lav with single handle faucet, floor drain

GWB, Paint Window Treatment:

n/a

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 334sf 8'-0" Wall:

Max. Net Area: - 9'-0" Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

Fire Protection

Minimum illumination 50 fc. Provide linear fluorescent lighting with occupancy sensor control

Resilient Flooring

Provide CATV outlet at television location

Electrical / Communication / Data Provide two duplex outlets on each wall

Min. Ceiling Height:

Acoustics:

STC 50

Provide wireless internet at this location only.

Provide coverage

Provide one data outlet on each wall.

Maintain specified temperature Yes

Not required

CCTV Coverage

STC 55

Area Ceiling

Max. Ceiling Height:

n/a pr 3'-0" min interior & exterior.; magnetic hold opens; passage latch, panic hardware w/ closer, narrow lite glazing;

MULTI-PURPOSE

Social gathering space, TV viewing, gaming, relaxation

Adjacencies: Lobby; Vending; Public Toilet; Dorm Management

Architectural

Operable windows. Interior relites desired but not required.

Finishes

Rubber Base

Coordinate furniture & equipment layout as described in appendix 15.

GWB, Paint

Area may be increased based on available area within Gross Building Area.

Sprinkler, Fire Alarm, & Mass Notification

Mechanical / Plumbing

Not required

GWB, Paint Window

Horizontal blinds & black out drapes

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 700sf 8'-0" Wall:

Max. Net Area: - 9'-0" Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

Fire Protection

Horizontal blinds & black out drapes

Sealed Concrete

None required

Electrical / Communication / Data Provide one duplex outlet by each door.

Min. Ceiling Height:

Acoustics:

STC 50

Provide coverage

One data outlet by each door.

Maintain specified temperature Yes

Not required

CCTV Coverage of all areas

STC 55

Area Ceiling

Max. Ceiling Height:

n/a

3'-0" min. personell door interior & exterior; 8'-0" insulated ovrhd sectionaldoor @ exterior.;

magnetic hold opens, panic hardware w/ closer, narrow lite glazing @ interior; panic hardware w/ closer @ exterior

BULK STORAGE

Storage for resident's gear (mobility bags, seasonal equipment, tires, boxes, etc.)

Adjacencies: Corridor, exterior

Architectural n/a impact protection

Finishes

Rubber Base

70.6 cu ft storage lockers, a minimum of one per Dorm-4-Airmen module.

(approx. 3' x 3' x 7'-10")

GWB, Paint

Area may be increased based on available area within Gross Building Area.

Sprinkler, Fire Alarm, & Mass Notification

Minimum illumination 20 fc. Provide linear fluorescent lighting with occupancy sensor control

Mechanical / Plumbing

Not required

GWB, Paint Window

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 230sf 8'-0" Wall:

Max. Net Area: - 9'-0" Flr/Clng:

Door(s):

Window(s):

Casework: Base: Wall: Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

3'-0" min.; passage latch, closer, half-lite glazing

Mechanical / Plumbing floor drain, laundry sink with faucet, floor sink for indirect laundry sink waste

GWB, Paint Window Treatment:

n/a

Resilient Flooring

None

Electrical / Communication / Data Provide dedicated receptacles for washing and drying machines. Provide one duplex outlet on each wall.

Fire Protection

Min. Ceiling Height:

Acoustics:

STC 50

None

None

Maintain specifed temperature Yes, dryer exhaust to the outdoors and make up air hot water, cold water, waste and vent

Provide linear fluorescent lighting. 30fc minimum. Wall-mounted occupancy switch.

CCTV Coverage

STC 55

Area Ceiling

Max. Ceiling Height:

Solid surface

LAUNDRY

Centralized Laundry Services equipment, located on each floor

Adjacencies: Corridor; Locate centraly in floorplate, stack on each floor, Architectural

Fixed (non-operable)

Finishes

Rubber Base or Integral Cove

1 large capacity washer / 6PN served - min.; 1 large capacity dryer / 6PN served - min.;

provide 1 commercial washer / 14PN served; 1 commercial dryer / 14 PN served.

Coordinate furniture & equipment layout as described in appendix 15

GWB, Paint

Mount Utility connections 3'-0" AFF; provide floor drains; Utility sink - Porcelain;

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 100sf 8'-0" Wall:

Max. Net Area: - 9'-0" Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

3'-"0 min.; storage latch, closer

Mechanical / Plumbing mop sink with faucet, floor drain

GWB, Paint Window Treatment:

n/a

Resilient flooring

None

Electrical / Communication / Data Provide one GFCI receptacle

Fire Protection

Min. Ceiling Height:

Acoustics:

STC 50

None

None

Maintain specified temperature Exhaust to the outdoors hot water, cold water, waste and vent

Linear fluorescent lighting. Wall-mounted occupancy switch None

STC 55

Area Ceiling

Max. Ceiling Height:

n/a

JANITOR / HOUSEKEEPING

Storage of housekeeping supplies Adjacencies: Laundry, Corridor, Architectural none

FRP to 7'-0" AFF min.

Finishes

Integral Cove

Mop Rack; Utility Sink; Floor Drain

GWB, Paint

Provide wall mounted Stainless Steel shelving (5' w x 1'd x 5' h); Provide space for 1 Commercial Vacuum (GFGI)

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 123sf 8'-0" Wall:

Max. Net Area: 300sf 9'-0" Flr/Clng:

Door(s):

Window(s):

Casework: Base: 3' min. Wall: 3' min. Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

3'-0" min.; Card Key Access; Peep hole; Closer; Sweep &gaskets

Mechanical / Plumbing double bowl - stainless steel, with faucet and spray

GWB, Paint Window Treatment:

If a window is provided then horizontal blinds & blackout drapes resilient flooring in kitchen/dining area and circulation, carpet in social space

Provide CATV outlets at two locations.

Comply with Unaccompanied Housing Design Guide.

Electrical / Communication / Data Provide duplex receptacles as required by NEC. Comply with Unaccompanied Housing Design Guide.

Fire Protection

Min. Ceiling Height:

Acoustics:

STC 50

None

Provide phone and data outlets at two locations. Comply with Unaccompanied Housing Design Guide.

Maintain specified temperature Yes, and range hood exhaust

Hot water, cold water, waste, vent, cold water to refrigerator

Minimum illumination 20 fc. Provide local switch at entryway. Provide ceiling-mounted lighting

None

STC 55

Area Ceiling

Max. Ceiling Height:

3' (2'min. adjcnt to sink)

SHARED COMMONS

Cooking, dining, social space, storage Adjacencies: Corridor, Bedrooms

Architectural not required / not prohibited

Finishes

Rubber Base

Two Burner stove top; Microwave / convection oven / hood unit; double compartment sink;

ceiling fan; space for an 18 cu.ft. refrigerator; fire extinguisher;

GWB, Paint

Provide layout for dining room and living room style seating for 4PN ea., storage for vacuum cleaner, ironing board, iron, cleaning supplies, personal storage cabinets 70.6 cu ft ea.

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 129sf 8'-0" Wall:

Max. Net Area: 150sf 9'-0" Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

Fire Protection

Horizontal blinds & black out drapes

Carpet w/ pad

Provide CATV outlets at two locations.

Comply with Unaccompanied Housing Design Guide.

Electrical / Communication / Data Provide duplex receptacles as required by NEC. Comply with Unaccompanied Housing Design Guide.

Min. Ceiling Height:

Acoustics:

STC 50

None

Provide phone and data outlets at two locations. Comply with Unaccompanied Housing Design Guide.

Maintain specified temperature Yes

None

None

STC 55

Area Ceiling

Max. Ceiling Height:

n/a

2'-10" min.; Card key access; peep hole; sweep & gaskets

SLEEPING ROOM

Private Area for living and sleeping Adjacencies: Shared Commons;

Private Bathroom;

Walk-in Closet

Architectural

Operable - Sliding or Double Hung

Finishes

Rubber Base

Full Bed; Desk w/ Chair; Nightstand; 5 Drwr Dresser; Floor Lamp; 3.6 cu.ft. mini-fridge;

waste basket;

GWB, Paint

Sprinkler, Fire Alarm, & Mass Notification

Minimum illumination 20 fc. Provide local switch at entryway. Provide ceiling mounted CFL light fixture and switched receptacle.

Mechanical / Plumbing

None

GWB, Paint

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 39sf 8'-0" Wall:

Max. Net Area: - 9'-0" Flr/Clng:

Door(s):

Window(s):

Casework: Base: 3' min. Wall: 2'-6" Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

2'-8" min.; privacy lockset

Mechanical / Plumbing

5'-0" tub/shower, shower head, mixing valve, toilet, bath faucet. Lav with single handle faucet

GWB, Paint Window Treatment:

n/a

Resilient Flooring

None

Supply air can be provided from adjancent space through undercut door

Electrical / Communication / Data Provide one dedicated GFCI duplex receptacle by sink

Fire Protection

Min. Ceiling Height:

Acoustics:

STC 50

None

None

Maintain specified temperature Supply air and exhaust to the outdoors

Hot water, cold water, waste and vent

Minimum illumination 20 fc. Local switch at door. Ceiling-mounted luminaire and vanity light fixture above mirror.

None

STC 55

Area Ceiling

Max. Ceiling Height:

3' min.

PRIVATE BATH

Private bath/shower, toilet, and sink Adjacencies: Bedroom

Architectural n/a

Ceramic Tile or Solid Surface at Tub

Finishes

Rubber base or Integral cove

Mirror; medicine cabinet; tp holder; hand towel bar; towel bar; robe hook; waste basket;

shower curtain rod, hooks, & curtain; shower shelf & soap dish; fan;

GWB, Paint

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 20sf 8'-0" Wall:

Max. Net Area: - 9'-0" Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/ a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

2'-8" min.; storage lockset w/ dead bolt

Mechanical / Plumbing not required

GWB, Paint Window Treatment:

n/a

Carpet w/ pad (match room adjacent)

Electrical / Communication / Data None

Fire Protection

Min. Ceiling Height:

Acoustics:

STC 50

None

None

Maintain specified temperature not required not required

Minimum illumination 10 fc. Provide local switch at entryway. Provide light fixture listed for closet.

None

STC 55

Area Ceiling

Max. Ceiling Height:

n/a

WALK-IN CLOSET

Walk-in Storage for personal gear and clothes

Adjacencies: Bedroom

Architectural n/a

Finishes

Rubber Base

Provide coat rod and shelf with a minimum length of 8' hanging space.

GWB, Paint

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 500sf 9'-0" Wall:

Max. Net Area: - Flr/Clng:

Door(s):

Window(s):

Casework: Base: 4' min. Wall: 4' min. Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

Fire Protection

Horizontal Blinds

Resilient flooring or Carpet

Provide one CATV outlet

Electrical / Communication / Data Provide two duplex outlets on each wall. Comply with Unaccompanied Housing Design Guide.

Min. Ceiling Height:

Acoustics:

STC 50

Provide intercom system for communication between Arctic Entry and Dorm Management.

Provide coverage

Provide two data outlets on each wall.

Comply with Unaccompanied Housing Design Guide.

Maintain specified temperature Yes

Hot water, cold water, waste, and vent

None

STC 55

Area Ceiling

Max. Ceiling Height:

4' min.

3'-0" min.;

DORM MANAGEMENT

Dorm Management Offices Adjacencies: Main Arctic Entry, Lobby, Supply Storage, Public Toilet, Vending, Multi-purpose, Architectural

Operable; Sliding or Double Hung

Finishes

Rubber Base

Coordinate furniture & equipment layout as described in appendix 15.

GWB, Paint

Provide one private office and two open office workstations. Area may be increased based on available area within Gross Building Area.

Sprinkler, Fire Alarm, & Mass Notification

Minimum illumination 50 fc.

Fluorescent lighting controlled by occupancy sensors.

Mechanical / Plumbing

Bar sink with faucet

Acoustic Ceiling Tile

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 135sf 8'-0" Wall:

Max. Net Area: 9'-0" Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

Fire Protection n/a

Sealed concrete

Electrical / Communication / Data One convenience duplex outlet

Min. Ceiling Height:

Acoustics:

STC 50

None

One data outlet by power outlet

Maintain speficied temperature Mechanical ventilation for cooling

Not required

None

STC 55

Area Ceiling

Max. Ceiling Height:

n/a

3'-0" min.; storage lockset, closer

MAIN ELECTRICAL

House primary electrical systems, primary electrical utility entry point and distribution

Adjacencies: 1st Floor

Architectural none

Finishes

Rubber Base

GWB, Paint

Sprinkler, Fire Alarm, & Mass Notification

Linear fluorescent lighting. Provide 50fc minimum. Local switch.

Mechanical / Plumbing

Not required

GWB, Paint

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 100sf 8'-0" Wall:

Max. Net Area: - 9'-0" Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

3'-0" min.; storage lockset; closer; sweep & gasket

Mechanical / Plumbing

Not required

GWB, Paint Window Treatment:

n/a

Sealed Concrete

Electrical / Communication / Data One convenience duplex outlet

Fire Protection

Min. Ceiling Height:

Acoustics:

STC 50

None

One data outlet by power outlet

Maintain speficied temperature Mechanical ventilation for cooling

Not required

Linear fluorescent lighting. Provide 50fc minimum. Local switch.

None

STC 55

Area Ceiling

Max. Ceiling Height:

n/a

ELECTRICAL

Satellite Electrical Closets located on each floor, Adjacencies:

Architectural none

Finishes

Rubber Base

GWB, Paint

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 100sf 8'-0" Wall:

Max. Net Area: - Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

3'-0" min.; storage lockset; closer; sweep & gaskets;

Mechanical / Plumbing

Not required

GWB, Paint Window Treatment:

n/a

Static Dissipative Tile

Electrical / Communication / Data One circuit per rack.

Fire Protection

Min. Ceiling Height:

Acoustics:

STC 50

None

Provide one data outlet.

Maintain specified temperature Positive pressure filitered per EIA/TIA 569, Equipment cooling

Not required

Linear fluorescent lighting. Provide 50fc minimum. Provide occupancy sensor control.

None

STC 55

Area Ceiling

Max. Ceiling Height:

n/a

COMM.

Communications closets located at each floor for distribution of communications systems

Adjacencies: Corridor

Architectural

None

Finishes

Rubber Base

GWB, Paint

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: 525sf 9'-0" Wall:

Max. Net Area: - - Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: 3' min. Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

pr 3'-0" min. @ exterior;

Mechanical / Plumbing floor drain, hot and cold water hose bibb

GWB, Paint Window Treatment:

n/a

Sealed Concrete

Electrical / Communication / Data Provide duplex receptacles on each wall.

Fire Protection

Min. Ceiling Height:

Acoustics:

STC 50

None

Provide data outlet for DDC panel.

Coordinate with mechanical

Maintain specified temperature Mechanical ventilation for cooling hot water, cold water, waste and vent

Provide linear fluorescent lighting.

Local switch. 30fc minimum None

STC 55

Area Ceiling

Max. Ceiling Height:

n/a

MAIN MECHANICAL

House primary Mechanical systems, primary mechanical utilities point of entry and distribution

Adjacencies: 1st floor

Architectural none

Finishes

Rubber Base

Floor Drain, Hot / Cold Water Hose Bib; Utility Sink; wall mounted cabinet for O&M manuals.

GWB, Paint

Provide a 4" concrete curb at perimeter walls of the room.

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: - - Wall:

Max. Net Area: - - Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

3'-0" min.; storage lockset; narrow lite

Mechanical / Plumbing

Hot/Cold hose bib, Floor drain

GWB, Paint Window Treatment:

n/a

Catwalk

Electrical / Communication / Data Provide duplex receptacles on each wall. Provide connections to mechanical equipment and motor controllers as required.

Fire Protection

Min. Ceiling Height:

Acoustics:

STC 50

None

Provide data outlet for DDC panel.

Coordinate with mechanical

Maintain specified temperature Not Required

Waste and vent

Provide linear fluorescent lighting.

Local switch. 20fc minimum

None

STC 55

Area Ceiling

Max. Ceiling Height:

n/a

MECHANCIAL - AIR HANDLERS

House mechanical fan units Adjacencies: Corridor; elevator;

Architectural none

Finishes

Air Handlers

GWB, Paint

NOTE; PLACEMENT OF AIRHANDLERS IN ATTIC SPACE IS PERMITTED AND WILL

NOT COUNT AGAINS GROSS BUILDING AREA (GBA) PROVIDED AVERAGE CEILING

HEIGHT OF THE SPACE DOES NOT EXCEED 7 FEET, OTHERWISE HALF OF THE

AREA OF THE ENCLOSED SPACE MUST BE INCLUDED IN THE GBA.

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: - 9'-0" Wall:

Max. Net Area: - Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

Fire Protection

Window Treatment:

n/a

Rubber

None

Electrical / Communication / Data

Min. Ceiling Height:

Acoustics:

n/a

PA coverage

Not required Not required

Not required

Fluorescent lighting

None

STC 55

Area Ceiling

Max. Ceiling Height:

n/a

ELEVATOR

Vertical transportation of furniture, appliances, and occasionally personnel.

Adjacencies: Corridor, Elevator Machine Room

Architectural none

Stainless Steel Flat Handrail

Finishes

Mtl - Powder coat

Stainless Steel

Elevator shall be sized to accommodate a 24" x 84" Ambulance gurney; Provide protection pads and hanging buttons

Sprinkler, Fire Alarm, & Mass Notification

Provide emergency 2-way voice communications per ASME A17.1

One duplex GFCI service receptacle

Mechanical / Plumbing

Not required

Stainless Steel

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: - 8'-0" Wall:

Max. Net Area: - 9'-0" Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

Fire Protection

Window Treatment:

n/a

Sealed Concrete

None

Hard piping of sump pump discharge to the building waste or discharge outdoors is not permitted

Electrical / Communication / Data

Min. Ceiling Height:

Acoustics:

STC 50

None

One data outlet

Maintain specified temperature exhaust to the outdoors

Not Required

None

STC 55

Area Ceiling

Max. Ceiling Height:

n/a

3'-0" min.; storage latch; closer

ELEVATOR MACHINE ROOM

Elevator Equipment location Adjacencies: Elevator, Corridor

Architectural none

Finishes

Rubber Base

GWB, Paint

Sprinkler, Fire Alarm, & Mass Notification

One duplex GFCI receptacle Provide linear fluorescent lighting.

Local switch. 30fc minimum

Mechanical / Plumbing

Not required

GWB, Paint

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: - 8'-0" Wall:

Max. Net Area: - - Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

Fire Protection n/a

Rubber at Landings, Risers, and Treads

None

Electrical / Communication / Data None

Min. Ceiling Height:

Acoustics:

STC 50

Provide coverage

None

Maintain specified temperature Yes

Not required

CCTV coverage

STC 55

Area Ceiling

Max. Ceiling Height:

n/a

3'-0" min.; Mtl.; rated; Narrow Lite; Panic Hardware; Closer; Sweeps & Gaskets;

STAIR(s)

Vertical Circulation, Emergency Egress

Adjacencies: Corridor, Exit

Architectural

None

Finishes

Rubber Base

GWB, Paint

Sprinkler, Fire Alarm, & Mass Notification

Minimum illumination 20 fc. Provide ceiling-mounted, impact-resistant, linear fluorescent lighting on stairwell landings.

Mechanical / Plumbing

Not required

GWB, Paint

W911KB-11-D-0003

EIE 326

Room NAME

Purpose:

Min. Net Area: - 8'-0" Wall:

Max. Net Area: - 9'-0" Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

Area Ceiling Acoustics:

Circulation / Corridors

Horizontal Circulation connecting all elements of the facility

Adjacencies: as required

Architectural

Rubber ACT

Min. Ceiling Height: STC 50 Max. Ceiling Height: STC 55 as required desired / not required / not prohibited n/a

Corner guards at outside corners

Finishes Carpet

Electrical / Communication / Data

GWB, Paint Window Treatment:

none Desirable

Mechanical / Plumbing Maintain specified temperature Yes

Not required Not required

Convenience outlets per code Minimum illumination 50 fc. Provide linear fluorescent lighting.

None CCTV Coverage

None Provide coverage

Fire Protection

EIE326 - ENLISTED DORMITORY

EIELSON, AFB

DESIGN-BUILD RFP

Room # / NAME

Purpose:

Min. Net Area: Wall:

Max. Net Area: Flr/Clng:

Door(s):

Window(s):

Casework: Base: Wall: Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

Mechanical / Plumbing

Window Treatment:

Electrical / Communication / Data

Min. Ceiling Height:

Acoustics:Area Ceiling

Max. Ceiling Height:

Adjacencies:

Architectural

Finishes

Fire Protection

EIE326 - ENLISTED DORMITORY

EIELSON, AFB

DESIGN-BUILD RFP

Room # / NAME

Purpose:

Min. Net Area: 9'-0" Wall:

Max. Net Area: Flr/Clng:

Door(s):

Window(s):

Casework: Base: n/a Wall: n/a Countertop:

Equipment / Appliances:

Floor:

Base: Ceiling:

Wall:

Wainscot:

Notes:

Heating: Ventilation:

Plumbing: Plumbing Fixtures:

Notes:

Electrical: Lighting:

Comm./Data: Security:

CATV: PA System:

Notes:

System Type:

Notes:

Fire Protection n/a

None

Electrical / Communication / Data Provide one duplex outlet on each wall

Min. Ceiling Height:

Acoustics:

STC 50

None

One data outlet adjacent to one duplex outlet.

Maintain specified temperature Yes

Not required

None

STC 55

Area Ceiling

Max. Ceiling Height:

n/a

3'-0" min. @ interior; pr 3'-0" min. @ exterior; Storage locksets, closers, SUPPLY STORAGE

Storage for Dorm management, excess furnishings, supplies, equipment

Adjacencies: Dorm Management

Architectural none

Finishes

Rubber Base

7 ea. - full size bed frame, bed in bag & pillow, 5 drwr dresser, desk w chair, night stand, mini fridge, waste baskets, black out shades, shower curtains, GWB, Paint

Sprinkler, Fire Alarm, & Mass Notification

Minimum illumination 20 fc.

Fluorescent lighting. Ceiling-mounted occupancy switch

Mechanical / Plumbing

Not required

GWB, Paint

Main Comm.
Summary
Main Arctic Entry
Lobby
Vending
Public Toilet
Multi-purpose
Bulk Storage
Laundry
Janitor
Shared Commons
Sleeping Room
Private Bath
Walk-in Closet
Dorm Management
Main Electrical
Electrical
Comm.
Main Mech.
Mech.- AirHandlers
Elevator
Elevator Machine
Stair
Circulation
Room
Supply Storage