DORMITORY, 168 PN EIELSON AFB, AK
SECTION 01 19 10.00 29
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 100sf 8'-0" Wall:
Max. Net Area: 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: Wall: Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
3'-0" min.; storage lockset; closer;
Mechanical / Plumbing
Not required
GWB, Paint Window Treatment:
n/a
Stattic Dissipative Tile
Electrical / Communication / Data One circuit per rack. Provide (2) double duplex outlet for TTB on designated circuit.
Fire Protection
Min. Ceiling Height:
Acoustics:
STC 50
None
Provide one data outlet.
Maintain specified temperature Positive pressure filitered per EIA/TIA 569, Equipment cooling
Not required
Linear fluorescent lighting. Provide 50fc minimum. Wall-mounted occupancy switch.
None
STC 55
Area Ceiling
Max. Ceiling Height:
MAIN COMMUNICATIONS
Primary Communications Utility entry point and distribution
Adjacencies: 1st Floor
Architectural none
Finishes
Rubber Base GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
W911KB-11-D-0003
EIE 326
Room Name Oty.
Common Areas Min. Max.
Main Arctic Entry 1 200 Lobby 1 250 Vending 1 128 Public Toilet - Accessible 1 65 100 Multi-purpose 1 344 Bulk Storage 1 638 Laundry 3 230 Janitor / House keeping 6 100
Dorm Module Shared Commons 42 288 Bedroom 168 131 Private Bathroom 168 39 Walk-in Closet 168 20
Dorm Management Dorm Management 1 500
Support Services Main Electrical 1 100 Electrical 6 100 Main Communications 1 100 Communications 5 100 Main Mechanical 1 Mechanical - Air Handlers 2 Elevator 1 Elevator Machine Room 1 Stair(s) 3 Circulation / Corridors
68,712
ROOM/AREA TABULATION
PR
O
G R
A M
A R
EA
S
Net Area - ft2
TOTAL GROSS AREA
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 250 sf 8'-0" Wall:
Max. Net Area: - 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Phone/Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Terminal heating unit sized for 4 ACHRs
Not required Mechanical / Plumbing
Mailboxes; Card key kiosk; Intercom call box; FAP; Security Camera(s);
provide 168 mail boxes (6"w x 5" h x 15.5" d); provide one out going mail drop box; provide location for card key kiosk.
GWB, Paint
Min. Ceiling Height:
not required / not prohibited
GWB, Paint Window Treatment:
n/a Rubber Base
Fire Protection
Provide dry sprinkler or dry pipe system as required.
Sprinkler, Fire Alarm, & Mass Notification
Provide intercom system for communication between arctic entry and dorm management office.
None
Card swipe at interior door and CCTV coverage
Two duplex outlets: One convenience outlet and one duplex outlet for temp.
card machine
Not required Not required
None required
Two data outlets; Card machine and intercom phone to Dorm Mgr's Office
Electrical / Communication / Data Minimum illumination 20 fc. Linear fluorescent lighting switched at circuit breaker.
Walk of grating, Walk off carpet
Glazed Storefront, 3'-0" min.; Exit hardware; Card key access on interior door to Lobby
MAIN ARCTIC ENTRY
Architectural
Provides a buffering entry zone for access to the main lobby & location for mailboxes.
Lobby, Dorm Management
Ceiling
Max. Ceiling Height:
n/a
Acoustics:
STC 50
STC 55
Area
Adjacencies:
Finishes
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 200sf 9'-0" Wall:
Max. Net Area: - - Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Glazed Storefront, 3'-0" min.; Exit hardware; access control on door to Main Arctic Entry
Mechanical / Plumbing
Not required
GWB, Paint Window Treatment:
Quarry Tile or Resilient flooring
Electrical / Communication / Data One duplex outlet on every wall.
Fire Protection
Min. Ceiling Height:
Acoustics:
STC 50
Provide coverage
One 2-port phone/data outlet.
Maintain specified temperature Yes
Not required
Linear fluorescent lighting switched at Dorm Mgr's office CCTV coverage
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
LOBBY
Central Circulation zone, Transition from exterior to interior
Adjacencies: Main Arctic Entry, Dorm Management, Public Toilet, Multi-purpose
Architectural not required / not prohibited
Finishes
Quarry Tile or Rubber Base
GWB, Paint
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 128sf 8'-0" Wall:
Max. Net Area: - 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
n/a
Mechanical / Plumbing
Not required
GWB, Paint Window Treatment:
n/a
Match room it opens to.
None
Electrical / Communication / Data 2 double duplex outlets on each vending machine wall. Provide two circuits per double duplex outlet.
Fire Protection
Min. Ceiling Height:
Acoustics:
STC 50
Provide coverage
Provide a data outlet for each vending equipment.
Maintain specified temperaure Not required
Not required
Linear fluorescent lighting switched with lobby.
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
VENDING
Area for the placement of vending machines.
Adjacencies: Lobby; Multipurpose;
Dorm Management;
Architectural n/a
Finishes
Rubber Base provide space for two vending machines. (GFGI)
GWB, Paint
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 65sf 8'-0" Wall:
Max. Net Area: 100sf 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Fire Protection
Minimum illumination 20 fc. Provide fluorescent vanity fixture above mirror and linear fluorescent fixture on ceiling.
Control all lighting with ceiling-mounted occ. sensor.
Ceramic Tile or Resilient Flooring
None
Electrical / Communication / Data One GFCI receptacle by sink location
Min. Ceiling Height:
Acoustics:
STC 50
Provide coverage as required
None
Maintain specified temperature Yes, and exhaust to outdoors
Hot water, cold water, waste and vent
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
3'-0" min.; privacy hardware w/ closer, PUBLIC TOILET - ACCESSIBLE
ADA Accessible toilet and sink for public use
Adjacencies: Lobby; Dorm management;
Multipurpose
Architectural n/a
Ceramic Tile to 5'-0" min.
Finishes
Ceramic Tile or Integral Cove mirror; soap dispenser; paper towel dispenser and waste receptacle; tp dispenser; grab bars;
GWB, Paint
Comply with all ABA required clearances, mounting heights, and ammenities.
Sprinkler, Fire Alarm, & Mass Notification
Mechanical / Plumbing toilet, lav with single handle faucet, floor drain
GWB, Paint Window Treatment:
n/a
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 334sf 8'-0" Wall:
Max. Net Area: - 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Fire Protection
Minimum illumination 50 fc. Provide linear fluorescent lighting with occupancy sensor control
Resilient Flooring
Provide CATV outlet at television location
Electrical / Communication / Data Provide two duplex outlets on each wall
Min. Ceiling Height:
Acoustics:
STC 50
Provide wireless internet at this location only.
Provide coverage
Provide one data outlet on each wall.
Maintain specified temperature Yes
Not required
CCTV Coverage
STC 55
Area Ceiling
Max. Ceiling Height:
n/a pr 3'-0" min interior & exterior.; magnetic hold opens; passage latch, panic hardware w/ closer, narrow lite glazing;
MULTI-PURPOSE
Social gathering space, TV viewing, gaming, relaxation
Adjacencies: Lobby; Vending; Public Toilet; Dorm Management
Architectural
Operable windows. Interior relites desired but not required.
Finishes
Rubber Base
Coordinate furniture & equipment layout as described in appendix 15.
GWB, Paint
Area may be increased based on available area within Gross Building Area.
Sprinkler, Fire Alarm, & Mass Notification
Mechanical / Plumbing
Not required
GWB, Paint Window
Horizontal blinds & black out drapes
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 700sf 8'-0" Wall:
Max. Net Area: - 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Fire Protection
Horizontal blinds & black out drapes
Sealed Concrete
None required
Electrical / Communication / Data Provide one duplex outlet by each door.
Min. Ceiling Height:
Acoustics:
STC 50
Provide coverage
One data outlet by each door.
Maintain specified temperature Yes
Not required
CCTV Coverage of all areas
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
3'-0" min. personell door interior & exterior; 8'-0" insulated ovrhd sectionaldoor @ exterior.;
magnetic hold opens, panic hardware w/ closer, narrow lite glazing @ interior; panic hardware w/ closer @ exterior
BULK STORAGE
Storage for resident's gear (mobility bags, seasonal equipment, tires, boxes, etc.)
Adjacencies: Corridor, exterior
Architectural n/a impact protection
Finishes
Rubber Base
70.6 cu ft storage lockers, a minimum of one per Dorm-4-Airmen module.
(approx. 3' x 3' x 7'-10")
GWB, Paint
Area may be increased based on available area within Gross Building Area.
Sprinkler, Fire Alarm, & Mass Notification
Minimum illumination 20 fc. Provide linear fluorescent lighting with occupancy sensor control
Mechanical / Plumbing
Not required
GWB, Paint Window
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 230sf 8'-0" Wall:
Max. Net Area: - 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: Wall: Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
3'-0" min.; passage latch, closer, half-lite glazing
Mechanical / Plumbing floor drain, laundry sink with faucet, floor sink for indirect laundry sink waste
GWB, Paint Window Treatment:
n/a
Resilient Flooring
None
Electrical / Communication / Data Provide dedicated receptacles for washing and drying machines. Provide one duplex outlet on each wall.
Fire Protection
Min. Ceiling Height:
Acoustics:
STC 50
None
None
Maintain specifed temperature Yes, dryer exhaust to the outdoors and make up air hot water, cold water, waste and vent
Provide linear fluorescent lighting. 30fc minimum. Wall-mounted occupancy switch.
CCTV Coverage
STC 55
Area Ceiling
Max. Ceiling Height:
Solid surface
LAUNDRY
Centralized Laundry Services equipment, located on each floor
Adjacencies: Corridor; Locate centraly in floorplate, stack on each floor, Architectural
Fixed (non-operable)
Finishes
Rubber Base or Integral Cove
1 large capacity washer / 6PN served - min.; 1 large capacity dryer / 6PN served - min.;
provide 1 commercial washer / 14PN served; 1 commercial dryer / 14 PN served.
Coordinate furniture & equipment layout as described in appendix 15
GWB, Paint
Mount Utility connections 3'-0" AFF; provide floor drains; Utility sink - Porcelain;
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 100sf 8'-0" Wall:
Max. Net Area: - 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
3'-"0 min.; storage latch, closer
Mechanical / Plumbing mop sink with faucet, floor drain
GWB, Paint Window Treatment:
n/a
Resilient flooring
None
Electrical / Communication / Data Provide one GFCI receptacle
Fire Protection
Min. Ceiling Height:
Acoustics:
STC 50
None
None
Maintain specified temperature Exhaust to the outdoors hot water, cold water, waste and vent
Linear fluorescent lighting. Wall-mounted occupancy switch None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
JANITOR / HOUSEKEEPING
Storage of housekeeping supplies Adjacencies: Laundry, Corridor, Architectural none
FRP to 7'-0" AFF min.
Finishes
Integral Cove
Mop Rack; Utility Sink; Floor Drain
GWB, Paint
Provide wall mounted Stainless Steel shelving (5' w x 1'd x 5' h); Provide space for 1 Commercial Vacuum (GFGI)
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 123sf 8'-0" Wall:
Max. Net Area: 300sf 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: 3' min. Wall: 3' min. Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
3'-0" min.; Card Key Access; Peep hole; Closer; Sweep &gaskets
Mechanical / Plumbing double bowl - stainless steel, with faucet and spray
GWB, Paint Window Treatment:
If a window is provided then horizontal blinds & blackout drapes resilient flooring in kitchen/dining area and circulation, carpet in social space
Provide CATV outlets at two locations.
Comply with Unaccompanied Housing Design Guide.
Electrical / Communication / Data Provide duplex receptacles as required by NEC. Comply with Unaccompanied Housing Design Guide.
Fire Protection
Min. Ceiling Height:
Acoustics:
STC 50
None
Provide phone and data outlets at two locations. Comply with Unaccompanied Housing Design Guide.
Maintain specified temperature Yes, and range hood exhaust
Hot water, cold water, waste, vent, cold water to refrigerator
Minimum illumination 20 fc. Provide local switch at entryway. Provide ceiling-mounted lighting
None
STC 55
Area Ceiling
Max. Ceiling Height:
3' (2'min. adjcnt to sink)
SHARED COMMONS
Cooking, dining, social space, storage Adjacencies: Corridor, Bedrooms
Architectural not required / not prohibited
Finishes
Rubber Base
Two Burner stove top; Microwave / convection oven / hood unit; double compartment sink;
ceiling fan; space for an 18 cu.ft. refrigerator; fire extinguisher;
GWB, Paint
Provide layout for dining room and living room style seating for 4PN ea., storage for vacuum cleaner, ironing board, iron, cleaning supplies, personal storage cabinets 70.6 cu ft ea.
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 129sf 8'-0" Wall:
Max. Net Area: 150sf 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Fire Protection
Horizontal blinds & black out drapes
Carpet w/ pad
Provide CATV outlets at two locations.
Comply with Unaccompanied Housing Design Guide.
Electrical / Communication / Data Provide duplex receptacles as required by NEC. Comply with Unaccompanied Housing Design Guide.
Min. Ceiling Height:
Acoustics:
STC 50
None
Provide phone and data outlets at two locations. Comply with Unaccompanied Housing Design Guide.
Maintain specified temperature Yes
None
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
2'-10" min.; Card key access; peep hole; sweep & gaskets
SLEEPING ROOM
Private Area for living and sleeping Adjacencies: Shared Commons;
Private Bathroom;
Walk-in Closet
Architectural
Operable - Sliding or Double Hung
Finishes
Rubber Base
Full Bed; Desk w/ Chair; Nightstand; 5 Drwr Dresser; Floor Lamp; 3.6 cu.ft. mini-fridge;
waste basket;
GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
Minimum illumination 20 fc. Provide local switch at entryway. Provide ceiling mounted CFL light fixture and switched receptacle.
Mechanical / Plumbing
None
GWB, Paint
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 39sf 8'-0" Wall:
Max. Net Area: - 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: 3' min. Wall: 2'-6" Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
2'-8" min.; privacy lockset
Mechanical / Plumbing
5'-0" tub/shower, shower head, mixing valve, toilet, bath faucet. Lav with single handle faucet
GWB, Paint Window Treatment:
n/a
Resilient Flooring
None
Supply air can be provided from adjancent space through undercut door
Electrical / Communication / Data Provide one dedicated GFCI duplex receptacle by sink
Fire Protection
Min. Ceiling Height:
Acoustics:
STC 50
None
None
Maintain specified temperature Supply air and exhaust to the outdoors
Hot water, cold water, waste and vent
Minimum illumination 20 fc. Local switch at door. Ceiling-mounted luminaire and vanity light fixture above mirror.
None
STC 55
Area Ceiling
Max. Ceiling Height:
3' min.
PRIVATE BATH
Private bath/shower, toilet, and sink Adjacencies: Bedroom
Architectural n/a
Ceramic Tile or Solid Surface at Tub
Finishes
Rubber base or Integral cove
Mirror; medicine cabinet; tp holder; hand towel bar; towel bar; robe hook; waste basket;
shower curtain rod, hooks, & curtain; shower shelf & soap dish; fan;
GWB, Paint
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 20sf 8'-0" Wall:
Max. Net Area: - 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/ a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
2'-8" min.; storage lockset w/ dead bolt
Mechanical / Plumbing not required
GWB, Paint Window Treatment:
n/a
Carpet w/ pad (match room adjacent)
Electrical / Communication / Data None
Fire Protection
Min. Ceiling Height:
Acoustics:
STC 50
None
None
Maintain specified temperature not required not required
Minimum illumination 10 fc. Provide local switch at entryway. Provide light fixture listed for closet.
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
WALK-IN CLOSET
Walk-in Storage for personal gear and clothes
Adjacencies: Bedroom
Architectural n/a
Finishes
Rubber Base
Provide coat rod and shelf with a minimum length of 8' hanging space.
GWB, Paint
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 500sf 9'-0" Wall:
Max. Net Area: - Flr/Clng:
Door(s):
Window(s):
Casework: Base: 4' min. Wall: 4' min. Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Fire Protection
Horizontal Blinds
Resilient flooring or Carpet
Provide one CATV outlet
Electrical / Communication / Data Provide two duplex outlets on each wall. Comply with Unaccompanied Housing Design Guide.
Min. Ceiling Height:
Acoustics:
STC 50
Provide intercom system for communication between Arctic Entry and Dorm Management.
Provide coverage
Provide two data outlets on each wall.
Comply with Unaccompanied Housing Design Guide.
Maintain specified temperature Yes
Hot water, cold water, waste, and vent
None
STC 55
Area Ceiling
Max. Ceiling Height:
4' min.
3'-0" min.;
DORM MANAGEMENT
Dorm Management Offices Adjacencies: Main Arctic Entry, Lobby, Supply Storage, Public Toilet, Vending, Multi-purpose, Architectural
Operable; Sliding or Double Hung
Finishes
Rubber Base
Coordinate furniture & equipment layout as described in appendix 15.
GWB, Paint
Provide one private office and two open office workstations. Area may be increased based on available area within Gross Building Area.
Sprinkler, Fire Alarm, & Mass Notification
Minimum illumination 50 fc.
Fluorescent lighting controlled by occupancy sensors.
Mechanical / Plumbing
Bar sink with faucet
Acoustic Ceiling Tile
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 135sf 8'-0" Wall:
Max. Net Area: 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Fire Protection n/a
Sealed concrete
Electrical / Communication / Data One convenience duplex outlet
Min. Ceiling Height:
Acoustics:
STC 50
None
One data outlet by power outlet
Maintain speficied temperature Mechanical ventilation for cooling
Not required
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
3'-0" min.; storage lockset, closer
MAIN ELECTRICAL
House primary electrical systems, primary electrical utility entry point and distribution
Adjacencies: 1st Floor
Architectural none
Finishes
Rubber Base
GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
Linear fluorescent lighting. Provide 50fc minimum. Local switch.
Mechanical / Plumbing
Not required
GWB, Paint
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 100sf 8'-0" Wall:
Max. Net Area: - 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
3'-0" min.; storage lockset; closer; sweep & gasket
Mechanical / Plumbing
Not required
GWB, Paint Window Treatment:
n/a
Sealed Concrete
Electrical / Communication / Data One convenience duplex outlet
Fire Protection
Min. Ceiling Height:
Acoustics:
STC 50
None
One data outlet by power outlet
Maintain speficied temperature Mechanical ventilation for cooling
Not required
Linear fluorescent lighting. Provide 50fc minimum. Local switch.
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
ELECTRICAL
Satellite Electrical Closets located on each floor, Adjacencies:
Architectural none
Finishes
Rubber Base
GWB, Paint
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 100sf 8'-0" Wall:
Max. Net Area: - Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
3'-0" min.; storage lockset; closer; sweep & gaskets;
Mechanical / Plumbing
Not required
GWB, Paint Window Treatment:
n/a
Static Dissipative Tile
Electrical / Communication / Data One circuit per rack.
Fire Protection
Min. Ceiling Height:
Acoustics:
STC 50
None
Provide one data outlet.
Maintain specified temperature Positive pressure filitered per EIA/TIA 569, Equipment cooling
Not required
Linear fluorescent lighting. Provide 50fc minimum. Provide occupancy sensor control.
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
COMM.
Communications closets located at each floor for distribution of communications systems
Adjacencies: Corridor
Architectural
None
Finishes
Rubber Base
GWB, Paint
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: 525sf 9'-0" Wall:
Max. Net Area: - - Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: 3' min. Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
pr 3'-0" min. @ exterior;
Mechanical / Plumbing floor drain, hot and cold water hose bibb
GWB, Paint Window Treatment:
n/a
Sealed Concrete
Electrical / Communication / Data Provide duplex receptacles on each wall.
Fire Protection
Min. Ceiling Height:
Acoustics:
STC 50
None
Provide data outlet for DDC panel.
Coordinate with mechanical
Maintain specified temperature Mechanical ventilation for cooling hot water, cold water, waste and vent
Provide linear fluorescent lighting.
Local switch. 30fc minimum None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
MAIN MECHANICAL
House primary Mechanical systems, primary mechanical utilities point of entry and distribution
Adjacencies: 1st floor
Architectural none
Finishes
Rubber Base
Floor Drain, Hot / Cold Water Hose Bib; Utility Sink; wall mounted cabinet for O&M manuals.
GWB, Paint
Provide a 4" concrete curb at perimeter walls of the room.
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: - - Wall:
Max. Net Area: - - Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
3'-0" min.; storage lockset; narrow lite
Mechanical / Plumbing
Hot/Cold hose bib, Floor drain
GWB, Paint Window Treatment:
n/a
Catwalk
Electrical / Communication / Data Provide duplex receptacles on each wall. Provide connections to mechanical equipment and motor controllers as required.
Fire Protection
Min. Ceiling Height:
Acoustics:
STC 50
None
Provide data outlet for DDC panel.
Coordinate with mechanical
Maintain specified temperature Not Required
Waste and vent
Provide linear fluorescent lighting.
Local switch. 20fc minimum
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
MECHANCIAL - AIR HANDLERS
House mechanical fan units Adjacencies: Corridor; elevator;
Architectural none
Finishes
Air Handlers
GWB, Paint
NOTE; PLACEMENT OF AIRHANDLERS IN ATTIC SPACE IS PERMITTED AND WILL
NOT COUNT AGAINS GROSS BUILDING AREA (GBA) PROVIDED AVERAGE CEILING
HEIGHT OF THE SPACE DOES NOT EXCEED 7 FEET, OTHERWISE HALF OF THE
AREA OF THE ENCLOSED SPACE MUST BE INCLUDED IN THE GBA.
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: - 9'-0" Wall:
Max. Net Area: - Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Fire Protection
Window Treatment:
n/a
Rubber
None
Electrical / Communication / Data
Min. Ceiling Height:
Acoustics:
n/a
PA coverage
Not required Not required
Not required
Fluorescent lighting
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
ELEVATOR
Vertical transportation of furniture, appliances, and occasionally personnel.
Adjacencies: Corridor, Elevator Machine Room
Architectural none
Stainless Steel Flat Handrail
Finishes
Mtl - Powder coat
Stainless Steel
Elevator shall be sized to accommodate a 24" x 84" Ambulance gurney; Provide protection pads and hanging buttons
Sprinkler, Fire Alarm, & Mass Notification
Provide emergency 2-way voice communications per ASME A17.1
One duplex GFCI service receptacle
Mechanical / Plumbing
Not required
Stainless Steel
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: - 8'-0" Wall:
Max. Net Area: - 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Fire Protection
Window Treatment:
n/a
Sealed Concrete
None
Hard piping of sump pump discharge to the building waste or discharge outdoors is not permitted
Electrical / Communication / Data
Min. Ceiling Height:
Acoustics:
STC 50
None
One data outlet
Maintain specified temperature exhaust to the outdoors
Not Required
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
3'-0" min.; storage latch; closer
ELEVATOR MACHINE ROOM
Elevator Equipment location Adjacencies: Elevator, Corridor
Architectural none
Finishes
Rubber Base
GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
One duplex GFCI receptacle Provide linear fluorescent lighting.
Local switch. 30fc minimum
Mechanical / Plumbing
Not required
GWB, Paint
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: - 8'-0" Wall:
Max. Net Area: - - Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Fire Protection n/a
Rubber at Landings, Risers, and Treads
None
Electrical / Communication / Data None
Min. Ceiling Height:
Acoustics:
STC 50
Provide coverage
None
Maintain specified temperature Yes
Not required
CCTV coverage
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
3'-0" min.; Mtl.; rated; Narrow Lite; Panic Hardware; Closer; Sweeps & Gaskets;
STAIR(s)
Vertical Circulation, Emergency Egress
Adjacencies: Corridor, Exit
Architectural
None
Finishes
Rubber Base
GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
Minimum illumination 20 fc. Provide ceiling-mounted, impact-resistant, linear fluorescent lighting on stairwell landings.
Mechanical / Plumbing
Not required
GWB, Paint
W911KB-11-D-0003
EIE 326
Room NAME
Purpose:
Min. Net Area: - 8'-0" Wall:
Max. Net Area: - 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Area Ceiling Acoustics:
Circulation / Corridors
Horizontal Circulation connecting all elements of the facility
Adjacencies: as required
Architectural
Rubber ACT
Min. Ceiling Height: STC 50 Max. Ceiling Height: STC 55 as required desired / not required / not prohibited n/a
Corner guards at outside corners
Finishes Carpet
Electrical / Communication / Data
GWB, Paint Window Treatment:
none Desirable
Mechanical / Plumbing Maintain specified temperature Yes
Not required Not required
Convenience outlets per code Minimum illumination 50 fc. Provide linear fluorescent lighting.
None CCTV Coverage
None Provide coverage
Fire Protection
EIE326 - ENLISTED DORMITORY
EIELSON, AFB
DESIGN-BUILD RFP
Room # / NAME
Purpose:
Min. Net Area: Wall:
Max. Net Area: Flr/Clng:
Door(s):
Window(s):
Casework: Base: Wall: Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Mechanical / Plumbing
Window Treatment:
Electrical / Communication / Data
Min. Ceiling Height:
Acoustics:Area Ceiling
Max. Ceiling Height:
Adjacencies:
Architectural
Finishes
Fire Protection
EIE326 - ENLISTED DORMITORY
EIELSON, AFB
DESIGN-BUILD RFP
Room # / NAME
Purpose:
Min. Net Area: 9'-0" Wall:
Max. Net Area: Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Fire Protection n/a
None
Electrical / Communication / Data Provide one duplex outlet on each wall
Min. Ceiling Height:
Acoustics:
STC 50
None
One data outlet adjacent to one duplex outlet.
Maintain specified temperature Yes
Not required
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
3'-0" min. @ interior; pr 3'-0" min. @ exterior; Storage locksets, closers, SUPPLY STORAGE
Storage for Dorm management, excess furnishings, supplies, equipment
Adjacencies: Dorm Management
Architectural none
Finishes
Rubber Base
7 ea. - full size bed frame, bed in bag & pillow, 5 drwr dresser, desk w chair, night stand, mini fridge, waste baskets, black out shades, shower curtains, GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
Minimum illumination 20 fc.
Fluorescent lighting. Ceiling-mounted occupancy switch
Mechanical / Plumbing
Not required
GWB, Paint
| Main Comm. |
| Summary |
| Main Arctic Entry |
| Lobby |
| Vending |
| Public Toilet |
| Multi-purpose |
| Bulk Storage |
| Laundry |
| Janitor |
| Shared Commons |
| Sleeping Room |
| Private Bath |
| Walk-in Closet |
| Dorm Management |
| Main Electrical |
| Electrical |
| Comm. |
| Main Mech. |
| Mech.- AirHandlers |
| Elevator |
| Elevator Machine |
| Stair |
| Circulation |
| Room |
| Supply Storage |