DORMITORY, 168 PN EIELSON AFB, AK
SECTION 01 19 10.00 29
W911KB-14-D-0017
EIE 326
Room Name Oty.
Common Areas Min. Recommended Max
Main Arctic Entry 1 250
Lobby 1 200
Vending 1 25 80
Public Toilet - Accessible 1 65 100
Multi-purpose (2 sf/person + 78 sf admin space) 1 270 414
Centralized Bulk Storage 1 Note 1
Centralized Laundry (optional) 3 Note 2
Janitor / Housekeeping 6 60 100
Dorm Module
Shared Commons (includes In-Module Laundry) 42 123 300
Bedroom 168 129 129-150 183
Private Bathroom 168 35 35
Walk-in Closet 168 20 20
Dorm Management
Dorm Management 1 500
Support Services
Main Electrical 1 135
Electrical 6 100
Main Communications 1 100
Communications 5 100
Main Mechanical 1 525
AM#5… ROOM/AREA TABULATION …AM#5
P
R O
G R
A M
A R
E A
S
Net Area - sf
Main Mechanical 1 525
Mechanical - Air Handlers 2
Elevator 1 Note 3 Note 3
Elevator Machine Room 1
Stair(s) 3
Circulation / Corridors
Supply Storage 1 100 100
Notes:
68,712TOTAL GROSS AREA
1. Provide (2) 3x3x7-10 cages (18 sf)/module plus circulation.
2. 7 Washers + 9 Dryers at 21 sf each (including circulation) equals 343 sf/Laundry Rm recommended.
3. Size for 24 inch x 84 inch Ambulance gurney, extended. Recommend 5'-5"x7'-8" center opening elev.
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: - 8'-0" Wall:
Recommended: 250 sf 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Phone/Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Walk of grating, Walk off carpet
Glazed Storefront, 3'-0" min.; Exit hardware; Card key access on interior door to Lobby
MAIN ARCTIC ENTRY
Architectural
Provides a buffering entry zone for access to the main lobby & location for mailboxes.
Lobby, Dorm Management
Ceiling
Max. Ceiling Height:
n/a
Acoustics:
STC 50
STC 55
Area
Adjacencies:
Finishes
None
Card swipe at interior door and CCTV coverage
Two duplex outlets: One convenience outlet and one duplex outlet for temp.
card machine
Not required Not required
None required
Two data outlets; Card machine and intercom phone to Dorm Mgr's Office
Electrical / Communication / Data Minimum illumination 20 fc. Linear fluorescent lighting switched at circuit breaker.
Fire Protection
Provide dry sprinkler or dry pipe system as required.
Sprinkler, Fire Alarm, & Mass Notification
Provide intercom system for communication between arctic entry and dorm management office.
Min. Ceiling Height:
not required / not prohibited
GWB, Paint Window Treatment:
n/a
Rubber Base
Terminal heating unit sized for 4 ACHRs
Not required Mechanical / Plumbing
Mailboxes; Card key kiosk; Intercom call box; FAP; Security Camera(s);
Provide 168 mail boxes (6"w x 5" h x 15.5" d); provide one out going mail drop box; provide location for card key kiosk. DESIGN CAUTION: Locating mail boxes in Arctic Entry/Lobby is only allowable per exception to UFC 4-010-01, Appendix B, Standard 13 Mail Rooms (On- Base Central Mail Processing exception). Designer is cautioned to verify current and near term mail handling procedures with EAFB personnel prior to design. Alterations to mail handling procedures may require full compliance with Standard 13 including mail boxes be located in Mail Room physically and/or mechanically isolated from other portions of building.
GWB, Paint
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: - 9'-0" Wall:
Recommended: 200 sf - Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
not required / not prohibited
Finishes
Quarry Tile or Rubber Base
GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
LOBBY
Central Circulation zone, Transition from exterior to interior
Adjacencies: Main Arctic Entry, Dorm Management, Public Toilet, Multi-purpose
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
Provide coverage
One 2-port phone/data outlet.
Maintain specified temperature Yes
Not required
Linear fluorescent lighting switched at Dorm Mgr's office
CCTV coverage
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
Glazed Storefront, 3'-0" min.; Exit hardware; access control on door to Main Arctic Entry
Mechanical / Plumbing
Not required
GWB, Paint
Window Treatment:
Quarry Tile or Resilient flooring
Electrical / Communication / Data One duplex outlet on every wall.
Fire Protection
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: 25 SF 8'-0" Wall:
Recommended: 80 SF 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
n/a
Finishes
Rubber Base provide space for two vending machines. (GFGI)
GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
VENDING
Area for the placement of vending machines.
Adjacencies: Lobby; Multipurpose;
Dorm Management;
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
Provide coverage
Provide a data outlet for each vending equipment.
Maintain specified temperaure Not required
Provide domestic cold water, recessed with isolation valve
Linear fluorescent lighting switched with lobby.
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a n/a
Mechanical / Plumbing
AM#4… Deleted …AM#4
GWB, Paint
Window Treatment:
n/a
Match room it opens to.
None
Provide and locate floor drain at/under AM#4… vending machine(s) …AM#4
Electrical / Communication / Data 2 GFCI double duplex outlets on each vending machine wall. Provide two circuits per double duplex outlet.
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: 65 sf 8'-0" Wall:
Max. Net Area: 100 sf 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
n/a
Ceramic Tile to 5'-0" min.
Finishes
Ceramic Tile or Integral Cove mirror; soap dispenser; paper towel dispenser and waste receptacle; tp dispenser; grab bars;
GWB, Paint
Comply with all ABA required clearances, mounting heights, and ammenities.
Sprinkler, Fire Alarm, & Mass Notification
Mechanical / Plumbing toilet, lav with single handle faucet, floor drain
GWB, Paint
Window Treatment:
n/a
PUBLIC TOILET - ACCESSIBLE
ADA Accessible toilet and sink for public use
Adjacencies: Lobby; Dorm management;
Multipurpose
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
Provide coverage as required
None
Maintain specified temperature Yes, and exhaust to outdoors
Hot water, cold water, waste and vent
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
3'-0" min.; privacy hardware w/ closer, Fire Protection
Minimum illumination 20 fc. Provide fluorescent vanity fixture above mirror and linear fluorescent fixture on ceiling.
Control all lighting with ceiling-mounted occ. sensor.
Ceramic Tile or Resilient Flooring
None
Electrical / Communication / Data One GFCI receptacle by sink location
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: 270 sf 8'-0" Wall:
Recommended: 414 sf 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Operable windows. Interior relites desired but not required.
Finishes
Rubber Base
AM#4… There is no set program for this space. Space to be used for a variety of activities including meetings, TV, video-gaming or fitness. Refer to Appendix 3, USAF Dormitory Design Guide for further information. …AM#4
GWB, Paint
Area may be increased based on available area within Gross Building Area.
Sprinkler, Fire Alarm, & Mass Notification
Mechanical / Plumbing
Not required
GWB, Paint
Window Treatment:
Horizontal blinds & black out drapes
MULTI-PURPOSE
Social gathering space, TV viewing, gaming, relaxation
Adjacencies: Lobby; Vending; Public Toilet; Dorm Management
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
Provide wireless internet at this location only.
Provide coverage
Provide one data outlet on each wall.
Maintain specified temperature Yes
Not required
CCTV Coverage
STC 55
Area Ceiling
Max. Ceiling Height:
n/a pr 3'-0" min interior & exterior.; magnetic hold opens; passage latch, panic hardware w/ closer, narrow lite glazing;
Fire Protection
Minimum illumination 50 fc. Provide linear fluorescent lighting with occupancy sensor control
Resilient Flooring
Provide CATV outlet at television location
Electrical / Communication / Data Provide two duplex outlets on each wall
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: See Equip 8'-0" Wall:
Recommended: See Equip 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
n/a impact protection
Finishes
Rubber Base
AM#5… For each Dorm-4-Airmen Module, provide (2) 3'x3'x7'-10" (141.2 cf/Module) storage lockers or caged enclosures, divided into equal sized upper and lower units, each with separate door and lock. (18 sf footprint/Module plus circulation) …AM#5
GWB, Paint
Area may be increased based on available area within Gross Building Area.
Sprinkler, Fire Alarm, & Mass Notification
Minimum illumination 20 fc. Provide linear fluorescent lighting with occupancy sensor control
Mechanical / Plumbing
Not required
GWB, Paint
Window Treatment:
BULK STORAGE
Storage for resident's gear (mobility bags, seasonal equipment, tires, boxes, etc.)
Adjacencies: Corridor, exterior
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
Provide coverage
One data outlet by each door.
Maintain specified temperature Yes
Not required
CCTV Coverage of all areas
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
3'-0" min. personell door interior & exterior; 8'-0" insulated ovrhd sectionaldoor @ exterior.;
magnetic hold opens, panic hardware w/ closer, narrow lite glazing @ interior; panic hardware w/ closer @ exterior
Fire Protection
Horizontal blinds & black out drapes
Sealed Concrete
None required
Electrical / Communication / Data Provide one duplex outlet by each door.
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: - 8'-0" Wall:
Recommended: 343 sf/Flr 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: Wall: Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Fixed (non-operable)
Finishes
Rubber Base or Integral Cove
AM#4… (1) Commercial Top Load Washer per 8 Persons, (1) Commercial Dryer per 6 Persons. (1) 24 inch deep by 60 inch long wall mtd countertop, set at 34 inches AFF, for folding of clothes. (1) recessed, cabinet-mounted fold-down ironing board. …AM#4
GWB, Paint
Mount Utility connections 3'-0" AFF; provide floor drains; Utility sink - Porcelain;
Sprinkler, Fire Alarm, & Mass Notification
LAUNDRY (OPTIONAL)
Centralized Laundry Services equipment, located on each floor.
(Note: Preference is for stackable W/Ds in each Dorm Module)
Adjacencies: Corridor; Locate centraly in floorplate, stack on each floor, Architectural
Min. Ceiling Height:
Acoustics:
STC 50
None
None
Maintain specifed temperature Yes, dryer exhaust to the outdoors and make up air hot water, cold water, waste and vent
Provide linear fluorescent lighting. 30fc minimum. Wall-mounted occupancy switch.
CCTV Coverage
STC 55
Area Ceiling
Max. Ceiling Height:
Solid surface
3'-0" min.; passage latch, closer, half-lite glazing
Mechanical / Plumbing floor drain, laundry sink with faucet, floor sink for indirect laundry sink waste
GWB, Paint
Window Treatment:
n/a
Resilient Flooring
None
Electrical / Communication / Data Provide dedicated receptacles for washing and drying machines. Provide one duplex outlet on each wall.
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: 60 sf 8'-0" Wall:
Recommended: 100 sf 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
none
FRP to 7'-0" AFF min.
Finishes
Integral Cove
Mop Rack; Utility Sink; Floor Drain
GWB, Paint
Provide wall mounted Stainless Steel shelving (5' w x 1'd x 5' h); Provide space for 1 Commercial Vacuum (GFGI)
Sprinkler, Fire Alarm, & Mass Notification
JANITOR / HOUSEKEEPING
Storage of housekeeping supplies Adjacencies: Laundry, Corridor, Architectural
Min. Ceiling Height:
Acoustics:
STC 50
None
None
Maintain specified temperature Exhaust to the outdoors hot water, cold water, waste and vent
Linear fluorescent lighting. Wall-mounted occupancy switch
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
3'-"0 min.; storage latch, closer
Mechanical / Plumbing mop sink with faucet, floor drain
GWB, Paint
Window Treatment:
n/a
Resilient flooring
None
Electrical / Communication / Data Provide one GFCI receptacle
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: 123sf 8'-0" Wall:
Recommended: 123-300 sf 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: 3' min. Wall: 3' min. Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
not required / not prohibited
Finishes
Rubber Base
Two Burner stove top; Microwave / convection oven / hood unit; double compartment sink;
ceiling fan; space for an 18 cu.ft. refrigerator; fire extinguisher; AM#4... full-sized stacked washer/dryer w/ top loading washer; (1) recessed, cabinet-mounted fold-down ironing board located convenient to laundry area. ...AM#4
GWB, Paint
Provide layout for dining room and living room style seating for 4PN ea., storage for vacuum cleaner, ironing board, iron, cleaning supplies, AM#5… Deleted …AM#5
Sprinkler, Fire Alarm, & Mass Notification
SHARED COMMONS
Cooking, dining, social space, storage Adjacencies: Corridor, Bedrooms
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
None
Provide phone and data outlets at two locations. Comply with Unaccompanied Housing Design Guide.
Maintain specified temperature Yes, and range hood exhaust
Hot water, cold water, waste, vent, cold water to refrigerator
Minimum illumination 20 fc. Provide local switch at entryway. Provide ceiling-mounted lighting
None
STC 55
Area Ceiling
Max. Ceiling Height:
3' (2'min. adjcnt to sink)
3'-0" min.; Card Key Access; Peep hole; Closer; Sweep &gaskets
Mechanical / Plumbing double bowl - stainless steel, with faucet and spray
GWB, Paint
Window Treatment:
If a window is provided then horizontal blinds & blackout drapes resilient flooring in kitchen/dining area and circulation, carpet in social space
Provide CATV outlets at two locations.
Comply with Unaccompanied Housing Design Guide.
Electrical / Communication / Data Provide duplex receptacles as required by NEC. Comply with Unaccompanied Housing Design Guide.
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: 129sf 8'-0" Wall:
Max. Net Area: 183 sf 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Operable - Sliding or Double Hung
Finishes
Rubber Base
Full Bed; Desk w/ Chair; Nightstand; 5 Drwr Dresser; Floor Lamp; 3.6 cu.ft. mini-fridge; waste basket;
GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
Minimum illumination 20 fc. Provide local switch at entryway. Provide ceiling mounted CFL light fixture and switched receptacle.
Mechanical / Plumbing
None
GWB, Paint
Window Treatment:
SLEEPING ROOM
Private Area for living and sleeping Adjacencies: Shared Commons;
Private Bathroom;
Walk-in Closet
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
None
Provide phone and data outlets at two locations. Comply with Unaccompanied Housing Design Guide.
Maintain specified temperature Yes
None
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
2'-10" min.; Card key access; peep hole; sweep & gaskets
Fire Protection
Horizontal blinds & black out drapes
Carpet w/ pad
Provide CATV outlets at two locations.
Comply with Unaccompanied Housing Design Guide.
Electrical / Communication / Data Provide duplex receptacles as required by NEC. Comply with Unaccompanied
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: 35 sf 8'-0" Wall:
Recommended: 35 sf 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: 3' min. Wall: 2'-6" Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
n/a
Ceramic Tile or Solid Surface at Tub
Finishes
Rubber base or Integral cove
Mirror; medicine cabinet; tp holder; hand towel bar; towel bar; robe hook; waste basket;
shower curtain rod, hooks, & curtain; shower shelf & soap dish; fan;
GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
PRIVATE BATH
Private bath/shower, toilet, and sink Adjacencies: Bedroom
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
None
None
Maintain specified temperature Supply air and exhaust to the outdoors
Hot water, cold water, waste and vent
Minimum illumination 20 fc. Local switch at door. Ceiling-mounted luminaire and vanity light fixture above mirror.
None
STC 55
Area Ceiling
Max. Ceiling Height:
3' min.
2'-8" min.; privacy lockset
Mechanical / Plumbing
5'-0" tub/shower, shower head, mixing valve, toilet, bath faucet. Lav with single handle faucet
GWB, Paint
Window Treatment:
n/a
Resilient Flooring
None
Supply air can be provided from adjancent space through undercut door
Electrical / Communication / Data Provide one dedicated GFCI duplex receptacle by sink
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: 20 sf 8'-0" Wall:
Recommended: 20 sf 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/ a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
n/a
Finishes
Rubber Base
Provide coat rod and shelf with a minimum length of 8' hanging space.
GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
WALK-IN CLOSET
Walk-in Storage for personal gear and clothes
Adjacencies: Bedroom
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
None
None
Maintain specified temperature not required not required
Minimum illumination 10 fc. Provide local switch at entryway. Provide light fixture listed for closet.
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
2'-8" min.; storage lockset w/ dead bolt
Mechanical / Plumbing not required
GWB, Paint
Window Treatment:
n/a
Carpet w/ pad (match room adjacent)
Electrical / Communication / Data None
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: 500sf 9'-0" Wall:
Max. Net Area: - Flr/Clng:
Door(s):
Window(s):
Casework: Base: 4' min. Wall: 4' min. Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Operable; Sliding or Double Hung
Finishes
Rubber Base
AM#4… Private Office: (1) Standard Desk (72"x32" desk w/ slide-out keyboard tray and box/box/file pedestal, and 48"x24" return w/ box/box/file pedestal), (1) Task Chair, (1) 4-drawer lateral file, (1) visitor chair. Open Office: (2) Workstations (72"x96" workstation w/ privacy panels, work surfaces, (2) file drawer pedestal, slide-out keyboard tray and overhead storage), (2) task chairs, (2) 4-drawer lateral files, (2) visitor chairs, 24"x60" printer countertop w/ double drawer base cabinet w/ adj. shelves. … AM#4
GWB, Paint
Provide one private office and two open office workstations. Area may be increased based on available area within Gross Building Area.
Sprinkler, Fire Alarm, & Mass Notification
Minimum illumination 50 fc.
Fluorescent lighting controlled by occupancy sensors.
Mechanical / Plumbing
Bar sink with faucet
Acoustic Ceiling Tile
Window Treatment:
DORM MANAGEMENT
Dorm Management Offices Adjacencies: Main Arctic Entry, Lobby, Supply Storage, Public Toilet, Vending, Multi-purpose, Architectural
Min. Ceiling Height:
Acoustics:
STC 50
Provide intercom system for communication between Arctic Entry and Dorm Management.
Provide coverage
Provide two data outlets on each wall.
Comply with Unaccompanied Housing Design Guide.
Maintain specified temperature Yes
Hot water, cold water, waste, and vent
None
STC 55
Area Ceiling
Max. Ceiling Height:
4' min.
3'-0" min.;
Fire Protection
Horizontal Blinds
Resilient flooring or Carpet
Provide one CATV outlet
Electrical / Communication / Data Provide two duplex outlets on each wall. Comply with Unaccompanied
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: 135sf 8'-0" Wall:
Max. Net Area: 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
none
Finishes
Rubber Base
GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
Linear fluorescent lighting. Provide 50fc minimum. Local switch.
Mechanical / Plumbing
Not required
GWB, Paint
Window Treatment:
MAIN ELECTRICAL
House primary electrical systems, primary electrical utility entry point and distribution
Adjacencies: 1st Floor
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
None
One data outlet by power outlet
Maintain speficied temperature Mechanical ventilation for cooling
Not required
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
3'-0" min.; storage lockset, closer
Fire Protection n/a
Sealed concrete
One convenience duplex outlet
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: 100sf 8'-0" Wall:
Max. Net Area: - 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
none
Finishes
Rubber Base
GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
ELECTRICAL
Satellite Electrical Closets located on each floor, Adjacencies:
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
None
One data outlet by power outlet
Maintain speficied temperature Mechanical ventilation for cooling
Not required
Linear fluorescent lighting. Provide 50fc minimum. Local switch.
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
3'-0" min.; storage lockset; closer; sweep & gasket
Mechanical / Plumbing
Not required
GWB, Paint
Window Treatment:
n/a
Sealed Concrete
Electrical / Communication / Data One convenience duplex outlet
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: 100sf 8'-0" Wall:
Max. Net Area: 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: Wall: Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
none
Finishes
Rubber Base
GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
MAIN COMMUNICATIONS
Primary Communications Utility entry point and distribution
Adjacencies: 1st Floor
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
None
Provide one data outlet.
Maintain specified temperature Positive pressure filitered per EIA/TIA 569, Equipment cooling
Not required
Linear fluorescent lighting. Provide 50fc minimum. Wall-mounted occupancy switch.
None
STC 55
Area Ceiling
Max. Ceiling Height:
3'-0" min.; storage lockset; closer;
Mechanical / Plumbing
Not required
GWB, Paint
Window Treatment:
n/a
Stattic Dissipative Tile
Electrical / Communication / Data One circuit per rack. Provide (2) double duplex outlet for TTB on designated circuit.
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: 100sf 8'-0" Wall:
Max. Net Area: - Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
None
Finishes
Rubber Base
GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
COMMUNICATIONS
Communications closets located at each floor for distribution of communications systems
Adjacencies: Corridor
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
None
Provide one data outlet.
Maintain specified temperature Positive pressure filitered per EIA/TIA 569, Equipment cooling
Not required
Linear fluorescent lighting. Provide 50fc minimum. Provide occupancy sensor control.
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
3'-0" min.; storage lockset; closer; sweep & gaskets;
Mechanical / Plumbing
Not required
GWB, Paint
Window Treatment:
n/a
Static Dissipative Tile
Electrical / Communication / Data One circuit per rack.
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: 525sf 9'-0" Wall:
Max. Net Area: - - Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: 3' min. Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
none
Finishes
Rubber Base
Floor Drain, Hot / Cold Water Hose Bib; Utility Sink; wall mounted cabinet for O&M manuals.
GWB, Paint
Provide a 4" concrete curb at perimeter walls of the room. Provide 4 inch high by 6 inch wide concrete curb around utility pit. Include fall protection (guardrail) around opening and fixed ladder down into pit.
Sprinkler, Fire Alarm, & Mass Notification
MAIN MECHANICAL
House primary Mechanical systems, primary mechanical utilities point of entry and distribution
Adjacencies: 1st floor
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
None
Provide data outlet for DDC panel.
Coordinate with mechanical
Maintain specified temperature Mechanical ventilation for cooling hot water, cold water, waste and vent
Provide linear fluorescent lighting.
Local switch. 30fc minimum
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a pr 3'-0" min. @ exterior;
Mechanical / Plumbing floor drain, hot and cold water hose bibb
GWB, Paint
Window Treatment:
n/a
Sealed Concrete
Electrical / Communication / Data Provide duplex receptacles on each wall.
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: - - Wall:
Max. Net Area: - - Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
none
Finishes
Air Handlers
GWB, Paint
NOTE; PLACEMENT OF AIRHANDLERS IN ATTIC SPACE IS PERMITTED AND WILL
NOT COUNT AGAINST GROSS BUILDING AREA (GBA) PROVIDED AVERAGE CEILING
HEIGHT OF THE SPACE DOES NOT EXCEED 7 FEET, OTHERWISE HALF OF THE
AREA OF THE ENCLOSED SPACE MUST BE INCLUDED IN THE GBA.
Sprinkler, Fire Alarm, & Mass Notification
MECHANCIAL - AIR HANDLERS
House mechanical fan units Adjacencies: Corridor; elevator;
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
None
Provide data outlet for DDC panel.
Coordinate with mechanical
Maintain specified temperature Not Required
Waste and vent
Provide linear fluorescent lighting.
Local switch. 20fc minimum
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
3'-0" min.; storage lockset; narrow lite
Mechanical / Plumbing
Hot/Cold hose bib, Floor drain
GWB, Paint
Window Treatment:
n/a
Catwalk
Electrical / Communication / Data Provide duplex receptacles on each wall. Provide connections to mechanical equipment and motor controllers as required.
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: See Notes 9'-0" Wall:
Max. Net Area: See Notes Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
none
Stainless Steel Flat Handrail
Finishes
Mtl - Powder coat
Stainless Steel
Elevator shall be sized to accommodate a 24" x 84" Ambulance gurney; Provide protection pads and hanging buttons. AM#5… Recommend 5'-5"x7'-8" elevator w/ center opening door.
…AM#5
Sprinkler, Fire Alarm, & Mass Notification
Provide emergency 2-way voice communications per ASME A17.1
One duplex GFCI service receptacle
Mechanical / Plumbing
Not required
Stainless Steel
ELEVATOR
Vertical transportation of furniture, appliances, and occasionally personnel.
Adjacencies: Corridor, Elevator Machine Room
Architectural
Min. Ceiling Height:
Acoustics:
n/a
PA coverage
Not required Not required
Not required
Fluorescent lighting
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
Fire Protection
Window Treatment:
n/a
Rubber
None
Provide sump and sump-pump with oil detection. Connect sump discharge to building waste through indirect connection. Comply with ASME A17.1, part 2.2.2.4.
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: - 8'-0" Wall:
Max. Net Area: - 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
none
Finishes
Rubber Base
GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
One duplex GFCI receptacle Provide linear fluorescent lighting.
Local switch. 30fc minimum
Mechanical / Plumbing
Not required
GWB, Paint
ELEVATOR MACHINE ROOM
Elevator Equipment location Adjacencies: Elevator, Corridor
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
None
One data outlet
Maintain specified temperature exhaust to the outdoors
Not Required
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
3'-0" min.; storage latch; closer
Fire Protection
Window Treatment:
n/a
Sealed Concrete
None
Follow ASME A17.1 requirements. Hard piping of sump pump discharge to the building waste or discharge outdoors is not permitted. Locate sump pump controls here.
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: - 8'-0" Wall:
Max. Net Area: - - Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
None
Finishes
Rubber Base
GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
Minimum illumination 20 fc. Provide ceiling-mounted, impact-resistant, linear fluorescent lighting on stairwell landings.
Mechanical / Plumbing
Not required
GWB, Paint
Window Treatment:
STAIR(s)
Vertical Circulation, Emergency Egress Adjacencies: Corridor, Exit
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
Provide coverage
None
Maintain specified temperature Yes
Not required
CCTV coverage
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
3'-0" min.; Mtl.; rated; Narrow Lite; Panic Hardware; Closer; Sweeps & Gaskets;
Fire Protection n/a
Rubber at Landings, Risers, and Treads
None
None
W911KB-14-D-0017
EIE 326
Room NAME
Purpose:
Min. Net Area: - 8'-0" Wall:
Max. Net Area: - 9'-0" Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
Fire Protection Sprinkler, Fire Alarm, & Mass Notification
Convenience outlets per code Minimum illumination 50 fc. Provide linear fluorescent lighting.
None CCTV Coverage
None Provide coverage
Electrical / Communication / Data
GWB, Paint Window Treatment:
none Desirable
Mechanical / Plumbing Maintain specified temperature Yes
Not required Not required n/a
Corner guards at outside corners
Finishes Carpet
Rubber ACT
Min. Ceiling Height: STC 50
Max. Ceiling Height: STC 55 as required desired / not required / not prohibited
Area Ceiling Acoustics:
CIRCULATION/ CORRIDORS
Horizontal Circulation connecting all elements of the facility
Adjacencies: as required
Architectural
W911KB-14-D-0017
EIE 326
Room # / NAME
Purpose:
Min. Net Area: 100 sf 9'-0" Wall:
Recommended: 100 sf Flr/Clng:
Door(s):
Window(s):
Casework: Base: n/a Wall: n/a Countertop:
Equipment / Appliances:
Floor:
Base: Ceiling:
Wall:
Wainscot:
Notes:
Heating: Ventilation:
Plumbing: Plumbing Fixtures:
Notes:
Electrical: Lighting:
Comm./Data: Security:
CATV: PA System:
Notes:
System Type:
Notes:
none
Finishes
Rubber Base
7 ea. - full size bed frame, bed in bag & pillow, 5 drwr dresser, desk w chair, night stand, mini fridge, waste baskets, black out shades, shower curtains, GWB, Paint
Sprinkler, Fire Alarm, & Mass Notification
Minimum illumination 20 fc.
Fluorescent lighting. Ceiling-mounted occupancy switch
Mechanical / Plumbing
Not required
GWB, Paint
Window Treatment:
SUPPLY STORAGE
Storage for Dorm management, excess furnishings, supplies, equipment
Adjacencies: Dorm Management
Architectural
Min. Ceiling Height:
Acoustics:
STC 50
None
One data outlet adjacent to one duplex outlet.
Maintain specified temperature Yes
Not required
None
STC 55
Area Ceiling
Max. Ceiling Height:
n/a
3'-0" min. @ interior; pr 3'-0" min. @ exterior; Storage locksets, closers, Fire Protection n/a
None
Provide one duplex outlet on each wall