Technical_Exhibit_B3_-_Electric_Meter_Specifications.pdf
PDF 407 KB Posted
- Attached to
- Open End Electrical Requirements Contract Federal contract opportunity
- Solicitation number
- W91151-16-B-0021
About this file
Exhibit B3 - Electric Meters Specifications
View the file
Other files for this federal contract opportunity
Show all 26
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADVANCED ELECTRIC METER SPECIFICATION (FORT HOOD, TX)
PART 1 GENERAL SECTION 26 27 13.10 30
1.1 REFERENCES
ELECTRIC METERS
09/10/2012
Revised May 7, 2015 Section: 3.1.2
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C2 (2007; Errata 2007; INT 2008) National Electrical Safety Code IEEE Std 100 (2000) The Authoritative Dictionary of IEEE Standards Terms
ANSI C2
ANSI CI2.1
ANSI C12.4
ANSI C12.10
ANSI C12.11
(2008) Code for Electricity Metering (1984; R 1990) Mechanical Demand Registers.
(1987) Electromechanical W a t t -hour Meters.
(1987; R 1993) Instrument Transformers for Revenue Metering, 10 kV BTL through 350 kV BIL (0.6 kV NSV through 69 kV NSV).
IEEE C2
IEEE C57.13
(1993) Instrument Transformers
1.2 DEFINITIONS
Unless otherwise specified or indicated, electrical and electronics terms used in this specification and on the drawings shall be as defined in IEEE Std 100.
1.3 SUBMITTALS
Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
a. Maintenance manual shall provide:
1. Condensed description of how the equipment operates.
2. Block diagram indicating major assemblies.
3. Troubleshooting information
4. Preventive maintenance\
5. Spare parts information.
b. Provide operation and maintenance manuals required by submittal item “SD-10 Operation and
Maintenance Data”.
SD-02 Shop Drawings SD-03 Product Data
LonWorks WNC WattNode Logger Electric Meter; G.
LonWorks ILON 600 IP/server; G.
Current Transformers; G.
NEMA 1, 8 inch tall x 10 inch wide x 4 inch deep enclosure with hinged door and latch for pad lock for Wattnode meter; G.
NEMA 1, 12 inch tall x 12 inch wide x 4 inch deep enclosure with hinged door and latch for pad lock for ILON 600 IP/Server connection point; G.
Submittals shall include manufacturer’s information for each component, device, and accessory provided with the meter or protocol module.
SD-06 Test Reports Acceptance checks and tests; G SD-10 Operation and Maintenance Data LonWorks WNC WattNode Logger Electric Meter; G.
LonWorks ILON 600 IP/Server; G.
Current Transformers; G.
NEMA 1 8 inch tall x 10 inch wide x 4 inch deep enclosure with hinged door and latch for pad lock for Wattnode meter; G.
NEMA 1, 12 inch tall x 12 inch wide x 4 inch deep enclosure with hinged door and latch for pad lock for ILON 600 IP/Server connection point; G.
SD-11 Closeout Submittals
System function verification; G
1.4 QUALITY ASSURANCE
1.4.1 Installation Drawings
Drawings shall indicate but not be limited to the following:
a. Elementary diagrams and wiring diagrams with terminals identified of kilowatt meter, current transformers, protocol modules, telephone lines. For each meter installation, provide a diagram identified by the building number.
b. One-line diagram, including meters, switch (es), current transformers, protocol modules, telephone outlets, and fuses. For each meter installation, provide a diagram identified by the building number.
1.4.2 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship. Products shall have been in satisfactory commercial or industrial use for 2 years prior to bid opening. The 2- year period shall include applications of equipment and materials under similar circumstances and of similar size. The product shall have been on sale on the commercial market through advertisements, manufacturer’s catalogs, or brochures during the 2-year period. Where two or more items of the same class of equipment are required, these items shall be products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.
1.4.3 Alternative Qualifications
Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers’ factory or laboratory tests, is furnished.
1.4.4 Material and Equipment Manufacturing Data
Products manufactured more than 2 years prior to date of delivery to site shall not be used, unless specified otherwise.
1.5 WARRANTY
The equipment items shall be supported by service organizations which are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.
1.6 SYSTEM DESCRIPTION
1.6.1 System Requirements
The metering and reading system, consisting of LonWorks WNC WattNode Electric Meter and ILON 600 IP/Server will be used to record the electricity consumption and other values as described in the sections that follow and as shown on the drawings.
1.6.2 Selection Criteria
Metering components are part of a system that includes the physical meter data recorder function and communications (modern) method. Every building site identified shall include sufficient metering components to measure the electrical parameters identified and to store and communicate the values as required in the following sections. Contractor shall verify that the metering system installed on any building site is compatible with the facility-wide communication and meter-reading protocol system.
a. The purpose of the following specifications is to achieve meter equipment compatibility with the
Army metering program pursuant to Public Law 109-58, Section 103 of the Energy Policy Act of
2005. The intent is for all advanced meters to report their data to an installation-centric energy reporting and management system such as a utility monitoring and control system (UMCS). The advanced meters must provide data at least daily and measure at least hourly consumption of electricity. The means for meter data transmission using open-protocols such as ANSUCEA
709.1 b (LonTalk) and over low cost transport media (ILAN). These specifications provide the needed support of data transmission system alternatives in addition to meeting the minimum standards for energy consumption data recording and reporting. The meters will be capable of integrating with the Army’s communication networks supported by Network Enterprise Command
(NEC).
PART 2 PRODUCTS
2.1 Current Transformers (CT)
Shall have an output of 333mv as required for the Wattnode of Model # type WNC-XX-XXX-FT10-L and sized as follows. Unless otherwise indicated, bar, wound, or window-type transformers are acceptable;
and except for window-type units installed over insulated buses, transformers shall have a BIL rating consistent with the rated BIL of the associated switchgear or electric power apparatus bushings, buses or conductors.
Current transformers shall have the indicated ratios. The continuous thermal-current rating factor (TCR) shall not be less than 2.0. Other thermal and mechanical ratings of current transformers and their primary leads shall be coordinated with the design of the circuit breaker and shall be not less than the momentary rating of the associated circuit breaker.
Circuit protectors shall be provided across secondary leads when a form meter is used of the current transformers to prevent the accident open-circuiting of the transformers while energized.
Each terminal of each current transformer when form meters or used shall be connected to a short-circuiting terminal block in the circuit interrupting mechanism cabinet, power transformer terminal cabinet, and in the associated instrument and relay cabinets. CT used with the Advanced Wattnode meter does not require TCR or CT shorting circuit terminal blocks. The output for the Wattnode CT’s is a standard 333mv.
CT Selection has two main criterions:
1. CT shall be sized so that 10-percent of the rated CT is equal to or less than the minimum load of the load being metered. While 10-11 percent is for electromagnetic metering equipment, 5-percent is for electronic metering equipment.
2. CT shall be sized so that the rated CT (with TCR) is slightly above the maximum load being metered.
3. Selection examples (all using TRF of 2.0, 3 phase configuration):
Examples Selection Discussion Comments
Exam #1: 500 kVA xmtr Full Load: 1380A Voltage: 208 VAC
- Apply 80% to full load (1380 x .8)=1,104A
- Low side excitement: (1104 x .1)=110A
- High side burden: (1,104A)
- Selected CT: 600:5
- 600:5 selection
- Low end excitement (600 x .1)=60A
- High side burden (600 x 2)=1,200A
- CT selection will be excited down to 60A – able to measure minimum load (110A), and a high side burden of 1,200A – capable of measuring max load (1,200) without degradation or meltdown.
Exam #2: 750 kVA xmtr Full Load: 900A Voltage: 480 VAC
- Apply 80% to full load (900 x .8)=720A
- Low side excitement: (720 x .1)=72A
- High side burden: (720A)
- Selected CT: 400:5
- 400:5 selection
- Low end excitement (400 x .1)=40A
- High side burden (400 x 2)=800A down to 40A – able to measure minimum load (72A), and a high side burden of 800A – capable of measuring max load (720A) without degradation or meltdown.
Exam #3: Primary Service Group of Bldg: 50 ea Avg Full Load: 100A ea Sec Voltage: 208 VAC Pri Voltage: 7.2KV
- Determine full load at 208VAC
- Full load: (50 x 100)=5,000A
- Apply 80% to full load (5,000 x .8)=4,000A
- Low side excitement: (4,000 x .1)=400A
- High side burden: (4,000A)
- Determine Loads @7.2KV (Primary):
- Assume PF: 90%
- Using 80% load, determine KW
@208VAC:
- KW high load: (208 x 4,000 x
1.73 x .90) / 1000) = 1,295KW
- Using low side load, determine
KW @208VAC:
- KW Low side: (208 x 400 x 1.73 x .9) /1000=129 KW
- Using KW high load, determine Amp @7.2KV
- Amp high load: (1,295x1000 / 7200 x 3 x .9)= 66A
- Using KW low load, determine Amp @7.2KV
- Amp low load: (129 x 1000 / 7200 x 3 x .9)= 7A
- Selected CT: 50:5
- NOTE: A set of Potential Transformers are required to step down 7.2KV to 120V (7200:120 ratio) for the transformer rated type meter.
- 50:5 selection down to 5A – able to measure minimum load (7A), and a high side burden of 100A – capable of measuring max load (66A) without degradation or meltdown.
NOTE: Use the following guidelines for specifying current transformers.
1. Use the above example guide to select the standard (CT) rating with a minimum TRF of 2.0.
2. Select a continuous-thermal-current rating factor (TRF) in accordance with the following Table:
Ratio TRF at 30 degrees C 50/5 4.0 100/5 3.0 200/5 4.0 300/5 3.0 400/5 4.0 600/5 3.0 800/5 2.0 1200/5 1.5 1500/5 1.5 2000/5 1.5 3000/5 1.33
3. Select an ANSI Metering Accuracy Class in accordance with the following table:
Primary Amp Rating (of CT) Accuracy Class
50-100 0.3 thru B-0.1
200 0.3 thru B-0.1
300-400 0.3 thru B-0.2
600-1200 0.3 thru B-0.5
1500 0.3 thru B-0.9
2000-3000 0.3 thru B-1.8
Current transformers shall conform to IEEE C57.13. Provide current transformers with a metering accuracy Class of 0.3 through B1.8 with a minimum TRF of 2.0 at 30 degrees C. with 600-volt insulation, and 10 kV BIL. Provide butyl-molded, window-type current transformers mounted on the transformer low-voltage bushings. Route current transformer leads in a location as remote as possible from the power transformer secondary cables to permit current measurements to be taken with hook-on-ammeters.
NOTE: See TM 5-811-I/AF AFJMAN 32-1080 for guidance regarding voltage transformers. Minimum standard potential transformer accuracies for metal-clad switchgear are not listed in ANSI C37.20.2.
Accuracy classes as listed in IEEE C57.13 are 0.3, 0.6, and 1.2. Standard burdens for each accuracy class are W, X, Y, ZZ, and M. The designer should check the burdens connected to determine the actual accuracy class and burden required. In general, ANSI C12.11 requires 0.3 accuracy class for up to Y burdens, except for voltages of 5 kV and below. Where metering potential transformers are provided, a
0.3 accuracy class should be specified, if available for the voltage rating and burden needed. Voltage transformers shall have indicated ratios. Units shall have an accuracy class rating of 0.3. Voltage transformers shall be of the draw out type having current-limiting fuses in both primary and secondary circuits. Mechanical interlocks shall prevent removal of fuses, unless the associated voltage transformers are in a draw out position. Voltage transformer compartments shall have hinged doors.
3.2 LonWorks WNC WattNode Logger Electric Meter
3.3 LONWORKS ILON 600 IP/ server
3.4 COMMUNICATIONS
3.4.1 Communications Method
3.4.1.1 (ILAN) Communication method shall be by ANSI ICEA-709.I b. protocol (Lon Talk) digital output using Standard Network Variable Types (SNVTs) for measured values for Lon
Works.
3.4.1.2 (RF) Communication method shall be implemented where ILAN is not available or as specified by the Contracting Officer.
PART 3 EXECUTIONS
3.1 INSTALLATION
Electrical installations shall conform to IEEE C2, NFPA 70, and to the requirements specified herein.
Provide new equipment and materials unless indicated or specified otherwise.
3.1.1 CURRENT TRANSFORMER INSTALLATION
Current transformer shall be installed in the Main distribution panel (MDP) cabinet in the electrical room.
Electric meters and associated metering hardware shall be installed in accordance with NFPA 70 close to or on the MDP and can be of split core type for ease of installation, manufacturer’s recommendation and as shown on plans. Enclosure shall be sized as required by the 2008 National Electrical Code.
3.1.2 LONWORKS WNC WATTNODE LOGGER METER INSTALLATION (ILAN)
LonWorks WNC WattNode Electric Meter shall be located in the electrical room Electric meters and associated metering hardware shall be installed in accordance with NFPA 70 close to or on the Main DP.
LonWorks WNC WattNode Electric Meter shall be installed in a NEMA 1, 8 inch tall x 10 inch wide x 6 inch deep enclosure with hinged door and Key Lock Mechanism standard key mech CH751. LonWorks WNC WattNode Electric Meter and associated metering hardware shall be installed in accordance with NFPA 70, and manufacturer’s recommendation and as shown on plans, on Main Distribution Panel. The voltage phase wires shall follow NEC code 230.82 with an added fusible disconnect located outside the MDP close to the Wattnode enclose. Fuses shall be rated .5 amps, 600v fast blow. A 2-conductor (22 AWG) LoN cable shall be routed from all meters to the ILON 600 location through appropriate sized conduit. Approximately 1-2 feet of cable shall be provided at both ends for final connection (termination) determined by the plans or by DPW Energy Branch. If the total distance from the ILON 600 location to any meter is greater than 500 M, then prior approval is required by the DPW Energy Branch.
WNC WattNode Logger Electric Meter
3.1.2.1 COMMISSIONING
All advanced electric meters shall be configured and commissioned with the most current Plug-IN software from the manufacture. The contractor shall as a requirement for installation acquire at their expense the necessary LonMark commissioning tool such as, Lon Watcher, Lon Builder, Lon Maker or equivalent. At final inspection performance verification test (PVT)) of the metering real-time data and communication system will be tested using the contractor’s tools and commissioning data bases. All DB’s will be turned over to the Energy Team at completion of final inspection.
3.1.4 LONWORKS ILON 600 IP/SERVER INSTALLATION
ILON 600 IP/Server shall be located in the communication’s room in the location shown in the drawings.
ILON 600 Smart server shall be installed in a NEMA 1, 12 inch tall x 12 inch wide x 4 inch deep enclosure with hinged door and latch for pad lock. ILON 600 Smart server shall be installed in accordance with NFPA 70, manufacturer’s recommendation and as shown on plans. A CAT 6 LAN communication cable shall be routed from the ILON 600 location through appropriate sized conduit to the patch panels.
Approximately 1-2 feet of cable shall be provided at both ends for final connection (termination) by DPW
Energy Branch. If the total distance from the ILON 600 location to any meter is greater than 500 feet, then prior approval is required by the DPW Energy Branch.
ILON 600 IP/Server
3.1.5 WLT – 900 Wireless LonWorks Transceiver Installation
Two AIC -WLT900 Wireless LonWorks Transceiver for Client and master with FIPS 140-2/AES 256 encryption shall be installed where ILAN is not available, or as specified by the Contracting Officer.
WLT900
Directional and Omni directional types of antennas shall be installed. Directional antennas will be installed at client transceiver sites and Omni directional shall be installed at master transceiver sites.
Exceptions may be given if determined to be beneficial by RF field survey and must be approved by Energy Management Branch. Antenna mounting locations for Client and Master sites shall be determined by the results of a RF spectrum analysis (902 – 928 MHZ range).
o Directional Omni Directional
AIC 24V 50 Watt Antenna Power Supply shall be installed
Coax Surge Protector shall be installed
A LMR600 Coax antenna cable will be installed to connect antenna to the WLT 900 and NOT TO EXCEED 30 Feet (with Male connector Prefabricated, if requested).
A 12”x12”x 6” NEMA4 metal lockable enclosure shall be installed to house the WLT900, power supply, AC 120V receptacle and surge suppressor. The location of the enclosure will be determined during the RF field survey.
3.1.6 SCHEDULING OF WORK AND OUTAGES
The Contract Clauses shall govern regarding permission for power outages, scheduling of work, coordination with Government personnel, and special working conditions.
3.2 FIELD APPLIED PAINTING
Where field painting of enclosures is required to correct damage to the manufacturer’s factory-applied coatings, provide manufacturer’s recommended coatings and apply in accordance with manufacturer’s instructions.
3.3 FIELD QUALITY CONTROL
3.3.1 Performance of Acceptance Checks and Tests
3.3.1.1 Meter Assembly
a. Visual and mechanical inspection
1. Compare equipment nameplate data with specification and approved shop drawings.
2. Inspect physical and mechanical condition.
3. Inspect all bolted electrical connections for high resistance using low-resistance ohmmeter, verifying tightness of accessible bolted electrical connections by calibrated torque-wrench method
4. Verify grounding of metering enclosure.
5. Verify the presence of surge arresters.
6. Verify that the CT ratio and the PT ratio are properly included in the meter multiplier or the programming of the meter.
b. Electrical tests
1. Verify that correct multiplier has been placed on face or meter where applicable.
2. Prior to system acceptance, the Contractor will demonstrate and confirm the meter is properly wired and is displaying correct and accurate electrical information.
3.3.1.2 Current Transformers
a. Visual and mechanical inspection
1. Compare equipment nameplate data with specification and approved shop drawings.
2. Inspect physical and mechanical condition.
3. Verify correct connection.
4. Inspect all bolted electrical connections for high resistance using low-resistance ohmmeter, verifying tightness of accessible bolted electrical connections by calibrated torque-wrench method.
5. Verify that required grounding and shorting connections provide good contact.
b. Electrical tests
1. Perform resistance measurements through all bolted connections with low-resistance ohmmeter, if applicable.
2. Perform insulation-resistance test.
3. Perform a polarity test.
4. Perform a ratio-verification test.
3.3.2 Follow-Up System Function Verification
Upon completion of acceptance checks and tests, the Contractor shall show by demonstration in service that circuits and devices are in good operating condition and properly performing that intended function.
As an exception to requirements stated elsewhere in the contract, the Contracting Officer shall be given 5 working days’ advance notice of the dates and times of checking and testing.
3.3.3 Performance Verification Testing (PVT)
The Contractor shall conduct the onsite Performance verification test (PVT) with a government representative on site for approval before the final inspection. This will give the contractor time to correct any meter reading errors before the final inspection. The PVT will consist of the contractor using their applied tools: external calibrated test equipment (Power quality Analyzer), Lon device commissioning software tool, and device Plug-in and Lon interface adaptor. Documenting and comparing the test equipment data: Volts, Amps, Watts, and PF data to the Lon device plug-in tool where the metered real time data can be viewed This test validates the meter real time readings against the external test equipment. Any negative power numbers or errors in readings will be corrected at this point before acceptance. The following Plug-in Views will be required for turn in with the Devices Lon DB, and PVT written documentation for future Warranty requirements and Final meter validation acceptance.
1. Plug-in Info Page
2. Plug-in Multi–meter page
3. Plug-in Power page
4. Plug-in Energy Page
4. TECHNICAL SUPPORT POC:
TECHNICAL SUPPORT (FORT HOOD, TX)
Hubert (Huey) Keaton Directorate of Public Works (DPW) Energy Management Phone (254)535-8558
DC # 145*2*40300
File details come from the government source that posted it. Updated .