ATT_Q_-_Transformer_Concrete_Pad_Detail.pdf

PDF 564 KB Posted

Attached to
Open End Electrical Requirements Contract
Solicitation number
W91151-16-B-0021
Issued by

About this file

Exhibit - Q - Transformer Concrete Pad Detail

View the file

Other files

File Type Posted
Tech_Exhibit_A_-_Bid_Schedule_REVISED_25AUG2016.xls XLS spreadsheet
W91151-16-B-00210-00002_Bid_Sheets_Revised.pdf PDF
Technical_Exhibit_B1_-_Division_1_Specifications_REVISED.pdf PDF
Technical_Exhibit_B2_-_Specifications_REVISED.pdf PDF
ATT_V_-_High_Mast_Poles_and_Foundations.docx DOCX document
ATT_A_Bid_Schedule_REVISED.xls XLS spreadsheet
W91151-16-B-00210-00001_RFI.pdf PDF
ATT_U_-_SPECIAL_PROVISIONS.pdf PDF
Technical_Exhibit_B_-_Division_1_Specifications.pdf PDF
ATT_C_-_Section_16510e_-_Interior_Light_Fixtures_Schedule.pdf PDF
ATT_B_-_Specifications.pdf PDF
ATT_D_-_Section_16520e_-_Exterior_Light_Fixtures_Schedule.pdf PDF
ATT_M_-_In-Line_Electrical_Primary_Riser_at_90_Degrees_to_Line_Detail.pdf PDF
ATT_P_-_Static_Ground_Details.pdf PDF
ATT_A_Bid_Schedule.xls XLS spreadsheet
ATT_J_-_Trench_and_Grounding_Details.pdf PDF
ATT_T__-_Electrical_GIS_SOP.pdf PDF
W91151-16-B-0021.pdf PDF
ATT_H_-_AR_190-11_-_Physical_Security_of_Arms _Ammunition _and_Explosives.pdf PDF
ATT_F_-_FM_10-67-1_-_Concepts_and_Equipment_of_Petroleum_Operations.pdf PDF
ATT_S_-_LED_FIXTURE_DETAIL.pdf PDF
ATT_L_-_In-Line_Electrical_Primary_Riser_Detail.pdf PDF
ATT_R_-_FH_REG_420-9_-_Energy_Conservation_Program.pdf PDF
ATT_K_-_Handhole_Details.pdf PDF
ATT_G_-_PAM_385-64_-_Ammunition_and_Explosives_Safety_Standards.pdf PDF
Technical_Exhibit_B3_-_Electric_Meter_Specifications.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PAD SHALL BE COMPACTED TO 95% IN ACCORDANCE

EXISTING GRADE AND BACKFILL UNDER CONCRETE

IN 5’ AS DETERMINED BY A 5’ STRAIGHT EDGE.

FINISHED TO PROVIDE A TRUE PLANE WITHIN +1/4"

1. PAD SHALL BE LEVEL WITHIN + 1/4 " IN 5’. TROWEL

NOTES:

SECTION A-A

12"

REBAR

WWF OR

12"

A

2"

10"

4’-4"(MIN)

SECONDARY

PRIMARY

12"

GROUND ROD

12"

6’-4"(MIN)

TROUGH AREA

1’

M

IN

3/4" CHAMFER

4 X 4 - W9 X W9 WWF

OR #3 BARS 4" O.C. EA.

WAY. PROVIDE 2" CLEARANCE

ALL AROUND.

A

BOLLARD (TYP.)

WITH ASTM D1557 UNLESS OTHERWISE NOTED.

NOT TO SCALE

BOLLARD (TYP.)

CONDUIT(S)

TRANSFORMER PAD DETAIL - TYP.

2. PAD SIZE WILL NEED TO VARY, ACCORDING TO

TRANSFORMER SIZE AND MANUFACTURER. COORDINATE

EXACT SIZE WITH TRANSFORMER SHOP DRAWINGS.

CONDUITS

(ONE SPARE)

CAPPED FOR

FUTURE USE

#4 ANCHORS @

4’ O.C. EACH WAY

TOP OF CONCRETE

HARDSTAND

Revisions

Symbol Descriptions Date Approved

FORT HOOD, TEXAS

PROJECT NO.

SHEET OF

SCALE REDUCED

0 1/2 ’’ 1’’ 2’’

REVEIWED BY:

DRAWING

DMI NO.DATE:

SCALE:

DRAWN BY:

DESIGNED BY:

AS NOTED

SEQ. NO.

FILE NAME

DIRECTORATE OF PUBLIC WORKS

1 1

DETAIL, TYPICAL

5/5/2003

WALTER THOMAS

WALTER THOMAS

WALTER THOMAS TRANSFORMER PAD DETAIL

Attachment Q - Transformer Concrete Pad Detail For Bidding Purposes Only

ATT Q - 1 02.01.2016

File details come from the government source that posted it. Updated .