ATT_J_-_Trench_and_Grounding_Details.pdf

PDF 1 MB Posted

Attached to
Open End Electrical Requirements Contract
Solicitation number
W91151-16-B-0021
Issued by

About this file

Exhibit J - Trench and Ground Details

View the file

Other files

File Type Posted
Tech_Exhibit_A_-_Bid_Schedule_REVISED_25AUG2016.xls XLS spreadsheet
W91151-16-B-00210-00002_Bid_Sheets_Revised.pdf PDF
Technical_Exhibit_B1_-_Division_1_Specifications_REVISED.pdf PDF
Technical_Exhibit_B2_-_Specifications_REVISED.pdf PDF
ATT_V_-_High_Mast_Poles_and_Foundations.docx DOCX document
ATT_A_Bid_Schedule_REVISED.xls XLS spreadsheet
W91151-16-B-00210-00001_RFI.pdf PDF
ATT_U_-_SPECIAL_PROVISIONS.pdf PDF
Technical_Exhibit_B_-_Division_1_Specifications.pdf PDF
ATT_C_-_Section_16510e_-_Interior_Light_Fixtures_Schedule.pdf PDF
ATT_B_-_Specifications.pdf PDF
ATT_D_-_Section_16520e_-_Exterior_Light_Fixtures_Schedule.pdf PDF
ATT_M_-_In-Line_Electrical_Primary_Riser_at_90_Degrees_to_Line_Detail.pdf PDF
ATT_P_-_Static_Ground_Details.pdf PDF
ATT_A_Bid_Schedule.xls XLS spreadsheet
ATT_T__-_Electrical_GIS_SOP.pdf PDF
W91151-16-B-0021.pdf PDF
ATT_H_-_AR_190-11_-_Physical_Security_of_Arms _Ammunition _and_Explosives.pdf PDF
ATT_Q_-_Transformer_Concrete_Pad_Detail.pdf PDF
ATT_F_-_FM_10-67-1_-_Concepts_and_Equipment_of_Petroleum_Operations.pdf PDF
ATT_S_-_LED_FIXTURE_DETAIL.pdf PDF
ATT_L_-_In-Line_Electrical_Primary_Riser_Detail.pdf PDF
ATT_R_-_FH_REG_420-9_-_Energy_Conservation_Program.pdf PDF
ATT_K_-_Handhole_Details.pdf PDF
ATT_G_-_PAM_385-64_-_Ammunition_and_Explosives_Safety_Standards.pdf PDF
Technical_Exhibit_B3_-_Electric_Meter_Specifications.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Revisions

Symbol Descriptions Date Approved

DIRECTORATE OF ENGINEERING & HOUSING

FORT HOOD, TEXAS

PROJECT NO.

SHEET OF

SCALE REDUCED

0 1/2 ’’ 1’’ 2’’

REVEIWED BY:

DRAWING

DMI NO.DATE:

SCALE:

DRAWN BY:

DESIGNED BY:

AS NOTED

SEQ. NO.

Revisions

Symbol Descriptions Date Approved

DIRECTORATE OF ENGINEERING & HOUSING

FORT HOOD, TEXAS

PROJECT NO.

SHEET OF

SCALE REDUCED

0 1/2 ’’ 1’’ 2’’

REVEIWED BY:

DRAWING

DMI NO.DATE:

SCALE:

DRAWN BY:

DESIGNED BY:

AS NOTED

SEQ. NO.

NO SCALE

BUTT-WRAPPED GROUND DETAIL

12’-0" MIN.

4 TURNS #6 BSD CU

AS REQUIRED

GALVANIZED STAPLES

STAPLED AS REQUIRED

WIRE 6 TURNS MIN.

#6 BSD CU GROUND

GROUND WIRE

(2 REQ’D)

BUSHING

GROUNDING

1/2 " IMC

(2 REQ’D)

PIPE STRAP

GROUND WIRE (2 REQ’D)

SIZED TO MATCH

BSD COPPER JUMPER

FINISHED GRADE

GROUND WIRE MOLDING

NOTE: REQ’D FOR EACH GROUND WIRE

SCALE: NONE

GROUND LINE PROTECTION DETAIL

18" 14" 20"

TRENCH AND GROUNDING DETAILS

1 1

4"MIN.

6"MIN.

O.D.

S A

N D

B E

D

TOP OF FINISHED GRADE

4 MIL MINIMUM X 6-INCH WIDE, POLYETHYLENE

IDENTIFYING LETTERING (1750 PSI LENGTHWISE

COMPACT EACH LAYER TO 95% MAXIMUM DENSITY.

BACKFILL MATERIAL CLASSIFIED SATISFACTORY; PLACE

IN LIFTS NOT EXCEEDING 6 INCHES (LOOSE) FOR HAND

OPERATED MACHINE COMPACTORS (8" FOR OTHERS).

X 1500 PSI CROSSWISE MINIMUM STRENGTH).

12"

36" MINIMUM FOR PRIMARY

24" MIN. FOR SECONDARY

CONDUIT

FOR TRENCH

3 TIMES

CONDUIT DIA.

WIDTH (12" MIN.).

MARKING TAPE (NO FOIL BACKING), RED, WITH

SANDBEDDING FOR SECONDARY, 3000 PSI CONCRETE

(RED) FOR PRIMARY.

PRIMARY OR SECONDARY CABLES IN CONDUIT SIZED

PER N.E.C. (CENTERED IN TRENCH). MIN SCH.40 PVC

DETAIL FOR UNDERGROUND ELECTRICAL PRIMARY OR SECONDARY

WITH TRANSITION TO STEEL LONG RADIUS ELBOW AT

RISE TO OVERHEAD. ( 1 PH.-2" MIN & 3 PH. - 4" MIN.)

N.T.S.

WALTER THOMAS

WALTER THOMAS

WALTER THOMAS

5/5/2003

Attachment J - Trench and Grounding Details For Bidding Purposes Only