Text version
NOT TO SCALE
NOT TO SCALE
PLAN
/4
FINISHED FLOOR
#10 BRASS BALL CHAIN
3/4 " PIPE OR ROD
3/4 " N.C. THREAD
"2 "218" DIA.
PAINT YELLOW
PAINT RED
GROUND
NOT TO SCALE
SECTION
/4
D
IA
CAST BRONZE
COVER, FRICTION FIT
BRASS PIN
EXOTHERMIC WELD (TYP.)
3/4 " DIA. X 10’ CU CLAD STEEL
GROUND ROD
CAST BRONZE
HOUSING
E4 E32
STATIC GROUND RECEPT. (AT
INTERIOR BAYS & TRAILER LOCATIONS)
#4 GROUNDING CONDUCTOR
(TYP.) INSTALL BELOW
CONCRETE FLOOR SLAB.
M
I N
PAINT THE WORD "GROUND"
IN 1" BLACK LETTERS AND
THE DATE TESTED IN 1/2 "
BLACK LETTERS
STATIC GROUND
RECEPTACLE
SET IN FLOOR
/8
2 3/4 " DIA.
Attachment P - Static Ground Details For Bidding Purposes Only
ATT P - 1 02.01.2016
File details come from the government source that posted it. Updated .