24 October 2007
Attachment R - Energy Conservation Program For Bidding Purposes Only
ATT R - 1 02.01.2016
DEPARTMENT OF THE ARMY *III CORPS & FH REG 420-9
HEADQUARTERS, III CORPS AND FORT HOOD
FORT HOOD, TEXAS 76544-5016
24 October 2007
Facilities Engineering Energy Conservation Program
History. This is an administrative revision.
This supersedes III Corps and Fort Hood Regulation 420-9 dated 11 May 1992.
Summary. This regulation establishes the policy and procedures for the Energy Conservation Program at Fort Hood.
Applicability. This regulation applies to all units and activities assigned, attached, conducting training, or residing on Fort Hood as tenants; contractor activities on Fort Hood and all organizations with leases using Fort Hood utilities;
persons using Fort Hood utilities; off-post facilities;
and other areas Fort Hood operates.
Supplementation. The Directorate of Public Works (DPW) prohibits supplementation of this regulation without prior approval.
Suggested Improvements. The proponent of this regulation is the DPW. Send comments and suggested improvements to:
Commander, III Corps and Fort Hood, ATTN: IMSW- HOD-PWE, Fort Hood, Texas 76544-5016.
FOR THE COMMANDER;
PAUL A. JONES
Major, GS Chief of Staff
Official:
CHARLES E. GREEN, SR.
Director, Human Resources
DISTRIBUTION:
IAW FH FORM 1853: S
Contents
Overview, 1, page 6 Purpose, 1a, page 6 References, 1b, page 6 Abbreviations and terms, 1c, page 6 Summary of change, 1d, page 6 Guidelines, 1e, page 7
Responsibilities, 2, page 7 Commanders, Directors, and activity chiefs, 2a, page 7
*Supersedes III Corps and Fort Hood Regulation 420-9 dated 11 May 1992.
Attachment R - Energy Conservation Program
ATT R - 2 02.01.2016
FH REG 420-9 24 October 2007
Directorate of Public Works (DPW), 2b, page 9 Energy conservation officers (ECOs) and building energy monitors (BEMs), 2c, Public affairs officers, 2d, page 11 Family housing occupants, 2e, page 11
Policy, 3, page 12 Energy conservation, 3a, page 12 Electrical demand reduction, 3b, page 12 Exceptions to policy, 3c, page 13 Facilities and building management, 3d, page 13 Army and Air Force Exchange Service (AAFES), 3e, page 14 Energy conservation surveys, 3f, page 14 Energy hot-line, 3g, page 15
Air conditioning and heating procedures, 4, page 15 Air vents, ducts, and returns, 4a, page 15 Windows and doors, 4b, page 15 Correction deficiencies, 4c, page 15 Filters, 4d, page 16 Thermostats, 4e, page 16 Temperature compliance, 4f, page 17 Thermal and solar gain, 4g, page 17 Supplemental equipment, 4h, page 17
Water procedures, 5, page 18 Routine use, 5a, page 18 Hot water, 5b, page 18 Vehicle washing, 5c, page 18 Landscape irrigation, 5d, page 18
Lighting procedures, 6, page 18 Conservation, 7a, page 18 Lighting athletic facilities, 7b, page 19 Illumination intensities, 7c, page 19 Ornamental lighting, 7d, page 19
Utility metering, 7, page 20 Individual buildings, 7a, page 20 Metering data, 7b, page 20 Construction projects, 7c, page 20 Metering criteria, 7d, page 20 Electric metering criteria, 7e, page 20
Attachment R - Energy Conservation Program
ATT R - 3 02.01.2016
24 October 2007 FH REG 420-9
Natural gas metering criteria, 7f, page 21 Water metering criteria, 7g, page 21 Remote metering, 7h, page 21 Chiller metering, 7i, page 21
Electrical appliances, 8, page 21 Safety, 8a, page 21 Washers and dryers, 8b, page 22 Refrigeration, 8c, page 22
Family housing, 9, page 22 Occupants, 9a, page 22
Training, 10, page 23 Energy training, 10a, page 23 Building energy manager, 10b, page 23
Areas of special emphasis, 11, page 23 Publicity, 11a, page 23 Temperature measurement techniques, 11b, page 23 Commonly used areas, 11c, page 23 Heating to air conditioning transition, 11d, page 24 Minimizing peak electrical demand (PED), 11e, page 24
Storing and dispensing procedures for petroleum. oil, and lubricants (POL) containers, 12, page 25 Mobility energy, 12a, page 25 Storage, 12b, page 25 Dispensing, 12c, page 25
Maintenance, 13, page 26 Equipment maintenance, 13a, page 26 Vehicle maintenance, 13b, page 26
Transportation, 14, page 26 Efficient use of vehicles, 14a, page 26 Driving, 14b, page 27 Tactical and nontactical vehicles, 14c, page 27
Energy conservation in training, 15, page 27 Fuel conservation actions, 15a, page 27 Aviation training, 15b, page 28
ATT R - 4 02.01.2016
Figures List B-1. Sample Memorandum, page 31 F-1. Relation of Space Temperature to Energy Consumption (Fahrenheit), page 36
Tables List C-1. Facility Type Table, page 32 D-1. Telephone Numbers, page 33 E-1. Prescribed Temperatures (Fahrenheit), page 34 G-1. Light Intensities for a Safe and Productive Environment, page 37
Appendices A. References, page 29 B. Sample Memorandum, page 31 C. Facility Type Table, page 32 D. Telephone Numbers, page 33 E. Prescribed Temperatures (Fahrenheit), page 34 F. Relation of Space Temperature to Energy Consumption (Fahrenheit), page 36 G. Light Intensities for a Safe and Productive Environment, page 37
Glossary, page 38
ATT R - 5 02.01.2016
OVERVIEW
Purpose This regulation prescribes policies, assigns responsibilities, and establishes procedures for the Energy Conservation Program at Fort Hood.
1a
References Appendix A lists required and related references.
1b
Abbreviations The glossary explains abbreviations and terms used in this regulation.
and terms 1c
Summary of Specifically, this revision dated 24 October 2007 – change
• Updates water temperature from 94 degrees Fahrenheit (34 degrees Celsius) to 110 degrees Fahrenheit (43 degrees Celsius).
• Updates Army and Air Force Exchange Service (AAFES) reference to Exchange Operation Procedure (EOP) 36-1.
• Adds statement to install utility metering equipment in paragraph 3d.
• Adds statement that screw base compact fluorescent lamp (CFL) shall be used in lieu of screw base incandescent lamps in paragraph 6a.
• Inserts the requirement of metering air conditioning chillers performance energy, kilowatt (KW) and tons of refrigeration (TR) in paragraph 7i.
1d
ATT R - 6 02.01.2016
Guidelines Effective energy management is a culmination of:
• Common sense.
• Imagination.
• Implementing innovative programs.
Energy awareness programs are required to achieve significant energy conservation and reduce energy consumption per Executive Order
13423 (Strengthening Federal Environmental, Energy, and Transportation Management). Energy consumption is one of Fort Hood’s significant environmental aspects under its environmental management system (EMS) and objectives and targets exist under the Fort Hood sustainability strategic plan to reduce energy consumption, and in conformance with the Fort Hood Environmental Policy. It is the responsibility of every Soldier, civilian, contractor, and tenant to adhere to this regulation.
1e
RESPONSIBILITIES
Commanders, Commanders, Directors, and activity chiefs shall:
Directors, and activity chiefs • Include energy management during staff and command inspection team visits per Army Regulation (AR) 1-201 (Army Inspection Policy).
• Actively promote command and community energy awareness and reduce consumption per Executive Order 13423.
• Develop, implement, maintain, and communicate command and unit energy conservation programs.
• Commanders shall appoint an energy conservation officer (ECO) and create orders, in writing, at every level of command down to the company level.
(continued on next page)
ATT R - 7 02.01.2016
Commanders, • Directorates shall appoint an ECO down to division level.
Directors, and Contractors and tenants shall appoint and ECO for their activity chiefs organization.
(continued) Note: ECOs may be commissioned officers, warrant officers, noncommissioned officers, sergeant first class or above, or civilians in a managerial position case of non-military, contractor, or tenant activities. In cases where ECOs are responsible for multiple facilities, organizations shall appoint and train an assistant building energy monitor (BEM).
• The ECO rosters and orders shall be updated annually or upon permanent change of station, termination, or transfer of civilian personnel.
• Instruct subordinates and act as the example for energy consumption and the reduction of consumption while maintaining the ability to meet mission requirements.
• Develop, publicize, communicate, and implement policies that achieve economical use of electrical appliances.
• Ensure all exterior lights are turned on and off at a reasonable time, optimizing use of daylight during daylight hours.
• Identify Direcorate of Public Works (DPW)-controlled high voltage equipment whose operation can be limited during peak electrical demand periods.
• Use incentive awards to promote and recognize excellent performance in energy conservation.
2a
ATT R - 8 02.01.2016
Directorate DPW shall:
of Public Works (DPW) • Appoint the Fort Hood energy coordinator (FHEC).
• Provide:
• Training.
• Guidance.
• Goals, targets, and metrics.
• Consider economics and benefits to incorporate the latest technology in energy conservation procedures and materials in the design of new facilities and renovation projects.
• Consider sustainability and EMS objectives and targets during all phases of development and design, as well as new technology on the installation.
• Conduct scheduled surveys of energy conservation practices at units, directorates, and activities.
• Conduct assessments and inquiries and work together with the environmental compliance assessment team when circumstances warrant immediate correction. Some incidences are, but are not limited to:
• Exterior lights being left on during daylight hours.
• Windows and doors open while facilities are being heated or air conditioned.
• Misuse, and violation of the installation water conservation plan is occurring.
2b
ATT R - 9 02.01.2016
Energy ECOs and their appointed assistant BEMs shall:
conservation officers • Design, document, and implement an energy conservation program (ECOs) and for their organization.
building energy • Advise Commanders, activity chiefs, and managers on the monitors requirements of this regulation.
(BEMs)
• Maintain all documentation and publications to provide a comprehensive source of technical information for energy conservation, including all Department of the Army (DA) pamphlets, regulations, plans, standard operating procedures (SOPs), and the DA BEM Handbook (Department of the Army Building Energy Monitor’s Handbook). To acquire the most recent publications, contact the DPW Environmental Division (see appendix D for telephone numbers).
• Maintain current and accurate SOPs that contain, but are not limited to the following:
• Specific responsibilities for energy conservation in the organization.
• Outline policies unique to the facility equipment used or controlled by the organization.
• The plan for managing the organization energy conservation program.
• Conduct regular facility inspections using Fort Hood (FH) Form 1073 (Checklist for Good Conservation of Utilities).
• Identify user-controlled high voltage (greater than 120 volts) electrical equipment in their facilities using FH Form 1073.
ATT R - 10 02.01.2016
Energy • Document and publicize energy conservation requirements, conservation including displaying DA and FH posters on bulletin boards and light officers switches.
(ECOs) and building • Conduct training on the Energy Conservation Program.
energy monitors (BEMs) (continued) 2c
Public affairs Public affairs officers (PAOs) will:
officers (PAOs) • Provide and maintain a single point of contact (POC) to expedite staff actions on energy matters.
• Provide FHEC with the POCs:
• Name.
• Location.
• Telephone number.
• Email.
• Publish information concerning energy related topics through the Fort Hood media network.
2d
Family Family housing occupants shall:
housing occupants • Comply with the policies and procedures discussed in this regulation.
• Practice energy conservation the same as a prudent homeowner, who is responsible for paying the utility bills.
2e
ATT R - 11 02.01.2016
POLICY
Energy The energy conservation program does not impair:
conservation
• Mission capability.
• Combat readiness.
• Deployment/Re-deployment ability .
• Training.
• Health or safety.
• Construction projects.
The Energy Conservation Program shall be considered when planning and executing military operations and quality of life functions.
Energy resources are intensively monitored and managed. Decisions about energy conservation are based on sound economic analysis and common sense to manage our natural resources in the most cost effective and practical manner.
Energy efficiency and availability is a factor in the decision making process and is stressed in the design, development, procurement, operation of equipment weapon systems, and facilities.
The Surgeon General develops criteria for the Army medical department’s energy policies governing lighting, humidity, heating, and cooling.
Energy conservation awareness shall continuously be promoted at all levels to eliminate energy waste and reduce consumption.
3a
Electrical Because of the installation’s rapid growth, a greater demand is placed demand on utility systems and the resources to pay for them.
reduction Electrical use shall be limited, during the peak electrical demand (PED) period.
ATT R - 12 02.01.2016
Electrical Some practical ways to achieve reduction are:
demand reduction • Use clothes washers and dryers before 1300 or after 1600.
(continued)
• Perform electricity intensive operations outside the PED time frame whenever possible.
• Adhere to time restriction for watering lawns as described in the Fort Hood water conservation plan.
3b
Exceptions to Activities or units may request an exception to policy when unusual policy circumstances warrant exception in order to perform the installation mission.
Activities or units requesting an exception to policy must send a memorandum requesting an exception to policy to DPW, ATTN: Environmental Division (appendix B contains a sample). In the memorandum include organization name, address, POC with phone number and email, and justification for request. Upon receipt of request, the DPW, Environmental Division staff will conduct a field survey to determine the disposition of request. Once approved, facilities are permanently placed on file pending annual review by DPW, Environmental Division.
Note: If a change in mission is noted, DPW notifies the user of pending removal from the file list. The user will have 14 working days to reply with justification. Once removed, a facility must resubmit a request for an exception to policy.
3c
Facilities and Energy consumption in facilities shall be reduced through low to no building cost action using common sense best management practices (BMP) management such as:
• Establish an organizational energy SOP.
ATT R - 13 02.01.2016
Facilities and • Control heating and cooling systems by some form of utility building monitoring and control system (UMCS) such as:
management (continued) • Frequency modulated controls.
• Timers.
• Other programmable devices.
• Installation-wide UMCS.
• Adhere to proper adjustment of thermostat and other controls as shown in appendix E.
• Remove lamps from fixtures in the event of excess lighting.
• Close doors and windows to prevent loss of energy required for heating and cooling.
• Ensure the appointment and training of ECOs and BEMs.
• Install utility metering equipment.
3d
Army and AAFES must follow the policies and procedures prescribed by EOP Air Force 36-1.
Exchange Service
(AAFES)
3e
Energy Organizations may request their facilities energy surveys or studies.
conservation Typical surveys are done for lighting, air conditioning, and heating;
surveys however, any energy related survey may be required. To request an energy survey, submit a memorandum for specific survey to DPW, ATTN: Environmental Division.
3f
ATT R - 14 02.01.2016
Energy Everyone is encouraged to use the Environmental Division energy hot-hot-line line (see appendix D for telephone numbers) to suggest:
• Energy savings ideas.
• Report energy waste.
• Comment on any topic related to the DPW Energy Conservation Program.
The hot-line is monitored from 0730 to 1630 Monday through Friday, excluding holidays.
3g
AIR CONDITIONING AND HEATING PROCEDURES
Air vents, Obstructions (such as furniture or drapes) will not block vents, air ducts, and returns, and air ducts.
returns Blockage prevents efficient operation of the circulation system which increases energy consumption.
4a
Windows and Keep windows closed and open exterior doors as little as possible doors when the air conditioning or heating system is in use.
4b
Correcting Correct energy wasting deficiencies such as defective weather deficiencies stripping, broken windows, inoperative door closers, and defective thermostats.
If the unit self-help team cannot correct deficiencies, request assistance from DPW work reception (see appendix D for telephone numbers).
Family housing occupants must request repairs through the maintenance contractor (see appendix D for telephone numbers).
4c
ATT R - 15 02.01.2016
Filters Inspect filters at a minimum of once a month, replacing disposable filters at least every 90 days.
Clean permanent (nondisposable) filters according to instructions on the equipment.
• This task should be performed by the unit self-help team according to FH Regulation (REG) 420-27 (Care, Maintenance, and Alterations of Facilities), paragraph 3d.
• The maintenance contractor performs his task in Family housing quarters.
4d
Thermostats Thermostat settings must comply with the temperature requirements prescribed in appendix E (also see appendix F).
At the end of each working day in work areas where the thermostat is readily accessible, the occupant turns off the air conditioning or sets the heating thermostat to 55 degrees Fahrenheit (12.8 degrees Celsius) or lower.
The same policy applies when any facility is expected to be unoccupied for more than 8 hours, unless damage to the facility or its contents would result.
Turn off air conditioning equipment which is not controlled by a thermostat when the outside temperature is lower than 78 degrees Fahrenheit (25.6 degrees Celsius).
Turn off heating equipment when the outside temperature is greater than 65 degrees Fahrenheit (18.3 degrees Celsius).
Do not locate heat generating appliances near thermostats.
• Operation of the heating or air conditioning equipment may be adversely affected by heat generated from the use of television sets, refrigerators, and other appliances.
4e
ATT R - 16 02.01.2016
Temperature Energy consumed for heating and cooling space will be carefully compliance controlled and monitored.
Appendix E illustrates the prescribed temperature ranges for various types of facilities.
All reasonable effort should be made to maintain temperatures that result in the least consumption of energy.
Appendix F illustrates the savings due to energy conservation.
If several occupied rooms are serviced by the same air duct system and temperature is controlled by a single thermostat, the lowest room space temperature determines compliance for heating and the highest room space temperature determines compliance for cooling.
4f
Thermal and Keep draperies and blinds closed on the sunny side of the building solar gain during the cooling season and open on sunny days during the heating season.
Turn off unwarranted lights to lessen the load for air conditioning systems.
4g
Supplemental Portable space heaters are prohibited.
equipment Electric space heaters may be permitted only when an exception to policy ( see paragraph 3b above) is granted in writing by DPW.
The criteria in AR 420-54 (Air Conditioning and Refrigeration), chapters 1 through 5, govern requests for supplemental or new air conditioning equipment.
Space temperature in buildings where thermostats are not accessible to occupants is checked by the DPW, Environmental Division during surveys.
Discrepancies are reported to the DPW work reception per FH Reg 420-27, appendix A.
4h
Attachment R - Energy Conservation Program
ATT R - 17 02.01.2016
WATER PROCEDURES
Routine Use Maintain faucets, valves, and bathroom fixtures in good repair. After each use, all faucets or valves must be closed. Water leaks from any source must be stopped promptly. Report leaks to the DPW work reception (see appendix D for telephone numbers). Pavement washing should be avoided (shovel or sweep away debris).
5a
Hot water Use hot water only when the task requires it. Administrative buildings with shower facilities are authorized hot water for those facilities. Water temperature will be regulated as prescribed in appendix E.
5b
Vehicle All military vehicles that require anything more than a superficial rinsing washing or maintenance-related cleaning are to be washed at a tactical vehicle wash facility (TVWF). Residents of Fort Hood may wash privately owned vehicles (POVs) at their home, minimizing water use and waste. All other commercial or government owned vehicles must be washed at a properly constructed car wash or wash rack. Charity or fund raising car wash events are reviewed on a case-by-case basis.
5c
Landscape Lawn watering should be kept to a minimum. Consider the demand irrigation reduction policy prior to watering lawns. Lawn sprinklers should not be left operating unsupervised or in one spot as to cause excessive saturation or wasteful runoff. DPW water conservation policy is distributed by the DPW, Environmental Division concerning water usage during the summer.
5d
LIGHTING PROCEDURES
Conservation Turn off lights in unoccupied areas and use only the lighting essential to a particular endeavor. Exterior lighting must be “off” during daylight hours and must be reduced to the minimum essential for safety and security purposes as required by Field manual (FM) 19-30 (Physical
(continued on next page)
Attachment R - Energy Conservation Program
ATT R - 18 02.01.2016
Conservation Security), chapter 6. Reduce the wattage of lighting whenever (continued) possible, particularly in seldom used areas such as storage areas and utility rooms.
Lighting should be reduced by disconnecting nonessential lamps, ballasts, or fixtures.
The replacement of low-efficiency lamps with high-efficiency lamps should be implemented. Replace fluorescent tubes which are blackened on the ends (blackened tubes emit half the light of a new tube). Screw base CFL compact fluorescent lamps shall be used in lieu of screw base incandescent lamps.
Only DPW maintenance shops disassembles unneeded lighting fixtures or ballasts.
6a
Lighting Manage the lighting systems at indoor or outdoor athletic facilities to athletic prevent waste of electricity. Turn off unnecessary lighting during facilities periods when these facilities are unoccupied and when daylight is adequate. Lighting at outdoor athletic facilities should not be used for normal security or crime prevention purposes.
6b
Illumination The general illumination intensity requirements are prescribed in intensities appendix G. DPW will assist in determining the required intensities to provide a safe and productive environment.
6c
Ornamental Reasonable use of inside and outside electrical ornamental lighting is lighting authorized during the Christmas season. Lighting is only authorized in Family housing areas and public assembly areas designated by the Garrison Commander to exhibit the spirit of the season. Lighting arrangements should be kept to a reasonable minimum. All ornamental lighting must be turned off after 2300 and during daylight hours. To avoid the possibility of a fire, lighting should be carefully inspected, controlled, and monitored. The Christmas season is defined as the period between 1 December through 1 January.
6d
ATT R - 19 02.01.2016
UTILITY METERING
Individual Individual building metering is the best method to evaluate building buildings modifications, monitor energy consumption, and identify peak energy characteristics.
This information allows the DPW, Environmental Division to establish normal energy use patterns (baselines) for a particular building type.
These baselines are used to validate studies by comparing actual energy savings (resulting from conservation retrofit measures) with predicted energy savings.
7a
Metering data Metering data is disseminated among DPW maintenance shops to help identify equipment deficiencies. Metering data can also be used to instill competition within organizations and among units. This will help increase the facility users awareness of the energy they consume, which will further assist efforts to reduce energy consumption.
7b
Construction Utility meters shall be incorporated into all major new construction and projects retrofit projects per Installation Designed Guide (IDG) 2005.
7c
Metering Activities who reimburse Fort Hood for utilities will install meters in new criteria facilities and when existing, service lines are upgraded. For facilities serving activities which do not reimburse Fort Hood for utilities, metering devices will be installed in certain instances. All the facilities listed in appendix C will be considered for metering devices. Criteria in paragraphs 7e, 7f, 7g, and 7i below shall be used to determine which meters are required. If an electrical meter is deemed appropriate, a gas meter should be given strong consideration.
7d
Electric Electric metering is required when total electrical demand is greater metering than or equal to 48 kilowatts and estimated peak demand is greater criteria than or equal to 25 kilowatts.
7e
ATT R - 20 02.01.2016
Natural gas Natural gas metering is required when the total design flow rate is metering greater than 100 cubic feet (2.8 cubic meters) per hour and design criteria heating load is greater than 25 British thermal unit/square feet (BTU/SF) (293,056 Joules/square meter).
7f
Water Water metering is required when a design load is greater than or metering equal to 3 million gallons (11.34 million liters) a year.
criteria 7g
Remote Single point or multiple system telemetry (remote) metering should be metering considered for installation in lieu of standard metering devices.
Remote metering provides rapid and accurate meter reading with little or no additional manpower required to locate, record, and log utility readings.
Remote metering allows hourly meter readings which can be used to establish a facility’s daily operation energy profile. This profile can be used to determine low or no cost energy consumption reduction opportunities for potential energy savings.
7h
Chiller Provide an electrical KW meter and an appropriately sized chilled metering water flow meter for chillers for 50 TR or larger capacity. The readings of KW and /or TR (chilled water flow) shall be integrated into the UMCS system for monitoring and comparison of chiller cooling efficiency.
7i
ELECTRICAL APPLIANCES
Safety All electrical appliances are subject to applicable safety regulations and FH Reg 420-1 (Fire Regulations), paragraph 2-22. Limit the use of electrical appliances for ornamental purposes such as aquariums, electric mobiles, disco lights.
ATT R - 21 02.01.2016
Safety • Use of specific ornamental appliances in areas of public assembly (continued) (i.e., clubs, day rooms, libraries) may be authorized by Commanders, Directors, and activity chiefs.
8a
Washers and Users are encouraged to use cold or warm water instead of hot water dryers for all laundry except white garments and heavily soiled fabrics.
Washers and dryers will not be overloaded or underloaded. Clear lint traps before drying each load. Electric washers and dryers will not be operated during the PED period.
8b
Refrigeration Do not keep refrigerator or freezer doors open longer than necessary.
worn or damaged gaskets must be replaced. Defrost refrigerator freezers regularly (frost over 1/4 inch (10 centimeters) thick acts as an insulator causing the refrigerator to work harder). Adjust the refrigerator thermostat to the minimum setting necessary, a mid-dial setting is usually adequate. Disconnect unnecessary or unused refrigeration equipment.
8c
FAMILY HOUSING
Occupants The use of kitchen ranges to supplement the heating system is prohibited.
Occupants departing their residence on vacations or other periods of absence longer than 8 hours will set thermostats to 55 degrees Fahrenheit (14 degrees Celsius) for heating or 88 degrees (Fahrenheit (31 degrees Celsius) for air conditioning. If no damage to the quarters or its contents will occur, further measures can be taken such as turning off the heating and air conditioning systems, all electrical appliances, refrigeration equipment whenever prudent, and all interior lighting.
9a
ATT R - 22 02.01.2016
TRAINING
Energy Energy training is provided by DPW, Environmental Division.
training Training consists of establishing energy conservation programs, identifying energy conservation opportunities, and discussing energy consumption and trends. Requests for training should be submitted by calling the DPW, Environmental Division energy hot-line (see appendix D for telephone numbers) or by a memorandum to DPW, ATTN: Environmental Division.
10a
Building ECOs and BEMs should be familiar with specific methods and training energy available to identify and implement good energy conservation manager practices.
10b
AREAS OF SPECIAL EMPHASIS
Publicity Commanders, Directors, and activity chiefs should actively promote energy conservation. Bulletin boards, posters, and signs and regular training are ways to increase energy conservation awareness. Contact DPW, Energy Office for training materials.
11a
Temperature Space temperature compliance is determined by the average of measurement thermometer readings taken at the center of a room, 2 feet (0.0609 techniques meters) from each wall, 4 to 5 feet (1.2 to 1.5 meters) above the floor.
Hot water temperature compliance is determined by a single thermometer reading taken during normal hot water use from a tap at an average distance from the hot water tank.
11b
Commonly Extraordinary management of utilities is required at athletic fields and used areas courts, chapels, dining facilities, physical fitness centers, showering areas, laundry rooms, motor pools, and swimming pools.
11c
ATT R - 23 02.01.2016
Heating to air Since the heating and air conditioning transition periods require DPW conditioning to employ special crews for several weeks, the establishment of transition seasonal transition dates is necessary to efficiently manage resources.
• Heating is turned off beginning the third Monday of March.
• Air conditioning is turned on beginning the first Monday of May.
• Air conditioning is turned off beginning the second Monday of October.
• Heating is turned on beginning the first Monday of November.
Occupants may experience some temporary discomfort resulting from abnormal weather during the transition periods.
11d
Minimizing PED is the maximum amount of power demand at each of the four peak electrical electrical substations located on Fort Hood. PED occurs once during demand (PED) the year, usually around 1530 on a hot summer day when most air conditioners are running. Reduction of PED is one of the most profitable conservation measures because it affects Fort Hood utility costs for the entire year. The PED period occurs from 1 May through 30 September between the hours of 1300 to 1700.
The operation of high voltage (greater than 120 volts) electrical equipment which should be routinely avoided during all or some of the PED period is prescribed on FH Form 1073 by the ECOs. However, mission readiness and training are the installation’s primary concern and will not be compromised. It is extremely important to intensify efforts to eliminate energy waste and conserve electricity during PED.
11e
ATT R - 24 02.01.2016
STORING AND DISPENSING PROCEDURES FOR PETROLEUM, OIL, AND
LUBRICANTS (POL) CONTAINERS
Mobility Mobility energy use includes all fuels used for transportation, research energy and development, training, and operational readiness on land, sea, and air. Effective energy conservation practices should be incorporated into all phases of training which use mobility fuels. The management plans herein are designed to reduce energy consumption of mobility fuels while maintaining readiness. If conservation programs should impact training readiness, the conflict is resolved outside this regulation. Training plans should consider energy conservation at all levels of the organization.
12a
Storage Store packaged petroleum products according to FM 10-69 (Petroleum Supply Point Equipment and Operations), chapter 16. Close partially full petroleum, oil, and lubricants (POL) product containers tightly at all openings to avoid contamination and spillage.
Grease containers should be tightly closed immediately after each dispensing to prevent contamination. POL cans of 1 gallon (4.55 liters) or less cannot be tightly closed because of the need to puncture the container in order to dispense the product. Puncturing (creating air holes) POL containers, which are provided with caps, bung plugs, and so forth, is prohibited because it causes undue waste by allowing product contamination and complicates the required turn-in of empty containers for recycle. Prevent fuel contamination regardless of use or storage method. Dispose of or use all contaminated fuels in accordance with FH Reg 200-1 (Environment and Natural Resources).
12b
Dispensing Basic loads are rotated by exchanging older products with fresher ones from the operational stock. Using the oldest product first prevents loss due to shelf life expiration or container deterioration.
Take necessary caution to prevent back surges and overflows when dispensing or transferring fuel.
12c
ATT R - 25 02.01.2016
MAINTENANCE
Equipment Intercept fuel by using funnels or drip catchers whenever equipment maintenance maintenance procedures generate waste, excess, or contaminated fuel. Store fuel in suitable containers until proper disposition can be made. Prevent fuel leaks through proper maintenance and careful operation of equipment. When leaks do occur, take prompt corrective action (turn off pumps and valves until leaking stops).
13a
Vehicle To ensure efficient fuel consumption, perform all scheduled maintenance maintenance including replacing all filters (air, fuel, and oil) and tuning vehicles according to their technical manuals (TMs). To confirm fuel economy, check vehicle logbook when refueling and calculate fuel consumption per mile or hour. When fuel consumption increases per mile or hour, schedule the vehicle for a maintenance check.
13b
TRANSPORTATION
Efficient use Schedule or arrange transportation to and from administrative of vehicles functions to minimize vehicle usage. Promote car pools within your unit or activity. Select vehicles according to the load they will carry (i.e., a heavy truck should not be used when a sedan could do the job). Do not leave the engine idling while a vehicle is being loaded, unloaded, or waiting. Use military vehicles for official purposes only.
Use available alternative fuels to reduce fleet petroleum consumption where allowed by Original Equipment Manufacturers (OEM) to meet the goals of Energy Policy Act (EPACT) 2005 and Executive Order 13423.
Whenever possible, eliminate trips if results can be achieved by telephone. Conduct meetings using the conference features of the telephone system.
14a
ATT R - 26 02.01.2016
Driving When driving observe speed limits and accelerate smoothly and moderately. Maintain a steady speed as much as possible. Try to avoid stop-and-go traffic. Plan routes and adjust speed to avoid unnecessary accelerations and decelerations.
14b
Tactical and Use nontactical vehicles to the maximum extent possible for essential nontactical administrative missions. Limit use of tactical vehicles only for essential vehicles tasks.
14c
ENERGY CONSERVATION IN TRAINING
Fuel During ground training:
conservation actions • Limit operational training involving aircraft and other fuel consuming equipment without affecting operational readiness.
• Limit weapons and equipment demonstration to the absolute minimum required for training.
• Modify training plans to eliminate use of nonessential motorized equipment.
• Limit field training exercises and increase command post exercises consistent with readiness requirements.
• Maximize foot movement to training and administrative areas.
• Leave unit equipment on-site during field training rather than returning equipment to post each day.
• Extend the length of required field training exercises to maximize use of equipment once in place.
• Increase the use of classroom instructional training aids in lieu of hands-on training with motorized equipment.
ATT R - 27 02.01.2016
Fuel • Ensure that equipment operators are aware of energy conservation conservation practices during operation and maintenance of their equipment.
actions (continued) • Optimize the use of simulators and miniranges by incorporating their uses into the units training program.
• Keep energy intensive exercises to the minimum required to maintain combat readiness.
15a
Aviation Achieve tactical aircrew training manual (TATM) requirements using training minimal fuel. Accomplish TATM requirements of operational aviators in conjunction with administrative and operational missions to the maximum extent possible. Reduce aviator transition training to the minimum required to meet operational requirements. Minimize turnaround times during airmobile training by using the most direct route and nearest training areas. Maximize use of synthetic flight trainers and simulators.
15b
ATT R - 28 02.01.2016
Appendix A References
Section I. Required Publications
EOP 36-1 (Cited in para 3e) Exchange Operation Procedure
FH Reg 200-1 (Cited in para 12b) Environment and Natural Resources
FH Reg 420-1 (Cited in para 8a) Fire and Emergency Services
FH Reg 420-27 (Cited in para 4d and 4h) Care, Maintenance, and Alterations of Facilities
FM 10-69 (Cited in para 12b) Petroleum Supply Point Equipment and Operations
IDG 2005 (Cited in para 7c) Fort Hood Installation Design Guide 2005
Section II. Related Publications
AR 1-201
Army Inspection Policy
AR 11-27
Army Energy Program
AR 30-1
The Army Food Service Program
AR 420-49
Heating, Energy Selection and Fuel Storage, Distribution, and Dispensing Systems
AR 420-54
Air Conditioning and Refrigeration
DA BEM Handbook Department of the Army Building Energy Monitor’s Handbook
Attachment R - Energy Conservation Program
ATT R - 29 02.01.2016
EPACT 2005
Energy Policy Act 2005
Executive Order 13423 Strengthening Federal Environmental, Energy, and Transportation Management
FM 19-30
Physical Security
FORSCOM Pam 11-3 Energy Program Guide (Draft)
FORSCOM Pam 11-27 FORSCOM Energy Resources Management Plan (Draft)
IES Lighting Handbook Illumination Engineering Society Lighting Handbook
Section III. Prescribed Forms This section not used.
Section IV. Referenced Forms
FH Form 1073 Checklist for Good Conservation of Utilities
FH Form 1853 Distribution Scheme
ATT R - 30 02.01.2016
Appendix B Sample Memorandum
DEPARTMENT OF THE ARMY
US ARMY INSTALLATION MANAGEMENT COMMAND
HEADQUARTERS, UNITED STATES ARMY GARRISON, FORT HO
BUILDING 1001 ROOM W321
FORT HOOD, TEXAS 76544-500
IMWE-HOD-PWE Date
MEMORANDUM FOR Directorate of Public Works, ATTN: Environmental Division
SUBJECT: Request for Exception to Policy for Climatic Control
1. Request Climatic Control of air-conditioning in building 35001 and 35002. (95th Maintenance Company, 1st Cavalry Division.)
2. Justification is the requirement that temperature control must be maintained for calibration standards as per TB 750-25, paragraph 4-4, page 4-1 (between 68-74 degrees Fahrenheit).
3. POC: CW3 Condition/SSG Weather, 287-5677. Email frank.weather@us.army.mil
ERNIE G. SAVER
MAJ, OD
Chief, Operation Division
Figure B-1. Sample Memorandum
ATT R - 31 02.01.2016
Appendix C Facility Type Table
Table C-1. Facility Type Table
Facility Type CAT Code Description
Dining halls 72210 - Enlisted personnel dine Barracks with admin and supply 72112 - Enlisted barracks with admin and supply
Barracks with dining, admin, and supply
72113 - Enlisted barracks with dining, admin, and supply
Administration and supply 72330 - Administration and supply
Brigade HQ 14182 - Regiment HQ building
Barracks with dining 72110 - Enlisted barracks with dining
Barracks without dining 72111 - Enlisted barracks without dining
Physical fitness center 74028 - Physical fitness center
Automated data processing 61031 - ADP building
Medical facility 54010 - Dental clinic
Instrument trainer 17110 - AC trainer building
Flight simulator 17112 - Flight simulator building
Cold storage 43210 - Cold storage warehouse
Legend:
AC – Air Conditioning Admin – Administration ADP – Automatic Data Processing CAT – Category HQ – Headquarters
Note:
All military buildings shall be metered per EPACT 2005.
ATT R - 32 02.01.2016
Appendix D Telephone Numbers
Table D-1. Telephone numbers
Office Telephone number DPW Environmental Division 254-287-7283 DPW Work Reception 254-287-2113 Energy Hot-Line 254-287-SAVE Maintenance Contractor 254-532-3133
Legend:
DPW – Directorate of Public Works
ATT R - 33 02.01.2016
Appendix E Prescribed Temperatures (Fahrenheit)
Table E-1. Prescribed Temperatures (Fahrenheit)
Area 1
Heating Temp Range2
Cooling Temp Range2 Hot Water Temp1 and 3
Family quarters 65– 70
(18.3 – 21.1)
75 – 80 (23.9 – 26.7)
(43.3)
Troop living 65 – 70 (18.3 – 21.1)
75 – 80 (23.9 – 26.7)
(43.3)
Administrative areas 65 – 70
(18.3 – 21.1)
75 – 80 (23.9 – 2-26.7)
Administrative shower facilities 110 (43.3)
Dining facility 65 – 70 (18.3 – 21.1)
75 – 80 (23.9 – 26.7)
General use – 140 (60) Prewash – 160 (71.1) Final rinse – 180 (82.2)
Recreation 65 – 70 (18.3 – 21.1)
75 – 80 (23.9 – 26.7
(35.6)
Motor pools 50 – 65 (10.0 – 15.6) N/A N/A
Dental clinics 70 – 75 (21.1 – 23.9)
70 – 75 (21.1 – 23.9)
(60)
Medical clinics 70 – 75 (21.1-23.9)
70 – 75 (21.1 – 23.9)
(60)
Child care 70 – 75 (21.1 – 23.9)
70 – 75 (21.1 – 23.9)
(35.6)
Operating-delivery 70 – 75 (21.1 – 23.9)
65 – 70 (18.3 – 21.1)
(60)
Intensive care 75 – 80 (23.9 – 26.7)
70 – 75 (21.1 – 23.9)
(60)
Paint shop 75 – 80 (23.9 – 26.7) N/A N/A
Warehouse 55 – 60 (12.8 – 15.6) N/A N/A
Automated facility PMS PMS N/A
ATT R - 34 02.01.2016
Table E-1. Prescribed Temperatures (Fahrenheit) (continued)
Legend:
N/A – Not applicable PMS – Per manufacturer’s specification (with DPW exception) Temp – (temperature)
1 Not to exceed without DPW exception.
2 Space temperature.
3 Temperature at the destination.
ATT R - 35 02.01.2016
Appendix F Relation of Space Temperature to Energy Consumption (Fahrenheit)
Figure F-1. Relation of Space Temperature to Energy Consumption (Fahrenheit)
ATT R - 36 02.01.2016
Appendix G Light Intensities for a Safe and Productive Environment
Table G-1. Light Intensities for a Safe and Productive Environment
Area1 Foot Candles2 Family quarters 10-50 Work station (desk, table, drafting, etc.) 50 Conference room 30 Classroom 30-50 Warehouse 30 Nonworking areas (halls, corridors, etc.) 10 Troop living 30
Legend:
DPW – Directorate of Public Works ETC – Et Cetera
1 Lamp wattages will not exceed equipment manufacturer’s specified rating.
2 Not to exceed without DPW exception.
ATT R - 37 02.01.2016
Glossary Section I. Abbreviations
AAFES
Army and Air Force Exchange Service
ADMIN
Administration
AC
Air Conditioning
ADP
Automatic Data Processing
ATTN
Attention
BEM
Building Energy Monitor
BMP
Best Management Practices
BTU/SF
British Thermal Unit per Square Feet
CAT
Category
CFL
Compact Fluorscent Lamp
DA
Department of the Army
DPW
Directorate of Public Works
ECO
Energy Conservation Officer
EMS
Environmental Management System
Attachment R - Energy Conservation Program
ATT R - 38 02.01.2016
EOP
Exchange Operation Procedure
ETC
Et Cetera
FH
Fort Hood
FHEC
Fort Hood Energy Coordinator
FM
Field Manual
HQ
Headquarters
IAW
In Accordance With
IDG
Installation Design Guide
IES
Illumination Engineering Society
FORSCOM
Forces Command
KW
Kilowatt
N/A Not Applicable
OEM
Original Equipment Manufacturer
PAO
Public Affairs Officer
ATT R - 39 02.01.2016
PED
Peak Electrical Demand
PMS
Per Manufacturer’s Specification
POC
Point of Contact
POL
Petroleum, Oil, and Lubricants
POV
Privately Owned Vehicle
REG
Regulation
SOP
Standard Operating Procedure
TATM
Tactical Aircrew Training Manual
TEMP
Temperature
TM
Technical Manual
TR
Tons of Refrigeration
TVWF
Tactical Vehicle Wash Facility
UMCS
Utility Monitoring and Control System
ATT R - 40 02.01.2016
Section II. Terms
Cooking appliance Cooking appliance for the purpose of energy conservation is defined as any household device which consumes energy in the form of electricity or natural gas and used in the preparation of food (i.e., toasters, hot plates, and electric skillets).
Electrical appliance Any device that uses electricity. Exempt from this definition are battery-operated devices and light fixtures.
Mobility energy Fuels and lubricants used for operation of vehicles, aircraft, and other motorized equipment which are not part of a facility system.
Peak electrical demand (PED) The time period in which the electrical peak demand may occur. This period is defined as 1 May through 30 September from 1300-1700 on weekdays.
Space temperature The average temperature reading in a given area measured between 4 and 5 feet (1.2 and 1.5 meters) above the finished floor.
Utilities Water, electricity, natural gas, and fuels consumed by the use of real property.
Utility meters Meters used to record the consumption of utilities.