Exhibit L - In-line Electrical Primary Riser Detail
View the file
Other files for this federal contract opportunity
Show all 26
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
15 KV HEAVY DUTY LOAD BREAK
FUSED CUTOUTS.
10KV INTERMEDIATE CLASS
SURGE ARRESTERS.
STIRRUP/HOT LINE CLAMP CONNECTION
WET PROCESS PORCELAIN
NO. 1/0 AWG CU GROUNDING
CONDUCTOR FOR SURGE ARRESTERS,
ISOLATED FROM ALL CURRENT
CONDUCTING EQUIPMENT & HARDWARE,
BONDED TO POLE GROUND BELOW GRADE.
SPARE CONDUIT CAPPED AT 18"
ABOVE GRADE.
CONNECT FIRST TO SURGE ARRESTER,
THEN TO FUSED CUTOUT.
TERMINATIONS.
NO. 6 AWG CU (MIN.) POLE GROUND.
NO SHARP BENDS ON PRIMARY CABLE.
USE CONDUIT VENTILATING CABLE
SUPPORT AT TOP OF RISER
3-PHASE TANGENT POLE DETAIL, RISER IN-LINE
POLE
GROUND
ARRESTER
GROUND
EXEROTHERMIC
WELD
3/4"x10’
GROUND
ROD
1’ Min.
FINISHED
GRADE
SPARE
CONDUIT
90 DEGREE
ELBOW
RGS TO PVC
ADAPTER
PVC CONDUIT
ENCASED IN
CONCRETE
RGS CONDUIT
RISER
CABLE
TERMINATOR,
TYPICAL
CROSSARM,
TYPICAL
FUSED CUTOUT,
TYPICAL
INSULATOR,
TYPICAL
ARRESTER,
TYPICAL
FINISHED
GRADE
SPARE
CONDUIT
FRONT VIEW SIDE VIEW
Revisions
Symbol Descriptions Date Approved
FORT HOOD, TEXAS
PROJECT NO.
SHEET OF
SCALE REDUCED
0 1/2 ’’ 1’’ 2’’
REVEIWED BY:
DRAWING
DMI NO.DATE:
SCALE:
DRAWN BY:
DESIGNED BY:
AS NOTED
SEQ. NO.
FILE NAME
DIRECTORATE OF PUBLIC WORKS
NO SCALE
BUTT-WRAPPED GROUND DETAIL
12’-0" MIN.
4 TURNS #6 BSD CU
AS REQUIRED
GALVANIZED STAPLES
STAPLED AS REQUIRED
WIRE 6 TURNS MIN.
#6 BSD CU GROUND
GROUND WIRE
(2 REQ’D)
BUSHING
GROUNDING
1" IMC
(2 REQ’D)
PIPE STRAP
GROUND WIRE (2 REQ’D)
SIZED TO MATCH
BSD COPPER JUMPER
FINISHED GRADE
GROUND WIRE MOLDING
NOTE: REQ’D FOR EACH GROUND WIRE
SCALE: NONE
GROUND LINE PROTECTION DETAIL
18" 14" 20"
4"MIN.
6"MIN.
O.D.
S A
N D
B E
D
TOP OF FINISHED GRADE
12"
36" MINIMUM FOR PRIMARY
24" MIN. FOR SECONDARY
CONDUIT
FOR TRENCH
3 TIMES
CONDUIT DIA.
WIDTH (12" MIN.).
DETAIL FOR UNDERGROUND ELECTRICAL PRIMARY OR SECONDARY
STIRRUP/
HOT-LINE
CLAMP,
TYPICAL
4 MIL MINIMUM X 6-INCH WIDE, POLYETHYLENE
MARKING TAPE (NO FOIL BACKING), RED, WITH
IDENTIFYING LETTERING, 1750 PSI LENGTHWISE
X 1500 PSI CROSSWISE MINIMUM STRENGTH.
BACKFILL MATERIAL CLASSIFIED SATISFACTORY;
PLACE IN LIFTS NOT EXCEEDING 6-INCHES (LOOSE)
FOR HAND OPERATED MACHINE COMPACTORS,
8-INCHES FOR OTHERS. COMPACT EACH LAYER
95% DENSITY.
PRIMARY OR SECONDARY CABLES IN CONDUIT SIZED
PER N.E.C., CENTERED IN TRENCH. MINIMUM SCH.
40 PVC WITH TRANSITION TO STEEL LONG RADIUS
AT RISER TO OVERHEAD. 1PHASE-2" MIN. AND
3 PHASE-4" MIN.
N.T.S.
SCALE: NONE
OVERHEAD-TO-UNDERGROUND
TRANSITION POLE DETAIL,
TRENCH DETAIL, POLE
BUTT-WRAP GROUNDING DETAIL,
AND POLE GROUND-LINE
PROTECTION DETAIL
JULY 2001
1 1
SANDBEDDING FOR SECONDARY, 3000 PSI CONCRETE
DYED RED REQUIRED FOR PRIMARY.
WALTER THOMAS
WALTER THOMAS
WALTER THOMAS
Attachment L - In-Line Electrical Primary Riser Detail For Bidding Purposes Only