ATT_M_-_In-Line_Electrical_Primary_Riser_at_90_Degrees_to_Line_Detail.pdf
PDF 586 KB Posted
- Attached to
- Open End Electrical Requirements Contract
- Solicitation number
- W91151-16-B-0021
About this file
Exhibit M - In-line Electrical Primary Riser at 90 Degrees to Line Detail
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FRONT VIEW SIDE VIEW
15 KV HEAVY DUTY LOAD BREAK
FUSED CUTOUTS.
10KV INTERMEDIATE CLASS
SURGE ARRESTERS.
STIRRUP/HOT LINE CLAMP CONNECTION
WET PROCESS PORCELAIN
NO. 1/0 AWG CU GROUNDING
CONDUCTOR FOR SURGE ARRESTERS,
ISOLATED FROM ALL CURRENT
CONDUCTING EQUIPMENT & HARDWARE,
BONDED TO POLE GROUND BELOW GRADE.
SPARE CONDUIT CAPPED AT 18"
ABOVE GRADE.
CONNECT FIRST TO SURGE ARRESTER,
THEN TO FUSED CUTOUT.
TERMINATIONS.
NO. 6 AWG CU (MIN.) POLE GROUND.
NO SHARP BENDS ON PRIMARY CABLE.
3-PHASE TANGENT POLE DETAIL, RISER AT 90 DEGREES TO LINE
USE CONDUIT VENTILATING CABLE
SUPPORT AT TOP OF RISER
10 FEB 99 N.T.S.
Attachment M - In-Line Electrical Primary Riser at 90 Degrees to Line Detail For bidding purpose only
ATT M - 1 02.01.2016