FS001_Amendment 002.pdf
PDF 171 KB Posted
- Solicitation number
- W50SC2-23-R-0001
- Issued by
-
Department of the Army National Guard
About this file
This document package includes a fire suppression system design specifications file and a related federal contract solicitation. The specifications file provides details for designing, installing, and testing fire suppression systems according to various codes and standards. It includes sprinkler system design criteria, notes, abbreviations, legends, and a site plan.
The federal contract solicitation seeks offers to construct an Aircraft Support Equipment and Vehicle Maintenance facility at Bradley Air National Guard Base in East Granby, Connecticut. Work will be performed according to contract drawings and technical specifications. The North American Industry Classification code is 236220 and size standard is $39.5 million average annual revenue. Project value is between $10-25 million. A single award is contemplated. Failure to submit an offer on all items will result in rejection. Instructions for drawings and specifications are in section 00100. Funds have not been appropriated and no award will be made until funds become available, which is anticipated prior to award as the project is on the National Guard priority list.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOT ALL SYMBOLS ARE USED
TC
ABBREVIATIONSYMBOL DESCRIPTION
BUTTERFLY VALVE WITH TAMPER
FLOW SWITCHFS
EAB ELECTRIC ALARM BELL
FDC FIRE DEPARTMENT CONNECTION (WALL-MOUNTED)
INSPECTOR'S TEST CONNECTION
WET PIPE RISER
OUTSIDE SCREW AND YOKE GATE VALVE W/TAMPER SWITCH
POST INDICATOR VALVE
DRY PIPE VALVE
PRESSURE REDUCING VALVE
CHECK VALVE
ANGLE VALVE
GLOBE VALVE
AV
GLV
CV
DPV
PRV
PIV
OS&Y
SP
CAPPED PIPE/OUTLET
PIPE TURNING DOWN
PIPE TURNING UP
AFF
AHJ
AVG
BFP
CFM
COTR
ELEV
FDC
FHV
FP
EOL
FPC
FVC
GALS
GPH
GPM
GV
JP
JPC
JOCKEY PUMP
GATE VALVE
GALLONS PER MINUTE
GALLONS PER HOUR
GALLONS
FIRE VALVE CABINET
FIRE PUMP CONTROLLER
FIRE PUMP
FIRE HOSE VALVE
END OF LINE RESISTOR
ELEVATION
CUBIC FEET PER MINUTE
AVERAGE
AUTHORITY HAVING JURISDICTION
DOUBLE CHECK BACKFLOW PREVENTER
CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE.
FIRE DEPARTMENT CONNECTION
WEATHER PROOFWP
UH
SQFT
SLC
NIC
NC
MIN
NP
PIV
PSIG
SOV
VLV
OS&Y
NAC
JOCKEY PUMP CONTROLLER
MINIMUM
NOTIFICATION APPLIANCE CIRCUIT
NOT PERMITTED
NONCOMBUSTIBLE
POST INDICATOR VALVE
NOT IN CONTRACT
OUTSIDE SCREW AND YOKE
POUNDS PER SQUARE INCH GAUGE
SIGNALING LINE CIRCUIT
SOLENOID VALVE
SQUARE FEET
UNIT HEATER
VALVE
ABOVE FINISHED FLOOR
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
OH ORDINARY HAZARD
TYP TYPICAL
FIRE SUPPRESSION GENERAL NOTESFIRE SUPPRESSION LEGEND FIRE PROTECTION ABBREVIATIONS
1. THE BUILDINGS MUST BE FULLY SPRINKLERED. THE SYSTEMS MUST BE DESIGNED, INSTALLED AND TESTED IN ACCORDANCE WITH
• UFC 3-600-01, 8 AUGUST 2016 WITH CHANGE 5, 24 SEPTEMBER 2020
• INTERNATIONAL BUILDING CODE, 2018 EDITION
• NFPA 1, FIRE CODE, 2018 EDITION
• NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2019 EDITION
• NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE SERVICE MAINS AND THEIR APPURTENANCES, 2019 EDITION
• CONTRACT SPECIFICATIONS
2. THE DESIGN IS BASED ON UFC 3-600-01, AND THE REQUIREMENTS LISTED BELOW. THE MORE STRINGENT REQUIREMENTS OF UFC 3-600-01 MUST APPLY.
3. VERIFY ALL LOCATIONS AND MEASUREMENTS AS CONDITIONS MAY VARY THROUGHOUT CONSTRUCTION. ALL CHANGES FROM THE ORIGINAL DESIGN MUST BE APPROVED BY THE AHJ.
4. INSTALL TAMPER AND FLOW SWITCHES AS INDICATED ON CONTRACT DRAWINGS. CONNECTIONS TO THE FIRE ALARM SIGNALING LINE CIRCUIT MUST BE MADE UNDER SPECIFICATION DIVISION 28.
5. DESIGN THE AUTOMATIC SPRINKLER SYSTEM BY MEANS OF HYDRAULIC CALCULATIONS IN ACCORDANCE WITH UFC 3-600-01, NFPA 13, AND CONTRACT SPECIFICATIONS REQUIREMENTS. REFER TO WATER SUPPLY AND DESIGN REQUIREMENTS ON THIS SHEET FOR CLARIFICATION. THE CONTRACTOR IS RESPONSIBLE FOR THE ENTIRE DESIGN OF THE SPRINKLER SYSTEM.
6. DRAWINGS INDICATE THE DESIGN INTENT. SHOP DRAWINGS MUST BE SUBMITTED TO INDICATE SPECIFIC PRODUCTS TO BE INSTALLED, HANGER DESIGN CRITERIA, ETC. IN ACCORDANCE WITH NFPA
13, CHAPTER 27.
7. OBTAIN ALL REQUIRED PERMITS AND APPROVALS FROM THE AHJ PRIOR TO COMMENCING WORK.
8. BUILDING SEISMIC DESIGN CATEGORY C. PROVIDE SEISMIC BRACING FOR SPRINKLER SYSTEM PIPING IN ACCORDANCE WITH NFPA 13.
HH HIGH HAZARD
AAV AUTOMATIC AIR VENT
OCCUPANCY
CLASSIFICATION
DESIGN DENSITY
(GPM / SQ. FT)
DESIGN AREA
(SQ. FT)
HOSE STREAM
ALLOWANCE (GPM)
DURATION
(MIN.)
LIGHT HAZARD (LH) 0.10 1,500 250 60
ORDINARY HAZARD
WET (OH)
0.20 2,500 250 60
COVERAGE PER
SPRINKLER
(SQ. FT)
SPRINKLER SYSTEM DESIGN CRITERIA
SPRINKLER HEAD
K-FACTOR
5.6
8.0
RESPONSE
TIME INDEX
(RTI)
QR
SR
VEHICLE OPERATIONS
PARKING (REFUELER) -
CEILING HEIGHT UP TO 30'
EXTRA HAZARD (EH)
0.30 2,500 500 60 100 11.2 SR
9. PROVIDE UPRIGHT SPRINKLERS IN ALL ROOMS WITH NO CEILINGS, AND CONCEALED OR RECESSED TYPE SPRINKLERS WITH COVERS IN SUSPENDED CEILINGS, GYPSUM CEILINGS AND SOFFITS.
COORDINATE COVER PLATE COLORS WITH ARCHITECT.
10. COORDINATE ALL FIRE PROTECTION, ELECTRICAL, PLUMBING, MECHANICAL, AND STRUCTURAL WORK WITH CEILING HEIGHTS AND ARCHITECTURAL WORK. WHERE CONFLICTS OCCUR COORDINATE
FINAL LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS.
11. THE FIRE SUPPRESSION SYSTEMS MUST BE SUPPLIED BY A DEDICATED FIRE MAIN. THE EXISTING HIGH PRESSURE FIRE MAIN IS SUPPLIED BY TWO 3,000 GPM @140 PSI FIRE PUMPS. BASE HYDRAULIC CALCULATIONS ON THE MOST RECENT FIRE PUMP TEST REPORTS, STATIC PRESSURE ON THE SYSTEM IS 170 PSI.
12. SPRINKLER PIPING MUST BE LABELED IN ACCORDANCE WITH UFC 3-600-01, 9-6.8.
13. FIRE SPRINKLER SYSTEM MUST BE FULLY COORDINATED WITH ALL DISCIPLINES PRIOR TO INSTALLATION.
14. PROVIDE AUXILIARY DRAINAGE FOR ALL LOW POINT AND TRAPPED SECTIONS OF WATER.
15. SPRINKLER TEMPERATURE RATING IN ACCORDANCE WITH NFPA 13.
16. SPRINKLERS MUST BE LOCATED SYMMETRICALLY WITHIN CEILING TILES.
17. FOR ALL PIPE PASSING THROUGH EXPANSION JOINTS PROVIDE UL LISTED AND FM APPROVED FLEXIBLE COUPLING.
18. PROVIDE BLACK STEEL SCHEDULE 40 MINIMUM THICKNESS FOR ALL FIRE SUPPRESSION PIPING.
19. PROVIDE AN AIR RELIEF VENT AT THE HIGH POINT OF EACH ZONE OF THE FIRE SPRINKLER SYSTEM IN ACCORDANCE WITH NFPA 13.
20. PROVIDE AN INSPECTORS TEST CONNECTION AT THE MOST HYDRAULICALLY REMOTE POINT ON THE SPRINKLER SYSTEM.
21. ALL DRAIN PIPING MUST BE PIPED TO THE BUILDING EXTERIOR TO WITHIN 6 INCHES ABOVE FINISHED GRADE. ALL DRAIN PIPING DISCHARGE LOCATIONS MUST BE PROVIDED WITH SPLASH
BLOCKS.
SIM
SP
TD TRAVEL DISTANCE
SMOKE PARTITION
SIMILAR
CIS COMMON INTELLIGIBILITY LEVEL
DOR
AFG ABOVE FINISHED GRADE
DESIGNER OF RECORD
SD SMOKE DAMPER
EX EXPLOSION PROOF
VEWSD VERY EARLY WARNING SMOKE DETECTION
LH
NS
LIGHT HAZARD
NOT SPRINKLERED
ORDINARY HAZARD
EXTRA HAZARD
OH
EH
ORDINARY HAZARD
DRY (OH)
0.20 3,500 250 60 130 8.0 SR
* DESIGN AREA MUST BE THE LESSER OF THE DESIGN AREA INDICATED OR THE ENTIRE AREA OF THE SPACE PROTECTED.
HATCHING
SYMBOL
FIRE SUPPRESSION SPRINKLER SYSTEM DESIGN CRITERIA
FIRE SUPPRESSION SITE PLAN
REFUELER MAINTENANCE -
CEILING HEIGHT GREATER
THAN 30' EXTRA HAZARD (EH)
0.30
3,600 OR
TOTAL AREA
OF ROOM
(WHICHEVER
IS LESS)
500 60 100 11.2 SR
DRY PIPE
ZONE
WET PIPE
ZONE 1
WET PIPE
ZONE 2
WET PIPE
ZONE 3
N
A
Designed:
Drawn:
Checked:
Date:
Drawing Title:
Jacobs Project No.:
Key Plan:
D3257200
B
C
D
2 3 4 5
THESE DOCUMENTS ARE FOR
INTERIM REVIEW AND NOT FOR
CONSTRUCTION, BIDDING, OR
PERMIT PURPOSES.
Phase: B-3 FINAL DESIGN
C O
N N
EC
TI
C U
T
AI
R N
AT
IO
N
AL
G U
AR
D
R D
A
IR
LI
FT
W
IN
G
BR
AD
LE
Y
AI
R
N
AT
IO
N
AL
G
U
AR
D B
AS
E
EA
ST
G R
AN
BY
, C O
N N
EC
TI
C U
T
C O
M P
O S
IT
E
A S
E A
N D
V M
X S
F A
C
IL
IT
Y
Drawing No.:
C D
A E
S
B
BI
M
U
S C
T_ D
0_
C
AN
G _A
SE
-V
M
XS
F ac ilit y/
D
0_ C
TA
N
G _A
SE
-V
M
XS
F
AC
IL
IT
Y_
FP
R O
.rv t
1/
/2
4:
:4
PM
M.OWENS
D.FOX
J.MCLAUGHLIN
03/31/2022
FS001
FIRE SUPPRESSION
GENERAL NOTES,
ABBREV., AND SYMBOLS
REV DESCRIPTION DATE
1 AMENDMENT 002 JAN 2023
File details come from the government source that posted it. Updated .