This solicitation is for the construction of an Aircraft Support Equipment and Vehicle Maintenance Facility at Bradley Air National Guard Base in East Granby, Connecticut. Work will include construction services in accordance with contract drawings and technical specifications. The project magnitude is between $10 million and $25 million, and the solicitation is unrestricted. The North American Industry Classification code is 236220 for commercial and institutional building construction, with a small business size standard of average annual revenue of $39.5 million for the past three years. A single award contract is contemplated. The solicitation and any amendments will be posted on sam.gov. Instructions for obtaining drawings and specifications are in Section 00100 of the solicitation. Funds have not yet been appropriated, but the project has been prioritized by the National Guard and funds are anticipated to be available before award. The Department of the Army National Guard is the contracting agency.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Connecticut Air National Guard 31 March 2022 Construct Composite ASE/VMXS Facility - CEKT179200 AMENDMENT 002 - JANUARY 2023 Bradley Air National Guard Base, East Grandby, Connecticut B-3 Final Design
FIRE EXTINGUISHERS 104416 - 1
SECTION 104416 - FIRE EXTINGUISHERS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes portable, hand-carried fire extinguishers and mounting brackets for fire extinguishers.
B. Related Requirements:
1. Section 104413 "Fire Protection Cabinets."
1.3 PREINSTALLATION MEETINGS
A. Preinstallation Conference: Conduct conference at Project site.
1. Review methods and procedures related to fire extinguishers including, but not limited to, the following:
a. Schedules and coordination requirements.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of product. Include rating and classification, material descriptions, dimensions of individual components and profiles, and finishes for fire extinguisher and mounting brackets.
B. Product Schedule: For fire extinguishers. Coordinate final fire-extinguisher schedule with fire-protection cabinet schedule to ensure proper fit and function. Use same designations indicated on Drawings.
1.5 INFORMATIONAL SUBMITTALS
A. Warranty: Sample of special warranty.
Connecticut Air National Guard 31 March 2022
Bradley Air National Guard Base, East Grandby, Connecticut B-3 Final Design
FIRE EXTINGUISHERS 104416 - 2
1.6 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For fire extinguishers to include in maintenance manuals.
1.7 COORDINATION
A. Coordinate type and capacity of fire extinguishers with fire-protection cabinets to ensure fit and function.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. NFPA Compliance: Fabricate and label fire extinguishers to comply with NFPA 10, "Portable Fire Extinguishers."
B. Fire Extinguishers: Listed and labeled for type, rating, and classification by an independent testing agency acceptable to authorities having jurisdiction.
2.2 PORTABLE, HAND-CARRIED FIRE EXTINGUISHERS
A. Fire Extinguishers: Type, size, and capacity for each fire-protection cabinet and mounting bracket indicated.
1. Source Limitations: Obtain fire extinguishers, fire-protection cabinets, and accessories, from single source from single manufacturer.
2. Handles and Levers: Manufacturer's standard.
3. Instruction Labels: Include pictorial marking system complying with NFPA 10, Appendix B, and bar coding for documenting fire-extinguisher location, inspections, maintenance, and recharging.
B. Multipurpose Dry-Chemical Type in Steel Container : UL-rated 10-A:120-B:C, 20-lb nominal capacity, with monoammonium phosphate-based dry chemical in enameled-steel container.
C. Carbon Dioxide Type : UL-rated 10-B:C, 20-lb nominal capacity, with carbon dioxide in manufacturer's standard enameled-metal container.
2.3 MOUNTING BRACKETS
A. Mounting Brackets: Manufacturer's standard steel, designed to secure fire extinguisher to wall or structure, of sizes required for types and capacities of fire extinguishers indicated, with plated or red baked-enamel finish.
1. Source Limitations: Obtain mounting brackets and fire extinguishers from single source from single manufacturer.
Connecticut Air National Guard 31 March 2022
Bradley Air National Guard Base, East Grandby, Connecticut B-3 Final Design
FIRE EXTINGUISHERS 104416 - 3
B. Identification: Lettering complying with authorities having jurisdiction for letter style, size, spacing, and location. Locate as indicated by Architect.
1. Identify bracket-mounted fire extinguishers with the words "FIRE EXTINGUISHER" in red letter decals applied to mounting surface.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine fire extinguishers for proper charging and tagging.
1. Remove and replace damaged, defective, or undercharged fire extinguishers.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. General: Install fire extinguishers and mounting brackets in locations indicated and in compliance with requirements of authorities having jurisdiction.
1. Mounting Brackets: Top of fire extinguisher to be at 42 inches above finished floor.
B. Mounting Brackets: Fasten mounting brackets to surfaces, square and plumb, at locations indicated.
END OF SECTION 104416