A-130 - A-137 - RCPs_ Amendment 001.pdf
PDF 3 MB Posted
- Solicitation number
- W50SC2-23-R-0001
- Issued by
-
Department of the Army National Guard
About this file
This solicitation is for the construction of an Aircraft Support Equipment (ASE) and Vehicle Maintenance (VM) Facility at Bradley Air National Guard Base in East Granby, Connecticut. Work includes all labor, materials, equipment, tools, supervision and services necessary to construct the facility in accordance with contract drawings and technical specifications. The project magnitude is estimated between $10-25 million. The North American Industry Classification code is 236220 with a small business size standard of $39.5 million average annual revenue. The solicitation allows for unrestricted competition and contemplates a single award. Offerors must submit a proposal on all items or risk rejection. Funding is not presently available but is expected to be appropriated prior to award, as this project is on the National Guard's priority list. No award will be made until funds are released.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 2 3 4
A
B
5 6 7 8 9 10
C
K'
J'
H'
G'
F'
E'
D'
C'
B'
A'
1.5
4.5
10.5
3.5
F
E
J
H
G
D
C.2
9.1
9.2
B.6
5.7
111123
ACCESS PANEL
RETURN AIR GRILLE; REFER TO MECHANICAL
SUPPLY AIR DIFFUSER; REFER TO MECHANICAL
RECESSED CAN DOWNLIGHT (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
2' x 4' HANGING LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
2' x 2' RECESSED LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE; REFER TO ELECTRICAL
STRIP LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
CEILING FIXTURES LEGEND
GYPSUM BOARD CEILING
ACOUSTICAL PANEL CEILING (APC) ASSEMBLY
COVERED OUTDOOR SPACE LIGHT FIXTURE (BLACK FILL
INDICATES EMERGENCY FIXTURE); REFER TO ELECTRICAL
CEILING SPEAKER; REFER TO TELECOM
MANUAL ROLLER SHADE
DUAL BLACKOUT SHADE
LINEAR PENDANT FIXTURE; REFER TO ELECTRICAL
LINEAR LED FIXTURE; REFER TO ELECTRICAL
CEILING MOUNTED SENSORS; REFER TO ELECTRICALOS VSPC
EMERGENCY LIGHTING; REFER TO ELECTRICAL
WALL-MOUNTED LIGHT FIXTURE; REFER TO ELECTRICAL
SECURITY CAMERA; REFER TO TELECOM
EMERGENCY EXIT SIGN; REFER TO ELECTRICAL
FIRE ALARM DEVICE; REFER TO FIRE PROTECTION
GENERAL NOTES
KEYNOTES
1. ALL GYPSUM BOARD AND ACOUSTICAL CEILINGS TO BE 10'-0"
ABOVE FINISH FLOOR UNLESS OTHERWISE NOTED
2. REFER TO PLUMBING, MECHANICAL, ELECTRICAL, FIRE SUPPRESSION, FIRE
ALARM, AND TELECOMMUNICATION DRAWINGS FOR ALL VENTS, SPRINKLER
HEADS, GRILLES, REGISTERS, DIFFUSERS, DUCTS, LIGHT FIXTURES,
DETECTORS, ETC.; COORDINATE THESE ITEMS AS REQUIRED.
3. COORDINATE ALL STRUCTURAL, PLUMBING, MECHANICAL, FIRE
SUPPRESSION, AND ELECTRICAL WORK WITH CEILING HEIGHTS AND
ARCHITECTURAL WORK. WHERE CONFLICTS OCCUR, COORDINATE FINAL
LOCATIONS WITH COR.
4. REFER TO ROOM FINISH SCHEDULE FOR CEILING MATERIALS, FINISHES, AND
HEIGHTS.
5. ALL CEILING-MOUNTED OR RECESSED ITEMS SHOWN - OR NOT - ON
REFLECTED CEILING PLANS (SUCH AS SPRINKLER HEADS, SPEAKERS,
SPEAKER STROBES, GRILLES, LIGHTS, ETC.) SHALL BE CENTERED IN THE LAY-
IN ACT PANELS. AT GYPSUM BOARD CEILINGS, INSTALL IN A CONSISTENT
PATTERN. LOCATE SPRINKLER HEADS IN CONSISTENT PATTERN AS
INDICATED. CEILING MOUNTED ELEMENTS DIMENSIONED TO CENTERLINES
UNLESS OTHERWISE NOTED.
6. NOTIFY COR OF ALL ITEMS NOT SHOWN ON REFLECTED CEILING PLAN AND
LOCATE PER COR DIRECTION.
7. REFER TO TELECOMMUNICATION DRAWINGS FOR CAMERA LOCATIONS.
8. REFER TO DETAILS FOR MECHANICAL, ELECTRICAL, AND PLUMBING ACCESS
PANELS IN A GYPSUM BOARD CEILING.
9. GRID LAYOUT AND LOCATIONS OF LIGHT FIXTURES AND DIFFUSERS ON THE
REFLECTED CEILING PLANS GOVERN OVER ELECTRICAL AND MECHANICAL
DRAWINGS.
10. REFER TO SPECIAL SYSTEMS DRAWINGS FOR SPEAKER TYPES & SIZES,
CAMERA TYPES & SIZES, ETC.
11. ALL CEILING PENETRATIONS SHALL BE TREATED AS PERIMETER CLOSURES
AND SHALL ALLOW A MINIMUM OF 3/8" CLEARANCE BY USE OF SUITABLE
ESCUTCHEONS OR CLOSURE DETAILS.
12. REFER TO A-510 FOR CEILING TRANSITION DETAILS.
N
8' 16' 32'
1/16" = 1'-0"
48'0
A
Designed:
Drawn:
Checked:
Date:
Drawing Title:
Jacobs Project No.:
Key Plan:
D3257200
B
C
D
2 3 4 5
Scales:
THESE DOCUMENTS ARE FOR
INTERIM REVIEW AND NOT FOR
CONSTRUCTION, BIDDING, OR
PERMIT PURPOSES.
Phase: B-3 FINAL DESIGN
C O
N N
E C
T
IC
U T
A
IR
N A
T
IO
N A
L G
U A
R D
R
D A
IR
L
IF
T
W
IN
G
B R
A D
L E
Y A
IR
N
A T
IO
N
L
G
U A
R D
B A
S E
E A
S T
G R
A N
B Y
C
O N
N E
C T
IC
U
T
C O
M P
O S
IT
E
A S
E A
N D
V
M X
S F
A C
IL
IT
Y
Drawing No.:
C
D
A E
S
B
ARCHITECTURAL
B
IM
/U
S C
T D
C
A N
G A
S E
-V M
X S
F a c ili ty /D
C
T A
N G
A
S E
-V M
X S
F A
C
IL
IT
Y
A
R C
H .r v t
/1
/2
:1
:0
P
M
B. HENDON
J. McKINNEY
J. PERRY
03/31/2022
A-130
OVERALL REFLECTED
CEILING PLAN -
ASE/VMXS FACILITY
1/16" = 1'-0"A1
OVERALL REFLECTED CEILING PLAN
111 METAL PANEL-WRAPPED HSS TUBE STEEL TRELLIS STRUCTURE AT OUTDOOR
BREAK AREA; REFER TO STRUCTURAL
123 SHEET METAL FASCIA AND SOFFIT PANELS FORMED BY INSULATED PANEL
MANUFACTURER, TYP.
REV DESCRIPTION DATE
1 AMENDMENT 001 JAN 2023
THESE DOCUMENTS ARE
INTERIM REVIEW AND NO
CONSTRUCTION, BIDDING
PERMIT PURPOSES.
3/31/2201/12/2023
K'
J'
H'
1.5
4.5
MATCHLINE
SEE SHEET A-132
MATCHLINE
SEE SHEET A-132
14' - 0"
14' - 0"
2" / 12"
2" / 12"
126126
ACCESS PANEL
RETURN AIR GRILLE; REFER TO MECHANICAL
SUPPLY AIR DIFFUSER; REFER TO MECHANICAL
RECESSED CAN DOWNLIGHT (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
2' x 4' HANGING LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
2' x 2' RECESSED LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE; REFER TO ELECTRICAL
STRIP LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
CEILING FIXTURES LEGEND
GYPSUM BOARD CEILING
ACOUSTICAL PANEL CEILING (APC) ASSEMBLY
COVERED OUTDOOR SPACE LIGHT FIXTURE (BLACK FILL
INDICATES EMERGENCY FIXTURE); REFER TO ELECTRICAL
CEILING SPEAKER; REFER TO TELECOM
MANUAL ROLLER SHADE
DUAL BLACKOUT SHADE
LINEAR PENDANT FIXTURE; REFER TO ELECTRICAL
LINEAR LED FIXTURE; REFER TO ELECTRICAL
CEILING MOUNTED SENSORS; REFER TO ELECTRICALOS VSPC
EMERGENCY LIGHTING; REFER TO ELECTRICAL
WALL-MOUNTED LIGHT FIXTURE; REFER TO ELECTRICAL
SECURITY CAMERA; REFER TO TELECOM
EMERGENCY EXIT SIGN; REFER TO ELECTRICAL
FIRE ALARM DEVICE; REFER TO FIRE PROTECTION
GENERAL NOTES
KEYNOTES
1. ALL GYPSUM BOARD AND ACOUSTICAL CEILINGS TO BE 10'-0"
ABOVE FINISH FLOOR UNLESS OTHERWISE NOTED
2. REFER TO PLUMBING, MECHANICAL, ELECTRICAL, FIRE SUPPRESSION, FIRE
ALARM, AND TELECOMMUNICATION DRAWINGS FOR ALL VENTS, SPRINKLER
HEADS, GRILLES, REGISTERS, DIFFUSERS, DUCTS, LIGHT FIXTURES,
DETECTORS, ETC.; COORDINATE THESE ITEMS AS REQUIRED.
3. COORDINATE ALL STRUCTURAL, PLUMBING, MECHANICAL, FIRE
SUPPRESSION, AND ELECTRICAL WORK WITH CEILING HEIGHTS AND
ARCHITECTURAL WORK. WHERE CONFLICTS OCCUR, COORDINATE FINAL
LOCATIONS WITH COR.
4. REFER TO ROOM FINISH SCHEDULE FOR CEILING MATERIALS, FINISHES, AND
HEIGHTS.
5. ALL CEILING-MOUNTED OR RECESSED ITEMS SHOWN - OR NOT - ON
REFLECTED CEILING PLANS (SUCH AS SPRINKLER HEADS, SPEAKERS,
SPEAKER STROBES, GRILLES, LIGHTS, ETC.) SHALL BE CENTERED IN THE LAY-
IN ACT PANELS. AT GYPSUM BOARD CEILINGS, INSTALL IN A CONSISTENT
PATTERN. LOCATE SPRINKLER HEADS IN CONSISTENT PATTERN AS
INDICATED. CEILING MOUNTED ELEMENTS DIMENSIONED TO CENTERLINES
UNLESS OTHERWISE NOTED.
6. NOTIFY COR OF ALL ITEMS NOT SHOWN ON REFLECTED CEILING PLAN AND
LOCATE PER COR DIRECTION.
7. REFER TO TELECOMMUNICATION DRAWINGS FOR CAMERA LOCATIONS.
8. REFER TO DETAILS FOR MECHANICAL, ELECTRICAL, AND PLUMBING ACCESS
PANELS IN A GYPSUM BOARD CEILING.
9. GRID LAYOUT AND LOCATIONS OF LIGHT FIXTURES AND DIFFUSERS ON THE
REFLECTED CEILING PLANS GOVERN OVER ELECTRICAL AND MECHANICAL
DRAWINGS.
10. REFER TO SPECIAL SYSTEMS DRAWINGS FOR SPEAKER TYPES & SIZES,
CAMERA TYPES & SIZES, ETC.
11. ALL CEILING PENETRATIONS SHALL BE TREATED AS PERIMETER CLOSURES
AND SHALL ALLOW A MINIMUM OF 3/8" CLEARANCE BY USE OF SUITABLE
ESCUTCHEONS OR CLOSURE DETAILS.
12. REFER TO A-510 FOR CEILING TRANSITION DETAILS.
N
4' 8' 16'
1/8" = 1'-0"
24'0
A
Designed:
Drawn:
Checked:
Date:
Drawing Title:
Jacobs Project No.:
Key Plan:
D3257200
B
C
D
2 3 4 5
Scales:
THESE DOCUMENTS ARE FOR
INTERIM REVIEW AND NOT FOR
CONSTRUCTION, BIDDING, OR
PERMIT PURPOSES.
Phase: B-3 FINAL DESIGN
C O
N N
E C
T
IC
U T
A
IR
N A
T
IO
N A
L G
U A
R D
R
D A
IR
L
IF
T
W
IN
G
B R
A D
L E
Y A
IR
N
A T
IO
N
A
R D
B A
S E
E A
S T
G R
A N
B Y
C
O N
N E
C T
IC
U
T
C O
M P
O S
IT
E
A S
E A
X
S F
A C
IL
IT
Y
Drawing No.:
C
D
A E
S
B
ARCHITECTURAL
B
IM
/U
S C
T D
C
A N
G A
S E
-V M
X S
F a c ili ty /D
C
T A
N G
A
S E
-V M
X S
F A
C
IL
IT
Y
A
R C
H .r v t
/1
/2
:1
:0
P
M
B. HENDON
J. McKINNEY
J. PERRY
03/31/2022
A-131
PARTIAL RCP -
ASE/VMXS FACILITY -
AREA A
1/8" = 1'-0"
A-200
A1
PARTIAL REFLECTED CEILING PLAN - ASE/VMXS FACILITY - AREA A
A-130
113 6"x6" CONTINUOUS SHEET METAL GUTTER, TYP.
123 SHEET METAL FASCIA AND SOFFIT PANELS FORMED BY INSULATED PANEL
MANUFACTURER, TYP.
126 EXPOSED STEEL SUPERSTRUCTURE AND ROOF DECK - PAINTED, TYP.
278 HANGING FAN; REFER TO MECHANICAL AND STRUCTURAL
REV DESCRIPTION DATE
1 AMENDMENT 001 JAN 2023
THESE DOCUMENTS ARE
INTERIM REVIEW AND NO
CONSTRUCTION, BIDDING
T75
PC
PC
OS
2 3 4 5
H'
G'
F'
E'
D'
C'
B'
1.5
4.53.5
MATCHLINE
SEE SHEET A-131
MATCHLINE
SEE SHEET A-133
MATCHLINE
SEE SHEET A-133
MATCHLINE
SEE SHEET A-131
123123
7' - 8"
12' - 0"
16' - 4"
12' - 0"
9' - 0"
B3
A-510
GENERAL NOTES
KEYNOTES
1. ALL GYPSUM BOARD AND ACOUSTICAL CEILINGS TO BE 10'-0"
ABOVE FINISH FLOOR UNLESS OTHERWISE NOTED
2. REFER TO PLUMBING, MECHANICAL, ELECTRICAL, FIRE SUPPRESSION, FIRE
ALARM, AND TELECOMMUNICATION DRAWINGS FOR ALL VENTS, SPRINKLER
HEADS, GRILLES, REGISTERS, DIFFUSERS, DUCTS, LIGHT FIXTURES,
DETECTORS, ETC.; COORDINATE THESE ITEMS AS REQUIRED.
3. COORDINATE ALL STRUCTURAL, PLUMBING, MECHANICAL, FIRE
SUPPRESSION, AND ELECTRICAL WORK WITH CEILING HEIGHTS AND
ARCHITECTURAL WORK. WHERE CONFLICTS OCCUR, COORDINATE FINAL
LOCATIONS WITH COR.
4. REFER TO ROOM FINISH SCHEDULE FOR CEILING MATERIALS, FINISHES, AND
HEIGHTS.
5. ALL CEILING-MOUNTED OR RECESSED ITEMS SHOWN - OR NOT - ON
REFLECTED CEILING PLANS (SUCH AS SPRINKLER HEADS, SPEAKERS,
SPEAKER STROBES, GRILLES, LIGHTS, ETC.) SHALL BE CENTERED IN THE LAY-
IN ACT PANELS. AT GYPSUM BOARD CEILINGS, INSTALL IN A CONSISTENT
PATTERN. LOCATE SPRINKLER HEADS IN CONSISTENT PATTERN AS
INDICATED. CEILING MOUNTED ELEMENTS DIMENSIONED TO CENTERLINES
UNLESS OTHERWISE NOTED.
6. NOTIFY COR OF ALL ITEMS NOT SHOWN ON REFLECTED CEILING PLAN AND
LOCATE PER COR DIRECTION.
7. REFER TO TELECOMMUNICATION DRAWINGS FOR CAMERA LOCATIONS.
8. REFER TO DETAILS FOR MECHANICAL, ELECTRICAL, AND PLUMBING ACCESS
PANELS IN A GYPSUM BOARD CEILING.
9. GRID LAYOUT AND LOCATIONS OF LIGHT FIXTURES AND DIFFUSERS ON THE
REFLECTED CEILING PLANS GOVERN OVER ELECTRICAL AND MECHANICAL
DRAWINGS.
10. REFER TO SPECIAL SYSTEMS DRAWINGS FOR SPEAKER TYPES & SIZES,
CAMERA TYPES & SIZES, ETC.
11. ALL CEILING PENETRATIONS SHALL BE TREATED AS PERIMETER CLOSURES
AND SHALL ALLOW A MINIMUM OF 3/8" CLEARANCE BY USE OF SUITABLE
ESCUTCHEONS OR CLOSURE DETAILS.
12. REFER TO A-510 FOR CEILING TRANSITION DETAILS.
ACCESS PANEL
RETURN AIR GRILLE; REFER TO MECHANICAL
SUPPLY AIR DIFFUSER; REFER TO MECHANICAL
RECESSED CAN DOWNLIGHT (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
2' x 4' HANGING LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
2' x 2' RECESSED LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE; REFER TO ELECTRICAL
STRIP LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
CEILING FIXTURES LEGEND
GYPSUM BOARD CEILING
ACOUSTICAL PANEL CEILING (APC) ASSEMBLY
COVERED OUTDOOR SPACE LIGHT FIXTURE (BLACK FILL
INDICATES EMERGENCY FIXTURE); REFER TO ELECTRICAL
CEILING SPEAKER; REFER TO TELECOM
MANUAL ROLLER SHADE
DUAL BLACKOUT SHADE
LINEAR PENDANT FIXTURE; REFER TO ELECTRICAL
LINEAR LED FIXTURE; REFER TO ELECTRICAL
CEILING MOUNTED SENSORS; REFER TO ELECTRICALOS VSPC
EMERGENCY LIGHTING; REFER TO ELECTRICAL
WALL-MOUNTED LIGHT FIXTURE; REFER TO ELECTRICAL
SECURITY CAMERA; REFER TO TELECOM
EMERGENCY EXIT SIGN; REFER TO ELECTRICAL
FIRE ALARM DEVICE; REFER TO FIRE PROTECTION
N
4' 8' 16'
1/8" = 1'-0"
24'0
A
Designed:
Drawn:
Checked:
Date:
Drawing Title:
Jacobs Project No.:
Key Plan:
D3257200
B
C
D
2 3 4 5
Scales:
THESE DOCUMENTS ARE FOR
INTERIM REVIEW AND NOT FOR
CONSTRUCTION, BIDDING, OR
PERMIT PURPOSES.
Phase: B-3 FINAL DESIGN
C O
N N
E C
T
IC
U T
A
IR
N A
T
IO
N A
L G
U A
R D
R
D A
IR
L
IF
T
W
IN
G
B R
A D
L E
Y A
IR
N
A T
IO
N
A
R D
B A
S E
E A
S T
G R
A N
B Y
C
O N
N E
C T
IC
U
T
C O
M P
O S
IT
E
A S
E A
X
S F
A C
IL
IT
Y
Drawing No.:
C
D
A E
S
B
ARCHITECTURAL
B
IM
/U
S C
T D
C
A N
G A
S E
-V M
X S
F a c ili ty /D
C
T A
N G
A
S E
-V M
X S
F A
C
IL
IT
Y
A
R C
H .r v t
/1
/2
:1
:0
P
M
B. HENDON
J. McKINNEY
J. PERRY
03/31/2022
A-132
PARTIAL RCP -
ASE/VMXS FACILITY -
AREA B
1/8" = 1'-0"
A-200
A1
PARTIAL REFLECTED CEILING PLAN - ASE/VMXS FACILITY - AREA B
A-130
113 6"x6" CONTINUOUS SHEET METAL GUTTER, TYP.
117 MECHANICAL EQUIPMENT; REFER TO MECHANICAL
120 5-TON BRIDGE CRANE; REFER TO STRUCTURE FOR STEEL SUPPORT FRAMING.
REFER TO EQUIPMENT DRAWINGS.
123 SHEET METAL FASCIA AND SOFFIT PANELS FORMED BY INSULATED PANEL
MANUFACTURER, TYP.
272 VEHICLE EXHAUST SYSTEM; REFER TO MECHANICAL
278 HANGING FAN; REFER TO MECHANICAL AND STRUCTURAL
REV DESCRIPTION DATE
1 AMENDMENT 001 JAN 2023
THESE DOCUMENTS ARE
INTERIM REVIEW AND NO
CONSTRUCTION, BIDDING
OS
OSOSOS
OS
VS
VS
VS
VS
VS VS
VS VS VS
VS VS
OSOSOSOSOS
OS
OS
VS
OS
T75
PC
PC PC PC PC
PC PC PC
OS
OS
VS
VS
1 2 3 4
A
B
5 6 7 8 9
C
B'
A'
1.5
3.5
MATCHLINE
SEE SHEET A-132
M A
T C
H L
IN
E
S E
E S
H E
E T
A -1
C.2
9.1
B.6
5.7
14'-0"
14'-0"
11'-0"
9'-0"
8'-0"
12'-0"
9'-0"
9'-0"
9'-0"
9'-0"
7'-4"
9'-0"
9'-0"
123123
123123
111111
123 113
A3
A-510
B3
A-511
PT-3
6'-0"
PT-3
MATCHLINE
SEE SHEET A-132
5' - 1" 3' - 0"
2' - 0"
3' - 0"
1' - 10" 1' - 6"
2' - 1"
2' - 1"
1' - 2"
1' - 0"
7' - 8" 1
EQ
5' - 1"
EQ
E Q
E Q
EQ EQ
EQ EQ
EQ EQ
E Q
E Q
9' - 0"
E Q
E Q
/2
5" 4' - 0" 4' - 0"
2' - 0"
1' - 8"
1' - 9"
2' - 7"
EQEQ
1' - 8" 1' - 6"
EQ
EQ
2' - 7" 1' - 9"
1' - 5" 1' - 10" 2' - 7"
3' - 2"
3' - 0"
1' - 10" 2' - 2" 2' - 0"
B3
A-510
GENERAL NOTES
KEYNOTES
1. ALL GYPSUM BOARD AND ACOUSTICAL CEILINGS TO BE 10'-0"
ABOVE FINISH FLOOR UNLESS OTHERWISE NOTED
2. REFER TO PLUMBING, MECHANICAL, ELECTRICAL, FIRE SUPPRESSION, FIRE
ALARM, AND TELECOMMUNICATION DRAWINGS FOR ALL VENTS, SPRINKLER
HEADS, GRILLES, REGISTERS, DIFFUSERS, DUCTS, LIGHT FIXTURES,
DETECTORS, ETC.; COORDINATE THESE ITEMS AS REQUIRED.
3. COORDINATE ALL STRUCTURAL, PLUMBING, MECHANICAL, FIRE
SUPPRESSION, AND ELECTRICAL WORK WITH CEILING HEIGHTS AND
ARCHITECTURAL WORK. WHERE CONFLICTS OCCUR, COORDINATE FINAL
LOCATIONS WITH COR.
4. REFER TO ROOM FINISH SCHEDULE FOR CEILING MATERIALS, FINISHES, AND
HEIGHTS.
5. ALL CEILING-MOUNTED OR RECESSED ITEMS SHOWN - OR NOT - ON
REFLECTED CEILING PLANS (SUCH AS SPRINKLER HEADS, SPEAKERS,
SPEAKER STROBES, GRILLES, LIGHTS, ETC.) SHALL BE CENTERED IN THE LAY-
IN ACT PANELS. AT GYPSUM BOARD CEILINGS, INSTALL IN A CONSISTENT
PATTERN. LOCATE SPRINKLER HEADS IN CONSISTENT PATTERN AS
INDICATED. CEILING MOUNTED ELEMENTS DIMENSIONED TO CENTERLINES
UNLESS OTHERWISE NOTED.
6. NOTIFY COR OF ALL ITEMS NOT SHOWN ON REFLECTED CEILING PLAN AND
LOCATE PER COR DIRECTION.
7. REFER TO TELECOMMUNICATION DRAWINGS FOR CAMERA LOCATIONS.
8. REFER TO DETAILS FOR MECHANICAL, ELECTRICAL, AND PLUMBING ACCESS
PANELS IN A GYPSUM BOARD CEILING.
9. GRID LAYOUT AND LOCATIONS OF LIGHT FIXTURES AND DIFFUSERS ON THE
REFLECTED CEILING PLANS GOVERN OVER ELECTRICAL AND MECHANICAL
DRAWINGS.
10. REFER TO SPECIAL SYSTEMS DRAWINGS FOR SPEAKER TYPES & SIZES,
CAMERA TYPES & SIZES, ETC.
11. ALL CEILING PENETRATIONS SHALL BE TREATED AS PERIMETER CLOSURES
AND SHALL ALLOW A MINIMUM OF 3/8" CLEARANCE BY USE OF SUITABLE
ESCUTCHEONS OR CLOSURE DETAILS.
12. REFER TO A-510 FOR CEILING TRANSITION DETAILS.
ACCESS PANEL
RETURN AIR GRILLE; REFER TO MECHANICAL
SUPPLY AIR DIFFUSER; REFER TO MECHANICAL
RECESSED CAN DOWNLIGHT (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
2' x 4' HANGING LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
2' x 2' RECESSED LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE; REFER TO ELECTRICAL
STRIP LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
CEILING FIXTURES LEGEND
GYPSUM BOARD CEILING
ACOUSTICAL PANEL CEILING (APC) ASSEMBLY
COVERED OUTDOOR SPACE LIGHT FIXTURE (BLACK FILL
INDICATES EMERGENCY FIXTURE); REFER TO ELECTRICAL
CEILING SPEAKER; REFER TO TELECOM
MANUAL ROLLER SHADE
DUAL BLACKOUT SHADE
LINEAR PENDANT FIXTURE; REFER TO ELECTRICAL
LINEAR LED FIXTURE; REFER TO ELECTRICAL
CEILING MOUNTED SENSORS; REFER TO ELECTRICALOS VSPC
EMERGENCY LIGHTING; REFER TO ELECTRICAL
WALL-MOUNTED LIGHT FIXTURE; REFER TO ELECTRICAL
SECURITY CAMERA; REFER TO TELECOM
EMERGENCY EXIT SIGN; REFER TO ELECTRICAL
FIRE ALARM DEVICE; REFER TO FIRE PROTECTION
N
4' 8' 16'
1/8" = 1'-0"
24'0
A
Designed:
Drawn:
Checked:
Date:
Drawing Title:
Jacobs Project No.:
Key Plan:
D3257200
B
C
D
2 3 4 5
Scales:
THESE DOCUMENTS ARE FOR
INTERIM REVIEW AND NOT FOR
CONSTRUCTION, BIDDING, OR
PERMIT PURPOSES.
Phase: B-3 FINAL DESIGN
C O
N N
E C
T
IC
U T
A
IR
N A
T
IO
N A
L G
U A
R D
R
D A
IR
L
IF
T
W
IN
G
B R
A D
L E
Y A
IR
N
A T
IO
N
A
R D
B A
S E
E A
S T
G R
A N
B Y
C
O N
N E
C T
IC
U
T
C O
M P
O S
IT
E
A S
E A
X
S F
A C
IL
IT
Y
Drawing No.:
C
D
A E
S
B
ARCHITECTURAL
B
IM
/U
S C
T D
C
A N
G A
S E
-V M
X S
F a c ili ty /D
C
T A
N G
A
S E
-V M
X S
F A
C
IL
IT
Y
A
R C
H .r v t
/1
/2
:1
:0
P
M
B. HENDON
J. McKINNEY
J. PERRY
03/31/2022
A-133
PARTIAL RCP -
ASE/VMXS FACILITY -
AREA C
1/8" = 1'-0"
A-200
A1
PARTIAL REFLECTED CEILING PLAN - ASE/VMXS FACILITY - AREA C
A-130
111 METAL PANEL-WRAPPED HSS TUBE STEEL TRELLIS STRUCTURE AT OUTDOOR
BREAK AREA; REFER TO STRUCTURAL
113 6"x6" CONTINUOUS SHEET METAL GUTTER, TYP.
123 SHEET METAL FASCIA AND SOFFIT PANELS FORMED BY INSULATED PANEL
MANUFACTURER, TYP.
199 OPERABLE PARTITION; REFER TO A-510 FOR DETAILS. COORDINATE WITH
STRUCTURAL TO HANG PARTITION TRACK FROM STRUCTURAL FRAMING.
PT-3 PAINT COLOR 3; REFER TO INTERIOR MATERIALS INDEX FOR BASIS OF DESIGN
REV DESCRIPTION DATE
1 AMENDMENT 001 JAN 2023
THESE DOCUMENTS ARE
INTERIM REVIEW AND NO
CONSTRUCTION, BIDDING
VS
VS
OSOS
O S
A
B
C
10.5
M A
T C
H L
IN
E
S E
E S
H E
E T
A -1
MATCHLINE
SEE SHEET A-135
F
E
G
D
C.2
9.1 9.2
12'-0"
9'-0"
123123
MATCHLINE
SEE SHEET A-135
EQ EQ
E Q
E Q
12' - 0" 16' - 0" 12' - 0"
"2' - 0"
117117
4' - 0" 6' - 4" 4' - 0"
3' - 8"
3' - 8"
126126
12' - 0" 16' - 0" 12' - 0"
GENERAL NOTES
KEYNOTES
1. ALL GYPSUM BOARD AND ACOUSTICAL CEILINGS TO BE 10'-0"
ABOVE FINISH FLOOR UNLESS OTHERWISE NOTED
2. REFER TO PLUMBING, MECHANICAL, ELECTRICAL, FIRE SUPPRESSION, FIRE
ALARM, AND TELECOMMUNICATION DRAWINGS FOR ALL VENTS, SPRINKLER
HEADS, GRILLES, REGISTERS, DIFFUSERS, DUCTS, LIGHT FIXTURES,
DETECTORS, ETC.; COORDINATE THESE ITEMS AS REQUIRED.
3. COORDINATE ALL STRUCTURAL, PLUMBING, MECHANICAL, FIRE
SUPPRESSION, AND ELECTRICAL WORK WITH CEILING HEIGHTS AND
ARCHITECTURAL WORK. WHERE CONFLICTS OCCUR, COORDINATE FINAL
LOCATIONS WITH COR.
4. REFER TO ROOM FINISH SCHEDULE FOR CEILING MATERIALS, FINISHES, AND
HEIGHTS.
5. ALL CEILING-MOUNTED OR RECESSED ITEMS SHOWN - OR NOT - ON
REFLECTED CEILING PLANS (SUCH AS SPRINKLER HEADS, SPEAKERS,
SPEAKER STROBES, GRILLES, LIGHTS, ETC.) SHALL BE CENTERED IN THE LAY-
IN ACT PANELS. AT GYPSUM BOARD CEILINGS, INSTALL IN A CONSISTENT
PATTERN. LOCATE SPRINKLER HEADS IN CONSISTENT PATTERN AS
INDICATED. CEILING MOUNTED ELEMENTS DIMENSIONED TO CENTERLINES
UNLESS OTHERWISE NOTED.
6. NOTIFY COR OF ALL ITEMS NOT SHOWN ON REFLECTED CEILING PLAN AND
LOCATE PER COR DIRECTION.
7. REFER TO TELECOMMUNICATION DRAWINGS FOR CAMERA LOCATIONS.
8. REFER TO DETAILS FOR MECHANICAL, ELECTRICAL, AND PLUMBING ACCESS
PANELS IN A GYPSUM BOARD CEILING.
9. GRID LAYOUT AND LOCATIONS OF LIGHT FIXTURES AND DIFFUSERS ON THE
REFLECTED CEILING PLANS GOVERN OVER ELECTRICAL AND MECHANICAL
DRAWINGS.
10. REFER TO SPECIAL SYSTEMS DRAWINGS FOR SPEAKER TYPES & SIZES,
CAMERA TYPES & SIZES, ETC.
11. ALL CEILING PENETRATIONS SHALL BE TREATED AS PERIMETER CLOSURES
AND SHALL ALLOW A MINIMUM OF 3/8" CLEARANCE BY USE OF SUITABLE
ESCUTCHEONS OR CLOSURE DETAILS.
12. REFER TO A-510 FOR CEILING TRANSITION DETAILS.
ACCESS PANEL
RETURN AIR GRILLE; REFER TO MECHANICAL
SUPPLY AIR DIFFUSER; REFER TO MECHANICAL
RECESSED CAN DOWNLIGHT (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
2' x 4' HANGING LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
2' x 2' RECESSED LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE; REFER TO ELECTRICAL
STRIP LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
CEILING FIXTURES LEGEND
GYPSUM BOARD CEILING
ACOUSTICAL PANEL CEILING (APC) ASSEMBLY
COVERED OUTDOOR SPACE LIGHT FIXTURE (BLACK FILL
INDICATES EMERGENCY FIXTURE); REFER TO ELECTRICAL
CEILING SPEAKER; REFER TO TELECOM
MANUAL ROLLER SHADE
DUAL BLACKOUT SHADE
LINEAR PENDANT FIXTURE; REFER TO ELECTRICAL
LINEAR LED FIXTURE; REFER TO ELECTRICAL
CEILING MOUNTED SENSORS; REFER TO ELECTRICALOS VSPC
EMERGENCY LIGHTING; REFER TO ELECTRICAL
WALL-MOUNTED LIGHT FIXTURE; REFER TO ELECTRICAL
SECURITY CAMERA; REFER TO TELECOM
EMERGENCY EXIT SIGN; REFER TO ELECTRICAL
FIRE ALARM DEVICE; REFER TO FIRE PROTECTION
N
4' 8' 16'
1/8" = 1'-0"
24'0
A
Designed:
Drawn:
Checked:
Date:
Drawing Title:
Jacobs Project No.:
Key Plan:
D3257200
B
C
D
2 3 4 5
Scales:
THESE DOCUMENTS ARE FOR
INTERIM REVIEW AND NOT FOR
CONSTRUCTION, BIDDING, OR
PERMIT PURPOSES.
Phase: B-3 FINAL DESIGN
C O
N N
E C
T
IC
U T
A
IR
N A
T
IO
N A
L G
U A
R D
R
D A
IR
L
IF
T
W
IN
G
B R
A D
L E
Y A
IR
N
A T
IO
N
A
R D
B A
S E
E A
S T
G R
A N
B Y
C
O N
N E
C T
IC
U
T
C O
M P
O S
IT
E
A S
E A
X
S F
A C
IL
IT
Y
Drawing No.:
C
D
A E
S
B
ARCHITECTURAL
B
IM
/U
S C
T D
C
A N
G A
S E
-V M
X S
F a c ili ty /D
C
T A
N G
A
S E
-V M
X S
F A
C
IL
IT
Y
A
R C
H .r v t
/1
/2
:1
:1
P
M
B. HENDON
J. McKINNEY
J. PERRY
03/31/2022
A-134
PARTIAL RCP -
ASE/VMXS FACILITY -
AREA D
1/8" = 1'-0"
A-200
A1
PARTIAL REFLECTED CEILING PLAN - ASE/VMXS FACILITY - AREA D
A-130
103 VINYL COVERED CHAIN-LINK ENCLOSURE WITH GATE; REFER TO A-545 FOR
CHAIN LINK ENCLOSURE DETAILS
108 STAINLESS STEEL ROOF ACCESS LADDER WITH OSHA COMPLIANT RAIL &
HARNESS FALL ARREST SYSTEM AS SPECIFIED; REFER TO SHEET A-541 & A-542
113 6"x6" CONTINUOUS SHEET METAL GUTTER, TYP.
117 MECHANICAL EQUIPMENT; REFER TO MECHANICAL
121 OLI - 3-TON BRIDGE CRANE; REFER TO STRUCTURE FOR STEEL SUPPORT
FRAMING. REFER TO EQUIPMENT DRAWINGS.
123 SHEET METAL FASCIA AND SOFFIT PANELS FORMED BY INSULATED PANEL
MANUFACTURER, TYP.
126 EXPOSED STEEL SUPERSTRUCTURE AND ROOF DECK - PAINTED, TYP.
272 VEHICLE EXHAUST SYSTEM; REFER TO MECHANICAL
276 FALL PROTECTION SUPPORT; REFER TO STRUCTURAL
278 HANGING FAN; REFER TO MECHANICAL AND STRUCTURAL
314 FALL ARREST SYSTEM TRACK; REFER TO STRUCTURAL AND EQUIPMENT FOR
ADDITIONAL INFORMATION
315 UNIT HEATER; REFER TO MECHANICAL
REV DESCRIPTION DATE
1 AMENDMENT 001 JAN 2023
THESE DOCUMENTS ARE
INTERIM REVIEW AND NO
CONSTRUCTION, BIDDING
PC
10 10.5
J
H
G
9.1
MATCHLINE
SEE SHEET A-134
MATCHLINE
SEE SHEET A-134
314314 117
126126
117117
5' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0" 5' - 0"
10' - 0" 10' - 0" 10' - 0" 10' - 0" 5' - 0"
5' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0" 5' - 0"
REFUELING
VEHICLE
SHOP
WASH
RACK
GENERAL NOTES
KEYNOTES
1. ALL GYPSUM BOARD AND ACOUSTICAL CEILINGS TO BE 10'-0"
ABOVE FINISH FLOOR UNLESS OTHERWISE NOTED
2. REFER TO PLUMBING, MECHANICAL, ELECTRICAL, FIRE SUPPRESSION, FIRE
ALARM, AND TELECOMMUNICATION DRAWINGS FOR ALL VENTS, SPRINKLER
HEADS, GRILLES, REGISTERS, DIFFUSERS, DUCTS, LIGHT FIXTURES,
DETECTORS, ETC.; COORDINATE THESE ITEMS AS REQUIRED.
3. COORDINATE ALL STRUCTURAL, PLUMBING, MECHANICAL, FIRE
SUPPRESSION, AND ELECTRICAL WORK WITH CEILING HEIGHTS AND
ARCHITECTURAL WORK. WHERE CONFLICTS OCCUR, COORDINATE FINAL
LOCATIONS WITH COR.
4. REFER TO ROOM FINISH SCHEDULE FOR CEILING MATERIALS, FINISHES, AND
HEIGHTS.
5. ALL CEILING-MOUNTED OR RECESSED ITEMS SHOWN - OR NOT - ON
REFLECTED CEILING PLANS (SUCH AS SPRINKLER HEADS, SPEAKERS,
SPEAKER STROBES, GRILLES, LIGHTS, ETC.) SHALL BE CENTERED IN THE LAY-
IN ACT PANELS. AT GYPSUM BOARD CEILINGS, INSTALL IN A CONSISTENT
PATTERN. LOCATE SPRINKLER HEADS IN CONSISTENT PATTERN AS
INDICATED. CEILING MOUNTED ELEMENTS DIMENSIONED TO CENTERLINES
UNLESS OTHERWISE NOTED.
6. NOTIFY COR OF ALL ITEMS NOT SHOWN ON REFLECTED CEILING PLAN AND
LOCATE PER COR DIRECTION.
7. REFER TO TELECOMMUNICATION DRAWINGS FOR CAMERA LOCATIONS.
8. REFER TO DETAILS FOR MECHANICAL, ELECTRICAL, AND PLUMBING ACCESS
PANELS IN A GYPSUM BOARD CEILING.
9. GRID LAYOUT AND LOCATIONS OF LIGHT FIXTURES AND DIFFUSERS ON THE
REFLECTED CEILING PLANS GOVERN OVER ELECTRICAL AND MECHANICAL
DRAWINGS.
10. REFER TO SPECIAL SYSTEMS DRAWINGS FOR SPEAKER TYPES & SIZES,
CAMERA TYPES & SIZES, ETC.
11. ALL CEILING PENETRATIONS SHALL BE TREATED AS PERIMETER CLOSURES
AND SHALL ALLOW A MINIMUM OF 3/8" CLEARANCE BY USE OF SUITABLE
ESCUTCHEONS OR CLOSURE DETAILS.
12. REFER TO A-510 FOR CEILING TRANSITION DETAILS.
ACCESS PANEL
RETURN AIR GRILLE; REFER TO MECHANICAL
SUPPLY AIR DIFFUSER; REFER TO MECHANICAL
RECESSED CAN DOWNLIGHT (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
2' x 4' HANGING LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
2' x 2' RECESSED LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE; REFER TO ELECTRICAL
STRIP LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
CEILING FIXTURES LEGEND
GYPSUM BOARD CEILING
ACOUSTICAL PANEL CEILING (APC) ASSEMBLY
COVERED OUTDOOR SPACE LIGHT FIXTURE (BLACK FILL
INDICATES EMERGENCY FIXTURE); REFER TO ELECTRICAL
CEILING SPEAKER; REFER TO TELECOM
MANUAL ROLLER SHADE
DUAL BLACKOUT SHADE
LINEAR PENDANT FIXTURE; REFER TO ELECTRICAL
LINEAR LED FIXTURE; REFER TO ELECTRICAL
CEILING MOUNTED SENSORS; REFER TO ELECTRICALOS VSPC
EMERGENCY LIGHTING; REFER TO ELECTRICAL
WALL-MOUNTED LIGHT FIXTURE; REFER TO ELECTRICAL
SECURITY CAMERA; REFER TO TELECOM
EMERGENCY EXIT SIGN; REFER TO ELECTRICAL
FIRE ALARM DEVICE; REFER TO FIRE PROTECTION
N
4' 8' 16'
1/8" = 1'-0"
24'0
A
Designed:
Drawn:
Checked:
Date:
Drawing Title:
Jacobs Project No.:
Key Plan:
D3257200
B
C
D
2 3 4 5
Scales:
THESE DOCUMENTS ARE FOR
INTERIM REVIEW AND NOT FOR
CONSTRUCTION, BIDDING, OR
PERMIT PURPOSES.
Phase: B-3 FINAL DESIGN
C O
N N
E C
T
IC
U T
A
IR
N A
T
IO
N A
L G
U A
R D
R
D A
IR
L
IF
T
W
IN
G
B R
A D
L E
Y A
IR
N
A T
IO
N
A
R D
B A
S E
E A
S T
G R
A N
B Y
C
O N
N E
C T
IC
U
T
C O
M P
O S
IT
E
A S
E A
X
S F
A C
IL
IT
Y
Drawing No.:
C
D
A E
S
B
ARCHITECTURAL
B
IM
/U
S C
T D
C
A N
G A
S E
-V M
X S
F a c ili ty /D
C
T A
N G
A
S E
-V M
X S
F A
C
IL
IT
Y
A
R C
H .r v t
/1
/2
:1
:1
P
M
B. HENDON
J. McKINNEY
J. PERRY
03/31/2022
A-135
PARTIAL RCP -
ASE/VMXS FACILITY -
AREA E
1/8" = 1'-0"
A-200
A1
PARTIAL REFLECTED CEILING PLAN - ASE/VMXS FACILITY - AREA E
A-130
113 6"x6" CONTINUOUS SHEET METAL GUTTER, TYP.
117 MECHANICAL EQUIPMENT; REFER TO MECHANICAL
123 SHEET METAL FASCIA AND SOFFIT PANELS FORMED BY INSULATED PANEL
MANUFACTURER, TYP.
126 EXPOSED STEEL SUPERSTRUCTURE AND ROOF DECK - PAINTED, TYP.
276 FALL PROTECTION SUPPORT; REFER TO STRUCTURAL
314 FALL ARREST SYSTEM TRACK; REFER TO STRUCTURAL AND EQUIPMENT FOR
ADDITIONAL INFORMATION
315 UNIT HEATER; REFER TO MECHANICAL
REV DESCRIPTION DATE
1 AMENDMENT 001 JAN 2023
THESE DOCUMENTS ARE
INTERIM REVIEW AND NO
CONSTRUCTION, BIDDING
S1 S2 S3 S4 S5
SB
SA
S7S6
12' - 3 1/2" 24' - 0" 24' - 0" 23' - 9" 11' - 1"
12' - 0" 24' - 0" 12' - 0"
E Q
E Q
OLI
23' - 0"
BASE BID
121' - 0"
161161
COVERED
VEHICLE
OPS
PARKING
S102
HEATED
VEHICLE
OPS
STORAGE
S101
GENERAL NOTES
KEYNOTES
1. ALL GYPSUM BOARD AND ACOUSTICAL CEILINGS TO BE 10'-0"
ABOVE FINISH FLOOR UNLESS OTHERWISE NOTED
2. REFER TO PLUMBING, MECHANICAL, ELECTRICAL, FIRE SUPPRESSION, FIRE
ALARM, AND TELECOMMUNICATION DRAWINGS FOR ALL VENTS, SPRINKLER
HEADS, GRILLES, REGISTERS, DIFFUSERS, DUCTS, LIGHT FIXTURES,
DETECTORS, ETC.; COORDINATE THESE ITEMS AS REQUIRED.
3. COORDINATE ALL STRUCTURAL, PLUMBING, MECHANICAL, FIRE
SUPPRESSION, AND ELECTRICAL WORK WITH CEILING HEIGHTS AND
ARCHITECTURAL WORK. WHERE CONFLICTS OCCUR, COORDINATE FINAL
LOCATIONS WITH COR.
4. REFER TO ROOM FINISH SCHEDULE FOR CEILING MATERIALS, FINISHES, AND
HEIGHTS.
5. ALL CEILING-MOUNTED OR RECESSED ITEMS SHOWN - OR NOT - ON
REFLECTED CEILING PLANS (SUCH AS SPRINKLER HEADS, SPEAKERS,
SPEAKER STROBES, GRILLES, LIGHTS, ETC.) SHALL BE CENTERED IN THE LAY-
IN ACT PANELS. AT GYPSUM BOARD CEILINGS, INSTALL IN A CONSISTENT
PATTERN. LOCATE SPRINKLER HEADS IN CONSISTENT PATTERN AS
INDICATED. CEILING MOUNTED ELEMENTS DIMENSIONED TO CENTERLINES
UNLESS OTHERWISE NOTED.
6. NOTIFY COR OF ALL ITEMS NOT SHOWN ON REFLECTED CEILING PLAN AND
LOCATE PER COR DIRECTION.
7. REFER TO TELECOMMUNICATION DRAWINGS FOR CAMERA LOCATIONS.
8. REFER TO DETAILS FOR MECHANICAL, ELECTRICAL, AND PLUMBING ACCESS
PANELS IN A GYPSUM BOARD CEILING.
9. GRID LAYOUT AND LOCATIONS OF LIGHT FIXTURES AND DIFFUSERS ON THE
REFLECTED CEILING PLANS GOVERN OVER ELECTRICAL AND MECHANICAL
DRAWINGS.
10. REFER TO SPECIAL SYSTEMS DRAWINGS FOR SPEAKER TYPES & SIZES,
CAMERA TYPES & SIZES, ETC.
11. ALL CEILING PENETRATIONS SHALL BE TREATED AS PERIMETER CLOSURES
AND SHALL ALLOW A MINIMUM OF 3/8" CLEARANCE BY USE OF SUITABLE
ESCUTCHEONS OR CLOSURE DETAILS.
12. REFER TO A-510 FOR CEILING TRANSITION DETAILS.
ACCESS PANEL
RETURN AIR GRILLE; REFER TO MECHANICAL
SUPPLY AIR DIFFUSER; REFER TO MECHANICAL
RECESSED CAN DOWNLIGHT (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
2' x 4' HANGING LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
2' x 2' RECESSED LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE; REFER TO ELECTRICAL
STRIP LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
CEILING FIXTURES LEGEND
GYPSUM BOARD CEILING
ACOUSTICAL PANEL CEILING (APC) ASSEMBLY
COVERED OUTDOOR SPACE LIGHT FIXTURE (BLACK FILL
INDICATES EMERGENCY FIXTURE); REFER TO ELECTRICAL
CEILING SPEAKER; REFER TO TELECOM
MANUAL ROLLER SHADE
DUAL BLACKOUT SHADE
LINEAR PENDANT FIXTURE; REFER TO ELECTRICAL
LINEAR LED FIXTURE; REFER TO ELECTRICAL
CEILING MOUNTED SENSORS; REFER TO ELECTRICALOS VSPC
EMERGENCY LIGHTING; REFER TO ELECTRICAL
WALL-MOUNTED LIGHT FIXTURE; REFER TO ELECTRICAL
SECURITY CAMERA; REFER TO TELECOM
EMERGENCY EXIT SIGN; REFER TO ELECTRICAL
FIRE ALARM DEVICE; REFER TO FIRE PROTECTION
N
4' 8' 16'
1/8" = 1'-0"
24'0
A
Designed:
Drawn:
Checked:
Date:
Drawing Title:
Jacobs Project No.:
Key Plan:
D3257200
B
C
D
2 3 4 5
Scales:
THESE DOCUMENTS ARE FOR
INTERIM REVIEW AND NOT FOR
CONSTRUCTION, BIDDING, OR
PERMIT PURPOSES.
Phase: B-3 FINAL DESIGN
C O
N N
E C
T
IC
U T
A
IR
N A
T
IO
N A
L G
U A
R D
R
D A
IR
L
IF
T
W
IN
G
B R
A D
L E
Y A
IR
N
A T
IO
N
A
R D
B A
S E
E A
S T
G R
A N
B Y
C
O N
N E
C T
IC
U
T
C O
M P
O S
IT
E
A S
E A
X
S F
A C
IL
IT
Y
Drawing No.:
C
D
A E
S
B
ARCHITECTURAL
B
IM
/U
S C
T D
C
A N
G A
S E
-V M
X S
F a c ili ty /D
C
T A
N G
A
S E
-V M
X S
F A
C
IL
IT
Y
A
R C
H .r v t
/1
/2
:1
:1
P
M
B. HENDON
J. McKINNEY
J. PERRY
03/31/2022
A-136
PARTIAL RCP -
VEHICLE OPS PARKING
BUILDING
1/8" = 1'-0"A1
REFLECTED CEILING PLAN - VEHICLE OPS PARKING BUILDING
117 MECHANICAL EQUIPMENT; REFER TO MECHANICAL
126 EXPOSED STEEL SUPERSTRUCTURE AND ROOF DECK - PAINTED, TYP.
136 GALVANIZED STEEL ACCESS LADDER WITH OSHA COMPLIANT RAIL & HARNESS
FALL ARREST SYSTEM; REFER TO A-541 & A-542
161 OLI - ADD ADDITIONAL BAY OF COVERED PARKING
315 UNIT HEATER; REFER TO MECHANICAL
REV DESCRIPTION DATE
1 AMENDMENT 001 JAN 2023
THESE DOCUMENTS ARE
INTERIM REVIEW AND NO
CONSTRUCTION, BIDDING
F'
1.5
4.5
L'
G'
H'
J'
K'
8' - 0"
8' - 0"
8' - 0"
8' - 0"
ASE
STORAGE
WASH
RACK
ASE
MAINTENANCE
AND
REPAIR
GENERAL NOTES
KEYNOTES
1. ALL GYPSUM BOARD AND ACOUSTICAL CEILINGS TO BE 10'-0"
ABOVE FINISH FLOOR UNLESS OTHERWISE NOTED
2. REFER TO PLUMBING, MECHANICAL, ELECTRICAL, FIRE SUPPRESSION, FIRE
ALARM, AND TELECOMMUNICATION DRAWINGS FOR ALL VENTS, SPRINKLER
HEADS, GRILLES, REGISTERS, DIFFUSERS, DUCTS, LIGHT FIXTURES,
DETECTORS, ETC.; COORDINATE THESE ITEMS AS REQUIRED.
3. COORDINATE ALL STRUCTURAL, PLUMBING, MECHANICAL, FIRE
SUPPRESSION, AND ELECTRICAL WORK WITH CEILING HEIGHTS AND
ARCHITECTURAL WORK. WHERE CONFLICTS OCCUR, COORDINATE FINAL
LOCATIONS WITH COR.
4. REFER TO ROOM FINISH SCHEDULE FOR CEILING MATERIALS, FINISHES, AND
HEIGHTS.
5. ALL CEILING-MOUNTED OR RECESSED ITEMS SHOWN - OR NOT - ON
REFLECTED CEILING PLANS (SUCH AS SPRINKLER HEADS, SPEAKERS,
SPEAKER STROBES, GRILLES, LIGHTS, ETC.) SHALL BE CENTERED IN THE LAY-
IN ACT PANELS. AT GYPSUM BOARD CEILINGS, INSTALL IN A CONSISTENT
PATTERN. LOCATE SPRINKLER HEADS IN CONSISTENT PATTERN AS
INDICATED. CEILING MOUNTED ELEMENTS DIMENSIONED TO CENTERLINES
UNLESS OTHERWISE NOTED.
6. NOTIFY COR OF ALL ITEMS NOT SHOWN ON REFLECTED CEILING PLAN AND
LOCATE PER COR DIRECTION.
7. REFER TO TELECOMMUNICATION DRAWINGS FOR CAMERA LOCATIONS.
8. REFER TO DETAILS FOR MECHANICAL, ELECTRICAL, AND PLUMBING ACCESS
PANELS IN A GYPSUM BOARD CEILING.
9. GRID LAYOUT AND LOCATIONS OF LIGHT FIXTURES AND DIFFUSERS ON THE
REFLECTED CEILING PLANS GOVERN OVER ELECTRICAL AND MECHANICAL
DRAWINGS.
10. REFER TO SPECIAL SYSTEMS DRAWINGS FOR SPEAKER TYPES & SIZES,
CAMERA TYPES & SIZES, ETC.
11. ALL CEILING PENETRATIONS SHALL BE TREATED AS PERIMETER CLOSURES
AND SHALL ALLOW A MINIMUM OF 3/8" CLEARANCE BY USE OF SUITABLE
ESCUTCHEONS OR CLOSURE DETAILS.
12. REFER TO A-510 FOR CEILING TRANSITION DETAILS.
ACCESS PANEL
RETURN AIR GRILLE; REFER TO MECHANICAL
SUPPLY AIR DIFFUSER; REFER TO MECHANICAL
RECESSED CAN DOWNLIGHT (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
2' x 4' HANGING LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
2' x 2' RECESSED LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE; REFER TO ELECTRICAL
STRIP LIGHT FIXTURE (BLACK FILL INDICATES
EMERGENCY FIXTURE); REFER TO ELECTRICAL
CEILING FIXTURES LEGEND
GYPSUM BOARD CEILING
ACOUSTICAL PANEL CEILING (APC) ASSEMBLY
COVERED OUTDOOR SPACE LIGHT FIXTURE (BLACK FILL
INDICATES EMERGENCY FIXTURE); REFER TO ELECTRICAL
CEILING SPEAKER; REFER TO TELECOM
MANUAL ROLLER SHADE
DUAL BLACKOUT SHADE
LINEAR PENDANT FIXTURE; REFER TO ELECTRICAL
LINEAR LED FIXTURE; REFER TO ELECTRICAL
CEILING MOUNTED SENSORS; REFER TO ELECTRICALOS VSPC
EMERGENCY LIGHTING; REFER TO ELECTRICAL
WALL-MOUNTED LIGHT FIXTURE; REFER TO ELECTRICAL
SECURITY CAMERA; REFER TO TELECOM
EMERGENCY EXIT SIGN; REFER TO ELECTRICAL
FIRE ALARM DEVICE; REFER TO FIRE PROTECTION
N
A
Designed:
Drawn:
Checked:
Date:
Drawing Title:
Jacobs Project No.:
Key Plan:
D3257200
B
C
D
2 3 4 5
Scales:
THESE DOCUMENTS ARE FOR
INTERIM REVIEW AND NOT FOR
CONSTRUCTION, BIDDING, OR
PERMIT PURPOSES.
AS INDICATED
Phase: B-3 FINAL DESIGN
C O
N N
E C
T
IC
U T
A
IR
N A
T
IO
N A
L G
U A
R D
R
D A
IR
L
IF
T
W
IN
G
B R
A D
L E
Y A
IR
N
A T
IO
N
A
R D
B A
S E
E A
S T
G R
A N
B Y
C
O N
N E
C T
IC
U
T
C O
M P
O S
IT
E
A S
E A
X
S F
A C
IL
IT
Y
Drawing No.:
C
D
A E
S
B
ARCHITECTURAL
B
IM
/U
S C
T D
C
A N
G A
S E
-V M
X S
F a c ili ty /D
C
T A
N G
A
S E
-V M
X S
F A
C
IL
IT
Y
A
R C
H .r v t
/1
/2
:1
:1
P
M
B. HENDON
J. McKINNEY
J. PERRY
03/31/2022
A-137
PARTIAL RCP - ASE
WASH RACK BID
OPTION
1/8" = 1'-0" A1
PARTIAL REFLECTED CEILING PLAN - ASE/VMXS FACILITY - ASE WASH RACK BID OPTION
REV DESCRIPTION DATE
1 AMENDMENT 001 JAN 2023
THESE DOCUMENTS ARE
INTERIM REVIEW AND NO
CONSTRUCTION, BIDDING
| Sheets |
| A-130 - OVERALL REFLECTED CEILING PLAN - ASE/VMXS FACILITY |
| A-131 - PARTIAL RCP - ASE/VMXS FACILITY - AREA A |
| A-132 - PARTIAL RCP - ASE/VMXS FACILITY - AREA B |
| A-133 - PARTIAL RCP - ASE/VMXS FACILITY - AREA C |
| A-134 - PARTIAL RCP - ASE/VMXS FACILITY - AREA D |
| A-135 - PARTIAL RCP - ASE/VMXS FACILITY - AREA E |
| A-136 - PARTIAL RCP - VEHICLE OPS PARKING BUILDING |
| A-137 - PARTIAL RCP - ASE WASH RACK BID OPTION |
| A-601 - FINISH SCHEDULE & TOILET ACCESSORIES SCHEDULE |
| A-610 - DOOR TYPES & DOOR SCHEDULE |
File details come from the government source that posted it. Updated .