This solicitation notice announces a construction project to replace an existing fire station at Mansfield Air National Guard Base in Mansfield, Ohio. The project includes building a new fire station facility with aircraft rescue firefighting and emergency management training space. The construction duration is estimated at 660 calendar days. Optional items include concrete paving connections to the flightline of varying widths, four-fold apparatus doors, and a five-ton bridge crane. The pre-bid conference is scheduled for November 5, 2019 and bids are due by November 26, 2019. The project is set aside for small businesses with a size standard of $39.5 million average annual revenue. The magnitude is estimated between $10-20 million. Interested contractors must register in the System for Award Management and plans and specifications are available on the Federal Business Opportunities website.
Volume 1 - Basis of Design
View the file
Other files for this federal contract opportunity
Show all 50
REPLACE FIRE STATION has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T Y P E B ‐ 3 F I N A L
Replace Fire Station Project Number PBXP929798
Volume 1 – Basis of Design
Prepared for
179th Civil Engineering Squadron Ohio Air National Guard
Mansfield LAHM ANG Base
August 2019
CH2M HILL – HDR JV
241 Taylor Street, Suite 100
Dayton, Ohio, 45402
CH2M HILL - HDR JV
Table of Contents
Volume 1 – Basis of Design
Type B‐3 Checklist
Part I – Design Intent
Cover Sheet
Tab A – Project Requirements
Tab B – Project Site Requirements
Tab C ‐ ANG Design Objectives and Procedures
Tab D ‐ ANG Design Policy
Tab E ‐ Project Approval Package
Part II – Design Narratives
Civil
Structural
Architecture
Fire Protection
Mechanical
Electrical
Communications
Appendices
A. Geotechnical Investigation Report
B. Sustainable Design and Energy Conservation
Volume 2 – Specifications (1 of 4)
Volume 3 – Specifications (2 of 4)
Volume 4 – Specifications (3 of 4)
Volume 5 – Specifications (4 of 4)
Volume 6 – Drawings
49 ANG Design Objectives and Procedures (Tab C) 16 APR 10
Attachment 12
TYPE B-3 FINAL DESIGN SUBMITTAL
CHECKLIST
BASE STATE DATE
PROJECT NUMBER
TITLE
CORRECTED FINAL DRAWINGS FOR ALL DISCIPLINES
FINAL SPECIFICATIONS INCLUDING DIVISION I GENERAL
PROVISIONS, INCLUDING SUMMARY OF WORK, BID STRUCTURING,
AND CONSTRUCTION PHASING PLAN (If required for this project.)
CORRECTED FINAL DETAILED CONSTRUCTION COST ESTIMATE
INCLUDING ABI's or BID OPTIONS
FINAL ANG SUSTAINABLE DESIGN AND ENERGY CONSERVATION
SCORE SHEET AND NARRATIVE
UPDATED BASIS OF DESIGN, PARTS I AND II
PREVIOUS REVIEW COMMENTS WITH A-E DISPOSITION
MANSFIELD LAHM ANG BASE OH AUG 2019
PBXP929798
REPLACE FIRE STATION
X
X
X
X
X
X
REPLACE FIRE STATION
MANSFIELD LAHM ANG BASE, MANSFIELD, OHIO
PBXP929798
Prepared By:
179th Civil Engineering Squadron 1947 Harrington Memorial Road, Mansfield, Ohio 44903
August 2019
COVER SHEET – SIGNATURES
Base Commander Base Civil Engineer
Using Organization Representative Environmental Manager
Fire Chief Security Chief
Safety Officer Communications Chief
Basis of Design Part I – Design Intent
Tab A – Project Requirements
Tab A – Facility Description
Base Name: Mansfield Lahm Air National Guard Base
Location: 1947 Harrington Memorial Road
Mansfield, Ohio 44903‐0179
Project Number: PBXP929798
Project Title: Replace Fire Station
Scope: 2,230 SM (24,002 SF)
This project is to construct a fire station utilizing conventional design and construction methods to accommodate the mission of the facility. Facilities will be designed as permanent construction in accordance with the Department of Defense (DoD) Unified Facilities Criteria (UFC) 1‐200‐01, General
Building Requirements and UFC 1‐200‐02, High Performance and Sustainable Building Requirements.
This facility shall be compatible with applicable DoD, Air Force, and base design standards. In addition, local materials and construction techniques shall be used, where cost effective. This project shall comply with DoD antiterrorism/force protection (ATFP) requirements pursuant to the UFC.
Special Construction Requirements: Facility capable of supporting flightline, aircraft, and structural firefighting mission, provide physical fitness, Emergency Management (EM), Emergency Control Center
(ECC), and Base Defense Operations Center (BDOC), and hands‐on training areas. Safe Haven requested by DWG and confirmed during A‐1 Charette Meeting.
Maximum Construction Cost:
Sustainability Goal: LEED Silver – This project shall be registered with the U.S. Green Building Council
(USGBC) under the 2009 version (LEED v3) Green Building Council (GBCI) and obtain USGBC LEED recognition sustainability certification for Guiding Principles.
Hours of Operations: 24 hour Operations
Building Occupancy: RSD 52 Full Time 20
Facility Description:
The scope of this project is to construct a new facility, not to exceed 2,230 square meters (24,002 square feet). The facility shall serve 20 full‐time and 52 part‐time employees for Base Operating Support and
Emergency Response, to include firefighters, emergency managers, and security forces. Activities in the facility include: administrative, rescue training, emergency and defense response call center, EM, equipment maintenance and storage, fire and emergency apparatus staging, and physical fitness training.
UFC 4-730-10
15 June 2006
4-1
CHAPTER 4 SPECIFIC DESIGN CRITERIA
4-1 INTRODUCTION.
This chapter identifies the specific design needs for each functional area as outlined in the space program. Tables 4-1 through 4-29 provide this data in a standard Functional Data Sheet format.
TABLE 4-1.0. APPARATUS BAY
Description/ Usage
The Apparatus Bays house the fire protection vehicles. Drive-through bays are preferable. All bays must accommodate the latest and largest structural and ARFF vehicles. Each bay of the Apparatus Room must include the required support utilities (drops) for vehicles such as exhaust, compressed air, hot and cold water, lighting, and power.
Min. Ceiling Ht. 4.26 m (14 ft.) minimum.
Finishes Walls. Concrete masonry units (CMU). Provide epoxy paints on all wall surfaces.
Floor. Provide a sealed concrete surface. A non-skid, low-maintenance traffic coating may also be acceptable. Slope floor to trench drains.
Ceiling. Ceiling not required; however, consider finishing exposed structure. Consider coordinating mechanical, electrical and plumbing components. Note that none of the ceiling components can be located below minimum ceiling height.
Plumbing Provide minimum 75-mm- (3-in.-) diameter water service with 62-mm- (2.5-in.-) diameter National Standard Threads ball-valve outlet to each vehicle. Provide an emergency eye wash fountain and shower. Provide foot-operated mop sink with mop hanging rack. Provide standard hot and cold water hose bibb for every two truck bays. Provide floor trench drains parallel to the centerline of each vehicle. All apparatus room drains should connect to an approved oil/water separator prior to discharge.
HVAC The Apparatus Bay is typically heated. Maintain 20 C (68 F) minimum temperature except in areas with very mild winter conditions. Determine exceptions on a case-by-case basis based on climatic conditions.
The Services will not air condition the Apparatus Bay except through exceptions. For the Army, refer to TI-800-1, Design Criteria for the appropriate exceptions. The Air Force will determine on a case-by-case basis based on climatic conditions how to condition the Apparatus Bay. In addition to considering climatic conditions, consider the energy costs and sustainability impacts.
Provide a Fire Apparatus Vehicle Exhaust Removal System (FAVERS) in compliance with NFPA 1500 to eliminate 100% of vehicle exhaust emissions. A direct vent system that evacuates vehicle exhaust directly to the outside is the preferred FAVERS. Make-up air should be distributed so as to minimize drafts and be introduced above apparatus level since diesel exhaust is heavier than air. In this way, the make-up air flow downward will assist in pushing the exhaust fumes out the Apparatus bay doors when open.
Provide compressed air system on self-retracting lines at each vehicle bay. Consider providing a floor radiant heating element at each bay door in colder climates to prevent the door from freezing to the pavement.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code. Locate all outlets at 900 mm (36 in) above finished floor. Provide self-retracting electric drop cords between vehicles that can reach to either end of the bay. Provide backup power sized to provide full unobstructed operation capability of the apparatus bays.
Provide power to each retractable bay door.
4-2
TABLE 4-1.0. APPARATUS BAY
Lighting Provide Lighting System per Paragraph 3-6.4.1. Provide energy efficient lighting with instant-start feature. Provide doors with a signaling system to indicate fully raised doors. A red/green indicator should be located on the driver’s side at 1800 mm (6 ft) above finished floor.
Communication CCTV. Provide interior and exterior outlets located to provide adequate coverage of the Apparatus Bay and facility’s main entrance.
CATV/Internal Video. None required.
PA/Audio. Provide speakers and horns with visual element.
Telephone. Provide one line with internal two-way communication.
Data. Provide data drops as required by equipment.
Security. None required.
Casework None required.
Furnishings Fixtures & Equipment
(FF&E)
Provide 4300 mm by 4300 mm (14 ft. by 14 ft.) apparatus bay doors, with electric eye, and/or automatic reverse device. For ARFF bays provide 5500 mm by 5500 mm (18 ft. by 18 ft.)
doors as recommended by NFPA 403. Even if ARFF vehicles are only intended to be housed on one side of a double bay, provide the 5500 mm by 5500 mm (18 ft. by 18 ft.) doors on both sides to permit drive through and to allow flexibility of use.
Provide manual means to open doors in case of power failure. If solid door panels are used, provide insulated doors. Consider providing doors with radio-operated closing devices that can be activated from the vehicle.
Special Requirements
Ensure both the internal floor slope and the approach drive slope allow the fire protection vehicles to transition into and out of the Apparatus Bay without bottoming-out or without impeding driver sightlines.
4-3
TABLE 4-2.0. PPE GEAR STORAGE
Description/ Usage
The Personal Protective Equipment (PPE) area provides storage for the firefighters’ protective gear. A well-ventilated locker is assigned to each member of the firefighting crew. Sufficient floor area in front of each locker is required for easy access during emergencies. The area is kept under constant negative pressure to evacuate gaseous emissions from stored gear.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. CMU. Provide a low-maintenance, durable finish such as industrial latex or epoxy paints on all wall surfaces.
Floor. Provide a sealed concrete surface sloped to the drain.
Ceiling. Consider providing durable ACP or GWB ceiling with industrial latex or epoxy paint if space is not a part of Apparatus Room.
Plumbing Provide a floor drain. If part of Apparatus Room, consider providing hose bib.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum. This room should be negatively pressurized with dedicated exhaust vented to the outside.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code.
Lighting 540 Lux (50 ft. candles). Provide fluorescent energy efficient light fixtures.
Communication CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide speakers and horns with visual element.
Telephone. None required.
Data. None required.
Security. None required.
Casework None required.
Furnishings Fixtures & Equipment
(FF&E)
Provide open 600 mm by 600 mm (24 in. by 24 in.) by 1800 mm (6 ft.) high wire mesh metal locker that includes shelves and clothes hook.
Special Requirements
Locker layout should permit free air circulation around and throughout clothing.
4-4
TABLE 4-3.0. HOSE STORAGE
Usage
This area provides for storage of hoses. Hoses are rolled and stored on fixed or mobile storage racks.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. CMU. Provide a low-maintenance, durable finish such as industrial latex or epoxy paints on all wall surfaces.
Floor. Provide a sealed concrete surface sloped to floor drain.
Ceiling. None required.
Plumbing Provide a floor drain. Consider providing a hose bibb.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum. Well ventilated.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code and dedicated outlets required to support drying equipment (if provided).
Lighting 540 Lux (50 ft. candles). Provide fluorescent energy efficient light fixtures.
Communication CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. None required.
Data. None required.
Security. None required.
Casework None required.
Furnishings Fixtures & Equipment
(FF&E)
Provide movable racks for roll-up hose storage. Consider providing hose drying oven in areas where required by climatic conditions.
Special
4-5
TABLE 4-4.0. SCBA MAINTENANCE/COMPRESSOR ROOM
Usage
The Self-Contained Breathing Apparatus (SCBA) Maintenance Room is used for the maintenance and minor repair of the SCBA equipment. It includes a work bench, ample task lighting, and shelving for storage of parts and equipment. The room also contains a Mask Pressure Testing Machine.
Separate but directly adjacent is the dedicated SCBA Compressor Room which houses the main compressor unit used to charge the apparatus with filtered air. Ensure direct access between these rooms. This space must include sound attenuation. A compressed air supply line is provided from this room to the SCBA Maintenance Room.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. CMU. Provide a low-maintenance, durable finish such as industrial latex or epoxy paints on all wall surfaces.
Floor. Provide a sealed concrete surface. A non-skid, low-maintenance traffic coating may also be acceptable.
Ceiling. None required in SCBA Maintenance Room.
Plumbing None required. Provide compressed air lines to Apparatus Bay and SCBA Maintenance Room.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum. Provide positive pressure ventilation to prevent contamination.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code.
Lighting 540 Lux (50 ft. candles). Provide fluorescent energy efficient light fixtures. In the SCBA Maintenance Room provide task lighting at the work/service bench.
Communication CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. Provide one line with internal two-way communication.
Data. None required.
Security. None required.
Casework None required.
Furnishings Fixtures & Equipment
(FF&E)
Provide industrial grade 610 mm (24 in) minimum work bench and storage shelving. Provide mask pressure testing machine, safety cage, scales, spare parts bin, and dry chemical extinguisher recharge kit.
Special
In the SCBA Compressor Room provide an STC rating of 50 to 55 to contain compressor noise.
4-6
TABLE 4-5.0. PROTECTIVE CLOTHING LAUNDRY
Usage
Protective Clothing Laundry Room is utilized to wash and disinfect firefighters’ protective clothing/gear. The room should accommodate large commercial-grade washers and dryers and a drip-dry rack. It must be directly accessible from the Apparatus Room and the outdoors.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. CMU. Provide a low-maintenance, durable finish such as epoxy paints on all wall surfaces.
Floor. Provide a sealed concrete surface sloped to floor drain. A non-skid, low-maintenance traffic coating may also be acceptable.
Ceiling. Provide durable, moisture-resistant ACP or GWB ceiling.
Plumbing Provide hot and cold water supply and an open-end drain to each washer. Provide a floor drain.
Connect all drains to oil/water separator with holding tank, if required by location. Refer to NFPA 1581 for more information.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum. Provide negative pressure ventilation in both rooms. Provide direct vents to the outside for each dryer.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code. Provide additional outlets and power as required by equipment.
Lighting 540 Lux (50 ft. candles). Provide fluorescent energy efficient light fixtures.
Communication CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. None required.
Data. None required.
Security. None required
Casework None required.
Furnishings Fixtures & Equipment
(FF&E)
Provide a stainless steel folding table. Consider providing hanging racks.
Special Requirements
Locate room with direct access to the exterior, Equipment Maintenance/Wash/ Disinfection Room, and Apparatus Bay.
4-7
TABLE 4-6.0. EQUIPMENT MAINTENANCE/WASH/DISINFECTION
Usage
The maintenance area is used for the minor repair and maintenance of firefighters’ equipment.
Provide a work bench with adequate lighting and ample storage.
The wash/disinfection area is located adjacent to the maintenance area. It includes a wash-off area where incoming equipment can be washed, desalinated, and dried. When fire trucks return from a fire or other event, equipment is brought into this area for cleaning and disinfection. The equipment is taken from the truck directly to the wash and disinfection area prior to the truck’s entry into the Apparatus Bay.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. CMU. Provide a low-maintenance, durable finish such as industrial latex or epoxy paints on all wall surfaces. Consider using stainless steel wainscot in wash area.
Floor. Provide a sealed concrete surface. A non-skid, low-maintenance traffic coating may also be acceptable.
Ceiling. Provide durable moisture resistant acoustical ceiling panel (ACP) or GWB ceiling.
Plumbing In the wash/disinfection area provide floor mop sink, with hose and spray nozzle. Provide a minimum three-compartment stainless steel sink and a drip dryer rack. Provide an oil-water separator with holding tank for wastewater from all drains. Provide compressed air supply to both Wash and Maintenance Rooms. Provide floor drain in maintenance area.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum. Provide negative pressure ventilation in both rooms.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code.
Lighting 540 Lux (50 ft. candles). Provide fluorescent energy efficient light fixtures. Provide task lighting at work/service bench.
Communication CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. Provide one line with internal two-way communication.
Data. None required.
Security. None required.
Casework None required.
Furnishings Fixtures & Equipment
(FF&E)
Provide a 2400 mm by 1200 mm (8 ft. by 4 ft.) stainless steel work table in the wash/disinfection room. Provide industrial grade 610 mm (24 in.) minimum work bench with storage shelving and spare parts bins. Consider providing hanging racks and open shelf storage units.
4-8
TABLE 4-7.0. EMT STORAGE AND MEDICAL STORAGE CABINET
Usage
The EMT Storage area is for storage of basic first aid supplies. It must be directly adjacent to the Apparatus Bay. The space must be fully conditioned. The Medical Storage Cabinet is often a cabinet or subspace within the EMT Storage area and is for storage of drugs, needles, and other restricted medical supplies. Access to EMT Storage is restricted and controlled to prevent theft and abuse of controlled substances.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. Provide CMU or GWB wall with a low-maintenance, durable finish such as industrial latex paint.
Floor. Provide low-maintenance sheet or tile vinyl flooring material with rubber base.
Ceiling. Provide ACP ceiling.
Plumbing None required.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code.
Lighting 540 Lux (50 ft. candles). Provide fluorescent energy efficient light fixtures.
Communication CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. None required.
Telephone. None required.
Data. None required.
Security. None required.
Casework None required.
Furnishings Fixtures & Equipment
(FF&E)
Provide wall or free standing shelving units. Provide a lockable cabinet for the EMT Storage to store drugs and other restricted supplies.
Special
Consider providing a keyed lock set at the access point to the space.
4-9
TABLE 4-8.0. HAZMAT/CBRNE EQUIPMENT STORAGE
Usage
HAZMAT/CBRNE Equipment Storage is a separate storage facility housing only equipment classified for use with hazardous materials. Provide sufficient floor and open shelf storage areas.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. CMU. Provide a low-maintenance, durable finish such as industrial latex paint.
Floor. Provide a sealed concrete surface. A non-skid, low-maintenance traffic coating may also be acceptable.
Ceiling. None required.
Plumbing None required.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum. This room should be negatively pressurized with dedicated exhaust vented to the outside.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code.
Lighting 215 Lux (20 ft. candles). Provide fluorescent energy efficient light fixtures.
Communication CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. None required.
Data. None required.
Security. None required.
Casework None required.
Furnishings Fixtures & Equip. (FF&E)
Provide industrial storage shelving units and racks.
4-10
TABLE 4-9.0. AGENT STORAGE
Usage
Agent Storage is typically a single-story structure separate from the fire station building. It should be located along the drive leading into the Apparatus Bay for ease of loading and unloading of firefighting agents. In some cases, it may be attached to the main structure.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. None required. Unless structure is wood or metal stud construction, provide plywood sheathing for protection.
Floor. Provide a sealed concrete surface.
Ceiling. None required.
Plumbing None required.
HVAC Provide heating where required by location to prevent agents from freezing.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code.
Lighting 215 Lux (20 ft. candles). Provide fluorescent energy efficient light fixtures.
Communication CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. None required.
Telephone. None required.
Data. None required.
Security. None required.
Casework
Furnishings Fixtures & Equipment
(FF&E)
Provide double or overhead-type exterior doors. Consider providing insulated doors in locations where required by climatic conditions.
4-11
TABLE 4-10.0. SPARE PPE GEAR STORAGE
Usage
This space serves to store extra PPE gear for firefighters and reservists currently not on duty, if required by Installation mission requirements. The space includes gear lockers with an open shelving storage system.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. CMU. Provide a low-maintenance, durable finish such as industrial latex or epoxy paints on all wall surfaces.
Floor. Provide a sealed concrete surface. A non-skid, low-maintenance traffic coating may also be acceptable.
Ceiling. None required.
Plumbing None required.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code.
Lighting 215 Lux (20 ft. candles). Provide fluorescent energy efficient light fixtures.
Communication CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. None required.
Data. None required.
Security. None required.
Casework None required.
Furnishings Fixtures & Equipment
(FF&E)
Provide open 600 mm by 600 mm by 1800 mm (24 in. by 24 in. by 6 ft.) high wire mesh metal lockers that include shelves and clothes hooks.
Special
4-12
TABLE 4-11.1. FIRE EXTINGUISHER (NON FLIGHTLINE)
MAINTENANCE AND STORAGE
Description/ Usage
The non-flightline Fire Extinguisher Maintenance and Storage includes an indoor storage/maintenance room and possibly an outdoor storage area. The indoor storage/maintenance room accommodates a work bench with adequate lighting to perform maintenance and service of extinguishers, safety cage, scale, recharge kit, and parts storage bins. Provide open shelving for storage of extinguishers.
The outdoor storage area is covered and enclosed with a secured screen.
This may be combined with the Flightline Fire Extinguisher Maintenance and Storage Area and made as one space with no dividing walls.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. CMU. Provide a low-maintenance, durable finish such as industrial latex or epoxy paints on all wall surfaces.
Floor. Provide a sealed concrete surface.
Ceiling. None required.
Plumbing Provide a hose bibb and floor drain. Provide eye wash fountain in Maintenance Room.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum. Provide negative pressure ventilation with an exhaust hood. Provide fume discharge to the exterior. Provide a compressed air system with self-retracting lines at the work bench.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code.
Lighting 540 Lux (50 ft. candles). Provide fluorescent energy efficient light fixtures. Provide task lighting at work/service bench.
Communication CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide quad outlet at work bench and in locations where required to accommodate equipment.
Security. None required.
Casework None required.
Furnishings Fixtures & Equipment
(FF&E)
Provide double leaf doors to exterior. Provide industrial grade 610 mm (24 in) minimum work bench, storage shelving, spare parts bin, flammable storage locker, and a floor scale.
Special Requirements
Locate access to Fire Extinguisher Maintenance and Storage away from Apparatus Bay exterior circulation.
4-13
TABLE 4-11.2. FIRE EXTINGUISHER (FLIGHTLINE)
MAINTENANCE AND STORAGE
Description/ Usage
The Fire Extinguisher Maintenance and Storage includes two parts: outdoor storage and indoor storage/maintenance room. The indoor storage/maintenance room accommodates a work bench with adequate lighting to perform maintenance and service of extinguishers, safety cage, scale, recharge kit, and parts storage bins.
The outdoor storage area is covered and enclosed with a secured screen and should accommodate tank recovery, spare tanks, and spare gaseous agent re-servicing tanks.
This may be combined with the Non-flightline Fire Extinguisher Maintenance and Storage Area and made into one space with no dividing walls.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. CMU. Provide a low-maintenance, durable finish such as industrial latex or epoxy paints on all wall surfaces.
Floor. Provide a sealed concrete surface.
Ceiling. None required.
Plumbing Provide a hose bibb and floor drain.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum. This room should be negatively pressurized with dedicated exhaust vented to the outside. Provide an exhaust hood. Provide a compressed air system with self-retracting lines at the work bench.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code.
Lighting 540 Lux (50 ft. candles) Provide fluorescent energy efficient light fixtures. Provide task lighting at work/service bench.
Communication CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide quad outlet at work bench and in locations where required to accommodate equipment.
Security. None required.
Casework None required.
Furnishings Fixtures & Equipment
(FF&E)
Provide double leaf or overhead-type doors to exterior. Provide industrial grade 610 mm (24 in.) minimum work bench, storage shelving, spare parts bin, flammable storage locker, agent and nitrogen storage, dry chemical extinguisher recharge kit, and a floor scale.
Provide cylinder for extinguishing agent recovery (if halon is used, accommodate a 690 kg (1500 lb) cylinder). Consider placing the agent recovery tanks outside the exterior wall of this room and connect via utility lines to a discharge point inside the room. If this approach is taken, provide a remote gauge in the room that displays the tank’s fill status.
Special Requirements
Locate access to Fire Extinguisher Maintenance and Storage away from Apparatus Bay exterior circulation.
4-14
TABLE 4-12.0. VEHICLE MAINTENANCE BAY
Usage
This space is mainly used to service and repair firefighting vehicles, if required by Installation mission requirements. At times, this bay may be used as an additional Apparatus Bay as well.
The bay is sized to accommodate the largest vehicle and the equipment required to service it.
Similar to the Apparatus Bay, the Vehicle Maintenance Bay should be a drive-through.
Min. Ceiling Ht. 4.26 m (14 ft.) minimum.
Finishes Walls. CMU. Provide epoxy paints on all wall surfaces.
Floor. Provide a sealed concrete surface. A non-skid, low-maintenance traffic coating may also be acceptable.
Ceiling. Ceiling not required; however, consider finishing exposed structure. Consider coordinating mechanical, electrical, and plumbing components. Note that none of the ceiling components can be located below minimum ceiling height.
Plumbing Provide minimum 75-mm- (3-in.-) diameter water service with 62-mm- (2.5 in) diameter National Standard Threads ball valved outlet to each vehicle. Provide standard hot and cold water hose bibb. Provide floor trench drains parallel to the centerline of each vehicle. Trench drain should connect to an approved oil/water separator prior to discharge to the sanitary sewer.
HVAC The Vehicle Maintenance Bay is typically heated. Maintain 20 C (68 F) minimum temperature except in areas with very mild winter conditions. Determine exceptions on a case-by-case basis based on climatic conditions.
The Services will not air condition the Vehicle Maintenance Bay except through exceptions. :
For the Army, refer to TI-800-1, Design Criteria for the appropriate exceptions. The Air Force will determine on a case-by-case basis based on climatic conditions how to condition the Apparatus Bay. In addition to considering climatic conditions, consider the energy costs and sustainability impacts.
Provide a Fire Apparatus Vehicle Exhaust Removal System (FAVERS) in compliance with NFPA 1500 to eliminate 100% of vehicle exhaust emissions. A direct vent system that evacuates vehicle exhaust directly to the outside is the preferred FAVERS. Make-up air should be distributed so as to minimize drafts and be introduced above apparatus level since diesel exhaust is heavier than air. In this way, the make-up air flow downward will assist in pushing the exhaust fumes out the Apparatus bay doors when open.
Provide compressed air system on self-retracting lines at each vehicle bay. Consider providing floor radiant heating element at each door in colder climates to prevent the door from freezing to the pavement.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code. Locate all outlets at 900 mm (36 in.) above finished floor. Provide self-retracting electric drop cords between vehicles. Provide backup power sized to provide full unobstructed operation capability of the Apparatus Bays and Vehicle Maintenance Bay.
Provide power to each retractable door.
Lighting Provide Lighting System per Paragraph 3-6.4.1. Provide energy efficient lighting with instant-start feature. Provide doors with signaling system indicating fully raised doors. A red/green indicator should be located on the driver’s side at 1800 mm (6 ft.) above finished floor.
Communication CCTV. Provide interior and exterior and cameras located to provide adequate coverage.
CATV/Internal Video. None required.
PA/Audio. Provide speakers and horns with visual element.
Telephone. Provide one line with internal two-way communication.
Data. Provide data drops as required by equipment.
Security. None required.
Casework None required.
4-15
TABLE 4-12.0. VEHICLE MAINTENANCE BAY
Furnishings Fixtures & Equip. (FF&E)
Provide tool storage bins and industrial work benches.
Special
Consider providing hydraulic lifts and/or overhead lift/crane.
4-16
TABLE 4-13.0. VEHICLE MAINTENANCE EQUIPMENT STORAGE
Usage
Vehicle Maintenance Equipment Storage is tied to the Vehicle Maintenance Bay and is used to store spare parts and tools required for vehicle maintenance and service. It is only provided if required by Installation mission requirements. It should accommodate shelving storage and adequate floor area for storage of large items such as tires and wheels.
Min. Ceiling Ht. 4.26 m (14 ft.) minimum.
Finishes Walls. CMU. Provide epoxy paints on all wall surfaces.
Floor. Provide a sealed concrete surface. A non-skid, low-maintenance traffic coating may also be acceptable.
Ceiling. Ceiling not required; however, consider finishing exposed structure. Consider coordinating mechanical, electrical, and plumbing components. Note that none of the ceiling components can be located below minimum ceiling height.
Plumbing None required.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code.
Lighting 215 Lux (20 ft. candles). Provide fluorescent energy efficient light fixtures.
Communication CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. Provide one line with internal two-way communication.
Data. None required.
Security. None required.
Casework None required.
Furnishings Fixtures & Equipment
(FF&E)
Provide industrial storage shelving units and racks.
Special Requirements
This space should be adjacent to the Vehicle Maintenance Office and Vehicle Maintenance Bay.
4-17
TABLE 4-14.0. DEPLOYMENT GEAR STORAGE
Usage
This storage space is utilized for storage of firefighting gear required for military deployment, if required by Installation mission requirements (always required for Air Force). This gear may be used by reservists and/or active duty military personnel. It includes ventilated lockers with open shelving.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. CMU. Provide epoxy paints on all wall surfaces.
Floor. Provide a sealed concrete surface.
Ceiling. None required.
Plumbing None required.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code.
Lighting 215 Lux (20 ft. candles). Provide fluorescent energy efficient light fixtures.
Communication CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. None required.
Data. None required.
Security. None required.
Casework None required.
Furnishings Fixtures & Equipment
(FF&E)
Provide open 600 mm by 600 mm by 1800 mm (24 in. by 24 in. by 6 ft.) high wire mesh metal lockers that include shelves and clothes hooks.
Special
4-18
TABLE 4-15.0. STATION OFFICER’S OFFICE/WATCH DESK
Usage
The Station Officer’s Office provides space for the station officer and/or company officers to perform their administrative functions. For Satellite stations the Station Officers office may serve to control public access to the station. If a Watch Desk function is required, it is typically included in the Station Officer’s Office. The Watch Desk receives emergency calls from the Dispatch and contains the security monitors for the station. It is usually occupied 24 hours a day/7 days a week.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. Provide a low-maintenance, durable finish such as egg-shell latex paint.
Floor. Provide low maintenance sheet or tile vinyl flooring material. Consider providing durable commercial carpeting.
Ceiling. Provide ACP ceiling system.
Plumbing None required.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code, and as needed to support the extensive equipment required. In addition to above-noted power requirements, provide two additional quad outlets at the control center console. Provide a switch controlling operation of Apparatus Bay doors.
Lighting 540 Lux (50 ft. candles). Provide fluorescent energy efficient light fixtures. Provide task lighting at control desk.
Firefighter Alert System: Provide light and audible control for the following elements when the firefighter alert system is activated: Dorm Room lights (the dedicated alert light), corridor lights from Dorm Rooms to Apparatus Bay, and the Apparatus Bay lights.
Communication CCTV. Provide outlets required to support required equipment.
CATV/Internal Video. Provide outlets required to support required equipment.
PA/Audio. Provide simultaneous light and audible control for the entire fire station.
Telephone. Provide regular and secure multi-telephone line required to support switch board operation, telephone, and fax.
Data. Provide regular and secure data outlets to support required equipment.
Security. Provide vision panel to the Apparatus Bay. Provide pin pad/cipher electric lock with remote push button release and manual key override.
Casework None required.
Furnishings Fixtures & Equipment
(FF&E)
Provide control center console. Provide modular component workstations to accommodate computers, monitor screens, two-way radios, and audio equipment. Provide recording system to record all emergency radio and telephone conversations. Provide wall-mounted Installation grid coordinate map. Provide map racks. Provide safes for classified technical manuals. Provide book cases and ergonomically designed seating.
Special Requirements
Provide a 920 mm (36 in) free access area around the entire control console. Provide space for Emergency Information Systems computer. Provide tinted widows with blinds. Consider providing handicapped-accessible toilet.
Provide an STC rating of 50 to 55.
4-19
TABLE 4-16.0. FIRE CHIEF’S AND DEPUTY FIRE CHIEF’S OFFICES
Usage
The Fire Chief’s and Deputy Fire Chief’s Offices are two separate offices that will not exist in every station. When they are both located in a station, they are adjacent to each other and to an administrative assistant and a Chief’s Conference Room. Each office includes a typical office space and workstation. An adjacent private bedroom and private toilet are shared by both offices and should be directly accessible by both offices. Consider making the bedroom/toilet portion part of the standard station dorm room area for added flexibility.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. Provide a low-maintenance, durable finish such as egg-shell latex paint. In toilet consider providing moisture and mildew resistant gypsum wall board, with ceramic tile wainscot, and semi-gloss industrial latex-based paint
Floor. Provide durable commercial carpeting with rubber base in office and sleeping areas.
Provide ceramic tile and ceramic tile base in toilet.
Ceiling. Provide ACP or gypsum board ceiling. Provide moisture resistant gypsum board ceiling in the toilet. Consider egg-shell latex paint in office and sleeping areas, and semi-gloss industrial paint in the toilet.
Plumbing Provide water closet, shower, and lavatory. Consider providing floor drain.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum. Provide exhaust fan in private toilet. Consider providing independent thermostat.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3. Provide smoke and CO detectors.
Power Provide outlets per code.
Lighting 540 Lux (50 ft. candles). Provide fluorescent energy efficient light fixtures. Consider providing task lighting at individual desks. Consider providing residential-style light fixtures.
In addition to the ambient and task lighting fixtures, provide a dedicated alert light fixture that is controllable from the Watch Desk/Dispatch and tied into the firefighting alert system with a red-tinted bulb or lens.
Communication CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide data outlets to support required equipment.
Security. None required.
Casework None required.
Furnishings Fixtures & Equipment
(FF&E)
Provide office desk, office chair, file cabinet, bookshelf, desk lamp, and additional side chair.
In the private bedroom provide twin bed, night stand, and a wardrobe. Provide window blinds.
Special Requirements
In Air Force and large Army/Navy facilities where an Assistant Fire Chief exists, he or she should share a private toilet with the Deputy Fire Chief, and the Fire Chief should be provided with his or her own private toilet.
There also may be a requirement for a Chief’s Conference Room. If required, this would be directly adjacent to or expand out of the Chief’s Office. It provides space for a small conference table for 8 to 10 people.
4-20
TABLE 4-17.0. OFFICES
Usage
General administrative office spaces in the station include the following: Assistant Chief/Shift Supervisor Office, Inspector’s Office(s), Training Officer Office, Vehicle Maintenance Office, EMS Office, Dispatch Supervisor (if provided), Administrative Assistant, Reservist Office (if provided), Assistant Chief of Fire Prevention (if provided), HAZMAT/Safety Officer (if provided), and Logistics Officer (if provided).
The offices are generally grouped together in the Administrative component of the Fire Station.
The Administrative Assistant is generally only provided if the Chief and Deputy Chief are resident in the station, in which case this area also doubles as the general reception area for the facility and is located directly off of the lobby (see Table 4-18).
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. Provide a low-maintenance, durable finish such as egg-shell latex paint.
Floor. Provide low maintenance sheet or tile vinyl flooring material with rubber base.
Consider providing durable commercial carpeting.
Ceiling. Provide ACP ceiling.
Plumbing None required.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code.
Lighting Provide Lighting System per Paragraph 3-6.4.1.
Communication CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. Provide one line with internal two-way communication.
Data. Provide data outlets to support required equipment.
Security. None required.
Casework None required.
Furnishings Fixtures & Equipment
(FF&E)
Provide office desk, office chair, file cabinet, bookshelf, desk lamp, and an additional side chair. For a more executive-level office, consider providing credenza and two additional side chairs.
Special Requirements
The Vehicle Maintenance Office will be located near the Vehicle Maintenance Bay and Storage. It will likely have CMU walls and more durable finishes than typical offices.
4-21
TABLE 4-18.0. LOBBY
Usage
The lobby is generally only provided if the Department Chief and Deputy Chief are resident in the station. It serves as the entrance to the facility and gathering/waiting space for the visiting public. The lobby should be adjacent to the administrative component of the facility. It should also be recognizable from the outside and a well-lit, inviting space.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. Provide a low-maintenance, durable finish such as industrial egg-shell latex paint.
Consider providing rubber or paper wall coverings
Floor. Provide low-maintenance sheet or tile vinyl flooring material with rubber base.
Consider stone or quarry tile with stone or tile base.
Ceiling. Provide acoustical and decorative ACP or gypsum board ceiling such as egg-shell latex paint for gypsum board ceiling.
Plumbing None Required. Consider providing a drinking fountain.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code. Consider outlets for display cases.
Lighting Provide Lighting System per Paragraph 3-6.4.1. Consider decorative lighting fixtures and task lighting.
Communication CCTV. Provide at least one outlet.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. Consider providing one line for local and toll-free calls or a pay phone.
Data. None required.
Security. None required.
Casework Consider providing display cases.
Furnishings Fixtures & Equipment
(FF&E)
Provide walk-off matt at entrance (consider a built-in mat), soft padded furniture, side tables, magazine rack, and tack surfaces.
Special
Provide airlock at main entrance when necessary and signage.
4-22
TABLE 4-19.0. DEPARTMENT TRAINING ROOM
Usage
Department Training Room is a classroom space used for the continuing education and training of the fire station staff and, occasionally, the public. It is typically sized to accommodate the entire on-duty population of the Department—provide sufficient seating and desks. Provide audiovisual capabilities with phone and Internet connections for each training station. See Figure D-4 for a sample layout of this space.
A storage closet is located adjacent to the Training Room and used for storage of audiovisual equipment, media, additional equipment, and furnishings.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. Provide a low-maintenance, durable finish such as egg-shell latex paint.
Floor. Provide low maintenance sheet or tile vinyl flooring material with rubber base.
Consider providing durable commercial carpeting.
Ceiling. Provide ACP ceiling.
Plumbing None required.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum. Provide separate thermostat for this room.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code. Consider providing direct power to each work table.
Lighting Provide Lighting System per Paragraph 3-6.4.1.
Communication CCTV. None required.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. Provide one line with internal two-way communication Data. Provide data outlets to every workstation.
Security. None required.
Casework None required.
Furnishings Fixtures & Equipment
(FF&E)
Provide overhead retractable screen, overhead projector, desks, chairs, printer, TV, VCR, and DVD player. Provide bulletin board with tack surface and dry-erase board.
If a separate testing area is not provided, provide computer/study/testing carols with individual computers.
Special Requirements
Consider acoustics and eliminating potential distractions. Provide a minimum STC rating of 50 to 55.
4-23
TABLE 4-20.0. TESTING/INDIVIDUAL STUDY AREA
Usage
This area consists of individual computer/study carols for study and testing of firefighters.
Each of these stations must be private to eliminate potential for cheating during testing and to facilitate quiet study. See Figure D-5 for a sample layout of this space.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. Provide a low-maintenance, durable finish such as egg-shell latex paint.
Floor. Provide low-maintenance sheet or tile vinyl flooring material with rubber base.
Consider providing durable commercial carpeting.
Ceiling. Provide ACP ceiling.
Plumbing None required.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum. Consider providing separate thermostat for this room.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code. Provide direct power to each computer/study carol and for other equipment such as printers.
Lighting 540 Lux (50 ft. candles). Provide fluorescent energy efficient light fixtures.
Communication CCTV. Provide video camera with monitor located in Testing Officer Office.
CATV/Internal Video. None required.
PA/Audio. Provide a speaker Telephone. None required.
Data. Provide data outlets to all workstations and equipment.
Security. None required.
Casework None required.
Furnishings Fixtures & Equipment
(FF&E)
Provide four computer/study carols (to accommodate one company) and printer(s), office chairs, and task lights.
Special
Provide a minimum STC rating of 50 to 55.
4-24
TABLE 4-21.0. DISPATCH
Usage
The Dispatch Room defines the similar functions for Fire-only Dispatch and Consolidated Dispatch Rooms. This room functions to receive and dispatch emergency related calls. Fire-only Dispatch rooms are solely responsible for receiving and dispatching fire related emergency calls. A Consolidated Dispatch Room handles fire, security, and medical response service calls.
Not every station includes a Dispatch. The Dispatch Room includes workstations sized to accommodate the necessary equipment for each individual dispatcher.
In larger Dispatch Rooms, a separate, adjacent room for the Dispatch Supervisor is required.
The finishes and mechanical/electrical requirements for this room are the same for Offices (see Table 4-17).
Dispatch Rooms also include a dedicated toilet and kitchenette directly adjacent to and accessible from to the room for staff use.
Figures D-6.1 and D-6.2 illustrate sample layouts of the Dispatch Room.
Min. Ceiling Ht. 2.4 m (8 ft.) minimum.
Finishes Walls. Provide a low-maintenance, durable finish such as industrial egg-shell latex paint.
Floor. Provide low-maintenance sheet or tile vinyl flooring material with rubber base.
Consider providing durable commercial carpeting.
Ceiling. Provide ACP ceiling.
Plumbing Provide a handicapped accessible toilet with a lavatory and water closet. Provide a kitchenette with a kitchen sink and disposal.
HVAC 20 C (68 F) minimum, 26 C (78 F) maximum. Provide independent environmental control equipment. Provide exhaust for the toilet as required by code.
Fire Protection Provide Fire Protection System per Paragraph 3-6.3.
Power Provide outlets per code and as needed to support all equipment, including charging equipment for handhelds. Provide a switch controlling open only operation of Apparatus Bay doors.
The generator must provide back-up power for all Dispatch Room systems. In addition, provide uninterrupted power supply (UPS) for all Dispatch Room systems.
The UPS will provide an uninterrupted flow of power to gap between the time of power loss and the time that generator is providing power.
Lighting 540 Lux (50 ft. candles). Provide fluorescent energy efficient light fixtures. Consider providing task lighting at control desk.
Firefighter Alert System: Provide light and audible control for the following elements when the firefighter alert system is activated: Dorm Room lights (the dedicated alert light), corridor lights from Dorm Rooms to Apparatus Bay, and the Apparatus Bay lights.
Communication CCTV. Monitors for the facility cameras will be located here. Provide outlets required to support equipment.
CATV/Internal Video. Provide outlets required to support equipment.
PA/Audio. Provide a speaker and a microphone.
Telephone. Provide regular and secure multi-telephone line required to support switchboard operation, telephone, and fax.
Data. Provide regular and secure data outlets to support required equipment.
Security. Provide vision panel to the Apparatus Bay. Provide pin pad/cipher electric lock with remote push…