This document contains a request for information and response regarding a federal contract solicitation to replace an existing fire station at Mansfield Air National Guard Base in Ohio. Key details include that the solicitation seeks construction of a new aircraft rescue and firefighting facility, with optional additions for concrete paving and apparatus doors. Interested contractors must attend a pre-bid conference on November 5th and submit bids no later than November 26th. The contract is set aside for small businesses with a value between $10-20 million. The response provides clarification on electrical and communications specifications, and notes that no substitutions are permitted for the fire alarm system. The Department of the Army Ohio Army National Guard is the contracting agency for this replacement project.
View the file
Other files for this federal contract opportunity
Show all 50
REPLACE FIRE STATION has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR INFORMATION
R E
Q U
E S
T O
R S
E C
T
IO
N
From: Date:
11/08/2019
To: Contracting Officer
Gordon Strom
1. Solicitation Number:
W50S8R-20-B-0001
2. Location of Project:
Fire Station - Mansfield Ohio ANG
3. Information Requested: (Include Specification Section and/or Drawing Number and Page if inquiring about a discrepancy)
Print E‐112, Note 3: What type and length of cord is required for the retractable cord reels in Apparatus Bay?
Print E‐100, E‐503 and E‐504: Are precast electrical man holes and hand holes acceptable and is there a spec to cover these? Is the hand hole detail on print E‐503 the design to be used for all hand holes except the ones designated for site lighting circuits?
SPEC Section 28 31 76, as well as Replace Fire Station‐ Fire Protection Design Narrative: Are we able to submit substitutions for the Monaco fire alarm system?
Replace Fire Station‐ Communications Design Narrative: Where is existing telecom vault MH‐19 located? Where is existing telecom hardhole HH‐102A located? Are these the two locations that we are required to run data conduit in order to connect to buildings 164 and 102 respectively? What are the requirements for conduit and cable running to Communications Tower? Are we responsible for any part of the Communications Tower?
Attachments:
Date Response Required:
By:
Title:
Requestor's FAX Number:
Requestor's Telephone Number:
R E
S P
O N
S E
To:
Date:
Response:
Print E‐112, Note 3: Provide type SO, 40’ length, Hubbell Series A cable reel or similar.
Print E‐100, E‐503 and E‐504: Yes, precast man and hand holes are acceptable. Provide per specifications SECTION 33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION. Yes, use E‐503 hand hole detail for all hand holes except site lighting circuits.
No substitutions permitted for the Monaco fire alarm system.
Below is an excerpt from the Civil Narrative, regarding Comm locations:
Communications to the building will be run in three separate locations. Conduit runs from an existing hand hole near Building 164 across the access drive across the parking area to the fire station building near the main entrance. A new hand hole will be placed just outside the building. The service will run beneath the building slab to enter the Communications Room. A self‐supported communications tower will be placed in the grassed area between Building 102 and the fire station. Conduits will run from the communications tower to the communications room. In addition, conduit will run from the existing communications vault on the east side of Building 102 to the fire station building. See the “Communications Design Narrative” for more information.
Yes, the Comm Tower will be provided and installed by the contractor. A 30’ Rohn 55G self‐supporting tower is the basis of design, other self‐supporting towers of equal height, equal corrosion resistance, and rated for 120 MPH Wind (3‐ second gust) are acceptable. Two 4” conduits to the tower are identified on CU103.
This information is a clarification of the solicitation/contract and does not change the contract terms or conditions.