RFI_09.pdf

PDF 107 KB Posted

Attached to
REPLACE FIRE STATION
Solicitation number
W50S8R-20-B-0001
Issued by

About this file

This document contains a request for information and response regarding a federal contract solicitation to replace an existing fire station at Mansfield Air National Guard Base in Ohio. Key details include that the solicitation seeks construction of a new aircraft rescue and firefighting facility, with optional additions for concrete paving and apparatus doors. Interested contractors must attend a pre-bid conference on November 5th and submit bids no later than November 26th. The contract is set aside for small businesses with a value between $10-20 million. The response provides clarification on electrical and communications specifications, and notes that no substitutions are permitted for the fire alarm system. The Department of the Army Ohio Army National Guard is the contracting agency for this replacement project.

View the file

Other files

File Type Posted
Abstract_FIRE_pg3.pdf PDF
Abstract_FIRE_signed.pdf PDF
bid opening attendees.pdf PDF
RFI_15.pdf PDF
RFI_17.pdf PDF
RFI_19.pdf PDF
A-601 - DOOR-WINDOW SCHEDULES.pdf PDF
RFI_21.pdf PDF
RFI_20.pdf PDF
RFI_21_attachment.pdf PDF
RFI_13.pdf PDF
RFI_18.pdf PDF
RFI_16.pdf PDF
A-602 - INTERIOR FINISH-COLOR SCHEDULE.pdf PDF
RFI_14.pdf PDF
RFI_08.pdf PDF
RFI_07.pdf PDF
RFI_12.pdf PDF
RFI_08 attach.pdf PDF
RFI_07 attach.pdf PDF
RFI_11.pdf PDF
RFI_10_attachment.pdf PDF
RFI_10.pdf PDF
RFI_06.pdf PDF
RFI_2.pdf PDF
RFI_4.pdf PDF
RFI_3.pdf PDF
RFI_1.pdf PDF
RFI_5.pdf PDF
Pre-Bid_minutes,_data.pdf PDF
RFI_3_attachment.pdf PDF
Attach6_Telecommunications.pdf PDF
Attach6_Civil_6b.pdf PDF
Attach6_Civil_6a.pdf PDF
Attach6_Mechanical.pdf PDF
Attach6_Civil_8b.pdf PDF
Attach6_Architectural.pdf PDF
Attach6_Plumbing.pdf PDF
Attach6_Fire_Protection.pdf PDF
W50S8R-20-B-0001.pdf PDF
Attach6_Civil_5d.pdf PDF
Attach7_Geotechnical_Report.pdf PDF
Attach6_General.pdf PDF
Attach6_Civil_4c.pdf PDF
Attach6_Civil_4a.pdf PDF
Attach6_Electrical.pdf PDF
Attach6_Civil_3.pdf PDF
Attach6_Structural.pdf PDF
Attach6_Civil_7.pdf PDF
Attach6_Civil_9.pdf PDF
Show 40 more

Latest 50 of 67 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR INFORMATION

R E

Q U

E S

T O

R S

E C

T

IO

N

From: Date:

11/08/2019

To: Contracting Officer

Gordon Strom

1. Solicitation Number:

W50S8R-20-B-0001

2. Location of Project:

Fire Station - Mansfield Ohio ANG

3. Information Requested: (Include Specification Section and/or Drawing Number and Page if inquiring about a discrepancy)

Print E‐112, Note 3: What type and length of cord is required for the retractable cord reels in Apparatus Bay?

Print E‐100, E‐503 and E‐504: Are precast electrical man holes and hand holes acceptable and is there a spec to cover these? Is the hand hole detail on print E‐503 the design to be used for all hand holes except the ones designated for site lighting circuits?

SPEC Section 28 31 76, as well as Replace Fire Station‐ Fire Protection Design Narrative: Are we able to submit substitutions for the Monaco fire alarm system?

Replace Fire Station‐ Communications Design Narrative: Where is existing telecom vault MH‐19 located? Where is existing telecom hardhole HH‐102A located? Are these the two locations that we are required to run data conduit in order to connect to buildings 164 and 102 respectively? What are the requirements for conduit and cable running to Communications Tower? Are we responsible for any part of the Communications Tower?

Attachments:

Date Response Required:

By:

Title:

Requestor's FAX Number:

Requestor's Telephone Number:

R E

S P

O N

S E

To:

Date:

Response:

Print E‐112, Note 3: Provide type SO, 40’ length, Hubbell Series A cable reel or similar.

Print E‐100, E‐503 and E‐504: Yes, precast man and hand holes are acceptable. Provide per specifications SECTION 33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION. Yes, use E‐503 hand hole detail for all hand holes except site lighting circuits.

No substitutions permitted for the Monaco fire alarm system.

Below is an excerpt from the Civil Narrative, regarding Comm locations:

Communications to the building will be run in three separate locations. Conduit runs from an existing hand hole near Building 164 across the access drive across the parking area to the fire station building near the main entrance. A new hand hole will be placed just outside the building. The service will run beneath the building slab to enter the Communications Room. A self‐supported communications tower will be placed in the grassed area between Building 102 and the fire station. Conduits will run from the communications tower to the communications room. In addition, conduit will run from the existing communications vault on the east side of Building 102 to the fire station building. See the “Communications Design Narrative” for more information.

Yes, the Comm Tower will be provided and installed by the contractor. A 30’ Rohn 55G self‐supporting tower is the basis of design, other self‐supporting towers of equal height, equal corrosion resistance, and rated for 120 MPH Wind (3‐ second gust) are acceptable. Two 4” conduits to the tower are identified on CU103.

This information is a clarification of the solicitation/contract and does not change the contract terms or conditions.

This information is a proposed change to the solicitation/contract. An amendment will be issued.